Siemens Milltronics BW100 Instruction Manual

Page 1
Instruction Manual February 2004
MILLTRONICS BW100
milltronics
BW100
Page 2
Safety Guidelines
Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed.
Qualified Personne l
This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.
Warning: This product can only function properly and safely if it is correctly transported,
stored, installed, set up, operated, and maintained.
Note: Always use product in accordance with specifications.
Copyright Siemens Milltronics Process
Disclaimer of Liability
Instruments Inc. 2004. All Rights Reserved
This document is available in bound version and in electronic version. We encourage users to purchase authorized bound manuals, or to view electronic versions as designed and authored by Siemens Milltronics Process Instruments Inc. Siemens Milltronics Process Instruments Inc. will not be responsible for the contents of partial or whole reproductions of either bound or electronic versions.
MILLTRONICS®is a registered trademark of Siemens Milltronics Process Instruments Inc.
Contact SMPI Tech nical Publications at t he following address:
Technical Publications Siemens Milltronics Process Instruments Inc. 1954 Technology Drive, P.O. Box 4225 Peterborough, Ontario, Canada, K9J 7B1 Email: techpubs@siemens-milltronics.com
While we have verified the contents of this manual for agreement with the instrumentation described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement.
Technical data subject to change.
For the library of SMPI instruction manuals, visit our Web site: www.siemens-milltronics.com
© Siemens Milltronics Process Instruments Inc. 2004
Page 3
Table of Contents
Table of Contents
Milltronics BW100 ......................................................................................................................................1
Milltronics BW100 Features .................................................................................................................1
Safety Notes .............................................................................................................................................2
The Manual ...............................................................................................................................................2
Specifications ...............................................................................................................................................3
Installation .....................................................................................................................................................6
Dimensions ..............................................................................................................................................6
Interconnection ........................................................................................................................................7
System Diagram .............................................................................................................................7
Terminal Block Layout .................................................................................................................8
Load Cell - Single ...........................................................................................................................9
Load Cell - Dual ...........................................................................................................................10
Speed Sensor ...............................................................................................................................11
Auto Zero ......................................................................................................................................12
Remote Totalizer 1 ......................................................................................................................12
Analog Output .............................................................................................................................12
Remote Totalizer 2 ......................................................................................................................13
Relay Output ................................................................................................................................13
Communication ......................................................................................................................................14
Bipolar Current Loop ..................................................................................................................14
Power Connections ..............................................................................................................................15
AC Power ......................................................................................................................................15
DC Power ......................................................................................................................................15
Comverter ................................................................................................................................................16
Optional Dolphin Interface ........................................................................................................16
Units Sticker ................................................................................................................................16
mmmmm
Start Up ...........................................................................................................................................................17
Orientation ..............................................................................................................................................17
Display and Keypad ...................................................................................................................17
PROGRAM Mode ..................................................................................................................................18
Maneuvering ................................................................................................................................18
Master Reset ..........................................................................................................................................21
Load Cell Balancing ..............................................................................................................................21
Quick Start ..............................................................................................................................................23
Start Up ....................................................................................................................................................24
Zero Calibration ..........................................................................................................................26
Span Calibration ..........................................................................................................................27
Recalibration ...............................................................................................................................................29
Belt Speed Compensation ..................................................................................................................29
Material Tests ........................................................................................................................................30
Design Changes .....................................................................................................................................31
Recalibration ...........................................................................................................................................31
i
Page 4
Routine Zero .................................................................................................................................32
Initial Zero .....................................................................................................................................33
Direct Zero ....................................................................................................................................34
Routine Span ................................................................................................................................35
Initial Span ...................................................................................................................................36
Direct Span ...................................................................................................................................37
Factoring ..................................................................................................................................................38
Linearization ...........................................................................................................................................39
Operation .......................................................................................................................................................42
Load Sensing ..........................................................................................................................................42
Speed Sensing .......................................................................................................................................42
Modes of Operation ..............................................................................................................................42
Damping ...................................................................................................................................................43
Analog Output ........................................................................................................................................43
Relay Output ...........................................................................................................................................44
Totalization ..............................................................................................................................................45
Auto Zero .................................................................................................................................................46
Communications ........................................................................................................................................47
Protocol ....................................................................................................................................................47
Data Field Descriptions ..............................................................................................................48
Message Requests .....................................................................................................................48
Message Responses ..................................................................................................................49
Parameters ....................................................................................................................................................50
Quick Start (P005 to P017) ..................................................................................................................50
Relay/Alarm Function (P100 - P117) .................................................................................................53
mA Output Parameters (P200 - P220) ..............................................................................................53
Load Cell Balancing Parameters (P291 - P295) .............................................................................55
Linearization Parameters (P390 - P396) ..........................................................................................57
Totalization (P619 - P648) .....................................................................................................................58
Communication (P751 - P761) .............................................................................................................61
Test and Diagnostic (P900 - P951) ....................................................................................................62
Troubleshooting ..........................................................................................................................................65
Maintenance ..........................................................................................................................................67
Software Updates .................................................................................................................................67
Appendix ........................................................................................................................................................68
Alphabetical Parameter List ...............................................................................................................68
Program Record .....................................................................................................................................70
Index .................................................................................................................................................................72
ii
Page 5
Milltronics BW100
Introduction
Note: The Milltronics BW100 is to be used only in the manner outlined in this
instruction manual.
The Milltronics BW100 is an economical integrator for use with belt scales. The speed and load signals from the conveyor and scale, are processed to derive rate of material flow and totalization.
The primary values of speed and load, and the derived values of rate and total are available for display on the local LCD, or as output in the form of analog mA, alarm relay and remote totalization. BW100 supports Milltronics proprietary bipolar current loop for long distance communication to PLC or computer. It is also compatible with Milltronics Dolphin interface for remote display, programming and software upgrading.
Milltronics BW1 00 Features
multi-field LCD display
two remote totalizer contacts
current loop for communications
Dolphin compatibility
programmable relay
isolated mA output
rate linearization
local keypad
•Auto Zero
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 1
Load
Speed
Material
total
Page 6
Safety Notes
Special attention must be paid to warnings and notes highlighted from the rest of the text by grey boxes.
mmmmm
Introduction
Note: means important information about the product or that part of the operating
manual.
The Manual
It is essential to refer to thismanual for proper installation and operation of your BW100 belt scale integrator. As the BW100 must be connected to a belt scale, and optionally a speed sensor, refer to their manuals as well.
The manual is designed to help you get the most out of your BW100, and it provides information on the following
WARNING means that failur e to observe the necessary pr ecautions can result in death, serious injury, and/or considerable material damage.
How to install the unit
How to program the unit
How to operate the keypad and read the display
How to do an initial Start Up
How to optimize and maintain accurate operation of the unit
Outline diagrams
Wiring diagrams
Parameter values
Parameter uses
Modbus register mapping
Modem configuration
Note: The Milltronics BW100 is to be used only in the manner outlined in this instruction manual.
If you have any questions, comments, or suggestions about the manual contents, please email us at techpubs@siemens-milltronics.com.
For the complete library of Siemens Milltronics manuals, go to www.siemens-milltronics.com.
