Siemens PXC-16 Compact, PXC Compact Series, PXC-24 Compact, PXC-36 Compact, PXC Modular Series Technical Reference Manual

PXC Compact Series
Technical Reference Manual
145-172
2018
-09-25 Restricted
Copyright Notice
2
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Copyright Notice
Notice
Document information is subject to change without notice by Siemens Industry, Inc. Companies, names, and various data used in examples are fictitious unless otherwise noted. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Siemens Industry, Inc.
Warning
This equipment generates, uses, and can radiate radio frequency energy. If equipment is not installed and used in accordance with the instructions manual, it may cause interference to radio communications. Equipment has been tested and found to comply within the limits for a Class B digital device pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference. Residential area equipment users are required to take whatever measures necessary to correct the interference at their own expense.
Service Statement
Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation. Siemens Industry, Inc. branch offices and authorized distributors offer Technical Support Programs that will ensure continuous, trouble-free system performance.
For further information, contact your nearest Siemens Industry representative. Copyright 2018 Siemens Industry, Inc.
FCC Regulations
The manual for an intentional or unintentional radiator shall caution the user that changes or modifications not expressly approved by the party responsible could void the user’s authority to operate the equipment.
For a Class B digital device or peripheral, the instructions furnished the user shall include the following or similar statement, placed in a prominent location in the text of the manual:
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not in­stalled and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
Copyright Notice
3 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
To the Reader
Your feedback is important to us. If you have comments about this manual, please submit them to: SBT_technical.editor.us.sbt@siemens.com
Credits
APOGEE, APOGEE GO, InfoCenter Administrator, InfoCenter Report Manager, InfoCenter Server, InfoCenter Suite, and Insight are registered trademarks of Siemens Industry, Inc.
Desigo® and Desigo® CC™ are registered trademarks of Siemens Schweiz AG. Other product or company names mentioned herein may be the trademarks of their
respective owners. Printed in the USA.
Cyber security disclaimer
Siemens provides a portfolio of products, solutions, systems and services that includes security functions that support the secure operation of plants, systems, machines and networks. In the field of Building Technologies, this includes building automation and control, fire safety, security management as well as physical security systems.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art security concept. Siemens’ portfolio only forms one element of such a concept.
You are responsible for preventing unauthorized access to your plants, systems, machines and networks which should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. Additionally, Siemens’ guidance on appropriate security measures should be taken into account. For additional information, please contact your Siemens sales representative or visit
https://www.siemens.com/global/en/home/company/topic-
areas/future-of-manufacturing/industrial-security.html.
Siemens’ portfolio undergoes continuous development to make it more secure. Siemens strongly recommends that updates are applied as soon as they are available and that the latest versions are used. Use of versions that are no longer supported, and failure to apply the latest updates may increase your exposure to cyber threats. Siemens strongly recommends to comply with security advisories on the latest security threats, patches and other related measures, published, among others, under
https://www.siemens.com/cert/en/cert-security-advisories.htm
.
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
4
| 100
Table of Contents
Cyber security disclaimer ................................................................................................ 3
Compact Series Product Overview ............................................................................. 7
Compatibility with the APOGEE Automation System ...................................................... 7
BACnet Protocol Compatibility .............................................................................. 8
TCP/IP Protocol Compatibility ............................................................................... 8
Required IP Addresses .......................................................................... 8
Device Registration ................................................................................ 8
Address Assignment .............................................................................. 8
System Program .............................................................................................................. 9
Minimum Firmware Revision Required ............................................................... 10
License Manager ................................................................................................. 10
Purpose of Licenses ............................................................................ 11
Supported Point Types .................................................................................................. 12
PXC Compact Series, Rev 1 Hardware, Point Types ......................................... 14
16- and 24-Point Compact Series Diagram ................................................................... 15
36-Point Compact Series Product Diagram .................................................................. 17
Hardware Features ................................................................................................... 19
24 Vdc External Sensor Power Source ......................................................................... 20
Shield Termination .............................................................................................. 20
Custom Sensor Support ...................................................................................... 21
Memory .......................................................................................................................... 21
Flash Read-Only Memory (Flash ROM) .............................................................. 22
Compressed ROM ............................................................................... 22
Auto-Restore and Database Backup to Flash ..................................... 22
Auto Save ............................................................................................ 23
File System Operations........................................................................ 23
Random Access Memory (RAM) ......................................................................... 23
Compact Series Backup Batteries ................................................................................. 23
AA Battery ........................................................................................................... 24
AA Battery ........................................................................................................... 25
Coin Cell Battery ................................................................................................. 26
Coin Cell Battery ................................................................................................. 27
Memory Size and Typical Battery Backup Time ................................................. 28
Compact Series Specifications ...................................................................................... 28
Sensor Limits ....................................................................................................... 33
Communication Connections ......................................................................................... 33
HMI and Tool Ports ............................................................................................. 34
Pin-Out Diagrams for HMI Connectors ................................................ 35
10B/100B Ethernet Port ...................................................................................... 36
5 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
RS-485 Port ......................................................................................................... 36
FLN Support ......................................................................................... 37
PXC Compact on P1 ............................................................................ 38
PXC Compact on P1 ............................................................................ 38
Virtual AEM .......................................................................................... 38
Virtual AEM .......................................................................................... 38
USB Host Port ..................................................................................................... 39
TX-I/O Island Bus ................................................................................................ 39
HOA (Hand-Off-Auto) Upgrade Kits .............................................................................. 39
HOA Specifications ............................................................................................. 40
Hardware Features.............................................................................................. 40
Default Mapping .................................................................................................. 40
Communication ................................................................................................... 41
Using the HOA Switches ..................................................................................... 42
PXC Compact on P1 ..................................................................................................... 44
What is a PXC Compact on P1? ......................................................................... 44
P1 Mode Application ........................................................................................... 45
P1 Mode Operation ............................................................................................. 46
P1 Mode Enhanced Field Panel Point Team ...................................................... 47
Tips for P1 Mode ................................................................................................. 48
Backing up and Restoring the PXC Compact Database ..................... 48
