Siemens Milltronics Millpulse 600 Instruction Manual

Page 1
Instruction Manual September 2006
milltronics
MILLPULSE 600MILLPULSE 600
Page 2
Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed.
Qualified Personnel: This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.
Unit Repair and Excluded Liability:
The user is responsible for all changes and repairs made to the device by the user or the user’s agent.
All new components are to be provided by Siemens Milltronics Process Instruments Inc.
Restrict repair to faulty components only.
Do not reuse faulty components.
Warning: This product can only function properly and safely if it is correctly transported, stored, installed, set up, operated, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2006. All Rights Reserved
This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.
While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement.
Technical data subject to change.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Technical Publications at the following address:
Technical Publications Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontario, Canada, K9J 7B1 Email: techpubs.smpi@siemens.com
For a selection of Siemens Milltronics level measurement manuals, go to: www. siemens.com/processautomation. Under Process Instrumentation, select
Measurement
For a selection of Siemens Milltronics weighing manuals, go to: www. siemens.com/processautomation. Under Weighing Technology, select
Weighing Systems
and then go to the manual archive listed under the product family.
and then go to the manual archive listed under the product family.
Level
Continuous
© Siemens Milltronics Process Instruments Inc. 2006
Page 3
Table of Contents
Safety Notes .............................................................................................................................................1
Safety marking symbols ..............................................................................................................1
The Manual ...............................................................................................................................................1
Milltronics Millpulse 600 ..................................................................................................2
Specifications ................................................... ................................................. ..................3
Installation ...........................................................................................................................5
Environment ..............................................................................................................................................5
Wiring .........................................................................................................................................................5
Interconnection ........................................................................................................................................6
Loading .......................................................................................................................................................7
Operation ......... ................................. ..................................... .................................. .............8
Dimensions ..........................................................................................................................9
Application ...... ......................... ..................... ........................ ..................... ........................10
Bucket Elevators ..........................................................................................................................10
Shafts .............................................................................................................................................10
Belt Conveyors .............................................................................................................................11
Screw Conveyors ......................................................................................................................... 11
Cleaning and Maintenance .............................................................................................12
i
Page 4
ii
Page 5
Safety Notes
Special attention must be paid to warnings and notes highlighted from the rest of the text by grey boxes.
1
WARNING1: means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage
Note:
means important information about the product or that part of the operating
manual.
Safety marking symbols
In manual On product Description
Protective Conductor Terminal
Both direct and alternating current
The Manual
Notes:
• Please follow the installation and operating procedures for a quick, trouble-free installation and to ensure the maximum accuracy and reliability of your Millpulse 600.
This manual will help you set up your Millpulse 60 0 for optimum performance. We always welcome suggestions and comments about manual content, design, and accessibility. Please direct your comments to techpubs.smpi@siemens.com
For other Siemens Milltronics process protection manuals, go to: www.siemens.com/processprotection
.
.
WARNING: Millpulse 600 is to be used on ly in th e ma n ner ou tl in e d in
this manual, otherwise protection provided by the equipment may be impaired.
1.
This warning symbol is used when there is no corresponding caution symbol on the product.
7ML19985DG02 Milltronics MillPulse 600 – INSTRUCTION MANUAL Page 1
Page 6
Milltronics Millpulse 600
Milltronics Millpulse 600 is a heavy-duty 2-wire motion sensor that provides a solid state switch output to a PLC reciprocating, or conveying equipment.
Milltronics Millpulse 600 has a circuit card and magnet assembly potted in the probe body and comes complete with mounting flange and locknut. Milltronics Millpulse 60 0 is connected in series with the PLC input (or other load) and acts as a switch, opening and closing as the ferrous targets of the machinery being monitored pass in front of the probe.
1
. It is used primarily for monitoring the speed of rotating,
1.
Milltronics Millpulse 600 is designed to work with Programmable Logic Control­lers (PLC) with input characteristics compatible with the electrical portion of the CENELEC 50040/36/37/38 standards for two wire proximity sensors.
