Warning notices must be observed to ensure personal safety as well as that of others, and to
protect the product and the connected equipment. These warning notices are accompanied
by a clarification of the level of caution to be observed.
Qualified Personne l
This device/system may only be set up and operated in conjunction with this manual.
Qualified personnel are only authorized to install and operate this equipment in accordance
with established safety practices and standards.
Warning: This product can only function properly and safely if it is correctly transported,
stored, installed, set up, operated, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2004. All Rights Reserved
This document is available in bound version and in
electronic version. We encourage users to
purchase authorized bound manuals, or to view
electronic versions as designed and authored by
Siemens Milltronics Process Instruments Inc.
Siemens Milltronics Process Instruments Inc. will
not be responsible for the contents of partial or
whole reproductions of either bound or electronic
versions.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Tech nical Publications at t he following address:
Technical Publications
Siemens Milltronics Process Instruments Inc.
1954 Technology Drive, P.O. Box 4225
Peterborough, Ontario, Canada, K9J 7B1
Email: techpubs@siemens-milltronics.com
While we have verified the contents of
this manual for agreement with the
instrumentation described, variations
remain possible. Thus we cannot
guarantee full agreement. The
contents of this manual are regularly
reviewed and corrections are included
in subsequent editions. We welcome
all suggestions for improvement.
Technical data subject to change.
For the library of SMPI instruction manuals, visit our Web site: www.siemens-milltronics.com
The Manual ...............................................................................................................................................2
Units Sticker ................................................................................................................................16
mmmmm
Start Up ...........................................................................................................................................................17
Start Up ....................................................................................................................................................24
Zero Calibration ..........................................................................................................................26
Belt Speed Compensation ..................................................................................................................29
Material Tests ........................................................................................................................................30
Analog Output ........................................................................................................................................43
Auto Zero .................................................................................................................................................46
Alphabetical Parameter List ...............................................................................................................68
Program Record .....................................................................................................................................70
Index .................................................................................................................................................................72
ii
Page 5
Milltronics BW100
Introduction
Note: The Milltronics BW100 is to be used only in the manner outlined in this
instruction manual.
The Milltronics BW100 is an economical integrator for use with belt scales. The speed
and load signals from the conveyor and scale, are processed to derive rate of material
flow and totalization.
The primary values of speed and load, and the derived values of rate and total are
available for display on the local LCD, or as output in the form of analog mA, alarm relay
and remote totalization. BW100 supports Milltronics proprietary bipolar current loop for
long distance communication to PLC or computer. It is also compatible with Milltronics
Dolphin interface for remote display, programming and software upgrading.
Special attention must be paid to warnings and notes highlighted from the rest of the text
by grey boxes.
mmmmm
Introduction
Note: means important information about the product or that part of the operating
manual.
The Manual
It is essential to refer to thismanual for proper installation and operation of your BW100
belt scale integrator. As the BW100 must be connected to a belt scale, and optionally a
speed sensor, refer to their manuals as well.
The manual is designed to help you get the most out of your BW100, and it provides
information on the following
WARNING means that failur e to observe the necessary pr ecautions
can result in death, serious injury, and/or considerable material
damage.
•How to install the unit
•How to program the unit
•How to operate the keypad
and read the display
•How to do an initial Start Up
•How to optimize and
maintain accurate operation
of the unit
•Outline diagrams
•Wiring diagrams
•Parameter values
•Parameter uses
•Modbus register mapping
•Modem configuration
Note: The Milltronics BW100 is to be used only in the manner outlined in this
instruction manual.
If you have any questions, comments, or suggestions about the manual contents, please
email us at techpubs@siemens-milltronics.com.
For the complete library of Siemens Milltronics manuals,
go to www.siemens-milltronics.com.
Note: The equipment must be protected by a 15 A fuse or a circuit breaker in the
building installation.
A circuit breaker or switch in the building installation, marked as the disconnect
switch, shall be in close proximity to the equipment and within easy reach of the
operator.