Loading Applications with WCIS .......................................................... 48
Merging Multiple Applications into One .ISB File ................................. 48
Using the P1 COMM Panel Team Point .............................................. 48
Miscellaneous ...................................................................................... 49
Referencing Points on the PXC Compact on P1 ................................. 49
Procedures for Advanced Features .................................................................... 49
Adding Unused I/O for PXC Compact on P1 (Optional) ...................... 49
Changing the Point Team Descriptor After Database Conversion ...... 50
Defining an L2SL from a PXC Compact on P1 into the Host Field
Panel 50
Identifying the Hardware Model Used in an Application Design .......... 51
Making Changes to the Original PXC Compact on P1 Database ....... 52
Program to Allow LPACI Points to Count Over the LAO Maximum
Value 53
Real Time Applications in a PXC Compact on P1 ............................... 54
Synchronizing System Time in a PXC Compact on P1 ....................... 58
Default Applications ............................................................................................ 59
Point Database for Application 3916 ................................................................... 60
Point Database for Application 3924 ................................................................... 61
PXM10S/T Product Overview and Description ............................................................. 62
Product Features ................................................................................................. 63
Communication Connections ............................................................... 63
Requirements ...................................................................................................... 63
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
6
| 100
Application Menus ............................................................................................... 64
Operator Display Specifications .......................................................................... 64
Operator Display Layout...................................................................................... 65
Operator Display Menu Tree ............................................................................... 68
Login and Logoff .................................................................................................. 68
Logging In ............................................................................................ 69
Logging Off .......................................................................................... 73
Navigation Menu ................................................................................................. 74
Alarms Application Menu..................................................................................... 75
Points (Command and Release) Application Menu ............................................ 77
Point Monitor Application Menu .......................................................................... 78
Login Application Menu ....................................................................................... 79
Settings Application Menu ................................................................................... 80
Unitary Equipment Controller ........................................................................................ 81
Unitary Equipment Controller Specifications ....................................................... 83
Compact Series Smoke Control Application Requirements ....................................... 86
Example ALN Configuration for Smoke Control Applications ....................................... 87
Service Information .................................................................................................. 88
Electrostatic Discharge .................................................................................................. 88
Ordering Replacement Parts ......................................................................................... 88
Replacing the Batteries ................................................................................................. 88
Reinstalling the Mounting Tabs ..................................................................................... 89
Troubleshooting Compact Field Panels ........................................................................ 90
Analog Input and Analog Output Points .............................................................. 90
BATT LOW LED .................................................................................................. 91
RUN LED ............................................................................................................. 92
TX and RX LEDs ................................................................................................. 92
Communication ................................................................................................... 93
Display ............................................................................................................. 93
Errors ............................................................................................................. 94
Troubleshooting the TX-I/O Island Bus ......................................................................... 94
Troubleshooting the LCD Panel Indications ........................................................ 95
Resetting an I/O Module to Factory Settings ...................................................... 97
Replacing a TX-I/O Plug-in Module ..................................................................... 98
Replacing a TX-I/O Module Assembly ................................................................ 98
Compact Series Product Overview
Compatibility with the APOGEE Automation System
7 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Compact Series Product Overview
The PXC Compact Series operates on the Automation Level Network (ALN) or the Field Level Network (FLN).
When connected to the ALN, the PXC Compact uses a logical point firmware
database to communicate directly with PXC Modulars, MBCs, RBCs, MECs, SCUs, and other nodes on the network.
When connected to the MS/TP FLN, the PXC Compact operates as a third-party
BACnet device.
When the PXC-16 or PXC-24 is connected to the P1 FLN, it operates as a P1
device.
– No license is required when using the PXC Compact as an FLN device. – PXC Compact on P1 displays as a TEC with application range 3000-3899.
The PXC Compact is available with 16, 24, or 36 point terminations. – Selected PXC-24 and PXC-16 models provide an extended temperature range
for the control of rooftop devices.
– Optional hot-swappable HOA (Hand/Off/Auto) Modules for the PXC Compact
Series enable output points to be manually placed into HAND, ON/OFF, or AUTO control.
Support for FLN Devices
Selected models in the PXC Compact Series can support P1 or MS/TP FLN
devices. Those which support FLN devices may require an additional license. Selected models can be purchased with the license already installed.
NOTE:
No license is required when the PXC Compact is being polled as an FLN device on the P1 or MS/TP FLN.
TX-I/O Island Bus Support
The PXC-36 supports the TX-I/O Island Bus, which uses TX-I/O modules to
expand the number of point terminations.
– Selected PXC-36 models require a license to support the TX-I/O Island Bus. – For more information on connecting the PXC-36 to the Island Bus, see the TX-
I/O Island Bus Technical Reference Manual (140-0914).
Compatibility with the APOGEE Automation System
The PXC Compact Series in P2 Mode is fully compatible with and will communicate with all the APOGEE or pre-APOGEE products in your facility. However, PXC Compact Series in P1 Mode is not designed for use on the FLN of a pre-APOGEE field panel.
CAUTION
When working on a network with multiple firmware revisions, always connect to the
operator interface at the field panel with the newest firmware revision. Otherwise, you cannot view features in newer firmware revisions, or the field panel may coldstart.
Compact Series Product Overview
Compatibility with the APOGEE Automation System
8
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
BACnet Protocol Compatibility
APOGEE BACnet is compatible with the BACnet/IP protocol.
CAUTION
When sharing data values from APOGEE P2 (proprietary) field panels to BACnet
devices, the Cross-Trunk Service does not support requests originating from BACnet devices to access points (objects) that reside in APOGEE P2 field panels.
If you plan to share data values from APOGEE P2 field panels with BACnet devices (field panels), you must do one of the following:
Install and enable the Insight BACnet Server Option.
Use PPCL in the APOGEE P2 field panels to command values in the BACnet
devices through the Insight Cross-Trunk service.
APOGEE P2 and BACnet Product Features Order of Implementation
The APOGEE field panel firmware supports the BACnet protocol as follows:
If both the BACnet and APOGEE protocols have a function, the BACnet function is
implemented.
If APOGEE provides a function that the BACnet protocol does not support, the
APOGEE function is retained.
This approach to BACnet implementation retains the APOGEE feature set while providing compatibility with standard BACnet/IP protocol.
TCP/IP Protocol Compatibility
PXC Compact Series controllers with BACnet/IP or Ethernet TCP/IP (P2) ALN provide the following:
100% compatibility with the TCP/IP protocol suite.
Support of Dynamic Host Configuration Protocol (DHCP) and Domain Name
Servers (DNS).
Support and auto detection of 10Base-T and 100Base-TX Ethernet.
Required IP Addresses
APOGEE BACnet/IP or Ethernet TCP/IP (P2) ALN uses:
One IP address per device (field panel or workstation).
One additional shared IP address per ALN for the multicast group (when using
multicast optimization).
Device Registration
Devices register with the DHCP server and Domain Name Server, if either is present.
Address Assignment
IP addresses are dynamically assigned by the DHCP server.
Compact Series Product Overview
System Program
9 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
If an address changes or is not recognized, the field panel firmware lets you release the dynamically assigned IP address and then reconnect the field panel to the DHCP server, accepting a new IP address assignment in the process.
If there is no DHCP server at the site, you must manually assign static IP addresses as part of the startup system configuration.
Physical Addressing
Each device on the BACnet/IP or Ethernet TCP/IP (P2) ALN has a hard-wired MAC address, which is printed on the product label.