Page 2 Milltronics MillPulse 600 – INSTRUCTION MANUAL 7ML19985DG02
Page 7
Specifications
Switching Capability
• voltage: 18 to 48 V AC/DC +/-10%, 50/60 Hz (Jumper In) 60 to 135 V AC/DC +/-10%, 50/60 Hz (Jumper Out)
• current 5 to 400 mA continuous 2 A surge for 20 msec at 1 operation per second
Voltage Drop
•8 V
Residual Current
•1.5 mA
Fuse
• 1A, 250 V, SLO-BLO, 4.5 x 14.5 mm (not operator replaceable)
Swi tch Dur ation
• on: 50 msec minimum
• off: 50 msec minimum
Operating Limit
• 600 pulses per minute maximum
Operating Temperature
• -45 to 60 °C (-45 to 140 °F)
Display
• red LED for switch status
Construction
• probe body: aluminum
• process mounting: 2” NPSL
• connection box: aluminum 3/4” NPT conduit entrance 4 screw terminals for maximum 12 AWG wire size
• gasketing: neoprene
7ML19985DG02 Milltronics MillPulse 600 – INSTRUCTION MANUAL Page 3
Page 8
Environmental
• location: indoor/ outdoor
• altitude: 2000 m (6 562 ft) max.
• ambient temperature: -45 to 60 °C (-45 to 140 °F)
• max. relative humidity: 80%
• enclosure rating: Type 4/NEMA 4, Type 4X/NEMA 4X, Type 6/NEMA 6, IP67
• installation category: II
• pollution degree: 4
Note:
• The use of approved watertight conduit hubs/glands is required for Type 4/NEMA 4, Type 4X/NEMA 4X, Type 6/NEMA 6, IP67 (outdoor applications).
Weight
• 2 kg (4.4 lbs.)
Approvals
•CE, CSA
• EMC performance available upon request
(C/US)
Page 4 Milltronics MillPulse 600 – INSTRUCTION MANUAL 7ML19985DG02
Page 9
Installation
WARNING: The probe is highly magnetic. Keep it away from magnetosensitive materials such as computer discs an d aud io or video tapes.
Environment
Milltronics Millpulse 600 should be mounted in an area that is within the temperature range specified and that is suitable to the housing rating and materials. The cap should be accessible to allow for wiring and viewing if the status display LED is used.
Milltronics Millpulse 600 should be mounted using the supplied mounting flange, onto a vibration-free structure. The gap between the face of the Milltronics Millpulse 600 and the target should be sufficient so there is no danger of the target damaging the unit. Refer to the chart in the respect to target velocity.
Operation
Note: In climates where direct sunlight may cause the Milltronics Millpulse 600
temperature to rise above the specified limit, shade the unit by installing a sun shield.
Wiring
Note: All wiring must be done by qualified personnel in accordance with all
governing regulations.
section (page 8) for the maximum allowable gap with
Where possible, the probe should be mounted such that the conduit entry is pointing down to avoid accumulation of condensation in the casing. Where wiring must be run in conduit, the use of flexible conduit is suggested for easier removal or adjustment of the probe.
It is advisable to keep the Milltronics Millpulse 600 away from high voltage or current runs, contactors and SCR drives.
WARNING: Do not connect Milltronics Mill pu l s e 6 00 direc t ly to supply.
Ensure that the switching current of the PLC input is above the residual current of the Milltronics Millpulse 600 and that the load resistance presented by the PLC input is low enough to ensure that the minimum operating current of the Milltronics Millpulse 600 is exceeded (see Loading graph). If your PLC does not meet the requirements, a resistor
across the PLC inputs can be used to increase the switching current.
Note:
• The protective earth terminal indicated by must be connected to reliable ground.
7ML19985DG02 Milltronics MillPulse 600 – INSTRUCTION MANUAL Page 5
Page 10
Interconnection
Operating Voltage:
jumper in
18 to 48 V AC/DC
jumper out
60 to 135 V AC/DC
jumper
fuse
1
2
3
4
Milltronics
Millpulse
600
PLC
input/load
Notes:
• The protective earth terminal indicated by must be connected to reliable ground.
• All wiring must be done by qualified personnel in accordance with all governing regulations.
• The equipment must be protected by a 15A fuse or circuit breaker in the building installation.
• A circuit breaker or switch in the building installation, marked as the disconnect switch, shall be in close proximity to the equipment and within easy reach of the operator.
WARNING : All f ield wir ing m ust h ave in sulati on su itable for a t leas t 135 V.
Page 6 Milltronics MillPulse 600 – INSTRUCTION MANUAL 7ML19985DG02
Page 11
Loading
7ML19985DG02 Milltronics MillPulse 600 – INSTRUCTION MANUAL Page 7
Page 12
Operation
Milltronics Millpulse 600 works on the principle of Faraday’s Laws of Electromagnetic Induction. When a ferromagnetic object (target) enters the probe’s permanent magnetic field, it distorts the flux causing it to cut the coil windings, thereby generating a voltage. This voltage is proportional to the speed at which the ferrous target passes through the flux and is inversely proportional to the square of the distance between the target and the probe.
