Siemens MJ-X Troubleshooting Manual

Page 1
MJ-X
Troubleshooting Guide
Siemens Power Transmission & Distribution
Proprietary Information
[AED-000025-04]
Revision History
Document Revision 04: 5 January 98 -
Document number (AED-000025-04) added.
This document was created from an original troubleshooting guide (dated May 93).
Page 2
MJ-X Troubleshooting Guide AED-000025-04
1. Troubleshooting the MJ-X
This document outlines a process for preliminary troubleshooting of the MJ-X. The major objectives are:
1. determine if the fault resides at the MJ-X
2. check for improper jumper arrangements or other easily correctable conditions
3. check for field/customer repairable fault (e.g., bad fuse or Neutralite bulb)
4. If necessary, document problem details for factory repairs.
2. Basic Approach
For efficient troubleshooting, the following basic approach is recommended.
1. Verify configuration (hardware & software.)
2. Make sure the control panel hardware & software support the feature(s) you want to use.
3. (Consult MJ-X software revision documents.)
4. Substitute a known good panel. Check if it duplicates the symptoms. If so, the problem is more
likely with the system or wiring rather than with the MJ-X. (This is not always the case.)
5. Use this troubleshooting guide to isolate and fix the problem if possible. If field fix not feasible,
document problem in detail for factory repair.
The following assumes you are familiar with both the MJ-X operation and the MJ Suitcase Simulator. For further information on these topics, refer to the appropriate user manuals. You also need to be familiar with safety procedures for electrical and electronic equipment.
3. Test Equipment
Siemens recommends the following test equipment: 1) MJ suitcase simulator, 2) True RMS Volt/Amp meter, and 3) PC running MJXplorer.
If using the MJ suitcase tester, connect to the PDS ("jack plug") cable. [As an alternative, provide a nominal 120VAC at the external power banana plugs and a 0-200 mA current source at the PDS C2/E1.] Unless otherwise noted, tests are performed with U2 and P2 at 120 VAC. [E must be connected to E1 at the PDS if the suitcase tester is used for these tests.] {Caution: If using external power, be aware that several of the PDS connections are hot.}
For tap motor direction sensing with the MJ-X, the “J” and “K” jack plug signals must have a minimal resistive load. If you’re not using the MJ simulator, connect load resistors (2.2K 10W) from J to E and K to E at the PDS (jack plug).
3.1. MJ Simulator Overview
The MJ suitcase simulator provides the following test capability: variable voltage sources (for U2 and P2), variable current source (for C2), toggle switch for Straight/Inverted regulator simulation, toggle switch for Inverted Source Side Potential Transformer (SSPT), Neutralite test button, Operations Counter test button, Drag Hands Reset indicator, “J” (Raise) indicator, and “K” (Lower) indicator. With the MJ suitcase simulator, you can simulate forward & reverse power flow, and leading/lagging power factor.
When pressed, the Neutralite and Operations Counter buttons ground (short to “E”) the jack plug signal U12 and U10, respectively. Otherwise, these signals are open. The Drag Hands Reset Indicator lights when the Drag Hands Reset signal (jack plug U11) has a nominal 120VAC. The “J” indicator lights when the jack plug “J” signal has a nominal 120VAC. The “K” indicator lights when the jack plug “K” signal has a nominal 120VAC.
Siemens T&D
LLC
2 version: 5 January 1998
Page 3
MJ-X Troubleshooting Guide AED-000025-04
MJ Simulator Voltage Source Connections: Straight/Inverted Switch
Inverted SSPT Switch
“L” Voltage Source Connection
“S” Voltage Source
Connection Straight Doesn’t matter Jack plug “P2” Jack plug “U2” Inverted INV SSPT Jack plug “U2” Jack plug “P2” Inverted Off Jack plug “U2” none
Toggling the Power Flow Switch from Forward to Reverse changes the voltage-to-current phase relationship from in-phase to 180° out-of-phase, respectively.
For tap motor direction sensing with the MJ-X, the MJ simulator must include load resistors (2.2K 10W) from J to E and K to E. Check if your MJ simulator has these resistors. If your simulator lacks these resistors, add them.