Port Numbers
The default TCP/IP port number for APOGEE BACnet/IP or Ethernet TCP/IP (P2) ALN communications is
5033. You can change the TCP/IP port number if necessary.
NOTE:
All devices on the network must use the same TCP/IP port number.
The default TCP/IP port number for Virtual AEM communications is 3001. You must specify a UDP port number when using multicast optimization. The default
UDP port number is
8.
Network Bandwidth
BACnet/IP or Ethernet TCP/IP (P2) ALN does not add significantly to your network overhead. Burst conditions for this product occur during:
Database downloading after coldstart.
Database uploading.
Trend data uploading.
Burst of alarms or COVs.
Data Exchange
BACnet/IP or Ethernet TCP/IP (P2) ALN sends and receives APOGEE data in TCP/IP packets.
BACnet/IP or Ethernet TCP/IP (P2) ALN synchronizes global data between all devices. Each device runs a global data replication engine that communicates with peer devices to:
Exchange new and changed global data.
Resolve conflicts when data does not match.
Device Naming Conventions
Field panel DNS node names are limited to 30 characters and cannot contain spaces.
Network Security
BACnet/IP or Ethernet TCP/IP (P2) ALN uses your intranet security within the firewall and a username/password combination to restrict access outside the firewall. You can use VLAN to improve internal security.
System Program
The PXC Compact contains a non-volatile system program called
firmware
, which can
be upgraded in the field. The firmware is stored in Flash ROM memory, which keeps it
Compact Series Product Overview
System Program
10
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
virtually immune to all forms of power fluctuations or failure, including battery failure. For more information on Flash ROM memory, see Memory [➙ 21].
General functionality of the firmware includes:
Executing control programs.
Communicating between other field panels and the workstation.
Monitoring points.
Managing point-related information.
Keeping track of real time (both clock and calendar time).
Executing self-test and error detection in the PXC Compact.
Minimum Firmware Revision Required
The APOGEE Field Panels Configuration and Sizing Guidelines (145-214) outlines the minimum firmware revision required for support of a specific feature with the PXC Compact Series.
License Manager
The licenses used to activate features are associated with a specific field panel through the ID_STRING. The ID_STRING uniquely identifies a piece of hardware; it is burned into the field panel’s EEPROM and read by software and firmware.
The ID_STRING is composed of the panel's part number, revision, year and week of manufacture, and serial number. Therefore, a license for one field panel will not work on another field panel. Information for the ID_STRING can be found:
Printed on a label adhered to the outside of the field panel,
Printed on a label adhered to the outside of the field panel shipping box, or
Burned into the field panel’s non-volatile memory and read through Commissioning
Tool (CT), Insight software, or the field panel HMI.
For PXC-36 field panels that include FLN support, a default license named FLNNode36_254 displays in the field panel configuration.
CAUTION
Licensed FLN support only works if the correct license is loaded on the field panel.
An FLN license for PXC-16 and PXC-24 field panels supports 32 FLN devices.
For field panels that include island bus support, a default license named TXIOExp_8 displays in the field panel configuration.
NOTICE
PXC Compact Series models with Island Bus support allow four TX-I/O modules.
See the APOGEE Field Panels Configuration and Sizing Guidelines (145-214) for more information on applications and functionality that can be activated through License Manager.
See the License to enable SNMP Agent on Siemens Modular or Compact hardware with BACnet Firmware Revision 3.2.3
(LSM-SNMP) for information on adding licensed
applications or functionality.
Compact Series Product Overview
System Program
11 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Purpose of Licenses
The use of licenses and features allows added flexibility for customers. Because many features add functionality to a field panel’s firmware, a single part number can be ordered and installed. Additional functionality can be added at a later date without the need to replace the hardware or perform a firmware flash.
Example
A PXC-16 or PXC-24 field panel with an FLN Expansion Module is installed on the ALN to serve as a director for FLN devices; it only passes information about FLN devices to other ALN devices. The customer orders product number PXC36-E.A, which does not provide FLN support or TX-I/O island bus support.
Two years later, the customer decides to add physical points. By adding the TX-I/O island bus license, the PXC-16 or PXC-24 is converted to product number PXC16.2­EF.A or PXC24.2-EF.A which provides FLN and TX-I/O island bus support. Without replacing the PXC-16 or PXC-24 hardware or firmware, the customer can now install TX-I/O modules and expand the number of physical points.
Compact Series Product Overview
Supported Point Types
12
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Supported Point Types
The PXC Compact Series provides software-configurable and dedicated points. The point types and their possible configurations are shown in the following tables.
PXC-16 Supported Point Types.
Configurable Points
Dedicated Points
Point Type
Universal Input (UI) Points 1-3
Universal Input/Output (U) Points 4-8
Analog Output (AO) Points 9-11
Digital Input (DI) Points 12-13
Digital Output (DO) Points 14-16
Analog Input
4
Voltage 0 to 10 Vdc
Current 4 to 20 mA
RTD Pt 1K1
RTD Ni 1K2
Thermistor 10K NTC3
Thermistor 100K NTC3
Digital Input
Status (Binary Input)
Pulse Accumulator (Counter)
Analog Output
Voltage 0 to 10 Vdc
Digital Output
Binary/Digital Output
1)
Platinum 1K 375 or 385 alpha.
2)
Siemens, Johnson Controls, and DIN Standard Nickel.
3)
10K and 100K Type 2 and 10K Type 3.
4)
Sensor supply 24 Vdc, 4.8W
PXC-24 Supported Point Types.
Configurable Points
Dedicated Points
Point Type
Universal Input (UI) Points 1-3
Universal Input/Output (U) Points 4-12
Super Universal (X) Points 13-16
Analog Output (AO) Points 17-19
Digital Output (DO) Points 20-24
Analog Input
5
Voltage 0 to 10 Vdc
Current 4 to 20 mA
RTD Pt 1K1
RTD Ni 1K2
Thermistor 10K NTC3
Thermistor 100K NTC3
Digital Input
Status (Binary Input)
Pulse Accumulator (Counter)
Compact Series Product Overview
Supported Point Types
13 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
PXC-24 Supported Point Types.
Configurable Points
Dedicated Points
Point Type
Universal Input (UI) Points 1-3
Universal Input/Output (U) Points 4-12
Super Universal (X) Points 13-16
Analog Output (AO) Points 17-19
Digital Output (DO) Points 20-24
Analog Output
Voltage 0 to 10 Vdc
Current 0 to 20 mA
Digital Output
Binary/Digital Output
4
1)
Platinum 1K 375 or 385 alpha.
2)
Siemens, Johnson Controls, and DIN Standard Nickel.
3)
10K and 100K Type 2 and 10K Type 3.
4)
Requires an external relay.