- SEN
LOAD CELLSPEED
ALARM
TX1
TX2
RX1
RX2
DC
TOTAL (1)
+
+
mA
OUT
L2/N
L1
BW100
LOAD CELL
COM. PORT
Installation
mmmmm
DC Power
12 Vdc Model24 Vdc Model
26
DC
TOTAL (1)
DC/AC
TOTAL(2)
+
+
mA
OUT
12 V
ALARM
+
BW100
BW100
TB1
LOWER
30
31
32
10 - 15 Vdc
SHIELD
112 7
1228
1329
1430
N.O.
COM
1531
1632
N.C.
MILLTRONICS
"dc model indicated on lid nameplate.
dc terminals shall be supplied from an SELV source in accordance with
IEC-1010-1 Annex H.
last parameter from
previous PROGRAM session
e.g. P005
Master Reset
Prior to programming, balancing and calibration, a master reset of the BW100 should be
done.
Refer to
Parameter P999 on
page 64.
Load Cell Balancing
If you are operating a two load cell belt scale, it is recommended that the load cells be
balanced electronically prior to initial programming and calibration, or after either or both
load cells have been reinstalled or replaced.
Note: Unbalanced load cells adversely affect the performance of your belt
conveyor weighing system.
Load Cell
’A’
test weight bar
typical dual load cell scale
With the conveyor stopped and locked out, lift the belt off the weighing idlers.
In order to achieve optimum accuracy in the rate computation, the belt speed displayed
must equal that of the actual belt speed. As the speeds are likely to differ, a belt speed
compensation should be performed.
Run the conveyor with the belt empty.
View the belt speed
12
Stop the conveyor and measure a length of the belt; marking the forward end (start time)
and the back end (stop time). Use the belt scale as the stationary reference.
Run the belt and measure the time for the belt length to pass over the scale.
speed = belt length m or ft.
times min.
Refer to
with conveyor
running empty
Maneuvering
on page 18 for parameter selection and value change.
run mode /speed display,
e.g. 0.750 m/s
PROGRAM mode assumed speede.g.
0.75 ms
%
If the BW100 constant speed input (TB1-5/6) is jumpered, the design speed (P014) is
automatically adjusted.
If a speed sensor is connected, the speed constant (P015) is automatically adjusted.
The display speed (used in the rate computation) now equals the actual speed.
Record the new value in Appendices/Program Record.
Perform material tests to verify the accuracy of the of the span calibration. If the material
tests indicate a repeatable deviation exists, a manual span adjust (P019) is then
performed. This procedure automatically alters the span calibration and adjusts the test
load (P017) value, yielding more accurate span recalibrations.
Note: Test weights are NOT used during material tests.
1.Run the belt empty.
2.Perform a zero calibration.
3.Put the BW100 into RUN mode
4.Record the BW100 total as the start value
5.Run material at a minimum of 50% of design rate over the belt scale for a minimum
of 5 minutes.
6.Stop the material feed and run the conveyor empty.
7.Record the BW100 total as the stop value
8.Subtract the start value from the stop value to determine the BW100 total
If the span adjust value is within the accuracy requirements of the weighing system, the
material test was successful and normal operation can be resumed.
If the span adjust value is not acceptable, repeat the material test to verify repeatability. If
the result of the second material test differs considerably, consult Milltronics or its agent.
If the span adjust values are significant and repeatable, perform a manual span adjust:
refer to
page 18 for
parameter selection
and value change
if % span adjust is
negative, be sure
to enter as
negative value
Maneuvering
,
PROGRAM
mode,
P019
enter %
span adjust,
e.g. 0.05
jumps to P017 adjusted
test load, e.g. 97.95
Verify the results of the span adjust by material test or return to normal operation
Design Changes
Where parameters have been changed with a resultant impact on the calibration or do
not take effect until a recalibration is done, the parameter warning icon is displayed. In
order to clear the icon, perform a zero and span recalibration after the reprogramming
session is complete.
If significant changes have been made, an initial zero (P377) and/or initial span (P388)
may be required.
