Model MKB-1 Annunciator/Keypad Module
The Model MKB-1 Annunciator from Siemens Industry, Inc., communicates with the MMB Main Control Board through the System network link. The MKB-1 provides the MXL with its primary control and annunciation.
The MKB-1 has an 80 character, backlit LCD alphanumeric display that continuously updates information about the System status and user defined device messages (See Figure 1). If there are multiple alarms, security conditions, supervisories, and/or troubles, the MKB-1 displays the highest priority event that occurred. The user can see additional event data by pressing the NEXT key. Press the HOLD key at any time to stop the display from scrolling.
There are switches for acknowledging fire alarms (ALARM ACK), silencing audibles (AUD SIL), acknowledging supervisories (SUPV ACK), System troubles (TRBL ACK), and security conditions (SEC ACK). There is also a separate key for resetting the Control Panel (RESET).
The 10 digit numeric keypad allows entry of the three levels of user passwords. It also performs specific menu driven operations as well as programming and maintenance functions.
INSTALLATION
Remove all system power before installation, first battery and then AC. (To power up,
connect the AC first, then the battery.)
Unpack the MKB-1. Inspect the module for such things as integrated circuits (ICs) not firmly seated in their sockets, bent IC pins, connectors not properly installed, dirt, and packing material on the board.
Setting the Network Address
(See Figure 2)
1 . Before installing the MKB-1 panel, set the
network address on S1, the switch on the ANN-1 board located on the back of the MKB-1. Use dipswitches SW1 and SW2 on switch Sl to set the network address of the MKB-1.
2. The MKB-1 module address is always set within network addresses 248 through 251. Set the individual switches as follows:
NOTE: Switches S1-SW3 and S1-SW4 are for
future use. The use of switch S1-SW5 is described below.
Another series of switches located on the MKB-1 allows the user access to the MXL Control menu. There are also System status indicator LEDs. The ALARM and TROUBLE LEDs function even if the main processor fails (See Figure 1).
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-090856-9
3. One supervised MKB-1 must be installed at network address 251. Other supervised MKBs may be at the other addresses.
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
Page 2
To Select Supervision
Mechanical Installation
Use Switch S1-SW5 on the ANN-1 to select or deselect supervision of the MKB-1. If your ANN-1 has a switch with position 1 indicated on the lefthand side, ignore the printing on the switch. SW1 on S1 is at the extreme right-hand side of S1, regardless of any other marking.
To set for supervision:
S1-SW5 = Closed (ON)
To set for non-supervision:
S1-SW5 = Open (OFF)
This supervision is independent of the network address.
The installation kit for the MKB-1 includes:
two nuts two 2 inch standoffs
1 . Mount the MKB-1 inside the main MXL
enclosure by placing the four holes in the mounting bracket over the four studs provided in the enclosure. These studs are placed two above and two below the MMB-1 board (See Figure 2).
When the MKB-1 is in position, it straddles the
middle of the MMB-1, leaving only the field wiring terminals on the MMB-1 exposed.
2. Fasten the MKB-1 bracket in the enclosure using the two 2 inch standoffs provided on top and the two nuts provided at the bottom.
3. Once the MKB-1 is mounted to the enclosure, connect the cable assembly on the back of the MKB-1 to connector P8 on the MMB-1.
Figure 1
MKB-1 Panel
ELECTRICAL RATINGS
tnerruCeludoMCDV5evitcAAm57
tnerruCeludoMCDV42evitcAAm0
tnerruCeludoMCDV42ybdnatSAm6
P/N 315-090856-9
Figure 2
Setting S1 on the ANN-1 Board
Figure 3
Placing the MKB-1 Module in the Enclosure