4. Jumper Tables
Make sure standard jumpers for both the power and main processor boards are in place for testing. See tables below.
Power Board Jumper Table
Jumper
Designation
Jumper Connection Jumper
Type
Jumper
Location
Jumper Purpose
JP401 "+P" to "BAL" ("E" gnd) T.B. J405 1-2 For connecting balancing winding JP402 "C" to "C2" T.B. J409 1-2 For connecting external current
meter
JP414 "U" to "U6" T.B. J405
10-11
JP415 "U6" to "U7" T.B. J405
12-13
For external control over tap motor power signals For external control of power for MJ-X's (Auto) Tap Control Relays
JP416 "J21" to "J22" T.B. J405 4-5 For external control of (Auto) Raise
signal ("J") path
JP417 "K21" to "K22" T.B. J405 8-9 For external control of (Auto) Lower
signal ("K") path
(J402),
(J410) (J408) (Version N power boards
External Source to Power Switch
only) Auto Inhibit Input: pulsed or latched
2 pin
header
3 pin
header
J402,
J410
J408:2-3
(pre-prod.
default)
For connecting an external source of "External Power" to SW403 Auto Inhibit Input. For latched: use J408:2-3. For pulsed: use J408:1-2.
(Version N power boards only)
Siemens T&D
LLC
3 version: 5 January 1998
Page 4
MJ-X Troubleshooting Guide AED-000025-04
Main Processor Board Jumper Table
Jumper
Jumper
Location
J104 pins
part of 24
6&8
J110 3 pin
J111 3 pin
J113 3 pin
J115 3 pin
J116 2 pin
J117 2 pin
J118 2 pin
J119 2 pin
J120 2 pin
J121 3 pin
J122 3 pin
J123 2 pin
Type
pin
header
header
header
header
header
header
header
header
header
header
header
header
header
Jumper
Jumper Purpose
Position
IN (SW
Vers.2.03)
Out (SW
Vers.2.10 & up)
Connects DSACK0- to ground. (Indicates to uP that the data bus is 8 bits rather than 16 bits.) This jumper needs to be removed for connecting the test connector (J104) to the Background Debug Mode (BDM) cable/interface.
2-3 1-2: For 128K x 8 Boot Flash device (28F001) at U2.
2-3: For 256K x 8 (any type) device (e.g., 28F020) at U2.
2-3 1-2: For 128K x 8 Boot Flash device (28F001) at U2.
2-3: For 256K x 8 (any type) device (e.g., 28F020) at U2.For
1-2 1-2: For 128K x 8 (or 32K x 8) Static RAM device at U3.
2-3: For 512K x 8 Static RAM device at U3.
1-2 1-2: Reset not asserted.
2-3: Reset asserted. (Connect this momentarily only.)
IN Connects D0 to pull down resistor. This connection is also
made with a trace on the circuit board for pre-production MP.
OUT Connects AGND to (digital) GND. Useful when testing MP
board by itself.
OUT Allows for a remote speaker to be used instead of the on
board speaker. (If remote used, remove on board speaker.)
OUT Connects (digital) GND to chassis, for protection.
IN For pre-production MP boards (version “0P”) only.
Connects data port connector shell to chassis, for protection.
1-2 1-2: For (local) data port wired as a "DCE".
2-3: For (local) data port wired as a "DTE".
1-2 1-2: For (local) data port wired as a "DCE".
2-3: For (local) data port wired as a "DTE".
IN For connecting DCE output handshake signals to local port
data connector (J106). (Out for DTE application.)
Unless otherwise noted, AC voltages are measured referenced to AC return ("E"). DC voltages are measured reference to logic ground (GND). The logic ground is necessarily dc-isolated from the AC return. Avoid connecting the logic ground to “E” or any other AC signals.
Note: The (local) data port should be jumpered as "DCE" for connecting to a terminal device (such as a notebook or laptop computer) when using a straight-through cable. The (local) data port should be jumpered as "DTE" for connecting to a modem when using a straight-through cable. Refer to MJ-X Application Note 5 for further information.