5)
Sensor supply 24 Vdc, 4.8W
PXC-36 Supported Point Types.
Configurable Points
Dedicated Points
Point Type
Super Universal (X) Points 1-6
Universal Input/Output (U) Points 7-24
Digital Input (DI) Points 25-28
Digital Output (DO) Points 29-36
Analog Input5 Voltage 0 to 10 Vdc
Current 4 to 20 mA
RTD Pt 1K1
RTD Ni 1K2
Thermistor 10K NTC3
Thermistor 100K NTC3
Digital Input Status (Binary Input)
Pulse Accumulator (Counter)
Analog Output
Voltage 0 to 10 Vdc
Current 0 to 20 mA
Digital Output
Binary/Digital Output
4
1)
Platinum 1K 375 or 385 alpha.
2)
Siemens, Johnson Controls, and DIN Standard Nickel.
3)
10K and 100K Type 2 and 10K Type 3.
4)
Requires an external relay.
5)
Sensor supply 24 Vdc, 4.8W
Compact Series Product Overview
Supported Point Types
14
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
PXC Compact Series, Rev 1 Hardware, Point Types
NOTE:
The following tables are for Revision 1 PXC Compact Series hardware.
16-Point PXC Compact Controller Connector Range and Supported Point Types—Revision 1 Hardware.
Physical Point Address
Point Type
Analog Inputs
Digital Inputs
Analog
Outputs
Digital Inputs
Voltage
Current
RTD
NTC
Thermistor
Status
(Binary
Supply)
Pulse
Accumulator
(Counter)
Voltage
Binary/
Digital
Output
0 to 10
Vdc
4 to 20
mA
PT 1K
(375)
PT 1K
(385)
Ni
1Ka
10Kb
100Kb
0 to 10
Vdc
UI 1 - 3
Universal Input (configurable)
U 4 – 8
Universal Input/Output (configurable)
AO 1 – 3
Voltage Analog Output (AOV), dedicated
DI 1 – 2
Digital Input, dedicated
DO 1 – 3
Digital Output, dedicated
a) Landis & GYR Nickel 1000.
b) Type 2.
24-Point PXC Compact Controller Connector Range and Supported Point Types—Revision 1 Hardware.
Physical Point Address
Point Type
Analog Inputs
Digital Inputs
Analog
Outputs
Digital Inputs
Voltage
Current
RTD
NTC
Thermistor
Status
(Binary
Supply)
Pulse
Accumulator
(Counter)
Voltage
Binary/
Digital
Output
0 to 10
Vdc
4 to 20
mA
PT 1K
(375)
PT 1K
(385)
Ni
1Ka
10Kb
100Kb
0 to 10
Vdc
UI 1 - 3
Universal Input (configurable)
U 4 – 16
Universal Input/Output (configurable)
AO 1 – 3
Voltage Analog Output (AOV), dedicated
DO 1 – 5
Digital Output, dedicated
a) Landis & GYR Nickel 1000.
b) Type 2.
Compact Series Product Overview
16- and 24-Point Compact Series Diagram
15 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
16- and 24-Point Compact Series Diagram
NOTE: The USB device port is now functional. It requires a computer device driver and standard computer terminal software, available on Standard Apps).
PXC-16 and PXC-24 Features, Symbols, and Status LEDs.
Terminal Block Connection
Label
Indicates
1
24V
~
Supply voltage, 24 Vac input.
2
System neutral.
3
Functional earth.
4 through 12 (PXC-16) 4 through 18 (PXC-24)
Digital Output relay, Normally Closed (NC), Common (C), Normally Open (NO).
A (22 through 24)
+ –
RS-485 port.
B
10B/100B Ethernet port.
C
USB Device port. Supports a generic serial interface for an HMI or Tool connection. Does not support firmware flash upgrades.
25, 27, 28
Universal Input (+) (UI1 through UI3).
26, 29
Signal Common.
30, 31, 33, 34, 36
Universal Input/Output (+) (U4 through U8).
Compact Series Product Overview
16- and 24-Point Compact Series Diagram
16
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
PXC-16 and PXC-24 Features, Symbols, and Status LEDs.
Terminal Block Connection
Label
Indicates
37, 39
24 Vdc external sensor power (+) source.
38, 40
Signal Common.
41, 43, 44, 46
Universal Input/Output (+) PXC-24 only (U9 through U12).
42, 45
Signal Common (PXC-24 only).
47, 49, 50, 52
Super Universal Input/Output (+) PXC-24 only (X13 through X16).
48, 51
Signal Common.
53, 55, 57
Analog Output (+) (PXC-16: AO9 through AO11; PXC-24: AO17 through AO19).
54, 56
-
Signal Common.
58, 60
Digital Input (+) PXC-16 only (DI12 through DI13).
59
Signal Common (PXC-16 only).
D
HMI
Human-Machine Interface port (RS-232 8-N-1 signal, RJ-45 8 pin connector, service only, will not dial out.)
Status LEDs
RUN LED
RUN
(green)
ON - Normal steady Green, unit is powered and running. May briefly flash while processor is booting.
OFF - Error.
24 Vac input is not present.
Power is ON, but the application firmware has not booted.
FAULT LED
FAULT
(red)
(for future use)
Normal Off, not currently implemented. May be Red if processor does not complete boot.
LOW BATT LED
LOW BATT
(red)
ON -
Error. RAM Battery (AA) is dead, low, missing or shipping
tab is not removed.
OFF - Normal operation.
Ethernet COMM LED
COMM
(yellow)
(BACnet/IP or
Ethernet TCP/IP
(P2) only)
ON - Linked to Ethernet hub.
OFF - No link to Ethernet hub.
RS-485 TX
RS-485 TX
(yellow) (RS-485
only)
Flashing - Transmitting information over the RS-485, RS-485 P2 or BACnet MS/TP ALN or P1 or MS/TP FLN (depending on how the port is defined).
OFF or ON solid - No device, no connection, or bad connection.
RS-485 RX
RS-485 RX
(yellow) (RS-485
only)
Flashing - Receiving information over the RS-485, RS-485 P2 or BACnet MS/TP ALN or P1 or MS/TP FLN (depending on how the port is defined).
OFF or ON solid - No device, no connection, or bad connection.
PXC-16: DO 14 through DO 16; PXC-24: DO 20 through DO 24
DO
XX
ON - Relay Energized.
Compact Series Product Overview
36-Point Compact Series Product Diagram
17 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
36-Point Compact Series Product Diagram
PXC-36 Features, Symbols, and Status LEDs.
Terminal Block Connection
Label
Indicates
1
24V
~
Supply voltage, 24 Vac input.
2
System neutral.
3
Functional earth.
4 through 27
Digital Output relay, Normally Closed (NC), Common (C), Normally
Open (NO).