Recalibration
In order to maintain the accuracy of the weighing system, periodic zero and span
recalibrations are required. Recalibration requirements are highly dependent upon the
severity of the application. Perform frequent checks initially, then as time and experience
dictate, the frequency of these checks may be reduced. Record deviations for reference.
Run the conveyor empty for several minutes to warm up the belt and insure that it is
empty. Test weights are not used during a zero calibration.
From the
run mode
initiate zero calibration
current zero count = ####
12
zero calculation,
load value displayed
12
zero deviation calculated
12
accept deviation
new zero count = ####
12
return to run mode
12
Note: E3 is an indication that the mechanical system is errant. The use of P377,
initial zero
investigation has been exercised.
The cause of the increased deviation must be found and rectified. A zero recalibration as
previously described can then be retried.
If the operator deems this deviation to be acceptable, set P377 to 1 to invoke an initial
zero calibration. Further deviation limits are now based on this new initial zero.
mmmmm
, should be used judiciously and only after a thorough mechanical
Use direct zero entry (P367) when replacing software or hardware, if it is not convenient
to perform an initial zero. A record of the last valid zero count is required.
Refer to
Maneuvering
on page 18 for parameter selection and value change.
To perform a routine span recalibration, run the conveyor until the belt is empty and stop
it. Suspend the test weights from the belt scale per its instruction manual.
Run the conveyor empty at maximum operating speed.
Initiate span
From the
zero calibration
12
12
calibration
current span count
= ####
span calculation,
load value
displayed
span deviation = ##
12
accept deviation
new span count = ####
12
return to run mode
12
Notes:
•E6 is a reminder that a zero calibration is strongly suggested before a span
calibration is initiated. Press ENTER to bypass this message.
•E4 is an indication that the mechanical system is errant. The use of P388, initial
span, should be used judiciously and only after a thorough mechanical
investigation has been exercised.
The cause of the increased deviation must be found and rectified. A span recalibration as
previously described can then be retried.
If the operator deems this deviation to be acceptable, set P388 to 1 to invoke an initial
span calibration. Further deviations are now based on this new initial span.
Note: Remove the test weight when the span calibration is complete.
Direct span entry (P368) is intended for use when replacing software or hardware, and
when it is not convenient to perform an initial span. A record of the last valid span count
is required.
Refer to
Maneuvering
on page 18 for parameter selection and value change.
jumps to P017
dynamic test load value
e.g. 76.03 kg / m
return to run mode
12
Page 43
Linearization
Conveyor applications where the belt scale is poorly located, or where there is a high
degree of variation in belt tension, typically cause the belt scale to report load nonlinearly. The BW100 provides a linearizing function (P390 - P396) in order to correct for the
deficiency in the weighing system and to provide an accurate report of the actual
process.
To verify that the cause of the non-linearity is not mechanical:
1.Run the conveyor belt empty and stop it.
2.Suspend various test weights to the scale to verify mechanical linearity. If the load
reported by the BW100 at these tests is non-linear, a mechanical problem is
indicated. Refer to the belt scale manual in order to resolve the non-linearity by
improved installation or repair.
If it is determined that the non-linearity is due to the weighing application,
and not the actual belt scale, apply linearization by performing the
following:
•zero calibration
•span calibration at 90 to 100% of design rate
•material tests at 90 to 100% of design rate
•manual span adjust if required
•material tests at 1 to 3 intermediary flow rates where compensation is required.
Notes:
•Compensation points must be at least 10% of the design load apart.
•E8 message occurs if a point is less than 10% of full scale or if points are less
than 10% apart.
•calculate the percentage compensation for each flow rate tested.
% compensation = actual weight - totalized weight x 100
A non-linearity with respect to the ideal response exists in a belt scale application with
design rate of 200 t/h. It is decided to do material tests at 25, 50 and 75% of the design
rate. After performing a zero and a span calibration at 100% of the design rate, followed
by material tests and manual span adjust, three material tests were performed at 50, 100
and 150 t/h, as indicated by the BW100. The following data was tabulated. (This example
is exaggerated for emphasis).
