Siemens PE-11C, PE-11T, PE-11 Installation Instructions Manual

These instructions are written in accordance with the installation guidelines of NFPA No. 72, National Fire Alarm Code, and CAN/ULC-S524, The Installation of Fire Alarm Systems.
DETECTOR PLACEMENT
For a clear air, 0 to 4000 ft/min velocity applica­tion, use 30 foot center spacing (900 sq ft) from NFPA Standard 72 Chapter 5 and CAN/ULC-S524 as a starting point for a detector installation layout. This spacing, however, is based on ideal conditions – smooth ceiling, no air movement, and no physical obstructions. In some applications, considerably less area is protected adequately by each smoke detector. In all installations, place the detector on the ceiling, a minimum of 6 inches from a side wall, or on a wall, 6 inches from the ceiling.
Follow the drawings provided or approved by Siemens Building Technologies, Inc. or by its authorized distributors.
See NFPA 72, National Fire Alarm Code, Chapter 5 for additional guidance on special issues such as beamed construction and high stockpiling.
TO AVOID NUISANCE ALARMS:
DO NOT locate the PE-11C/PE-11T detector where excessive smoke concentrations exist under normal conditions, or in areas of prolonged high relative humidity where condensation occurs.
DO NOT locate the PE-11C/PE-11T detector next to an oil burner, kitchen, or garage where exhaust fumes can trigger an alarm. Other causes of false alarms are dust accumulation, heavy concentrations of steam, heavy pipe or cigar smoke, and certain aerosol sprays.
AIR CURRENTS
Before a detector can sense a fire, the products of combustion or smoke must travel from the fire to the detector. Since their travel is especially influenced by air currents, consider the movement of air in the design of the system.
Installation/Wiring Instructions Models PE-11C/PE-11T
Siemens Building Technologies
Fire Safety
P/N 315-095626-6
While combustion products tend to rise, drafts from hallways, air diffusers, fans, etc., may help or hinder the travel of combustion products to the detector. When positioning a detector at a particular location, give consideration to windows and doors, both open and closed, and to influencing air movement. Never install a detector in the air stream of a room air supply diffuser. It is better to position a detector closer to an air return.
SPECIFICATIONS
Environmental
Temperature: 320F (00C) to 1000F (380C). Humidity: Up to 93% RH, non condensing Air Pressure: No effect. Thermal Alarm Temp.: 1350F (570C)
Electrical
Voltage: 16-27 VDC Ripple: 3V peak-to-peak Supervisory Current: 110µA max Alarm Current: 33-50mA Start-up Time: 50 seconds max
DETECTOR WIRING
The PE-11C/PE-11T should be connected as shown in Figure 1 using the separate mounting base, Model DB-11. Follow the control panel wiring connection drawing installed on the inside face of each control panel cover. See DB-11 instruction, P/N 315-094193, for base mounting.
Duplicate wiring information is also in the Installation, Operation, and Maintenance Manual provided
with every control panel. Note any
limitations on t
he number of detectors and restrictions on the use of remote devices permitted for each circuit.
INSTALLATION / REMOVAL OF DETECTOR
TO INSTALL:
• Align LED in detector with LED symbol on base
and insert detector into base.
• Rotate detector counterclockwise while gently
pressing on it until the detector drops fully into base.
2
• Then rotate the detector clockwise until it stops and locks in place. Insert optional locking screw (Order Model LK-11).
TO REMOVE:
• Loosen locking screw, if installed. Then rotate the detector counter clockwise until stop is reached.
• Pull detector out of base.
LED INDICATOR OPERATION
The PE-11C/PE-11T contains an LED indicator capable of flashing either one of three distinct colors: green, yellow, or red. Every seven seconds, the microprocessor based detector checks the following:
for smoke in its sensing chamber
that its smoke sensitivity is within the range
indicated on the nameplate label
that its critical smoke sensing electronics are
operating.
Based on the results of these checks, the LED indicator flashes as follows:
Flash Color
Condition
Flash
Interval
(Seconds)
Green
Normal supervisory operation. Smoke sensitivity is within rated limits.
7
Yellow
Detector requires service (cleaning or repair) or is operating beyond its environmental specifications.
7-30
Red Alarm
No Flashes
Detector is not powered, or requires repair.
-
TESTING AND MAINTENANCE
To assure proper operation of the detector and control panel, it is required that both the Sensitivity test and the Functional test be conducted.
SENSITIVITY TEST
The PE-1C1/PE-11T monitors its smoke sensitivity automatically and requires no test equipment. A green flash of the detector LED about every seven seconds indicates that the smoke sensitivity is within its listed limits.
FUNCTIONAL TEST
To test the detector and control panel for functional operation, use SIEMENS Test Gas, P/N 315-
282747. Follow the instructions on the gas canister label.
CLEANING PROCEDURE
(See Figure 2)
1. Notify the proper personnel that the fire alarm system is being serviced.
2. Remove the detector to be cleaned from its base. (See removal section.)
3. Using a small blade screwdriver, remove the cover from the rest of the detector by releasing the 2 cover tabs located on the outside of the cover. Separate the foam screen from the cover.
4. PE-11C: Remove the labyrinth from the sensing chamber by squeezing the labyrinth sides along the release axis and pulling out.
PE-11T: Carefully remove the labyrinth/ thermal holder assembly being sure not to damage or disconnect the thermal wires.
Figure 1 Installation And Wiring Diagram for PE-11C/PE-11T Conventional Detector
CAUTION:
1. Do not use looped wire under base terminal 5. Break wire run to provide supervision of connection.
2. When a remote relay is used to control a critical system function, the relay and its associated detector and optional module(s) must be the ONLY devices on the initiating circuit.