Page 2 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 7
Specifications
Power
• standard: 100/115/200/230 Vac ± 15%, 50/60 Hz, 15VA
• optional: 10 - 15 V dc, 15 W
Application
• compatible with Siemens Milltronics belt scales or equivalent
Accuracy
• 0.1% of full scale
Resolution
• 0.02% of full scale
18 - 30 V dc, 15 W
Specifications
mmmmm
Environmental
• location: indoor / outdoor
• altitude: 2000 m max
• ambient temperature: -20 to 50 °C (-5 to 122 °F)
• relative humidity: suitable for outdoor
• installation category: II
• pollution degree: 4
Enclosure
• polypropylene alloy
• Type 4X / NEMA 4X / IP 65
• sealed electronics compartment
• integral junction box with termination block for 0.2 - 4 mm solid or
0.2 - 2.5 mm stranded (12 - 24 AWG)
Programming
• via local 4 member keypad with silicone boot and/or Dolphin interface
Display
• 38 x 100 mm (1.5 x 4") multi-field liquid crystal display
Memory
• program stored in non-volatile FLASH memory, upgradable via Dolphin interface
• parameters stored in non-volatile EEPROM
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 3
Page 8
Inputs
• load cell: 0 - 45 mV dc per load cell
• speed sensor: pulse train: 0-5 V low, 5-15 V high, 1 to 2000 Hz, or
open collector switch
or
relay dry contact
• auto zero: dry contact from external device
Outputs
• analog: - optically isolated 0/4 - 20 mA
max loading
- 750
• resolution: - 0.1% of 20 mA
mmmmm
Specifications
• load cell: - 10 Vdc compensated for strain gauge type, 2 cells max
• speed sensor: - 12 Vdc, 50 mA max excitation
• remote totalizer 1: - contact closure 32 - 288 ms duration
- open collector switch rated 30 Vdc, 100 mA max
• remote totalizer 2: - contact closure 32 - 288 ms duration
- open collector switch rated 240 Vac/dc, 100 mA max
• relay output: programmable function 1 form C SPDT relay contact rated
5 A at 250 Vac, non-inductive
Communications
• Dolphin compatible
• proprietary bipolar current loop
Cable/Separation:
• one load cell/LVDT: non-sensing: Belden 8404, 4 wire shielded, 20 AWG or equivalent,
150 m (500 ft.) max.
sensing: Belden 9260, 6 wire shielded, 20 AWG or equivalent,
300 m (1000 ft.) max.
• two load cells: non-sensing: Belden 9260, 6 wire shielded, 20 AWG or equivalent,
150 m (500 ft.) max.
sensing: Belden 8418, 8 wire shielded, 20 AWG or equivalent,
300 m (1000 ft.) max.
• speed sensor Belden 8770, 3 wire shielded, 18 AWG or equivalent, 300 m (1000 ft.) max.
• auto zero: Belden 8760, 1 pair, twisted/shielded, 18 AWG, 300 m (1000 ft.) max.
• remote total: Belden 8760, 1 pair, twisted/shielded, 18 AWG, 300 m (1000 ft.) max.
Page 4 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 9
• analog output: Belden 8760, 1 pair, twisted/shielded, 18 AWG or
• bipolar current: Belden 9552, 2 pair, twisted/shielded, 18
• (comm. port) AWG, 3000 m (10,000 ft.) max. loop
• remote total Belden 8760, 1 pair, twisted/shielded, 18AWG,
• t1 (dc) 300 m (1000 ft.) max.
Options:
• Speed Sensor: - Siemens Milltronics MD-36 series, or equivalent
• Dolphin: - Milltronics Windows based software interface and
Approvals:
•CE*, CSA
*EMC performance available upon request
NRTL/C
equivalent
infrared ComVerter link
Specifications
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 5
Page 10
Installation
Notes:
Installation shall only be performed by qualified personnel and in accordance with local governing regulations.
This product is susceptible to electrostatic shock. Follow proper grounding procedures.
Dimensions
270mm
(10.6")
254 mm
(10")
138 mm
(5.4")
69 mm
(2.7")
mmmmm
Installation
sealed enclosure
integral junction box (cover removed) with terminal block and voltage selection switch
Conduit entry area. Recommend drilling the enclosure with a hole saw and the use of suitable cable glands to maintain ingress rating.
74 mm
(2.9")
mounting hole
6.4 mm (1/4") Ø
Note: Non metallic enclosure does not provide grounding between connections.
Use grounding type bushings and jumpers.
Page 6 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
5 mm
(0.2")
Page 11
Interconnection
Note: Wiring may be run via common conduit. However these may not be run in
the same conduit as high voltage contact or power wiring.
System Diagram
Milltronics
BW10 0
1
mA output
relay output
2
Siemens
1
1
Milltronics belt scale, see
Specifications, page 3
speed sensor, optional, see
Specifications, page 3
customer device
customer alarm, or control device
remote
2
totalizer
bipolar current loop
1
(Milltronics communications)
customer’s remote totalizing device
customer device
Note: Typical system capability. Not all components or their maximum quantity
may be required.
Installation
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 7
Page 12
Terminal Block Layout
ac supply
dc supply
117
- SIG B - EXC
218
+ SIG B
319
- SIG A +SEN
420
+ SIG A + EXC
521
CNST. SPD.
COM.
622
+ SIG
723
+ EXC
824
+
925
AUTO ZERO
10 26
SHIELD
11 27
12 28
DC/AC TOTAL( 2)
13 29
14 30
N.O.
COM
15 31
16 32
N.C.
ALARM
MILLTRONICS
- SEN
LOAD CELLSPEED
SHIELD
TX1
TX2
RX1
RX2
DC TOTAL (1)
+
+
mA OUT
L2/N
L1
BW100
LOAD CELL
COM. PORT
117
mmmmm
Installation
- SIG B - EXC
+ SIG B
218
319
- SIG A +SEN
420
+ SIG A + EXC
521
CNST. SPD.
COM.
622
+ SIG
723
+ EXC
824
+
925
AUTO ZERO
10 26
SHIELD
11 27
12 28
DC/AC TOTAL(2)
13 29
14 30
N.O.
COM
15 31
16 32
N.C.
ALARM
MILLTRONICS
LOAD CELLSPEED
- SEN
SHIELD
TX1
TX2
RX1
RX2
DC TOTAL (1)
+
+
mA OUT
-
24 V
+
BW100
LOAD CELL
COM. PORT
117
- SIG B - EXC
218
+ SIG B
319
- SIG A +SEN
420
+ SIG A + EXC
521
CNST. SPD.
COM.
622
+ SIG
723
824
+ EXC
+
925
AUTO ZERO
10 26
11 2 7
SHIELD
12 28
DC/AC TOTAL(2)
13 29
14 30
N.O.
15 31
COM
N.C.
ALARM
16 32
MILLTRONICS
- SEN
LOAD CEL LSPEED
SHIELD
TX1
TX2
RX1
RX2
DC TOTAL ( 1)
+
+
mA OUT
-
+
BW100
LOAD CEL L
COM. PORT
All field wiring must have insulation suitable for at least 250 V.
dc terminals shall be supplied from a SELV source in accordance with IEC-
1010-1 Annex H.
Page 8 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 13
Load Cell - Single
BW100
TB1
UPPER
Belt Scale
+
S
I
s h
l
d
G
g
r
n
+
S
I
G
w
h
t
E
E
X
X
C
C
b
r
l
e
k
d
+
SIG B
LOADCELL
+
SIG A
CNST. SPD.
SIG B
SIG A
LOADCELL
EXC
SEN
+ SEN
+
EXC
SHIELD
BW100
TB1
LOWER
*
*
customer
junction box
Installation
mmmmm
Note: If load cells are supplied with
sense wiring: terminate brown with black = T17 and blue with red = T20 at junction box
Where separation between the BW100 and belt scale exceeds 150 m (500 ft.):
1. remove the jumpers BW100 TB1 – 17/18 and TB1 19/20
2. run additional conductors from: BW100 TB1 – 18 to scale ‘– EXC’ BW100 TB1 – 19 to scale ‘+ EXC’
If the load cell wiring colours vary from those shown, or if extra wires are provided, consult Siemens Milltronics.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 9
Page 14
Load Cell - Dual
’A’
Belt Scale
’B
load cells
s h
l
d
BW100
TB1
UPPER
SIG B
b
r e d
w
g
w
g
l
h
r
h
r
k
t
n
t
n
customer
+
SIG B
SIG A
LOADCELL
+
SIG A
CNST. SPD.
BW100
TB1
LOWER
EXC
mmmmm
Installation
LOADCELL
SEN
+
SEN
+
EXC
SHIELD
Note: If load cells are supplied with
sense wiring: terminate brown with black = T17 and blue with red = T20 at junction box
junction
box
Where separation between the BW100 and belt scale exceeds 150 m (500 ft.):
1. remove the jumpers BW100 TB1 – 17/18 and TB1 19/20
2. run additional conductors from: BW100 TB1 – 18 to scale ‘– EXC’ BW100 TB1 – 19 to scale ‘+ EXC’
If the load cell wiring colours vary from those shown, or if extra wires are provided, consult Siemens Milltronics.