The material tests should be run at same belt speed, representative of normal operation;
in this case 1.2 m/s. For each rate, record the corresponding load value by scrolling to the
BW100 load display during running conditions or by calculation.
load = rate
speed
BW100 load
kg/m
11.64.24.9-14.3
23.28.47. 610.5
34.712.613.7-8.0
material test
tonnes
BW100 total
tonnes
*calculation example: % compensation = 4.2 - 4.9 x 100
4.9
= - 14.3
20
15
actual weight per material test
totalized weight by BW100
Often only one point of compensation is required, usually at a low load value. In the prior
example, if compensation was only required at 11.6 kg/m, the programming could be as
follows. Compensation is optimized by establishing the next load value that agrees with
the material test, hence where compensation is zero and entering it as the next
compensation point.
In order for the BW100 to calculate rate and hence totalize material flow along the belt
conveyor, a load signal representative of weight of material on the belt is required. The
load signal is provided by the belt scale. The BW100 is compatible with belt scales fitted
with one or two strain gauge type load cells.
Refer to
requirements and connection.
Specifications
on page 3 and
Installation/Load Cell
on page 6 for belt scale
Speed Sensing
In order for the BW100 to calculate rate and hence totalize material flow along the belt
conveyor, a speed signal representative of belt speed is required. In constant speed
applications (no speed sensor), the BW100 can be programmed to provide an internal
speed signal. This is achieved by entering the design speed (P014) and providing a jumper
across speed input terminals (TB1-5/6). Speed constant (P015) defaults to 100.
For optimum accuracy of the weighing system, both constant and variable speed
applications, a speed sensor is required. Again, the design speed and speed constants
need to be programmed, however the jumper across the speed input has to be removed
and the speed sensor connected.
Refer to
sensor requirements and connection.
Specifications
on page 3 and
Installation/Speed Sensor
on page 6 for speed
Modes of Operation
RUN is the normal or reference mode of operation. It continuously processes the load
signal from the belt scale to produce internal load and rate signals, which are in turn used
as the basis for totalization, mA output and relay control. The RUN display is programmed
(P081) to scroll through rate, totalization, load and speed; either manually by pressing the
ENTER key, or automatically. A bar graph is continuously displayed. It is proportional to
the analog output as programmed (see
From the RUN mode, access to the PROGRAM mode on and zero and span calibration is
made.
The PROGRAM mode allows viewing and, with security permission (P000), changing
parameter values. During PROGRAM, RUN mode functions are still active, i.e.: rate, relay,
analog output and totalization. Error interrupts are suppressed and the bar graph is
disabled.
mmmmm
If the PROGRAM mode is left idle for a period of ten minutes, it automatically reverts to
the RUN mode.
Damping (P080) controls the speed at which the displayed readings and output functions
respond to changes in their respective input function; load, speed and the internal rate
signals. Changes in the displayed rate of material flow, material loading and belt speed
are controlled by the damping. Relay alarm functions based on input functions of flow,
load and speed, respond to the damped value.
If the specific mA output damping parameter (P220) is enabled (value other than 0), then
the damping (P080) as it pertains to the mA function is overridden, and the output value
and bar graph respond independently at the specified mA output damping rate (P220).
Analog Output
The BW100 provides one isolated analog output. The output can be assigned (P201) to
represent rate, load or speed. The output range can be set to 0 - 20 mA or 4 - 20 mA
(P200). The 0 or 4 mA value corresponds to empty or zero condition, whereas the 20 mA
value corresponds to the associated design value: rate (P011), load (P952) or speed
(P014). The analog output can be limited for over range levels of 0 mA minimum and 22
mA maximum (P212 and P213 respectively). The output 4 and 20 mA levels can also be
trimmed (P214 and P215 respectively) to agree with a millammeter or other external mA
input device.
Operation
mmmmm
The BW100 LCD provides a bar graph as a function of analog output. It displays the mA
value as percentage of the mA range.
The mA output value can be tested using parameter P911. Refer to
page 62.
The BW100 offers one single pole double throw (SPDT) relay that can be assigned (P100)
to one of the following alarm functions:
mmmmm
Operation
•rate: relay alarms on high and/or low material flow rate.