5. Symptom Based Troubleshooting
Apply power and determine trouble symptom. Use Troubleshooting Symptom Tables below. [Find the symptom that most completely describes what you are observing.]
Using MJXplorer, save the present MJ-X configuration and load “default” configuration.
To troubleshoot, use “known working” Power Board, Main Processor (MP) board, and MJ-X overlay. To isolate faults, substitute the known good board/assembly. Make sure the "known good" board/assembly has correct jumpering and configuration.
Siemens T&D
LLC
4 version: 5 January 1998
Page 5
MJ-X Troubleshooting Guide AED-000025-04
5.1. Troubleshooting Overview
Notes
1. Caution: Disconnect power source when removing cover. Observe ESD and safety precautions when performing checks.
2. To isolate a problem, substitute “known good” component (i.e., board assembly, device, or part) and check operation.
3. Refer to Instruction Manual for operating details.
4. For Any “Open Box” troubleshooting, always perform “Not Powering Up—Open Box” checks.
5. Check if 16-pin Terminal Block is seated and its jumpers are secure.
Symptom
Not Powering Up q Power Switch in correct position?
Displays Incorrect or no Characters Indicator(s) won’t light (or won’t turn off)
Keypad fault q Some keys work?
No Source Voltage q “Type” configured correctly? Blown Sensing Fuse?
Calibration Off > 2% (incorrect metering) Cycles “Testing…” q Good power source (80-140 VAC)? See Notes 4&5. >> Isolate to Power or MP board. Calibrate if needed. Tap won’t Raise/ Lower in Auto/Remote
Won’t Raise/Lower in Manual Drag Hands Reset (DHR) Failure Voltage Cal. Terminals: No voltage “Neutralite” off at Neutral
Tap position incorrect (See Notes 4&5.)
Operations Counter not incrementing (See Notes 4&5.) Data Port not communicating
Auto Inhibit Input (T.B.) won’t work Auto Inhibit Output (T.B.) won’t work Term. Block VRC won’t work Time/Date incorrect q Time/Date needs resetting? Battery low?
“Closed Box” {Perform these first}
q Blown Power and/or Sensing fuses? q Blown External Source fuse? q If used, PDS (jack plug) connected properly? q Term. Block (16-pin) seated and jumpers secure? q Good power source (80-140 VAC)?
>> See Note 4 & “Open Box”. See Note 4 & “Open Box”. q Displays (DS1&DS2) seated properly in sockets? q LEDs turn on in-sequence at power-up?
Noà probable overlay failure. Yesà Likely MP fault. >> See Note 4 & “Open Box”.
Yesà probable overlay failure. >> See Note 4 & “Open Box”.
>> See Notes 4&5. q Configuration settings correct (U2, P2,C2 ratios)? >> See Notes 4&5.
q Term. Block (16-pin) seated and jumpers secure? q Auto Inhibit active? Low Current Inhibit active?
Set MJ-X R/A/M switch to Remote. With MJXplorer, perform “Raise/Lower”. Verify J/K signal activates. PDS J/K go active for Manual Raise/Lower attempt? >> See Notes 4&5. q When DHR switch on, U11 has nominal 120VAC? >> See Notes 4&5. For Inverted Reg.s w/o SSPT, there is no “P2”voltage”. >> See Notes 4&5. q Neutralite illuminates with Neutralite Test Switch? Noà probable bad bulb. Yesà continue. q Closing PDS-U12 to E illuminates indicator? If no, probable power board fault. >> See Notes 4&5. q Set MJ-X R/A/M switch to Remote. With MJXplorer,
perform “Raise/Lower”. Raise/Lower sensing OK?
q Configuration error? q Closing PDS-U10 to E increments Operations Count? Yesà configuration error? Noà See “Open Box”.
q Connect data port loopback (pins 2 & 3 shorted). q Run “Backdoor Mode” Data Port Loopback test.
Failsà See “Open Box”. Passesà Check external cabling. Verify internal MJ-X jumpers. q “Backdoor” Auto Inhibit input Test good? Configured correctly? See “Open Box”.
q Configuration error? q Connect “wetted” load to verify. q “Backdoor” VRC input Test good?
q Configured correctly? Auto Inhibit inactive? q “Backdoor Mode” Real Time Clock test good?