A
10B/100B Ethernet port.
B
USB Device port. Supports a generic serial interface for an HMI or Tool connection. Does not support firmware flash upgrades.
30, 32, 33, 35, 36, 38
Super Universal (+). (X1 through X6)
31, 34, 37
Signal Common.
39, 41, 50, 52, 53, 55, 56, 58, 59, 61, 62, 64, 65, 67, 68, 70, 71, 73
Universal Input/Output (+). (U7 through U24)
40, 51, 54, 57, 60, 63, 66, 69, 72
Signal Common.
42, 44, 46, 48
24 Vdc external sensor power (+) source.
Compact Series Product Overview
36-Point Compact Series Product Diagram
18
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
PXC-36 Features, Symbols, and Status LEDs.
Terminal Block Connection
Label
Indicates
43, 45, 47, 49
Signal Common.
74, 76, 77, 79
Digital Input (+) (DI25 through DI28)
75, 78
Signal Common
82 through 84
CD CS
Island Bus Communication
85 through 87 and 88 through 90
+ –
RS-485 port.
C
USB Host port
D
HMI
Human-Machine Interface port (RS-232 8-N-1 signal, RJ-45 8 pin connector, service only, will not dial out.)
Status LEDs
RUN LED
RUN
(green)
ON - Normal steady Green, unit is powered and running. May briefly flash while processor is booting.
OFF - Error.
24 Vac input is not present.
Power is ON, but the application firmware has not booted.
FAULT LED
FAULT
(red) (for future
use)
Normal Off, not currently implemented. May be Red if processor does not complete boot.
LOW BATT LED
LOW BATT
(red)
ON - Error. RAM Battery (AA) is dead, low, missing or shipping tab is not removed.
OFF - Normal operation.
COMM LED
COMM
(yellow)
(BACnet/IP or Ethernet
TCP/IP (P2) only)
ON - Linked to Ethernet hub.
OFF - No link to Ethernet hub.
RS-485 TX
A TX
(yellow)
Flashing - Transmitting information over RS-485 P1 (FLN 1) or MS/TP FLN.
B TX
(yellow)
Flashing - Transmitting information over , RS-485 P2 or BACnet MS/TP ALN or P1 or MS/TP FLN (depending on how the port is defined)..
A TX or B TX
OFF or ON solid - No device, no connection, or bad connection.
RS-485 RX
A RX
(yellow)
Flashing - Receiving information over RS-485 P1 (FLN 1) or MS/TP FLN.
B RX
(yellow)
Flashing - Receiving information over , RS-485 P2 or BACnet MS/TP ALN or P1 or MS/TP FLN (depending on how the port is defined).
A RX
or
B RX
OFF or ON solid - No device, no connection, or bad connection.
DO 29 through DO 36
DO
XX
ON - Relay Energized.
Hardware Features
36-Point Compact Series Product Diagram
19 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Hardware Features
CAUTION
Adjacent point connections on the PXC Compact Series share a Common
connection. See the Figure,
Common and Sensor Power Connections
.
NOTE:
The common for input and output analog points is floating and is not connected to the common of the 24 Vac input.
Figure 1: Compact 16/24 Shared Ground Connections.
Hardware Features
24 Vdc External Sensor Power Source
20
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Figure 2: Compact 36 Shared Ground Connections.
24 Vdc External Sensor Power Source
The 24 Vdc Sensor Power source on the PXC Compact should only be used to supply power to sensors. No accessories of any kind can be powered by this connector.
For powering actuators, use either the 24V ACTUATORS connector on the Service Box or an external power supply.
Shield Termination
Terminating shield on the enclosure is the preferred method. The "-" termination next to the 24 Vdc sensor power termination may be used as either a ground for the power or as a cable shield connection. "-" is not connected to earth ground.
Hardware Features
Memory
21 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Custom Sensor Support
In both P2 Mode (ALN device) and P1 Mode (FLN device), the PXC Compact supports three custom sensor inputs for the AI points: Johnson Controls Nickel 1000, DIN Standard Nickel 1000, and Thermistor 10K Type 3. These sensors display as an option under the Sensor type HMI prompt when entering an AI point at the HMI.
>Sensor type : ­> 1) I ( Current ) > 2) V ( Voltage ) > 3) P ( Pneumatic ) > 4) T ( Thermistor 100K ) > 5) O ( Thermistor 10K ) > 6) S ( Thermistor 10K Type 3 ) > 7) M ( RTD 1K Platinum 375 ) > 8) R ( RTD 1K Platinum 385 ) > 9) N ( RTD 1K Nickel )
> 10) J ( RTD 1K Nickel JCI ) > 11) D ( RTD 1K Nickel DIN )
> 12) L ( L-Type ) > 13) C ( Custom ) Enter option # or <C> for Cancel> 1-
For the two RTD sensors, use the following updated
Intercept Adjustments
table to
create the value entered at the > Wire resistance adjustment : prompt.
Intercept Adjustments.
RTD Type and temperature coefficient1
Intercept Formula for Fahrenheit
2 3
Intercept Formula for Celsius
2 4
(M) RTD 1K Platinum 375 I - (R × ft)/2.117 I - (R × m)/3.8102
(R) RTD 1K Platinum 375 I - (R × ft)/2.171 I - (R × m)/3.9080
(N) RTD 1K Nickel I - (R × ft)/2.459 I - (R × m)/4.427
(J) RTD 1K Nickel JCI I - (R × ft)/2.9667 I - (R × m)5.3400
(D) RTD 1K Nickel DIN I - (R × ft)/3.0589 I - (R × m)5.5060
1)
Intercept Formula uses average temperature coefficient for the sensor connected.
2)
Resistance (R) is from the wire specification or the typical wire resistance table.
3)
I is for the intercept from the field panel Slope/Intercept table and ft is the wire length in feet.
4)
I is for the intercept from the field panel Slope/Intercept table and m is the wire length in meters.
Memory
The APOGEE firmware (program), its point database, PPCL program, trend data, and other information reside in the field panel memory. Memory consists of two areas: Flash Read-Only Memory (Flash ROM) and Random Access Memory (RAM).
Hardware Features
Memory
22
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Flash Read-Only Memory (Flash ROM)
Flash Read-Only Memory (Flash ROM) is the non-volatile, permanent memory of the PXC Compact, which stores the operating system, the APOGEE firmware, and the language files. A limited amount of secondary storage is provided in Electrically Erasable Programmable Read-Only Memory (EEPROM) for the field panel address or name, communication speeds, and other set-up parameters. In the event of a power surge, a power loss, or failure of the battery backup, the Flash ROM and EEPROM contents stay intact.
PXC Compact Flash ROM size cannot be upgraded in the field.