•auto zero: relay alarms when an attempted auto zero calibration reports an out of
range condition (E9).
•speed: relay alarms on high and/or low belt speed.
•load: relay alarms on high and or low belt load.
•error: relay alarms on any error condition as it is reported.
•Refer to
Troubleshooting
, page 65.
Except for alarm on ‘auto zero’ and ‘error’, the high and low alarm setpoints (P101 and
P102 respectively) are required and must be entered in the appropriate units.
The on / off actuation at both setpoints is buffered by the damping (P080) and the
programmable dead band (P117), to prevent relay chatter due to fluctuations. The relay is
normally energized; i.e. the normally closed (n.c.) contact held open. Upon an alarm
condition, the relay is de-energized and the alarm icon on the BW100 display appears.
Once in alarm, the relay and icon remain in alarm status until the alarm condition is
removed.
The totalization function is based on the internal rate (mass per unit time) signal
proportional to belt speed and load on the associated belt scale. It is not affected by the
damping function (P080). The rate signal is sampled several times a second to accurately
count the mass of material conveyed. The count is held in the master totalizer used to
increment the internal totalizers and to produce a pulse signal for the remote totalizers.
The BW100 provides four separate totalizer functions:
•internal totalizer 1
•internal totalizer 2
•remote totalizer 1
•remote totalizer 2
To avoid totalizing material at low flow rates, the totalizer drop out limit (P619) is set to a
percentage of the design rate. Below this limit, totalization stops. When material flow
returns to a rate above the drop out limit, totalization resumes.
Totalizer resolution or count value is set by the respective control parameters, P631 -P639. If the resolution selected causes the totalizer to lag behind the count rate, an E2
error is displayed after making the parameter entry. The error is rectified by selecting a
greater resolution value.
Example: Internal totalizer 1
Operation
mmmmm
Given:P005 = 1 (t/h)
P631 = 4
Then:totalizer count increments by 10 for each 10 metric tonnes registered
External totalizer 1
Given: P005 = 1 (t/h)
P638 = 5
Then:contact closure occurs once for every 10 metric tonnes registered
For remote totalization, the contact closure duration is set by the respective control
parameters, P643 and P644. The value is automatically calculated upon entry of the
design rate (P011) and remote totalizer parameters (P638 and P639), so that the duration
of contact closure allows the relay response to track the total up to the design rate. The
value can be changed to suit specific contact closure requirements, such as in the case
of programmable logic controllers. If an E2 error is displayed, P638 or P639 has to be
increased.
The totalizers are reset through the master reset (P999), the totalizer reset (P648) or
through the keypad.
•master reset: the reset of all totalizer functions is included in the master reset.
•totalizer reset: totalizer reset can be used to resets internal totalizers 1 and 2, or
totalizer 2 independently.
•keypad: pressing simultaneously while in the RUN mode resets
internal totalizer 1, as well as the internal counts for both remote
totalizers.
Page 50
mmmmm
Auto Zero
Operation
Placing the internal totalizers on to the display scroll of the RUN mode is controlled by the
totalizer display parameter (P647); displaying either one or both totalizers.
The Auto Zero function allows a zero calibration to be initiated automatically under the
following conditions.
•the auto zero input (TB1-9/10) is in a closed state; jumper or remote switch
•the load is less than 2% of the design load
If the resulting zero deviation is less than an accumulated 2% from the last operator
initiated zero, the auto zero is accepted.
If the deviation is greater than an accumulated 2%, an E9 error is displayed and the relay,
if so programmed, goes into alarm (refer to
error is cleared after five seconds.
If material feed resumes during an auto zero function, the totalizing function is
maintained.
The BW100 bipolar current loop provides long distance communication to a customer
device.
BW10 0
host
device
Bipolar
Converter
Operation
mmmmm
The BW100 communication port (TB1-21 to 25) is software set for baud (P751) and mode
enable (P760). Refer to
Installation/Communication
on page 14 for wiring details.