“Open Box”
q PROM oriented/seated correctly (no bent pins)? q Connectors mated/seated/oriented properly? q Socketed parts oriented/seated properly? q Fuse connectors mated properly? q Jumpers in correct positions? q Components sheared off or missing? q Charred/damaged parts or circuit board area?
>> Isolate to Power or MP board.
>> Isolate to Display Devices or “other” (MP board).
q Connector J102 mated/seated/oriented properly? q Overlay cable damaged or cut?
>> Isolate to Front Panel Overlay or MP board.
q Connector J102 mated/seated/oriented properly? q Overlay cable damaged or cut?
>> Isolate to Front Panel Overlay or MP board. >> Isolate to Power or MP board.
>> Isolate to Power or MP board. Calibrate if needed.
>> Isolate to Power or MP board. >> Verify Solid State Relay. (Substitute known good part.)
q Switches SW401& SW402 functional? q Switch SW404 functional? q U2/P2 Switch (SW405) functional? q “Backdoor” Mode Neutralite Test good?
q “Backdoor” Mode Op Count Test good? q “Backdoor” Mode Neutralite Test good?
q “Backdoor” Mode Op Count Test good? q “Backdoor” Mode Neutralite Test good?
>> Isolate to Power or MP board. q Verify data port jumpers (J121-123). >> Isolate to MP board.
>> Isolate to Power or MP board.
>> Isolate to Power or MP board. q “Backdoor” VRC input Test good? >> Isolate to Power or MP board. q “Backdoor” Mode Battery Test > 2.4V?
Siemens T&D
LLC
5 version: 5 January 1998
Page 6
MJ-X Troubleshooting Guide AED-000025-04
6. “Alert” Based Troubleshooting
Diagnose system and control panel problems using the Alert Messages and the table below. Rule out “Normal Causes” first. Troubleshoot starting with “Problem Causes” and “What to Check”.
System transients may produce MJ-X Alert messages. If possible, determine if this is the case before proceeding with an in-depth troubleshooting effort.
Alert Name
Low Current
Auto Inhibit Tap Track Error
Neutral Sig. Err Tap Pos ????
Low PT Thresh
Over Current
NV RAM Reset
Low Battery
High Voltage
Not In Auto
R Limit Reached L Limit Reached Self Test Fault Pseudo Manual
Normal Causes Problem Causes What to Check
Load current < low current threshold (cfg.)
Auto Inhibit active via Term. Block or communications Incorrect tap tracking configuration, MJ-X needs to sense Neutral Incorrect tap tracking configuration Incorrect tap tracking configuration, MJ-X needs to sense Neutral
Load Voltage < PT threshold (cfg.)
Load current > over current threshold (cfg.)
PROM update. Electrical transient causes loss of
Battery needs replacing. MJ-X circuit fault (on MP board.) Indicates that it is time to replace the Lithium Battery (on the MP
Load Voltage > high voltage threshold (145 VAC)
Remote/Local-Auto/Local Manual (R/A/M) switch not in Auto Tap position reaches MJ-X Raise Limit (cfg.) Tap position reaches MJ-X Lower Limit (cfg.)
Remote communications control in effect.
Bad C/C2 connections; MJ-X circuit failure
Bad AutoInhibit input contacts; MJ-X circuit failure Bad regulator signals (U10, U12); MJ-X circuit failure (J,K, U10, U12 sense) Bad regulator signal (U12); MJ­X circuit failure (U12 sense) Bad regulator signals (U10, U12); MJ-X circuit failure (J,K, U10, U12 sense)
MJ-X circuit failure (U2/P2 voltage sense circuits)
Static RAM data. (Log & min/max data lost.)
MJ-X circuit failure (U2/P2 voltage sense circuits)
MJ-X sensing for R/A/M Switch inoperative; defective switch
See “Tap Pos ??” Alert See “Tap Pos ??” Alert
See “Tap Pos ??” Alert See “Tap Pos ??” Alert
PROM programmed incorrectly. Bad RAM.