Compressed ROM
The PXC Compact has a large amount of high performance RAM. To allow for future features and to provide high system performance, the APOGEE firmware is stored in ROM in a compressed state; it is de-compressed into RAM on system power-up. As a result, the entire onboard RAM is not available for the point database, the PPCL program, and trend data.
Auto-Restore and Database Backup to Flash
APOGEE Firmware Revision 2.8.4/3.1 and later supports Auto-Restore and Database Backup to Flash.
Database Backup to Flash allows the user to manually save a copy of the
database in flash memory of the controller.
The field panel may be configured to automatically restore the database from flash
memory after a coldstart.
– When auto-restore is enabled, a coldstart does not result in the same downtime
as with earlier revisions of APOGEE Firmware. Because there is no waiting on a full download from the backup system, the database is restored from flash so quickly that there is little to no downtime. However, the accumulated trend data is deleted from memory.
– Database restoration from flash is disabled by default. – When FLN Mode is selected for the PXC Compact or UEC, database
restoration from flash is automatically enabled.
– When P1 Mode is selected for the PXC Compact, database restoration from
flash is automatically enabled and 128K of memory is reserved for ISB files.
The field panel may be configured to automatically restore the database from flash
memory after a coldstart.
– When auto-restore is enabled, a coldstart does not result in the same downtime
as with earlier revisions of APOGEE firmware. Because there is no waiting on a full download from the backup system, the database is restored from flash so quickly that there is little to no downtime. However, the accumulated trend data is deleted from memory.
– Database restoration from flash is disabled by default.
For procedures on using Auto-Restore and Database Backup to Flash, see the APOGEE P2 ALN Field Panel User's Manual (125-3019) or the APOGEE BACnet ALN Field Panel User's Manual (125-3020).
Hardware Features
Compact Series Backup Batteries
23 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Auto Save
This feature allows the database to be backed up automatically whenever database is changed, instead of being an operator selected function. It does not provide any safeguard and or protection against power loss while the process is underway. However, this feature sends messages to HMI that the auto save operation is in progress or finished.
The feature may be turned on or off using a prompt similar to the existing Autorestore prompt. See the APOGEE BACnet ALN Field Panel User's Manual (125-3020) for more information.
File System Operations
File System Operations provide many features and works on three drives of a field panel.
The following is a list of supported features:
List Drives — list the drives on the field panel where A: is the RAM drive, B: is the
USB drive if attached, and
IFD: is the internal Flash Drive.
Set_drive — identifies the drive that you want to perform other functions on.
listDirectory — lists the files and folders contained on the selected drive.
Change_dir — changes the current directory to allow you to view the contents of
subfolders on the drive.
File_ops — opens up the file control menu which allows you to copy, rename,
delete and move files in the panel. These functions work on the drive that was selected by the Set_drive function.
File_ops/Copy_file — allows you to copy files within a drive or to another drive.
File_ops/Rename_file — allows you to rename a file.
File_ops/Move_file — allows you to move a file within a drive or to another drive.
File_ops/Delete_file — allows you to delete a file.
USB Media Support
Support for USB mass storage devices (Memory sticks or USB hard drives).
Backup of database, storage for graphics, Web Server upgrades
Random Access Memory (RAM)
Synchronous Dynamic Random Access Memory (SDRAM) is the working memory of the PXC Compact. When the PXC Compact has booted and is operating normally, the APOGEE firmware, the PPCL control program, the point database, and trend data have been transferred from Flash ROM. Information stored in RAM, such as the point database or PPCL, may be viewed, modified, deleted, activated, or deactivated from an operator terminal by any high-level authorized user. In the event of a power loss, the contents of RAM are kept intact by a backup battery.
PXC Compact RAM size cannot be upgraded in the field. The program length, number of database points, and number of trend entries is limited
only by available memory.
Compact Series Backup Batteries
The PXC Compact Series contains one non-rechargeable AA (LR6) battery and one non-rechargeable coin cell (BR2032) battery that serve as a power backup in the event
Hardware Features
Compact Series Backup Batteries
24
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
of a power failure. The batteries only discharge during a power loss. They do not recharge.
CAUTION
Only use a 3.6 Volt lithium battery in PXC Compact models with extended
temperature range operation. Only use a 1.5 Volt alkaline battery in standard PXC Compact models.
• The 3.6 Volt lithium battery is designed to operate at both high and low temperature extremes, and it provides a long service life in an extended temperature environment.
• The 1.5 Volt alkaline battery is not guaranteed to provide backup protection in models with extended temperature range operation, even if the controller is operating in a room-temperature environment.
• If a 3.6 Volt lithium battery is used in standard PXC Compact models, the battery quickly discharges and provides much less backup protection than a 1.5 Volt alkaline battery.
AA Battery
CAUTION
Batteries
Failure to change DEAD alkaline battery will eventually result in battery leakage, causing permanent damage and loss of building control.
Failure to change a DEAD lithium battery will result in loss of trend and database if not backed up, causing loss of data or building control.
Establish a preventative maintenance schedule based on expected battery usage and life cycle.
The AA battery maintains databases and volatile data, such as Trend, in RAM
when power to the controller is off.
If reserve power in the AA battery is low, the battery status is reported as LOW or
DEAD and the red LOW BATT LED on the field panel is lit. When this occurs, replace the battery; do not wait until it goes dead.
Using PPCL and the $BATT point, the PXC Compact can be programmed to signal
an alarm printer and an operator terminal with a battery replacement message.
For more information, see the APOGEE Powers Process Control Language (PPCL) User's Manual (125-1896).
Using Auto Restore and Database Backup to Flash
RAM is cleared if the AA battery is dead, disabled, or missing when power to the
field panel is off. In this case, if Auto Restore and Database Backup to Flash have been enabled, the database reloads in RAM when power returns; however, Trend data is lost.
If a power failure lasts longer than the protection offered by the battery, and Auto
Restore and Database Backup to Flash are not enabled, the information stored in RAM must be either reloaded from an Insight workstation, Datamate Base or Datamate Advanced, or entered again by an operator.
Hardware Features
Compact Series Backup Batteries
25 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
AA Battery
CAUTION
Batteries
Failure to change DEAD alkaline battery will eventually result in battery leakage, causing permanent damage and loss of building control.
Failure to change a DEAD lithium battery will result in loss of trend and database if not backed up, causing loss of data or building control.
Establish a preventative maintenance schedule based on expected battery usage and life cycle.
The AA battery maintains databases and volatile data, such as Trend, in RAM
when power to the controller is off.
If reserve power in the AA battery is low, the battery status is reported as LOW or
DEAD and the red LOW BATT LED on the field panel is lit. When this occurs, replace the battery; do not wait until it goes dead.
Using PPCL and the $BATT point, the PXC Compact can be programmed to signal
an alarm printer and an operator terminal with a battery replacement message.