Page 10 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 15
Speed Sensor
P
MD - 36 series
speed sensor
+
CNST. SPD.
SPEED
AUTO ZERO
SHIELD
SIG A
COM
+
SIG
+
EXC
+
BW100
TB1
UPPER
OR
OR
1 5 V
C
C
C
W
W
G
C
N
O
D
M
RBSS
or
encoder
r e d
b
w
l
h
k
t
Installation
TASS
mmmmm
b
r n
b
b
l
l
u
k
! Connect the BW100 TB1 – 7 to the MD - 36 series speed sensor terminal:
‘2’ for clockwise speed sensor shaft rotation
‘3’ for counter-clockwise speed sensor shaft rotation.
MD shaft rotation is viewed from the front cover side of the MD enclosure.
# If a speed sensor is not used, a jumper must be connected across the BW100 TB1 –
5 / 6. If a speed sensor is used, insure that the jumper is removed.
! Input device in the form of open collector transistor or dry contact across TB1 – 6 / 7
will also serve as a suitable speed signal.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 11
Page 16
Auto Zero
BW100
TB1
UPPER
+
AUTO ZERO
Remo te Totalizer 1
BW100
TB1
LOWER
prefeed activated dry contact
DC
TOTAL (1)
mmmmm
Installation
+
26
27
28
29
30
-
+
supply
maximum 30
V dc, 100 mA
remote
totalizer
Analog Output
BW100
TB1
LOWER
mA
OUT
+
to customer instrumentation isolated mA output, 750 models only
mA output on dc models is not isolated
maximum load ac
Page 12 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 17
Remo te Totalizer 2
BW100
TB1
UPPER
DC/AC
TOTAL (2)
Relay Output
BW100
TB1
UPPER
n.o.
com
n.c.
supply
maximum
240 V ac/dc
relay shown in de-energized state, contacts rated 5 A at 250V non-inductive
remote
totalizer
Installation
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 13
Page 18
Communication
Bipolar Current Loop
Customer
Device
T R A N S
M
I
T
S H
I E L D
R E C E
I V E
BW100
TB1
LOWER
SHIELD
TX1
TX2
RX1
RX2
mmmmm
21
22
23
24
25
25 24 23 22
Installation
Connect shield at one device only, e.g. BW100 TB1 - 21
Maximum loop length 3000 m (10,000 ft.)
Page 14 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 19
Power Connections
AC Power
OFF
230 V
L2/N
BW100
TB1
LOWER
100 V
200 V
115 V
117
- SIG B - EXC
+ SIG B
218
- SIG A +SEN
319
+ SIG A + EXC
420
CNST. SPD. SHIELD
521
COM.
622
+ SIG
723
824
+ EXC
+
925
AUTO ZERO
10 26
11 2 7
SHIELD
12 28
DC/AC TOTAL(2)
13 29
14 30
N.O.
15 31
COM
16 32
N.C.
MILLTRONICS
L1
Note: The equipment must be protected by a 15 A fuse or a circuit breaker in the
building installation. A circuit breaker or switch in the building installation, marked as the disconnect switch, shall be in close proximity to the equipment and within easy reach of the operator.
- SEN
LOAD CELLSPEED
ALARM
TX1
TX2
RX1
RX2
DC TOTAL (1)
+
+
mA OUT
L2/N
L1
BW100
LOAD CELL
COM. PORT
Installation
mmmmm
DC Power
12 Vdc Model 24 Vdc Model
26
DC TOTAL (1)
DC/AC TOTAL(2)
+
+
mA OUT
12 V
ALARM
+
BW100
BW100
TB1
LOWER
30
31
32
10 - 15 Vdc
SHIELD
11 2 7
12 28
13 29
14 30
N.O.
COM
15 31
16 32
N.C.
MILLTRONICS
" dc model indicated on lid nameplate.
dc terminals shall be supplied from an SELV source in accordance with IEC-1010-1 Annex H.
"
é
BW100
TB1
LOWER
30
31
32
18 - 30 Vdc
11 27
SHIELD
12 28
DC/AC TOTAL(2)
13 29
N.O.
14 30
15 31
COM
ALARM
N.C.
16 32
MILLTRONICS
26
DC TOTAL (1)
+
+
mA OUT
24 V
+
BW100
"
é
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 15
Page 20
Comverter
Optional Dolphin Interface
Milltronics BW100
Comverter
Refer to Dolphin instruction manual for interconnection details.
Units Sticker
mmmmm
Installation
Remove the appropriate units sticker from the sheet supplied, and affix to your BW100 as shown.
Page 16 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 21
Start Up
Note: For successful start up, ensure that all related system components such as
belt scale and speed sensor are properly installed and connected.
Orientation
Display and Keypad
LCD
balance switch, SW2
balance potentiometer, P1
Keypad
The BW100 operates under two modes: RUN and PROGRAM. When the unit is initially powered, it starts in the PROGRAM mode.
1 2 3
If the PROGRAM mode is idle, it reverts to the run mode after 10 minutes.
Installation
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 17
Page 22
PROGRAM Mode
LCD
KeyPad
access RUN mode
PROGRAM mode
parameter value
1 2 3
status icon,
refer to
RUN Mode
alternates PROGRAM mode between select parameter and change value
parameter number
scroll
up
’change value’ accessed
scroll
down
Maneuvering
To Select a Parameter:
if not in the PROGRAM mode
from the RUN mode
mmmmm
Start Up
if in the PROGRAM mode
1 2
1 2 3
Page 18 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
1 2 3
Page 23
Speed Scroll
OR
To speed scroll up or down press the up or down key and hold, then press the ENTER key and hold. Release to stop.
To Change a Parameter Value:
select parameter, e.g. P005 = 1
1 2 3
initiate change function
1 2 3
security must be disabled
must be pressed to save change
increase or decrease to the desired value.
if no response, security not disabled
Start Up
mmmmm
save and return to select parameter function,
e.g. P005 = 3
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 19
Page 24
Express:
Param eter
to jump back to P005 or
Value
to jump to the factory setting
e.g. P999
jump back to P005
To Access RUN Mode:
e.g. from the PROGRAM mode, P005
exit and return to RUN mode
1 2
mmmmm
Start Up
Page 20 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 25
To Access the PROGRAM Mode:
from the run mode
1 2
e.g. rate display
last parameter from previous PROGRAM session e.g. P005
Master Reset
Prior to programming, balancing and calibration, a master reset of the BW100 should be done.
Refer to
Parameter P999 on
page 64.
Load Cell Balancing
If you are operating a two load cell belt scale, it is recommended that the load cells be balanced electronically prior to initial programming and calibration, or after either or both load cells have been reinstalled or replaced.
Note: Unbalanced load cells adversely affect the performance of your belt
conveyor weighing system.
Load Cell
’A’
test weight bar
typical dual load cell scale
With the conveyor stopped and locked out, lift the belt off the weighing idlers.
Load Cell
’B’
Start Up
mmmmm
belt travel
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 21
Page 26
Place the BW100 into the PROGRAM mode at P291.
test weight on load cell B side
’B’ ’A’
SW2
’B’
test weight
test weight
closed
select P291 ensure SW2
is closed
SW2
open
enter and auto advance to P292,
open SW2
SW2
open
’A’
enter and auto advance to P293,
leave SW2 open
test weight on
load cell A side
mmmmm
Start Up
Remove the test weight, insure that the BW100 SW2 is in ‘close’ position and that P1 is left as set.
Note: Performing a balance procedure requires a subsequent zero and span
recalibration.
Page 22 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
enter and auto advance to P294,
close SW2
enter and auto advance to P295
SW2
closed
P1
adjust until ## = 0 +/- 5
Page 27
Quick Start
Quick Start parameters (P005 to P017) must be programmed for all applications.
Record parameter in Program Record on page 70.
1 2 3
Upon completion of Quick Start programming, a Zero and Span calibration are required for successful entry into the RUN mode.
units
design rate
design speed
speed constant
belt length
test load
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 23
Start Up
mmmmm
Page 28
Start Up
Program P005 - P017
refer to on page 18 for parameter selection and changing values.