Note: If communicating via Milltronics Dolphin software, the baud rate must be
set to 4800.
Protoc ol
Protocol refers to the format, sequence and value of the data fields used in
communication messages. Each data field of a BW100 message contains one or more
bytes of ASCII binary code.
BW100 start of message, ASCII character = STX (Hex Value = 02).
DEVICE
Identifies the BW100 to which the message applies. The device is a 2 character number
that equals the Unit I.D. code, (P761). ASCII characters = 00 to 15.
MT
Identifies the 2 character message type transmitted, ASCII characters:
50 = material flow rate
51 = material load
mmmmm
Communications
READING
Contains the measurement value in the engineering units of measure selected during
BW100 programming. The number of bytes in this data field varies dependent upon the
reading value. Up to 8 ASCII characters including the decimal point may be transmitted.
Three ASCII characters identify the totalizer engineering units (MT=53 and MT=54). The
first character is always a space. The remaining characters may be:
t = tonnes
T = tonnes
LT = long tonnes
kg = Kilograms
lb = pounds
eom
BW100 end of message, ASCII character = CR (Hex Value = 0D).
Message Requests
Message requests must be transmitted from the host to the BW100 in the following
format.
som DEVICE MT eom
Example:
Data ASCII Example
Field CharacterDescription
som STX start of message
DEVICE 01for BW100 # 1
MT 50 material flow rate request
eom CRend of message
Locks out the programming change value function such that the values of P001 through
P999 cannot be changed. This however does not prevent the select function from use; i.e.
for viewing values.
Programming is locked out if the value of P000 is other than 1954.
Entry:
mmmmm
1954 = unlocked
1954 = locked
f
Communications
Quick Start (P005 to P017)
Note: Quick Start is the minimum parameter programming required before
attempting a calibration and successful entry into the RUN mode.
P005 Design Rate Units
Determines the units for programming and measurement.
Entry:
f
1
= t/hr (tonnes per hour)
2 = kg/hr (kilograms per hour)
3 = LT/Hr (long tons per hour)
4 = T/h (short tons per hour)
5 = lb/hr (pounds per hour)
Changing this parameter does not affect the rate (P011), belt speed (P014) or belt length
(P016) parameters. These parameters should be re-entered for conformity in units.
t = 1000 kg
LT = 2240 lb.
T = 2000 lb.
P011 Design Rate
Specifies the design rate of material flow for the belt scale.
Enter the design rate from the supplied design data sheet
This parameter allows adjustment to the speed constant (P015).
Initially, this parameter displays the dynamic speed of the belt. If the displayed speed is
not equal to the actual speed, enter the actual belt speed.
For speed sensor applications, the value of P015 is automatically adjusted.
For constant speed (TB1 5/6 jumper) the value of P014 is automatically adjusted.
P019 Manual Span Adjust
This parameter allows adjustment to the span calibration.
The adjustment value is generally determined by performing material tests. Refer to
Recalibration/Material Tests,
Enter the calculated adjustment.
page 30.
P022 Minimum Speed Frequency
Sets the minimum frequency that the speed sensor can reliably read. Signals at low
frequencies are erratic, adversely affecting the performance of the weighing system.
Entry:
1 = 1 Hz (at 1 Hz, it takes 1 sec before defaulting to 0 speed)
mmmmm
2 = 2 Hz (at 2 Hz, it takes 0.5 sec before defaulting to 0 speed)
Parameters
P080 Damping
Sets the speed of response to which the displayed readings (rate, load and speed), and
outputs (alarm and mA) react to change.
Note: The effect of damping (P080) on mA output can be overridden by mA output
damping (P220).
The greater the damping value, the slower the response.
Enter damping value, range 1 - 9999.
P081 Display Mode
Sets the display mode. Normally, the display shows rate, or the last manually selected
function. If set to alternating, the display alternates between rate and totalizer (1 and/or
2, as programmed by P647).
Note: These parameters are used for verifying or balancing the load cells (2) on
the associated conveyor belt scale. Refer to
procedure for use of these parameters.