(Rule out “Normal” causes first!)
Caution: Keep current circuit “Closed” while connected to regulator. Measure C/C2 current. Check C/C2 Terminal Block jumper. Check E1 and C2 wiring. Calibrate the current. Perform backdoor-mode test on Auto Inhibit input contacts.
Perform backdoor-mode test on these signals.
Check the Neutral (PDS-U12) and Operations Counter (PDS­U10) inputs using Backdoor-Mode test. May indicate a temporary fault condition (failure to detect a transition within the allowed time window on one of several input lines.) Check the Neutral (PDS-U12) and Operations Counter (PDS-U10) inputs using Backdoor-Mode test. If necessary, substitute in the "known good" power board to isolate the problem to the faulty (board) assembly. This alert does not (necessarily) indicate an MJ-X fault condition. Check to see if this alert condition goes away when both U2 and P2 are above the (configurable) PT Threshold. If condition persists, try substituting in the "known good" power board to isolate the problem to the faulty (board) assembly. This alert does not (normally) indicate an MJ-X fault condition. Check to see if this alert condition goes away when an in-range current (0-200 mA) is applied at C2/E1. If condition persists, try substituting in the "known good" power board to isolate the problem to the faulty (board) assembly. May indicate a temporary fault condition. If condition appears repeatedly, consult factory. Additional surge suppression may be required for your installation.
board.) If condition persists after a good battery is installed, check that the battery was installed properly. If fault persists, substitute "known good" Main Processor board to isolate the problem. May indicate a temporary system fault condition. If condition persists when in-range voltages (90-140 VAC) are applied to both PDS-U2 and PDS-P2 inputs, perform calibration and input voltage test. If condition persists, try substituting in the "known good" power board to isolate the problem to the faulty (board) assembly. Substitute "known good" power board to isolate the problem to the faulty (board) assembly. Check R/A/M switch operation.
Replace PROM. If problem persists, substitute "known good" Main Processor board to isolate the problem. Replace PROM. If problem persists, substitute "known good" Main Processor board to isolate the problem.
Siemens T&D
LLC
6 version: 5 January 1998
Page 7
MJ-X Troubleshooting Guide AED-000025-04
7. Voltage and Current Calibration
Connect an external true RMS meter at the test point(s) for the signal. Apply the nominal calibration voltage or current (per the table). Display the corresponding MJ-X calibration screen; (view these under the <DIAGNOSTICS> menu.) Press the change key, then the up or down arrow to get the displayed value to match the external meter value, then press the Save key.
Signal to Calibrate
U2 PDS -- U2 Voltage Test
P2 PDS -- P2 Voltage Test
ILO PDS -- C2 to E1 C/C2 (J409- 1&2) 10 mA (AC RMS) ILO Cal IMED PDS -- C2 to E1 C/C2 (J409- 1&2) 80 mA (AC RMS) IMED Cal IHI PDS -- C2 to E1 C/C2 (J409- 1&2) 200 mA (AC RMS) IHI Cal
Test Signal Application Point
Test Signal Measurement Point
Terminals
Terminals
Nominal Calibration Signal Magnitude
120 VAC (RMS) U2 Cal SW405 = U2
120 VAC (RMS) P2 Cal SW405 = P2
MJ-X Calibration Screen
Conditions
8. MJ-X Self Tests
At start up, the MJ-X performs several self-tests, including: LED Indicator test, RAM read/write, and PROM checksum.
The start-up LED Indicator test flashes all front panel LEDs three times. If one or more fail to flash, this indicates a problem with the overlay, the overlay cable/connector, or the MJ-X Main Processor board.
The start-up RAM read/write test verifies the MJ-X non-volatile static RAM without effecting RAM­stored non-volatile data (e.g., log and min./max. data). RAM failures produce varying symptoms. For complete failure, the MJ-X program will not run, and the MJ-X will appear “dead” with the exception of display flickering when you power it. For loss of non-volatile data, the MJ-X clears all RAM-stored non­volatile data, and reports this in the Alert message “NV RAM Reset”. The MJ-X also displays the “NV RAM Reset” alert message when the MJ-X detects a program memory (PROM) update or a checksum error.