Maneuvering
program mode P005, units e.g. 1, t/h
P011, design rate * e.g. 200 t/h
* from design data sheet, if provided
#for constant speed
applications, TB1 - 5/6 jumpered, value is locked at 100.
mmmmm
P014, design speed * e.g. 0.5 m/s
P015, speed constant * e.g. 100.3 pulse / m
P016, belt length e.g. 65.72 m
#
Start Up
Page 24 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
P017, test load * e.g. 55.56 Kg / m
Examples are typical
Page 29
Test load value should be less than design load (P952). If not, contact Siemens or their agent.
Calibration Note: The duration of Zero and Span Calibration is dependent upon
speed (P014), length (P016) and revolutions (P360) of belt.
1 2 3
1 2
Note: To cancel a Zero or Span calibration in progress, press
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 25
Start Up
mmmmm
Page 30
Zero Calibration
Note: Run the conveyor for several minutes to warm up the belt and insure that it
is empty. Test weights are not used during a zero calibration.
zero calibration required
1 2 3
initial zero count
1 2 3
zero calculation, frequency count displayed
1 2
zero deviation calculated, initial deviation = 0
1 2
mmmmm
Start Up
zero deviation accepted, initial zero count = ### Record this value for future
1 2
reference
Perform Span Calibration,
see next page
Page 26 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 31
Span Calibration
Run the conveyor until the belt is empty and stop it. Suspend the test weight from the scale per its instruction manual. Run the conveyor belt empty.
initial span count
1 2
span calculation, frequency count displayed
1 2
1 2
1 2
Remove the test weight when the Span calibration is complete.
1 2
span deviation calculated initial deviation = 0
span deviation accepted initial span count = #### Record this value for future reference
Start Up
mmmmm
successful entry into run, display rate
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 27
Page 32
RUN Mode
LCD
reading
1 2 3
mA bar
graph
Keypad
totalization in process
access PROGRAM mode
= relay status,
appears on alarm
1,2 = remote totalizer
$ flashes at rate
totaling 3 = parameter alert, zero and span calibration required
scroll display
display scroll r= rate t1 = totalizer 1 t2 = totalizer 2 L = load S = speed
initiate zero
initiate span
mmmmm
Start Up
Page 28 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 33
Recalibration
Belt Speed Compensation
In order to achieve optimum accuracy in the rate computation, the belt speed displayed must equal that of the actual belt speed. As the speeds are likely to differ, a belt speed compensation should be performed.
Run the conveyor with the belt empty.
View the belt speed
1 2
Stop the conveyor and measure a length of the belt; marking the forward end (start time) and the back end (stop time). Use the belt scale as the stationary reference.
Run the belt and measure the time for the belt length to pass over the scale.
speed = belt length m or ft.
time s min.
Refer to
with conveyor running empty
Maneuvering
on page 18 for parameter selection and value change.
run mode /speed display, e.g. 0.750 m/s
PROGRAM mode ­assumed speede.g.
0.75 ms
%
If the BW100 constant speed input (TB1-5/6) is jumpered, the design speed (P014) is automatically adjusted.
If a speed sensor is connected, the speed constant (P015) is automatically adjusted.
The display speed (used in the rate computation) now equals the actual speed.
Record the new value in Appendices/Program Record.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 29
enter calculated speed e.g. 0.8 m/s
jumps to P014 or P015 showing new value
Start Up
mmmmm
Page 34
Material Tests
Perform material tests to verify the accuracy of the of the span calibration. If the material tests indicate a repeatable deviation exists, a manual span adjust (P019) is then performed. This procedure automatically alters the span calibration and adjusts the test load (P017) value, yielding more accurate span recalibrations.
Note: Test weights are NOT used during material tests.
1. Run the belt empty.
2. Perform a zero calibration.
3. Put the BW100 into RUN mode
4. Record the BW100 total as the start value
5. Run material at a minimum of 50% of design rate over the belt scale for a minimum of 5 minutes.
6. Stop the material feed and run the conveyor empty.
7. Record the BW100 total as the stop value
8. Subtract the start value from the stop value to determine the BW100 total
9. Weigh the material sample if not already known.
_ _ _ _ _ _
_ _ _ _ _ _
kg / lb
0
BW500
start total
BW500
stop total
scale
kg / lb
scale
BW100 total = _ _ _ _ _ _ material sample weight = _ _ _ _ _ _
Calculate the span adjust value:
% span adjust = BW100 total - material sample weight x 100
material sample weight
mmmmm
Recalibration
Page 30 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 35
If the span adjust value is within the accuracy requirements of the weighing system, the material test was successful and normal operation can be resumed.
If the span adjust value is not acceptable, repeat the material test to verify repeatability. If the result of the second material test differs considerably, consult Milltronics or its agent.
If the span adjust values are significant and repeatable, perform a manual span adjust:
refer to page 18 for parameter selection and value change
if % span adjust is negative, be sure to enter as negative value
Maneuvering
,
PROGRAM mode, P019
enter % span adjust, e.g. 0.05
jumps to P017 adjusted test load, e.g. 97.95
Verify the results of the span adjust by material test or return to normal operation
Design Changes
Where parameters have been changed with a resultant impact on the calibration or do not take effect until a recalibration is done, the parameter warning icon is displayed. In order to clear the icon, perform a zero and span recalibration after the reprogramming session is complete.
If significant changes have been made, an initial zero (P377) and/or initial span (P388) may be required.
Recalibration
In order to maintain the accuracy of the weighing system, periodic zero and span recalibrations are required. Recalibration requirements are highly dependent upon the severity of the application. Perform frequent checks initially, then as time and experience dictate, the frequency of these checks may be reduced. Record deviations for reference.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 31
Recalibration
mmmmm
Page 36
Routine Zero
Run the conveyor empty for several minutes to warm up the belt and insure that it is empty. Test weights are not used during a zero calibration.
From the run mode
initiate zero calibration current zero count = ####
1 2
zero calculation, load value displayed
1 2
zero deviation calculated
1 2
accept deviation new zero count = ####
1 2
return to run mode
1 2
Note: E3 is an indication that the mechanical system is errant. The use of P377,
initial zero
investigation has been exercised.
The cause of the increased deviation must be found and rectified. A zero recalibration as previously described can then be retried.
If the operator deems this deviation to be acceptable, set P377 to 1 to invoke an initial zero calibration. Further deviation limits are now based on this new initial zero.
mmmmm
, should be used judiciously and only after a thorough mechanical
Recalibration
Page 32 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 37
Initial Zero
Perform an initial zero if necessary when a calibration is out of range message is shown.
Refer to
Maneuvering
on page 18 for parameter selection and value change.
select P377
invoke initial zero, enter 1
current zero count
1 2
1 2
1 2
1 2
Perform Initial Span
zero calculation frequency count displayed
zero deviation
zero deviation accepted initial zero count = ####
Recalibration
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 33
Page 38
Direct Zero
Use direct zero entry (P367) when replacing software or hardware, if it is not convenient to perform an initial zero. A record of the last valid zero count is required.
Refer to
Maneuvering
on page 18 for parameter selection and value change.
current zero count
%
enter previously recorded zero count
new zero count accepted
mmmmm
Recalibration
Page 34 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 39
Routine Span
To perform a routine span recalibration, run the conveyor until the belt is empty and stop it. Suspend the test weights from the belt scale per its instruction manual.
Run the conveyor empty at maximum operating speed.
Initiate span
From the zero calibration
1 2
1 2
calibration current span count = ####
span calculation, load value displayed
span deviation = ##
1 2
accept deviation new span count = ####
1 2
return to run mode
1 2
Notes:
E6 is a reminder that a zero calibration is strongly suggested before a span calibration is initiated. Press ENTER to bypass this message.
E4 is an indication that the mechanical system is errant. The use of P388, initial span, should be used judiciously and only after a thorough mechanical investigation has been exercised.
The cause of the increased deviation must be found and rectified. A span recalibration as previously described can then be retried.
If the operator deems this deviation to be acceptable, set P388 to 1 to invoke an initial span calibration. Further deviations are now based on this new initial span.