Square profile targets work better than round because they present a sharper transition in ferrous mass. Minimizing the gap is more effective than an increase in target size beyond 5 cm x 5 cm x 2.5 cm (2” x 2” x 1”), except at very low velocities.
The voltage generated from the probe coil is fed to a processing circuit. The processing circuit controls a semiconductor switch that opens and closes in response to the incoming pulses. The switch is normally open (LED off) and closes when a pulse is generated (LED on). The switch duration times are held to a minimum of 50 msec to give the PLC sufficient time to read the switch states.
The amplifier has been tuned for a response typical to the range of speed encountered in industrial applications. This response governs the relationship between target speed and probe to target gap, as demonstrated in the following chart. The resultant curves indicate the maximum velocity is about 33 cm/sec. (65 ft/min), and with a velocity of 1 cm/sec. (2 ft/min), a maximum gap of 3.1 cm (1.25”) is possible.
2"x1"x2"
ferrous target
‘A’
2"x2"x1"
ferrous target
‘B’
2"x1"x1"
ferrous target
‘C’
This graph was plotted from tests using four ferrous blocks set equidistant on a 41 cm (16”) diameter circle on a non-ferrous disc.
Page 8 Milltronics MillPulse 600 – INSTRUCTION MANUAL 7ML19985DG02
Page 13
Dimensions
10-32 screw, 4 places. Tighten
screws to 1.1 to 1.7 N-m (10 to
15 in-lb) of torque
terminal
block
LED
earth/ground
screw (min M4)
3/4” NPT conduit
entrance
DETAIL “A”
2” NPSL
o.d.
133 mm
(5.25”)
cap,
aluminum,
with LED
window
casing, aluminum
cap gasket, neoprene
95 mm (3.75”) dia.
probe clearance hole
226 mm
(8.9”)
locknut, plated
casing gasket, neoprene mounting flange, see detail “A”
aluminum probe
197 mm
(7.75”)
127 mm
(5”)
60mm (2.38”)
2“ NPSL
MOUNTING
6 mm (0.25”) dia. hole for 1/4-20 bolt on 114 mm (4.5”) BCD, 4 places
6 mm (0.25”) dia. hole for 1/4-20 bolt or drill and tap on 114 mm (4.5”) BCD, 4 places
Note: Install safety shields where required.
7ML19985DG02 Milltronics MillPulse 600 – INSTRUCTION MANUAL Page 9
Page 14
Application
Bucket Elevators
ferrous buckets less
than 75 mm (3”)
apart
negligible
side travel
non-ferrous buckets with ferrous bolts or
buckets greater than
75 mm (3”) apart
Milltronics Millpulse 600 side
mounting
Shafts
Milltronics
Millpulse
600
shaft
paddle
Note: Install safety shields where required.
Milltronics Millpulse 600 front or back
mounting
key or keyway
Milltronics
Millpulse 600
shaft
Page 10 Milltronics MillPulse 600 – INSTRUCTION MANUAL 7ML19985DG02
Page 15
Belt Conveyors
ferrous blocks or spoked wheel
Screw Convey ors
idler end
Milltronics
Millpulse 600
clearance and
mounting hole,
Dimensions
See
page 9
,
Milltronics
Millpulse
600
Window Detail
Milltronics
Millpulse
600
Milltronics Millpulse 600
mounting
bracket
Milltronics Millpulse 600 with supplied flange and
locknut
conveyor troughing
bracket
window
plate
Install a non-ferrous window for screw conveyors with troughing over 3 mm (0.125”) thick or for high temperature applications. The dimensions shown for the plate, window, and bracket are the minimum recommended. Use series 300 stainless steel, brass, or aluminum. Milltronics Millpulse 60 0 must not touch the plate if temperatures are in excess of 60 °C (140 °F).
7ML19985DG02 Milltronics MillPulse 600 – INSTRUCTION MANUAL Page 11
Page 16
Cleaning and Maintenance
Millpulse 600 can be cleaned by wiping the enclosure exterior with a damp cloth. No other maintenance is required for this device.
Page 12 Milltronics MillPulse 600 – INSTRUCTION MANUAL 7ML19985DG02
Page 17
Notes
Page 18
Notes
Page 19
Page 20