Monitoring the State of the AA Battery
The resident AI point $BATT monitors the state of the AA battery. – Status is reported as ALIVE for a value of 100. – Status is reported as DEAD for a value of 0.
Access BATT from the HMI or PPCL using one of the following: – “!Field panel
<node>
:BATT” for RS-485 P2 or BACnet MS/TP ALN
“!<Node Name>
:BATT” for BACnet/IP or Ethernet TCP/IP (P2) ALN
– “*:BATT” where wildcard is permitted. – The short name $BATT in PPCL.
For more information, see the APOGEE Powers Process Control Language (PPCL) User's Manual (125-1896).
Using Auto Restore and Database Backup to Flash
RAM is cleared if the AA battery is dead, disabled, or missing when power to the
field panel is off. In this case, if Auto Restore and Database Backup to Flash have been enabled, the database reloads in RAM when power returns; however, Trend data is lost.
If a power failure lasts longer than the protection offered by the battery, and Auto
Restore and Database Backup to Flash are not enabled, the information stored in RAM must be either reloaded from an Insight workstation, Datamate Base or Datamate Advanced, or entered again by an operator.
NOTE:
The information stored in RAM may also be reloaded using Commissioning Tool (CT).
If Auto Restore and Database Backup to Flash have been enabled, the AA battery
may be removed from the PXC Compact if there is not a requirement to maintain volatile data, such as Trend, over a power cycle.
Hardware Features
Compact Series Backup Batteries
26
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Coin Cell Battery
The coin cell battery is present on all PXC-36 Compact Series and on Version 2 or later of PXC-16 and PXC-24. The hardware version is indicated in the Product Number as follows:
The number after
PXC16
or
PXC-24
indicates the hardware version. For example,
PXC24
.2-PE.A is Version 2.
No number after
PXC16
or
PXC-24
is Version 1 hardware. For example, PXC24-
PE.A is Version 1.
CAUTION
Batteries
Failure to change a DEAD lithium coin cell battery will result in loss of current time­date, which may cause loss of data or building control.
Establish a preventative maintenance schedule based on expected battery usage and life cycle.
The coin cell battery maintains the current time-date in the Real Time Clock (RTC)
when power to the field panel is off.
There is no physical status on the field panel for a dead coin cell battery.
If the coin cell battery is dead or missing when power is off, then RTC time-date is
reset as follows:
– If the field panel resides on an ALN with an Insight workstation, the Insight
workstation sets the time-date when the field panel returns to the network.
– If the field panel resides on an ALN without an Insight workstation, the time-
date is synchronized with the network time during the next automatic daily time update.
When the PXC Compact is operating in P1 mode, if the coin cell battery is dead or
missing when power is off, RTC time-date is reset to the factory default. RTC time­date and must be set manually or by PPCL to ensure time-date based applications operate as expected.
For more information on time synchronization, see the APOGEE P2 ALN Field Panel User's Manual (125-3019) or the APOGEE BACnet ALN Field Panel User's Manual (125-3020) (125-3019 or 125-3020).
Hardware Features
Compact Series Backup Batteries
27 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Coin Cell Battery
The coin cell battery is present on all PXC-36 Compact Series and on Version 2 or later of PXC-16 and PXC-24. The hardware version is indicated in the Product Number as follows:
The number after
PXC16
or
PXC-24
indicates the hardware version. For example,
PXC24
.2-PE.A is Version 2.
No number after
PXC16
or
PXC-24
is Version 1 hardware. For example, PXC24-
PE.A is Version 1.
CAUTION
Batteries
Failure to change a DEAD lithium coin cell battery will result in loss of current time­date, which may cause loss of data or building control.
Establish a preventative maintenance schedule based on expected battery usage and life cycle.
The coin cell battery maintains the current time-date in the Real Time Clock (RTC)
when power to the field panel is off.
There is no physical status on the field panel for a dead coin cell battery.
If the coin cell battery is dead or missing when power is off, then RTC time-date is
reset as follows:
– If the field panel resides on an ALN with an Insight workstation, the Insight
workstation sets the time-date when the field panel returns to the network.
– If the field panel resides on an ALN without an Insight workstation, the time-
date is synchronized with the network time during the next automatic daily time update.
When the PXC Compact is operating in P1 mode, if the coin cell battery is dead or
missing when power is off, RTC time-date is reset to the factory default. RTC time­date and must be set manually or by PPCL to ensure time-date based applications operate as expected.
For more information on time synchronization, see the APOGEE P2 ALN Field Panel User's Manual (125-3019) or the APOGEE BACnet ALN Field Panel User's Manual (125-3020) (125-3019 or 125-3020).
Monitoring the State of the Coin Cell Battery
Resident AI point BATT2 monitors the state of the RTC oscillator when power is
applied to the field panel either during a coldstart or a warmstart.
– If the oscillator is stopped, BATT2 is set to value 0. – If the RTC oscillator is valid, BATT2 is set to value 100. – Status is reported as DEAD for a value of 0. – Status is reported as OK for a value of 100.
NOTE:
The value of
BATT2
is also set to
100
by a coldstart command. Since the controller is powered and the RTC oscillator does not stop, the value of BATT2 is valid and a time-date reset will not occur.
Hardware Features
Compact Series Specifications
28
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Access BATT2 from the HMI or PPCL using one of the following: – “!Field panel
<node>
:BATT2” for RS-485 P2 or BACnet MS/TP ALN
“!<Node Name>
:BATT2” for BACnet/IP or Ethernet TCP/IP (P2) ALN
– “*:BATT2” where wildcard is permitted.
In PPCL, BATT2 cannot be automatically accessed using the short name $BATT2;
instead, use the full name. That is,
“!Field panel
<node>
:BATT2” for RS-485 P2 or
BACnet MS/TP ALN or
“!<Node Name>
:BATT2” for BACnet/IP or Ethernet TCP/IP
(P2) ALN.
Memory Size and Typical Battery Backup Time
Memory Size and Typical Battery Backup Time.
Compact Model
RAM Flash ROM
Total Memory
Typical Battery Backup RAM and Real Time Clock Data
1
PXC-16 and PXC-24 16 MB 8 MB 24 MB
Non-rooftop models: 180 days (accumulated) Rooftop models: 330 days (accumulated)
PXC-16 and PXC-24 “F” and “F32”
32 MB 8 MB 40 MB
Non-rooftop models (accumulated): 110 days (accumulated) Rooftop models: (accumulated): 200 days (accumulated)
PXC-36 64 MB 16 MB 80 MB 60 days (accumulated)
1)
Installing a coin cell battery provides up to 10 years backup power of the Real Time Clock for non­rooftop applications, and 18 months backup power for rooftop applications. These are typical accumulated times while power is off.