Note: Remove the test weight when the span calibration is complete.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 35
Recalibration
mmmmm
Page 40
Initial Span
Note: Perform an initial span when a calibration out of range message appears.
Refer to
Maneuvering
on page 18 for parameter selection and value change.
select P388
invoke initial span
current span count = ####
1 2
span calculation, frequency count displayed
1 2
span deviation = ##
1 2
span deviation accepted initial span count = ####
1 2
return to run mode
1 2
mmmmm
Recalibration
Page 36 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 41
Direct Span
Direct span entry (P368) is intended for use when replacing software or hardware, and when it is not convenient to perform an initial span. A record of the last valid span count is required.
Refer to
Maneuvering
on page 18 for parameter selection and value change.
current span count
%
enter previously recorded span count
new span count accepted
Recalibration
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 37
Page 42
Factoring
In order to calculate the value of a new or unknown test weight to the current span, the factoring procedure is used.
Note: For optimum accuracy in the factoring results, a routine zero calibration is
recommended.
Refer to
Maneuvering
on page 18 for parameter selection and value change.
With the conveyor stopped and the belt empty:
hang new test weight onto belt scale, then run the conveyor empty
P359 selected
enter
initiated Factoring, current test load value e.g. 76.11 kg / m
mmmmm
Recalibration
Page 38 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
dynamic test load value e.g. 76.03 kg / m
jumps to P017 dynamic test load value e.g. 76.03 kg / m
return to run mode
1 2
Page 43
Linearization
Conveyor applications where the belt scale is poorly located, or where there is a high degree of variation in belt tension, typically cause the belt scale to report load non­linearly. The BW100 provides a linearizing function (P390 - P396) in order to correct for the deficiency in the weighing system and to provide an accurate report of the actual process.
To verify that the cause of the non-linearity is not mechanical:
1. Run the conveyor belt empty and stop it.
2. Suspend various test weights to the scale to verify mechanical linearity. If the load reported by the BW100 at these tests is non-linear, a mechanical problem is indicated. Refer to the belt scale manual in order to resolve the non-linearity by improved installation or repair.
If it is determined that the non-linearity is due to the weighing application, and not the actual belt scale, apply linearization by performing the following:
zero calibration
span calibration at 90 to 100% of design rate
material tests at 90 to 100% of design rate
manual span adjust if required
material tests at 1 to 3 intermediary flow rates where compensation is required.
Notes:
Compensation points must be at least 10% of the design load apart.
E8 message occurs if a point is less than 10% of full scale or if points are less than 10% apart.
calculate the percentage compensation for each flow rate tested. % compensation = actual weight - totalized weight x 100
totalized weight
Where: actual weight = material test
totalized weight = BW100 total
Recalibration
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 39
Page 44
Example:
A non-linearity with respect to the ideal response exists in a belt scale application with design rate of 200 t/h. It is decided to do material tests at 25, 50 and 75% of the design rate. After performing a zero and a span calibration at 100% of the design rate, followed by material tests and manual span adjust, three material tests were performed at 50, 100 and 150 t/h, as indicated by the BW100. The following data was tabulated. (This example is exaggerated for emphasis).
The material tests should be run at same belt speed, representative of normal operation; in this case 1.2 m/s. For each rate, record the corresponding load value by scrolling to the BW100 load display during running conditions or by calculation.
load = rate
speed
BW100 load
kg/m
11.6 4.2 4.9 -14.3
23.2 8.4 7. 6 10.5
34.7 12.6 13.7 -8.0
material test
tonnes
BW100 total
tonnes
*calculation example: % compensation = 4.2 - 4.9 x 100
4.9
= - 14.3
20
15
actual weight per material test totalized weight by BW100
belt scale response linearized BW100 response
% compensation span (100%)
compensation*
%
-8.0
10
weight = tonnes
5
010
mmmmm
Recalibration
Page 40 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
10.5
3
-14.0
20 30 40 50
load - kg / m
Page 45
Program the BW100 as follows: P390 = 1
P391 = 11.6 P392 = -14.3 P393 = 23.2 P394 = 10.5 P395 = 34.7 P396 = -8
Often only one point of compensation is required, usually at a low load value. In the prior example, if compensation was only required at 11.6 kg/m, the programming could be as follows. Compensation is optimized by establishing the next load value that agrees with the material test, hence where compensation is zero and entering it as the next compensation point.
P390 = 1 P391 = 11.6 P392 = -14.3 P393 = 23.2 P394 = 0 P395 = 34.7 P396 = 0
20
15
actual weight per material test totalized weight by BW100
belt scale response linearized BW100 response
% compensation span (100%)
10
weight = tonnes
5
-14.0
010
3
20 30 40 50
load - kg / m
Recalibration
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 41
Page 46
Operation
Load Sensing
In order for the BW100 to calculate rate and hence totalize material flow along the belt conveyor, a load signal representative of weight of material on the belt is required. The load signal is provided by the belt scale. The BW100 is compatible with belt scales fitted with one or two strain gauge type load cells.
Refer to requirements and connection.
Specifications
on page 3 and
Installation/Load Cell
on page 6 for belt scale
Speed Sensing
In order for the BW100 to calculate rate and hence totalize material flow along the belt conveyor, a speed signal representative of belt speed is required. In constant speed applications (no speed sensor), the BW100 can be programmed to provide an internal speed signal. This is achieved by entering the design speed (P014) and providing a jumper across speed input terminals (TB1-5/6). Speed constant (P015) defaults to 100.
For optimum accuracy of the weighing system, both constant and variable speed applications, a speed sensor is required. Again, the design speed and speed constants need to be programmed, however the jumper across the speed input has to be removed and the speed sensor connected.
Refer to sensor requirements and connection.
Specifications
on page 3 and
Installation/Speed Sensor
on page 6 for speed
Modes of Operation
RUN is the normal or reference mode of operation. It continuously processes the load signal from the belt scale to produce internal load and rate signals, which are in turn used as the basis for totalization, mA output and relay control. The RUN display is programmed (P081) to scroll through rate, totalization, load and speed; either manually by pressing the ENTER key, or automatically. A bar graph is continuously displayed. It is proportional to the analog output as programmed (see
From the RUN mode, access to the PROGRAM mode on and zero and span calibration is made.
The PROGRAM mode allows viewing and, with security permission (P000), changing parameter values. During PROGRAM, RUN mode functions are still active, i.e.: rate, relay, analog output and totalization. Error interrupts are suppressed and the bar graph is disabled.
mmmmm
If the PROGRAM mode is left idle for a period of ten minutes, it automatically reverts to the RUN mode.
Recalibration
Page 42 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Analog Output on
page 43).
Page 47
Damping
Damping (P080) controls the speed at which the displayed readings and output functions respond to changes in their respective input function; load, speed and the internal rate signals. Changes in the displayed rate of material flow, material loading and belt speed are controlled by the damping. Relay alarm functions based on input functions of flow, load and speed, respond to the damped value.
If the specific mA output damping parameter (P220) is enabled (value other than 0), then the damping (P080) as it pertains to the mA function is overridden, and the output value and bar graph respond independently at the specified mA output damping rate (P220).
Analog Output
The BW100 provides one isolated analog output. The output can be assigned (P201) to represent rate, load or speed. The output range can be set to 0 - 20 mA or 4 - 20 mA (P200). The 0 or 4 mA value corresponds to empty or zero condition, whereas the 20 mA value corresponds to the associated design value: rate (P011), load (P952) or speed (P014). The analog output can be limited for over range levels of 0 mA minimum and 22 mA maximum (P212 and P213 respectively). The output 4 and 20 mA levels can also be trimmed (P214 and P215 respectively) to agree with a millammeter or other external mA input device.
Operation
mmmmm
The BW100 LCD provides a bar graph as a function of analog output. It displays the mA value as percentage of the mA range.
The mA output value can be tested using parameter P911. Refer to page 62.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 43
Parameter P911
on
Page 48
Relay Output
The BW100 offers one single pole double throw (SPDT) relay that can be assigned (P100) to one of the following alarm functions:
mmmmm
Operation
rate: relay alarms on high and/or low material flow rate.
auto zero: relay alarms when an attempted auto zero calibration reports an out of range condition (E9).
speed: relay alarms on high and/or low belt speed.
load: relay alarms on high and or low belt load.
error: relay alarms on any error condition as it is reported.