The MJ-X continuously runs PROM self-tests and reports the results in the <Diagnostics> menu “Checksum” screen. MJ-X reports the checksum as “Pass” or “Fail”. A failed checksum indicates a problem with the PROM.
9. MJ-X Internal Power Supply Signals
If you suspect an internal supply problem, verify the MJ-X power supply circuits per these specifications:
PDS-U2 VDC_U
(J403-7) Vac min vdc max vdc min vdc max vdc min vdc max vdc Min vdc max vdc 90 14 20 4.75 5.25 8 15 8 15 145 32 40 4.75 5.25 18 25 18 25
Note: VISO1+ measured referenced to ISO1GND (J411-2). VISO2+ measured referenced to ISO2GND (J411-4). VCC and VDC_U are measured referenced to (digital) ground (J403- 5&6).
Siemens T&D
LLC
VDC_U (J403-7)
VCC (J403-13)
VCC (J403-13)
7 version: 5 January 1998
VISO1+ (J411-1)
VISO1+ (J411-1)
VISO2+ (J411-3)
VISO2+ (J411-3)
Page 8
MJ-X Troubleshooting Guide AED-000025-04
10. Backdoor Tests
Enter the “Backdoor Test” mode as follows:
1. For MJ-X Main Processor software versions prior to 2.30: Adjust input voltage or the MJ-X Voltage
and Bandwidth setpoints to achieve an in-band condition—i.e., deactivate J and K outputs.
2. Display the "Data Stat = XXXX" screen under the <COMMUNICATIONS> menu.
3. Set the Remote/Auto/Manual (“R/A/M”) Switch to Remote and the U2/P2 Switch to U2.
4. Press the following keys in the order listed: Left Arrow, Right Arrow, Left Arrow, Right Arrow, +/-.
While in the backdoor test mode, the Alert LED blinks continuously (at a slower rate than for the normal product code.) Cycle the power or perform the watchdog test to exit the Backdoor Test mode.
10.1. “Backdoor” Tests
When entering the backdoor test mode, the MJ-X runs automatic checks and displays diagnostic messages if appropriate. The MJ-X displays: "Test Code XXXXXX", where XXXXX is the backdoor test date code.
Keypad Test
Set the Remote/Auto/Manual (“R/A/M”) switch to Remote or Manual. Press any key. The MJ-X displays the key’s name. Press the same key multiple times. The MJ-X alternately displays the key name and a blank screen.
Remote/Auto/Manual Test
Toggle the Remote/Auto/Manual switch. The MJ-X displays the active switch position. For “AL” series MJ-X units only: With the R/A/M switch in the Manual position, toggle the Tap Raise/Lower switch. The
MJ-X displays the Tap Raise/Lower switch position.
Indicator LEDs Test
Set Remote/Auto/Manual (“R/A/M”) switch to Manual. Set Tap Raise/Lower switch to Lower. The Overlay LEDs (except Alert) turn on sequentially from top to bottom. The Alert LED blinks independently at a regular rate. [This test may not always work. Use the Power-on LED test as a substitute.]
Neutral Sense
Short the Neutralite signal (jack plug U12) to “E”. The MJ-X displays "Neutral Pos ON". Remove the “E” ground connection. The MJ-X displays "Neutral Pos OFF".
Operations Counter Sense
Short the Operations Counter signal (jack plug U10) to “E”. The MJ-X displays: "Op Counter ON". Remove the “E” ground connection. The MJ-X displays "Op Counter OFF".
VRC1(2) and Auto Inhibit Sense Test
Short the VRC1(2) terminals. The MJ-X displays "VRC En1(2) ON". Remove the short. The MJ-X displays "VRC En1(2) OFF". Short the Auto Inhibit terminals. The MJ-X displays " Auto Inh ON". Remove the short. The MJ-X displays " Auto Inh OFF".
Display Test
[Set the Remote/Auto/Manual switch to Auto. Press the Bandwidth key.] Turns on all segments, writes test screens, changes brightness, then blanks the character display. This test continues until the Bandwidth key is pressed again or some other key is pressed.