P291 Calculator Input 1
This register displays the count associated with the summation of load cell A and B
signals, when balancing the A and B load cells of the associated belt scale.
P292Calculator Input 2
This register displays the count associated with the load B signal, when balancing the A
and B load cells of the associated belt scale.
P293 Calculator Input 3
Start Up
, page 17, for details and
This register displays the count associated with the load cell B signal, when balancing
the A and B load cells of the associated belt scale.
P294 Calculator Input 4
This register displays the count associated with the summation of load cell A and B
signals, when balancing the A and B load cells of the associated belt scale.
P295 Load Cell Balance
Used in conjunction with balance calculator parameters (P291 - P 294), this parameter
displays the adjustment required to complete the load cell balance procedure.
End of balancing parameters
P341 Run Time
The cumulative days that the application device has been in service. The time is recorded
once daily in a non-resetable counter. Periods of less than 24 hr. are not recorded, nor
accumulated.
This parameter provides additional security to the global lock (P000).
Entry:
0 = view parameters, perform zero and span, no reset of totalizer 1
1 = same as level 0, but cannot perform span
2 = same as level 0, but cannot perform zero and span
P359 Factoring
Factoring is used as a method of calculating the value of the test load (P017) to a new
physical test weight.
Entry:
0 = idle
1 = factor
Note: Totalization is halted during the factoring procedure, and resumed only
upon return to the RUN mode.
P360 Calibration Duration
Sets the number of belt revolutions to use during a zero or span calibration.
mmmmm
Enter number of belt revolutions, range 1 - 99.
Parameters
P367 Direct Zero
This parameter allows the zero reference count to be viewed or entered directly.
Direct entry is intended for use when replacing software or hardware and it is not
convenient to perform an initial zero at that time.
P368 Direct Span
This parameter allows the span reference count to be viewed or entered directly.
Direct entry is intended for use when replacing software or hardware and it is not
convenient to perform an initial span at that time.
P370 Zero Limit
Sets the zero calibration deviation limit from the last initial zero. If the accumulated
deviation exceeds the limit, the zero calibration is aborted (E3).
Entry:
0 = +/- 12.5% of initial zero
1 = +/- 2% of initial zero
The initial zero is the reference zero to which all subsequent operator initiated zero
calibrations are compared in determining whether they have deviated beyond the zero
limit (P370).
Entry:
0 = idle
1 = initial zero
Note: Refer to
Recalibration/Initial Zero
on page 33 for use of this function.
P388 Initial Span
The initial span is the reference to which all subsequent span calibrations are compared
in determining whether they have deviated beyond 12.5% of the initial span.
Entry:
0 = idle
1 = initial span
Note: Refer to R
ecalibration/Initial Span
on page 36 for use of this function.
Linearization Parameters (P390 - P396)
Note: These parameters are used to compensate for non-linear response of the
weighing system to the BW100. Refer to Recalibration/Linearization for details and
example on the use of these parameters.
Parameters
mmmmm
P390 Linearization
Enables or disables the linearization function.
Entry:
0 = OFF
1 = ON
P391 Linearizer, Point 1
Enter the load, in units of P017, for point 1
P392 Compensation, Point 1
Enter the calculated compensation, in percent, for compensation point 1
The value of this parameter represents a multiple of 32 ms of contact closure for remote
totalizer 1. The value is automatically calculated upon entry of P1 (design rate) and P638
(totalizer 1 resolution, external) so that the duration of contact closure allows the
transistor switch response to track the total, up to the design rate.
The value can be changed to suit specific contact closure requirements, such as in the
case of programmable logic controllers. If a message E2 is displayed, P638 has to be
increased.
The value of this parameter represents a multiple of 32 ms of contact closure for remote
totalizer 2. The value is automatically calculated upon entry of P1 (design rate) and P639
mmmmm
Parameters
(totalizer 2 resolution, external) so that the duration of contact closure allows the
transistor switch response to track the total, up to the design rate.
The value can be changed to suit specific contact closure requirements, such as in the
case of programmable logic controllers. If a message E2 is displayed, P639 has to be
increased.