Compact Series Specifications
Dimensions (L × W × D)
PXC-16 and PXC-24
10.7" × 5.9" × 2.45"
(272 mm × 150 mm × 62 mm)
PXC-36
11.5" × 5.9" × 3.0"
(293 mm × 150 mm × 77 mm)
DIN rail (EN 60715 TH 35-7.5, steel)
1.38" × 0.30" × 0.04"
(35 mm × 7.5 mm × 1 mm)
Hardware Features
Compact Series Specifications
29 |
100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Processor, Battery, and Memory
Processor and Clock Speed PXC-16 and PXC-24: Freescale MPC852T, 100 MHz
PXC-36: Freescale MPC885, 133 MHz
Memory PXC-16 and PXC-24: 24 MB (16 MB SDRAM, 8 MB Flash ROM)
PXC-16/24 “F” and “F32”: 40 MB (32 MB SDRAM, 8 MB Flash ROM)
PXC-36: 80 MB (64 MB SDRAM, 16 MB Flash ROM)
NOTE:
See the Configuration and Sizing Guidelines document for supported memory size.
New PXC models will now support high speed 480 Mbps communication (PXC-36 only).
Serial EEPROM 4 KB
Battery backup of Synchronous Dynamic (SD) RAM (field replaceable)
Non-
rooftop Models
AA (LR6) 1.5 Volt Alkaline (non-rechargeable)
PXC-16 and PXC-24: 180 days (accumulated)
PXC-16 and PXC-24 F and F32: 110 days (accumulated)
PXC-36: 60 days (accumulated)
Rooftop (Extended
Temperature) Models
AA (LR6) 3.6 Volt Lithium (non-rechargeable): 90 days (accumulated)
32MB SDRAM Rooftop (lithium): 200 days
16MB SDRAM Rooftop (lithium): 330 days
Battery backup of Real Time Clock
Non-
rooftop Models
10 years (32°F to 122°F (0°C to 50°C))
Coin cell (BR2032) 3 Volt lithium
Rooftop (Extended Temperature) Models
18 months (-40°F to 158°F (-40°C to 70°C))
Coin cell (BR2032) 3 Volt lithium
These are typical accumulated times while power is off.
Communication
BACnet/IP or Ethernet TCP/IP (P2) Automation Level Network (ALN) or BACnet/IP or Ethernet TCP/IP (P2) Floor Level Network (FLN)
10Base-T or 100Base-TX compliant
10 Mbps or 100 Mbps (autoswitching) over Ethernet cable, RJ-45 jack, shielded, 328 ft (100
m) max. from the field panel to the nearest active hub, router, or signal repeater. Up to 100
nodes per BACnet/IP or Ethernet TCP/IP (P2) ALN or FLN.
10Base-
T Connection Requirements
UTP/STP Category 3 or 5 or better cable
100Base-TX Connection Require
ments
UTP/STP Category 5 or better cable
Supports CSMA/CD protocol, compatible with IEEE 802.xx compliant devices.
PXC-36 supports Auto-MDIX
BACnet MS/TP Automation Level Network (ALN)
9600 bps to 115.2 Kbps, up to 10 nodes per MS/TP ALN
RS-485 Automation Level Network (ALN)
1200 bps to 115.2 Kbps over 24-gauge, low capacitance shielded twisted pair cable, 4000 ft
(1220 m) max. @ 57.6 Kbps or less, 3280 ft (1 km) max. @ 115.2 Kbps. Up to 100 nodes per
RS-485 ALN.
Human-Machine Interface (HMI)
Three wire, full-duplex, asynchronous serial RS-232 compliant, 1200 bps to 115.2 Kbps, 8-N-
1, no hardware flow control (Xon/Xoff supported). RJ-45 jack, 50 ft (16 m) max. cable length.
Supports dial-in modem.
Factory-
set HMI Communication Speed
PXC-16 and PXC-24: 9600 bps
PXC-36: 115.2 Kbps
Hardware Features
Compact Series Specifications
30
| 100
Siemens Industry, Inc.
Technical Reference Manual
145-172
Building Technologies
Restricted
2018-09-25
Communication
USB Device port (for non-smoke control applications only)
Prior to June 2013
USB 1.1 (12 Mbps) and 2.0 (480 Mbps), Type B female connector.
Self-powered, does not use or supply USB power.
USB 1.0 (1.5 Mbps) and 1.1 (12 Mbps).
NOTE:
See the
Configuration and Sizing Guidelines
documentation for supported speeds per
controller model.
USB Host port (for ancillary smoke control applications only).
Prior to June 2013
USB 1.0 (1.5 Mbps), 1.1 (12 Mbps), and 2.0 (480 Mbps), Type A female connector.
USB unit loads (5V, 500 mA).
USB 1.0 (1.5 Mbps) and 1.1 (12 Mbps), Type A female connector.
NOTE:
See the
Configuration and Sizing Guidelines
documentation for supported speeds per
controller model..
FLN Support available on selected models, license may be required
RS-485 P1 Field Level Network (FLN)
4800 bps to 38.4 Kbps over 24-gauge, low capacitance shielded twisted pair cable, 4000 ft
(1220 m) max. @ 38.4 Kbps.
PXC-16 and PXC-24: Up to 32 FLN devices supported.
PXC-36: For full-load FLN devices, up to 32 devices per FLN port.
For 1/8-load FLN devices, up to 96 devices per field panel.
BACnet MS/TP Field Level Network (FLN) 9600 bps to 115.2 Kbps
PXC-16 and PXC-24: Up to 32 FLN devices supported.
PXC-36: For full-load FLN devices, up to 32 devices per FLN port.
For 1/8-load FLN devices, up to 96 devices per field panel.
Electrical
Power Requirements 24 Vac ±20% input @ 50/60 Hz
Power Consumption (Maximum) PXC-16: 18 VA @ 24 Vac
PXC-24: 20 VA @ 24 Vac
PXC-36: 35 VA @ 24 Vac
A/D Resolution (analog in) 16 bits
D/A Resolution (analog out) 10 bits
AC Power and Digital Outputs NEC Class 1 Power Limited
Communication and all other I/O NEC Class 2
Digital Input
Dedicated Points
PXC-16:
Points 12-
13
PXC-36:
Points 25-
28
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Does not support counter inputs
Open Circuit Voltage: 24 Vdc
Short Circuit Current: 10 mA
Configurable Points
PXC-16:
Points 1-
8
PXC
-
24:
Points 1-
16
PXC
-
36:
Points 1-
24
Contact Closure Sensing
Dry Contact/Potential Free inputs only
Digital Input (10 ms settling time)
Supports counter inputs up to 20 Hz, minimum
pulse duration 20 ms (open or closed)
Loading...
+ 70 hidden pages