Speaker Test [Set the Remote/Auto/Manual switch to Auto. Press the Voltage Level key.]
Siemens T&D
LLC
8 version: 5 January 1998
Page 9
MJ-X Troubleshooting Guide AED-000025-04
Turns on speaker driver with audio tone. (~ 2 seconds)
Battery Level Test [Set the Remote/Auto/Manual switch to Auto. Press Time Delay.] Displays MJ-X battery voltage.
Local Port (SCI) Loopback Test
[Connect a loopback cable/connector (pins 2 & 3 shorted) to the MJ-X data port. Set the Remote/Auto/Manual switch to Auto. Press the Alert key.] The MJ-X sends a canned message out the data port and verifies that the same message is received back.
Reset Status Register
[Set the Remote/Auto/Manual switch to Auto. Press the Voltage Limit Control key.] The MJ-X reads its MPU reset status register and displays the reset type, abbreviated as: "X" = external, "P" = power up, "W" = watchdog, "H" = halt, "C" = loss of clock, "S" = system, and "T" = test module. The reset types that will normally be observed include "X", "P", and "W". Other types may indicate a problem with the MJ-X. [MJXplorer also reads/displays the Main Processor Reset Status Register.]
Watchdog Test
[Set the Remote/Auto/Manual switch to Auto. Press the Operations Counter key.] The MJ-X discontinues updating the “watchdog timer”, forcing a reset. After resetting, the MJ-X resumes normal product operations (i.e., the backdoor test mode is exited upon reset.)
Serial EEPROM (“SEEP”) Write/Read Test
[Set the Remote/Auto/Manual switch to Auto. Press the Cancel/Reset key.] The MJ-X performs a non-destructive read/write test of the Serial EEPROM. Several memory locations are written and then read back. The MJ-X reports Pass/Fail results.
Serial EEPROM (“SEEP”) Read Only Test
[Set the Remote/Auto/Manual switch to Auto. Press the Change or Save key. See below.] The MJ-X reads/displays the values stored at a particular address within the SEEP. If the Change key is pressed first (to initiate the SEEP read test), the SEEP read address starts at 20 (hex). If the Save key is pressed first (to initiate the SEEP read test), the SEEP read address starts at 30 (hex). Subsequently, pressing the Change key increments the SEEP address by 1. Pressing the Save key increments the SEEP address by 16 (10 hex).
Serial EEPROM (“SEEP”) Erase
[Set the Remote/Auto/Manual switch to Auto. Press the Max/Min key. The MJ-X requests confirmation before proceeding. Be sure you want to do this! Write down the settings for “MP BD VERS” and “PWR BD VERS” before proceeding!]
The MJ-X re-initializes its configuration data to default values for whatever MP software version is loaded into the program memory. After erasing, verify all configuration data. Restore the settings for “MP BD VERS” and “PWR BD VERS”.
Real Time Clock (RTC) Tests
Note: For all RTC tests, set the Remote/Auto/Manual switch to Auto. Press key indicated in “[ ]”.
Read/Write: [Reactance] Reads/writes the RTC Control register. The MJ-X reports pass or fail. Clear RTC Power Sense: [Menu] This performs no meaningful function. Enable RTC Power Sense: [Up Arrow] This performs no meaningful function. Status Register Read: [Down Arrow] The MJ-X displays the hex value for the RTC Status Register. Interrupt Register Read: [Left Arrow] The MJ-X displays the hex value for the RTC Interrupt Register. Control Register Read: [Right Arrow] The MJ-X displays the hex value for the RTC Control Register.
Siemens T&D
LLC
9 version: 5 January 1998
Page 10
MJ-X Troubleshooting Guide AED-000025-04
11. “Backdoor Mode” Summary
1. For MJ-X Main Processor software versions prior to 2.30: Adjust input voltage or the MJ-X Voltage
and Bandwidth setpoints to achieve an in-band condition—i.e., deactivate J and K outputs.