Refer to
Troubleshooting
, page 65.
Except for alarm on ‘auto zero’ and ‘error’, the high and low alarm setpoints (P101 and P102 respectively) are required and must be entered in the appropriate units.
The on / off actuation at both setpoints is buffered by the damping (P080) and the programmable dead band (P117), to prevent relay chatter due to fluctuations. The relay is normally energized; i.e. the normally closed (n.c.) contact held open. Upon an alarm condition, the relay is de-energized and the alarm icon on the BW100 display appears. Once in alarm, the relay and icon remain in alarm status until the alarm condition is removed.
Example:
P014 = 2m/s, design speed P100 = 3, belt speed P101 = 100% (2m/s)
2 m/s
0.4 m/s
high
100%
actual OFF
low
20%
2%
22%
actual ON
20%
alarm ON is with relay de-energized
Page 44 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 49
Totalization
The totalization function is based on the internal rate (mass per unit time) signal proportional to belt speed and load on the associated belt scale. It is not affected by the damping function (P080). The rate signal is sampled several times a second to accurately count the mass of material conveyed. The count is held in the master totalizer used to increment the internal totalizers and to produce a pulse signal for the remote totalizers.
The BW100 provides four separate totalizer functions:
internal totalizer 1
internal totalizer 2
remote totalizer 1
remote totalizer 2
To avoid totalizing material at low flow rates, the totalizer drop out limit (P619) is set to a percentage of the design rate. Below this limit, totalization stops. When material flow returns to a rate above the drop out limit, totalization resumes.
Totalizer resolution or count value is set by the respective control parameters, P631 -­P639. If the resolution selected causes the totalizer to lag behind the count rate, an E2 error is displayed after making the parameter entry. The error is rectified by selecting a greater resolution value.
Example: Internal totalizer 1
Operation
mmmmm
Given: P005 = 1 (t/h)
P631 = 4
Then: totalizer count increments by 10 for each 10 metric tonnes registered
External totalizer 1
Given: P005 = 1 (t/h)
P638 = 5
Then: contact closure occurs once for every 10 metric tonnes registered
For remote totalization, the contact closure duration is set by the respective control parameters, P643 and P644. The value is automatically calculated upon entry of the design rate (P011) and remote totalizer parameters (P638 and P639), so that the duration of contact closure allows the relay response to track the total up to the design rate. The value can be changed to suit specific contact closure requirements, such as in the case of programmable logic controllers. If an E2 error is displayed, P638 or P639 has to be increased.
The totalizers are reset through the master reset (P999), the totalizer reset (P648) or through the keypad.
master reset: the reset of all totalizer functions is included in the master reset.
totalizer reset: totalizer reset can be used to resets internal totalizers 1 and 2, or
totalizer 2 independently.
keypad: pressing simultaneously while in the RUN mode resets
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 45
internal totalizer 1, as well as the internal counts for both remote totalizers.
Page 50
mmmmm
Auto Zero
Operation
Placing the internal totalizers on to the display scroll of the RUN mode is controlled by the totalizer display parameter (P647); displaying either one or both totalizers.
The Auto Zero function allows a zero calibration to be initiated automatically under the following conditions.
the auto zero input (TB1-9/10) is in a closed state; jumper or remote switch
the load is less than 2% of the design load
If the resulting zero deviation is less than an accumulated 2% from the last operator initiated zero, the auto zero is accepted.
If the deviation is greater than an accumulated 2%, an E9 error is displayed and the relay, if so programmed, goes into alarm (refer to error is cleared after five seconds.
If material feed resumes during an auto zero function, the totalizing function is maintained.
Operation/Relay Output,
page 44). The E9
Page 46 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 51
Communications
The BW100 bipolar current loop provides long distance communication to a customer device.
BW10 0
host
device
Bipolar
Converter
Operation
mmmmm
The BW100 communication port (TB1-21 to 25) is software set for baud (P751) and mode enable (P760). Refer to
Installation/Communication
on page 14 for wiring details.
Note: If communicating via Milltronics Dolphin software, the baud rate must be
set to 4800.
Protoc ol
Protocol refers to the format, sequence and value of the data fields used in communication messages. Each data field of a BW100 message contains one or more bytes of ASCII binary code.
Each byte contains:
» 8 data bits » no parity bit » 1 stop bit
+ 20 mA
0
– 20 mA
s
1
2
3
4
5
6
7
t
s
n
r
t
t
t
t
a
t
d
d
h
h
h
h r t
8
s
t
t
h
o p
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 47
Page 52
Data Field Descriptions
The following data fields are used.
som
BW100 start of message, ASCII character = STX (Hex Value = 02).
DEVICE
Identifies the BW100 to which the message applies. The device is a 2 character number that equals the Unit I.D. code, (P761). ASCII characters = 00 to 15.
MT
Identifies the 2 character message type transmitted, ASCII characters:
50 = material flow rate 51 = material load
mmmmm
Communications
READING
Contains the measurement value in the engineering units of measure selected during BW100 programming. The number of bytes in this data field varies dependent upon the reading value. Up to 8 ASCII characters including the decimal point may be transmitted.
52 = belt speed 53 = totalizer 1, internal 54 = totalizer 2, internal
UNITS
Three ASCII characters identify the totalizer engineering units (MT=53 and MT=54). The first character is always a space. The remaining characters may be:
t = tonnes T = tonnes LT = long tonnes kg = Kilograms lb = pounds
eom BW100 end of message, ASCII character = CR (Hex Value = 0D).
Message Requests
Message requests must be transmitted from the host to the BW100 in the following format.
som DEVICE MT eom
Example:
Data ASCII Example Field Character Description
som STX start of message DEVICE 01 for BW100 # 1 MT 50 material flow rate request eom CR end of message
Page 48 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 53
Message Responses
The BW100 response to a flow rate (MT=50) load (MT=51) or speed (MT=52) message request is in the following format.
som DEVICE MT READING eom
Example:
Data ASCII Example Field Character Description
som STX start of message DEVICE 00 from BW100 # 0 MT 50 material flow rate response READING 392.5 is 392.5 eom CR end of message
The response to a material total (MT=53) message request is in the following format.
som DEVICE MT READING UNITS eom
Example:
Communications
mmmmm
Data ASCII Example Field Character Description
som STX start of message DEVICE 01 from BW100 # 1 MT 53 material total response READING 129.2 is 129.2 UNITS t metric tonnes eom CR end of message
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 49
Page 54
Parameters
Note: f denotes factory default.
P000 Security lock
Locks out the programming change value function such that the values of P001 through P999 cannot be changed. This however does not prevent the select function from use; i.e. for viewing values.
Programming is locked out if the value of P000 is other than 1954.
Entry:
mmmmm
1954 = unlocked 1954 = locked
f
Communications
Quick Start (P005 to P017)
Note: Quick Start is the minimum parameter programming required before
attempting a calibration and successful entry into the RUN mode.
P005 Design Rate Units
Determines the units for programming and measurement.
Entry:
f
1
= t/hr (tonnes per hour)
2 = kg/hr (kilograms per hour) 3 = LT/Hr (long tons per hour) 4 = T/h (short tons per hour) 5 = lb/hr (pounds per hour)
Changing this parameter does not affect the rate (P011), belt speed (P014) or belt length (P016) parameters. These parameters should be re-entered for conformity in units.
t = 1000 kg LT = 2240 lb. T = 2000 lb.
P011 Design Rate
Specifies the design rate of material flow for the belt scale.
Enter the design rate from the supplied design data sheet
Page 50 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 55
P014 Design Speed
Specifies the design speed for the conveyor belt.
Speed unit s are:
metre/s if P005 = 1 or 2
feet/min. if P005 = 3, 4 or 5
P015 Speed Constant
This value multiplied with the speed sensor frequency, calculates the actual belt speed.
Entry: If speed input is wired for constant speed (TB1 5/6 jumpered), value defaults to
100.