Selects the totalizer combination to be displayed, either manually through the scroll
display key or automatically by control of the display mode (P081).
Note: These parameters are used for test and diagnostic purposes.
P900 Software Revision
Displays the EPROM (Flash ROM) software revision level.
P901 Memory
Tests the memory. Test is initiated by scrolling to the parameter or repeated by pressing
ENTER.
Display:
PASS = normal
FAIL = consult Siemens Milltronics.
P907 Programmer Interface
Tests the infrared communications link. Test is initiated by scrolling to the parameter or
repeated by pressing ENTER.
Display:
mmmmm
Parameters
PASS = normal
FAIL = consult Siemens Milltronics.
infrared communication
link
mirror
BW100
P911 mA Output Value
Displays the value from the previous measurement. A test value can be entered and the
displayed value is transmitted to the output. Upon returning to the RUN mode, the
parameter assumes the actual mA output level.
P940 Load Cell A, mVin
Displays the mV signal input from the load cell. Range 0.00 - 60.00 mV.
Displays the mV signal input from the load cell. Range 0.00 - 60.00 mV.
P942 V/F converter, Vin
Displays the input voltage to the voltage to frequency converter.
Range 0 - 3.98 V
P943 V/F converter, f
Displays the output frequency of the voltage to frequency converter.
Range 0 - 131,072
out
P944 Power sensor
Displays a voltage supply reference for diagnostic purposes.
P949 Diagnostic Errors
Enables or disables diagnostic error checking, E101 - E104
Entry:
0 = disable
1 = enable
Refer to
Troubleshooting on
page 65
.
P950 Zero register
Parameters
mmmmm
Registers the number of zero calibrations that have been done since the last master
reset.
P951 Span Register
Registers the number of span calibrations that have been done since the last master
reset.
P952 Design Load
Displays the value of the design load, which corresponds to the full scale value for alarm
and mA output functions. The design load is calculated, based on the design rate and
design speed.
beyond 100% of design load
(P952). Replace test weight
with a heavier or lighter weight
and try factoring again.
Page 70
message diagnosis action
E101 (run)
E102 (run)
E103 (run)
load cell A mV reading is out
of range
load cell B mV reading is out
of range
combined mV signal from
load cell A and B is out of
range
error will appear if:
• mV signal from load cell A or
B is out of the 0-50 mV range
• the mV signal from load cell
A or B is less than the zero
calibration mV level minus
one half the span mV level
• A or B mV is greater than 4
times the span mV value
check load cell mV signal and
ensure that it is within range
check wiring
error will appear if the combined mV signal from load cell
A and B is too low
check both load cell signals
and ensure that they are
greater than 0 mV
check wiring
cycle power and perform memory test (P901)
E104 (run) faulty memory location found
if error reappears, the BW 100
must be repaired or replaced.
OF
no speed signal check speed circuit or run con-
veyor
•Error messages are cleared when the condition is remedied.
•RUN mode errors are suppressed during PROGRAM mode, zero or span calibration.
•Zero and span errors are cleared when zero or span is initiated. Errors that happen
mmmmm
during the calibration require re-starting the procedure.
•Program errors are cleared when any key is pressed.
Troubleshooting
•The messages E101 through E104 can be turned off (P949).
•The load cell errors are detected by certain conditions where it is apparent that the
load cell is not functioning or incorrectly wired. It is not a conclusive test, since even
with incorrect wiring, the resulting input from the load cell may be within a valid
range.
The external surface of the enclosure may be cleaned using a vacuum cleaner and a
clean dry paint brush. The display window should be cleaned with a moist non-abrasive
cloth.
It is a good idea to check the associated load sensing device, according to its instruction
manual.
Software Updates
The software can be updated from a floppy disk by use of a PC (IBM Compatible) with
Milltronics Dolphin software. It is recommended that a reset (P999) is done after the
software update followed by zero and span calibrations.
Direct zero entry (P367) and direct span entry (P368) will suffice in lieu of dynamic zero
and span calibrations. Therefore, zero and span counts should be recorded prior to doing
the software update.