2. Display the "Data Stat = XXXX" screen under the <COMMUNICATIONS> menu.
3. Set the Remote/Auto/Manual (“R/A/M”) Switch to Remote and the U2/P2 Switch to U2.
4. Press the following keys in the order listed: Left Arrow, Right Arrow, Left Arrow, Right Arrow, +/-.
Backdoor Test How to Start Conditions Expected Results
Auto Inhibit Sense Short or Open Term. Block
Battery Level Press Time Delay Key. R/A/M in Auto. Displays battery level. (Good battery reads > 2.4V) Data Port (Loop Back test) Press Alert Key. R/A/M in Auto. Pins 2&3
Display Press Bandwidth Key. R/A/M in Auto. Turns on all segments, writes test screens, changes
Indicator LEDs Raise/Lower switch in
Keypad Press any key. R/A/M in Manual. MJ-X displays key name. Alternately blanks for
Neutral Sense Close/Open jack plug “U12”
Operations Counter Sense Close/Open jack plug “U10”
Remote/Auto/Manual Switch Real Time Clock (RTC) Read/Write Reset Status Register [MJXplorer also reads/displays the MJ-X Main Processor Reset Status Register.] Serial EEPROM Erase
Caution! Causes loss of stored configuration data.
Serial EEPROM Read Only Press Change or Save to start.
Serial EEPROM Read/Write Speaker Press the Voltage Level key. R/A/M in Auto. Turns on speaker driver with audio tone. (~ 2 seconds) Tap Raise/Lower Toggle Raise/Lower Switch. R/A/M in Manual. For AL series units ONLY, the MJ-X displays Tap
VRC1, VRC2 Short or Open Term. Block
Watchdog Press the Operations Counter
Unused tests: (all with R/A/M in Auto) Clear RTC Power Sense—Menu key, Enable RTC Power Sense—Up Arrow key, RTC Status Register Read—Down Arrow key, RTC Interrupt Register Read—Left Arrow key, RTC Control Register Read—Right Arrow key.
contacts.
Lower.
to “E”.
to “E”. Toggle R/A/M switch. MJ-X displays the switch position.
Press the Reactance Key. R/A/M in Auto. Displays pass/fail results of RTC test
Press the Voltage Limit Control key.
Press the Max/Min key. {MJ-X request confirmation}
Subsequent Change key presses increment the address by 1. Pressing the Save key increments the (hex) address by 16. Press the Cancel/Reset key. R/A/M in Auto. Displays pass/fail results of non-destructive Serial
contacts.
key.
“Remote Auto Inhibit” Indicator turns on when contacts closed
shorted for looping back.
R/A/M in Manual. Tap Raise/Lower in Lower.
R/A/M in Auto. Displays last reset type: "X", "P", and "W" are normal.
R/A/M in Auto. Write down “MP BD VERS” and “PWR BD VERS” before proceeding!]
R/A/M in Auto. Pressing Change first initiates the read address to 20 (hex). Pressing Save first initiates the read address starts to 30 (hex).
R/A/M in Auto. MJ-X forces watchdog reset, exits Backdoor mode.
Display toggles from “AutoInh On” to “AutoInh Off”
Displays pass/fail results for data port test (is transmitted message received back?)
brightness, then blanks the character display. Repeats. The Overlay LEDs (except Alert) turn on sequentially from top to bottom. {The Alert LED blinks independently at a regular rate.}
multiple keypresses. Display toggles from “Neutral Pos ON” to “Neutral Pos OFF” Display toggles from “Op Counter ON” to “Op Counter OFF”
Others may indicate an MJ-X problem. [X=external, P=power up, W=watchdog, H=halt, C=loss of clock, S=system, and T=test module.]
Re-initializes configuration data to defaults for
whatever MP software version is loaded into the program memory. After erasing, verify configuration
data. Restore settings for “MP BD VERS” and “PWR BD VERS”. Displays Serial EEPROM binary data.
EEPROM read/write test.
Raise/Lower switch position. Display toggles from “VRC EnN ON” to VRC EnN OFF” (where N = 1 or 2)
************** These need to be included in the next update: *********************** Fault Isolation for:
q Expansion Rack q Communications Module
Siemens T&D
LLC
10 version: 5 January 1998
Loading...