Enter the speed constant = from the supplied design data sheet
or
= speed sensor pulses per revolution* pulley circumference (m or ft)/ revolution
* refer to speed sensor nameplate or consult Siemens Milltronics or their agent.
Note: Common speed sensor pulses per revolution:
RBSS - 150.4 pulses/meter (45.8 pulses/ft.) TASS - 9.947 pulses/meter (3.03 pulses/ft.)
P016 Belt Length
The length of the conveyor belt (one belt revolution).
Length units are:
metre if P005 = 1 or 2
feet if P005 = 3, 4 or 5
Enter the belt length
P017 Test Load
The load to be referenced when performing a span.
Load units are:
Parameters
mmmmm
kg/m if P005 = 1 or 2
lb./ft. if P005 = 3, 4 or 5
The value for P017 can be calculated as follows:
Test Load=Total weight of of all test weights (kg) or (lb) idler spacing (m) (ft)
End of Quick Start parameters. A calibration can now be performed.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 51
Page 56
P018 Speed Constant Adjust
This parameter allows adjustment to the speed constant (P015).
Initially, this parameter displays the dynamic speed of the belt. If the displayed speed is not equal to the actual speed, enter the actual belt speed.
For speed sensor applications, the value of P015 is automatically adjusted.
For constant speed (TB1 5/6 jumper) the value of P014 is automatically adjusted.
P019 Manual Span Adjust
This parameter allows adjustment to the span calibration.
The adjustment value is generally determined by performing material tests. Refer to
Recalibration/Material Tests,
Enter the calculated adjustment.
page 30.
P022 Minimum Speed Frequency
Sets the minimum frequency that the speed sensor can reliably read. Signals at low frequencies are erratic, adversely affecting the performance of the weighing system.
Entry:
1 = 1 Hz (at 1 Hz, it takes 1 sec before defaulting to 0 speed)
mmmmm
2 = 2 Hz (at 2 Hz, it takes 0.5 sec before defaulting to 0 speed)
Parameters
P080 Damping
Sets the speed of response to which the displayed readings (rate, load and speed), and outputs (alarm and mA) react to change.
Note: The effect of damping (P080) on mA output can be overridden by mA output
damping (P220).
The greater the damping value, the slower the response.
Enter damping value, range 1 - 9999.
P081 Display Mode
Sets the display mode. Normally, the display shows rate, or the last manually selected function. If set to alternating, the display alternates between rate and totalizer (1 and/or 2, as programmed by P647).
Entry:
0 = normal 1 = alternating
Page 52 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 57
Relay/Alarm Function (P100 - P1 17)
Note: These parameter are specific to the use of the relay/alarm function. Refer
to
Operation/Relay Output
P100 Relay Set Up
Sets the alarm mode for the relay.
Entry:
0 = off 1 = rate 2 = auto zero 3 = belt speed 4 = belt load 5 = error
P101 High Alarm
, page 13.
Sets the high alarm setpoint for relay functions P100 = 1, 3 or 4.
Enter the value in % of full scale.
P102 Low Alarm
Sets the low alarm setpoint for relay functions P100 = 1, 3 or 4.
Enter the value in % of full scale.
P1 17 Alarm D ead Band
Sets the dead band to prevent relay chatter due to fluctuations at the high or low setpoint.
Enter the value in % of full scale
End of relay/alarm parameters.
mA Output Parameters (P200 - P220)
Parameters
mmmmm
Note: These parameters are specific to the use of the mA output. Refer to
Operation
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 53
on page 42 for details.
Page 58
P200 mA Range
Sets the range for the mA output.
Entry:
1 = 0 - 20 mA 2 = 4 - 20 mA
P201 mA Function
Assigns the mA output to track one of the integrator functions.
Entry:
1 = rate 2 = load 3 = speed
P212 mA Min Limit
Limits the lower mA range (0 or 4 mA) to a minimum output value.
Enter limit value, range 0 - 22.
P213 mA Max Limit
Limits the upper mA range (20 mA) to a maximum output value.
mmmmm
Parameters
Enter limit value, range 0 - 22.
P214 4 mA Trim
Adjusts the 4 mA output level to agree with a milliammeter or other external mA input device.
Enter trim value, range 0 - 9999.
P215 20 mA Trim
Adjusts the 20 mA output level to agree with a milliammeter or other external mA input device.
Enter trim value, range 0 - 9999
P220 mA Output Damping
Sets the speed at which the mA output reacts to change.
The greater the damping value, the slower the response. If the value is 0, the mA output assumes the damping set in P080.
Enter the damping value, range 0 - 9999
End of mA output parameters.
Page 54 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 59
Load Cell Balancing Parameters (P291 - P295)
Note: These parameters are used for verifying or balancing the load cells (2) on
the associated conveyor belt scale. Refer to procedure for use of these parameters.
P291 Calculator Input 1
This register displays the count associated with the summation of load cell A and B signals, when balancing the A and B load cells of the associated belt scale.
P292 Calculator Input 2
This register displays the count associated with the load B signal, when balancing the A and B load cells of the associated belt scale.
P293 Calculator Input 3
Start Up
, page 17, for details and
This register displays the count associated with the load cell B signal, when balancing the A and B load cells of the associated belt scale.
P294 Calculator Input 4
This register displays the count associated with the summation of load cell A and B signals, when balancing the A and B load cells of the associated belt scale.
P295 Load Cell Balance
Used in conjunction with balance calculator parameters (P291 - P 294), this parameter displays the adjustment required to complete the load cell balance procedure.
End of balancing parameters
P341 Run Time
The cumulative days that the application device has been in service. The time is recorded once daily in a non-resetable counter. Periods of less than 24 hr. are not recorded, nor accumulated.
Parameters
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 55
Page 60
P350 Calibration Security
This parameter provides additional security to the global lock (P000).
Entry:
0 = view parameters, perform zero and span, no reset of totalizer 1 1 = same as level 0, but cannot perform span 2 = same as level 0, but cannot perform zero and span
P359 Factoring
Factoring is used as a method of calculating the value of the test load (P017) to a new physical test weight.
Entry:
0 = idle 1 = factor
Note: Totalization is halted during the factoring procedure, and resumed only
upon return to the RUN mode.
P360 Calibration Duration
Sets the number of belt revolutions to use during a zero or span calibration.
mmmmm
Enter number of belt revolutions, range 1 - 99.
Parameters
P367 Direct Zero
This parameter allows the zero reference count to be viewed or entered directly.
Direct entry is intended for use when replacing software or hardware and it is not convenient to perform an initial zero at that time.
P368 Direct Span
This parameter allows the span reference count to be viewed or entered directly.
Direct entry is intended for use when replacing software or hardware and it is not convenient to perform an initial span at that time.
P370 Zero Limit
Sets the zero calibration deviation limit from the last initial zero. If the accumulated deviation exceeds the limit, the zero calibration is aborted (E3).
Entry:
0 = +/- 12.5% of initial zero 1 = +/- 2% of initial zero
Page 56 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 61
P377 Initial Zero
The initial zero is the reference zero to which all subsequent operator initiated zero calibrations are compared in determining whether they have deviated beyond the zero limit (P370).
Entry:
0 = idle 1 = initial zero
Note: Refer to
Recalibration/Initial Zero
on page 33 for use of this function.
P388 Initial Span
The initial span is the reference to which all subsequent span calibrations are compared in determining whether they have deviated beyond 12.5% of the initial span.
Entry:
0 = idle 1 = initial span
Note: Refer to R
ecalibration/Initial Span
on page 36 for use of this function.
Linearization Parameters (P390 - P396)
Note: These parameters are used to compensate for non-linear response of the
weighing system to the BW100. Refer to Recalibration/Linearization for details and example on the use of these parameters.
Parameters
mmmmm
P390 Linearization
Enables or disables the linearization function.
Entry:
0 = OFF 1 = ON
P391 Linearizer, Point 1
Enter the load, in units of P017, for point 1
P392 Compensation, Point 1
Enter the calculated compensation, in percent, for compensation point 1
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 57
Page 62
P393 Linearizer, Point 2
Enter the load, in units of P017, for point 2.
P394 Compensation, Point 2
Enter the calculated compensation, in percent, for compensation point 2.
