Siemens QAA2280.xWNC,QAA2280.xWSC,QAA3280.xWNC,QAA2281.xWSC,QAA3280.xWSC Installation Instructions Manual

Installation Instructions
CAUTION
Equipment damage or loss of
specified.
Document No. 129-484
April 17, 2014
3200 Combination RH&T Room Units,
Product Description
These room units allow users to view and adjust points in the controller using the room unit buttons and digital display.
They work with various Terminal Equipment Controllers (TECs) and Actuator Terminal Controllers (ATECs) offered by Siemens Industry, Inc. These devices incorporate a solid state or 10K NTC sensing element to detect temperature (and humidity for QFA models). The effective sensing and setpoint range is 55°F to 95°F (13°C to 35°C).
These room units can be mounted on electrical boxes, stud-type mounting brackets, or drywall. Obtain the necessary mounting hardware and follow the appropriate mounting procedures for the type of installation required.
Product Numbers
QAA2280.xWNC QFA3280.xWNC QAA2280.xWSC QFA3280.xWSC QAA2281.xWSC
Expected Installation Time
20 minutes
Required Tools
If using non-terminated or damaged cables, you also need:
Phillips sizes 1 and 2 screwdrivers
Small and medium, flat-blade screwdrivers
1/16-inch hex key or 544-643A Passke y
(includes hex bit)
Medium-duty electric drill
3/16-inch (4.8 mm) drill bit
One-inch (25 mm) hole saw
Small level
Tape measure
Marker or pencil
Room unit connector tool (RJ-11 crimping
tool – SBT P/N 540-140 or third-party tool)
Room unit connector kit (SBT P/N 540-141)
Accessories
AQA2200-INTL Room Unit Back Plate (10-pack) AQA2200-2X4 Room Unit Back Plate (Single) 563-102 GSKT Kit Room Sensor Insulating
Gasket (10-pack) (For hollow wall in s ta llations)
TEC to Room Sensor Cable Yellow, 6-pin m ale with RJ -11 jacks on both ends (Choose 1, a cable may already be installed): 588-100A 25-foot 588-100B 50-foot 588-100C 100-foot
Caution Notations
data may occur if you do not
Item Number 129-484, Rev. JA Page 1 of 3
follow a procedure as
Prerequisites
Review these instructions before beginning.
Installed: appropriate field wiring (standard
six-conductor room unit cables, plenum or non-plenum as required) within the maximum wiring run length for the individual equipment controller. The maximum recommended length is 100 feet (30 m).
All wiring must comply with Nationa l Electric Code (NEC) and local regulations.
Figure 1. Temperature Room Unit.
Document No. 129-484 Installation Instructions April 17, 2014
Mounting Information
Always mount the room unit vertically, on a flat wall. Locate the room unit:
according to design specif i c ations and loc a l regulations.
where the air circulates around it freely (not in recessed areas or behind doors).
allowing a minimum of 4 inches (10 cm) free space above and below for proper airflow, the hex bit or passkey tool, and the computer communication cable.
away from drafts caused by doors, windows, outside walls, air registers, pipes , return air plenums, etc.
away from heat sources such as strong lights, fireplaces, direct sunlight, etc.
on an inside wall (preferably), about 5 feet (1.5 m) above the finished floor, or per code (ANSI, ADA, or local regulation).
Figure 2. Insulating Gasket.
4. Pull about three inches (75 mm) of the cable through the hole in the base plate.
Drywall Mounting (No Rough-in), Typical
1. Mark the center (cable) hole and the mounting hole locations, using the room unit base pl ate as a template. See Figure 2.
2. Drill two 3/16-inch (4.8 mm) mounting holes and mount the two plastic wall anchors flush to below the wall surface for stable mounting of the device.
3. Cut a 1-inch (25 mm) center hole with a hole saw.
NOTE: It is recommended that you use the
optional Insulating Gasket on the back of the Sensor Base for hollow wall installations.
When applying the adhesive-backed gasket to the back of the Sensor Base, orient the gasket so that the cut-out arrow portion of the gasket is in the upper lefthand quadrant of the Sensor Base. The Sensor Base has an UP arrow molded into the surface in the same quadrant location.
NOTE: See Figure 2 for details on optional
Gasket application.
Figure 2. Drywall Mounting (No Rough-in), Typical.
5. Mount the room unit base plate on the wall, noting the "UP" arrow:
NOTE: If required, position the Back Plate
behind the Room Unit Base, aligning the top and bottom mounting holes, prior to mounting to the wall:
a. Install the two mounting screws provided,
but do not tighten.
b. Level the room unit base plate for
appearance.
c. Tighten the two mounting screws to the
room unit base plate.
Page 2 of 3 Siemens Industry, Inc.
Loading...
+ 1 hidden pages