Siemens QPA228.FWNC Series, QPA228.FWSC Series, QAA2280.FWNC, QAA2280.FWSC, QFA3280.FWNC Operator Interface Manual

...
Operator Interface Guide
Room Unit for TEC, and ATEC
Overview
These devices are used with BACnet Terminal Equipment Controllers (TEC), BACnet Actuat or TEC (ATEC) Controll ers, and BACnet Programmable Controllers (PTEC).
Product Numbers
Docume nt No. 125- 703
September 19, 2017
QAA2280.FWNC QPA228x.FWSC QAA2280.FWSC QFA3280.FWNC QPA228x.FWNC QFA3280.FWSC
Accessories
Description Product Number
Passkey 544-643A 25-foot (7.6 m) cable with
connections 50-foot (15.2 m) cable with
connections 100-foot (30.5 m) cable with
connections Replacement Relative
Humidity Sensing Element for QFA and QP A
Replacement Housing Base (QAA, QF A types) Replacement Housing Base
(QPA types) Room Unit Backplate,
10-pack Power Supply (QPA types) Wall Gasket, 10-pack
588-100A
588-100B 588-100C
AQF3060
563-102-01
563-120 AQM2200-INTL
AQM2200 563-102 GSKT KIT
Operation
Operation modes
Figure 1. Operation Modes.
Normal Mode
In Normal Mode, the displ ay is updated with temperature, humi dity, carbon dioxide, and/or occ upied status (all where appl icable) on a set time cycle.
The display shows tem perature in the desired units (as set by the cli pable j umper on the PCA). Depending on the model, the humidity and/or carbon dioxide value(s) will be displayed as well. When multiple variables need to be displayed (temperature, relative humidity, and/or carbon dioxide) the display will cycle through the required values at a rate of one change every three to five seconds.
Page 1 of 4
Document No. 125-703 Operator Interface Guide September 19, 2017
Operation modes, Continued
Occupied Mode
If the TEC is currently in Unoccupied Mode (display shows man outside of the house), pressing the override button (button designated by an image of a man inside a house) results in the display showing the word OCCUPIED and the request is sent to the TEC to override the unoccupied mode. If the TEC does not get overridden, and stays in unoccupied mode, the display on the sensor reverts back to the unoccupied symbol as soon as possible.
If the TEC is currently in occupied mode, pressing the override button flashes the word OCCUPIED, and does nothing else. This functionality is intended solely to let the user know that the butt on press was recognized.
Occupied Mode Unoccupied Mode
Display Display
Setpoint Adjustment Mode
The temperature setpoint is adjusted by using the plus and minus buttons. The resulting changes in setpoint are displayed on t he di spl ay in 1.0°F or 0.5°C increments.
The setpoint adjustment will display for three seconds. If, during those three seconds, a setpoint button is pressed again, the setpoint will be adjusted accordingly and be displayed, and t he three- second count down will restart. If there is no user input for more than three seconds, the room unit will return to Normal Mode.
Press the plus/minus buttons t o scroll through the various options available for each parameter to display the desired option.
Press the occupancy override button again to move to the next user adjustable parameter.
When fi nished, remove the passkey f rom t he HMI port. User setti ng changes will be saved when the passkey is removed.
Figure 2. Inserting the Passkey.
NOTE: When the passkey is plugged i n,
communication between the room unit and the TEC is disabled. See note in Laptop Pass-thru Mode section for more information.
Settings
Set Pt Disp - determines how the user views the
temperature setpoint adjustment. The default setting is NUMERIC, and displ ays in degrees. The user can select between a NUMERIC and a GRAPHIC setpoint displ ay.
Set Pt Min - determines the minimum temperature
setpoint value. The default setting is 55°F (12.5°C). The user selects the minimum setpoint the room unit should request. The setpoint limit is ultimately defined in the controller. If the setpoint is displayed graphically as a sliding bar, this sets the left end of the slider bar. The limits are 55°F to the Set Pt Max value. The adj ustm ent step size is 1°F (0.5°C).
Passkey Mode
Insert the passkey in the sensor HMI (Human-Machine Interface) port to setup all of the user functionality listed below. For each parameter, use the following sequence:
Press the occupancy override button to edit the parameter.
Page 2 of 4 Siemens Industry, Inc.
Set Pt Max - determines the maximum temperature setpoint value. The default setting is 95°F (35°C). The user selects the max imum setpoint the sensor should request. The setpoint limit is ultimately defined in the controller. If the setpoint is displayed graphically as a sliding bar, this sets the right end of the slider bar. The limits are Set Pt Min to 95°F (35°C). The adjustment step size is 1°F (0.5°C).
Loading...
+ 2 hidden pages