P395 Linearizer, Point 3
Enter the load, in units of P017, for point 3.
P396 Compensation, Point 3
Enter the calculated compensation, in percent, for compensation point 3.
End of Linearization Parameters.
Totalization (P619 - P648)
The following parameters are specific to the use to the BW100 totalizers. Refer also to
Operation/Totalization
mmmmm
Parameters
Note: If the resolution (P631 - P639) selected would cause the totalizer to lag
behind the count rate, a message E2 is displayed after making the entry.
Select a greater resolution value.
Example
Given: P005 = 1 (t/h)
Then: totalizer count increments by 10 for each 10 metric tonne registered
P619 Totalizer Drop Out
This parameter sets the limit, in percent of design rate, below which material rates are not totalized.
, page 45.
P631 = 5
The value of 0 is reserved to allow both negative and positive totalization.
Enter drop out value in % of design rate.
Page 58 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 63
P631 Totalizer 1 Resolution, Internal
This parameter sets the resolution of internal totalizer 1.
Entry:
1 = 0.001 (one thousandth) 2 = 0.01 (one hundredth) 3 = 0.1 (one tenth) 4 = 1 (unit) 5 = 10 (x ten) 6 = 100 (x hundred) 7 = 1000 (x thousand)
P632 Totalizer 2 Resolution, Internal
This parameter sets the resolution of internal totalizer 2.
Entry:
1 = 0.001 (one thousandth) 2 = 0.01 (one hundredth) 3 = 0.1 (one tenth) 4 = 1 (unit) 5 = 10 (x ten) 6 = 100 (x hundred) 7 = 1000 (x thousand)
Parameters
P638 Totalizer 1 Resolution, External
This parameter sets the resolution of external totalizer 1.
Entry:
1 = 0.001 (one thousandth) 2 = 0.01 (one hundredth) 3 = 0.1 (one tenth) 4 = 1 (unit) 5 = 10 (x ten) 6 = 100 (x hundred) 7 = 1000 (x thousand)
P639 Totalizer 2 Resolution, External
This parameter sets the resolution of external totalizer 2.
Entry:
1 = 0.001 (one thousandth) 2 = 0.01 (one hundredth) 3 = 0.1 (one tenth) 4 = 1 (unit) 5 = 10 (x ten) 6 = 100 (x hundred) 7 = 1000 (x thousand)
mmmmm
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 59
Page 64
P643 Totalizer 1 Contact Closure, External
The value of this parameter represents a multiple of 32 ms of contact closure for remote totalizer 1. The value is automatically calculated upon entry of P1 (design rate) and P638 (totalizer 1 resolution, external) so that the duration of contact closure allows the transistor switch response to track the total, up to the design rate.
The value can be changed to suit specific contact closure requirements, such as in the case of programmable logic controllers. If a message E2 is displayed, P638 has to be increased.
Entry:
1 = 32 ms 2 = 64 3 = 96 4 = 128 5 = 160 6 = 192 7 = 224 8 = 256 9 = 288
P644 Totalizer 2 Contact Closure, External
The value of this parameter represents a multiple of 32 ms of contact closure for remote totalizer 2. The value is automatically calculated upon entry of P1 (design rate) and P639
mmmmm
Parameters
(totalizer 2 resolution, external) so that the duration of contact closure allows the transistor switch response to track the total, up to the design rate.
The value can be changed to suit specific contact closure requirements, such as in the case of programmable logic controllers. If a message E2 is displayed, P639 has to be increased.
Entry:
1 = 32 ms 6 = 192 2 = 64 7 = 224 3 = 96 8 = 256 4 = 128 9 = 288 5 = 160
P647 Totalizer Display
Selects the totalizer combination to be displayed, either manually through the scroll display key or automatically by control of the display mode (P081).
Entry:
1 = totalizer 1 2 = totalizer 2 3 = totalizers 1 and 2
Page 60 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 65
P648 Totalizer Reset, Internal
Resets the internal totalizers.
Entry:
0 = idle 1 = reset totalizer 2 2 = reset totalizers 1 and 2
End of Totalization parameters.
Communication (P751 - P761)
These parameters are specific to the use of the communication parameters. Refer also to
Communications
P751 Baud Rate
Sets the baud rate for the proprietary bi-polar current loop. This baud rate is not applicable to communication via Milltronics Comverter.
Entry:
, page 47.
300, 1200, 2400, 4800 or 9600 baud
4800 baud is required for Dolphin communications over the bi-polar current loop.
P760 Communication Mode
Selects the communication mode.
bi-polar current loop: interface with the host device (PLC or computer)
infrared link: communication is made using the Milltronics ComVerter.
maintenance: communication is made via the bi-polar current loop for RUN mode operations and infrared link for PROGRAM mode operations
Entry:
1 = bipolar current loop 2 = infrared link 3 = maintenance
P761 Identification Number
Parameters
mmmmm
Sets the identification number for the unit.
Enter the desired identification number, range 0 - 15.
End of communication parameters.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 61
Page 66
Test and Diagnostic (P900 - P951)
Note: These parameters are used for test and diagnostic purposes.
P900 Software Revision
Displays the EPROM (Flash ROM) software revision level.
P901 Memory
Tests the memory. Test is initiated by scrolling to the parameter or repeated by pressing ENTER.
Display:
PASS = normal FAIL = consult Siemens Milltronics.
P907 Programmer Interface
Tests the infrared communications link. Test is initiated by scrolling to the parameter or repeated by pressing ENTER.
Display:
mmmmm
Parameters
PASS = normal FAIL = consult Siemens Milltronics.
infrared communication link mirror
BW100
P911 mA Output Value
Displays the value from the previous measurement. A test value can be entered and the displayed value is transmitted to the output. Upon returning to the RUN mode, the parameter assumes the actual mA output level.
P940 Load Cell A, mVin
Displays the mV signal input from the load cell. Range 0.00 - 60.00 mV.
Page 62 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 67
P941 Load Cell B, mVin
Displays the mV signal input from the load cell. Range 0.00 - 60.00 mV.
P942 V/F converter, Vin
Displays the input voltage to the voltage to frequency converter. Range 0 - 3.98 V
P943 V/F converter, f
Displays the output frequency of the voltage to frequency converter. Range 0 - 131,072
out
P944 Power sensor
Displays a voltage supply reference for diagnostic purposes.
P949 Diagnostic Errors
Enables or disables diagnostic error checking, E101 - E104
Entry:
0 = disable 1 = enable
Refer to
Troubleshooting on
page 65
.
P950 Zero register
Parameters
mmmmm
Registers the number of zero calibrations that have been done since the last master reset.
P951 Span Register
Registers the number of span calibrations that have been done since the last master reset.
P952 Design Load
Displays the value of the design load, which corresponds to the full scale value for alarm and mA output functions. The design load is calculated, based on the design rate and design speed.
End of test and diagnostic parameters.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 63
Page 68
P999 Master Reset
Resets parameters and totalizers to their factory setting.
mmmmm
Parameters
Page 64 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 69
Troubleshooting
message diagnosis action
E1 (program) security code required enter access code into P000
E2 (run) totalizer resolution too low increase value (P631 - P639)
zero out of range consider an initial zero P377,
E3 (run)
span out of range consider an initial span P388,
E4 (run)
refer to
Zero
on page 33
refer to
Span
on page 36
Recalibration/Initial
Recalibration/Initial
E5 (run)
E6 (run) zero calibration required do a zero calibration
E7 (run) span calibration required do a span calibration
E8 (program) parameter value error check that value is valid
E9(run)
E10 (run)
E11 (run)
parameter not entered check parameters P005 - P017
for entry
auto zero out of range auto zero has accumulated
deviation beyond 2% from last operator initial zero. If error is not caused by material on belt, then do an operator initiated zero.
rate or span out of range loading on belt is 300% of rated
load or greater. Investigate and if no mechanical cause, check to see if re-rating the design rate is required.
speed greater than twice the
design speed
check design belt speed against actual belt speed, check speed constant, per­form speed constant adjust (P018) if necessary
Parameters
mmmmm
E12 (factoring)
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 65
span out of range test load is either too low or
beyond 100% of design load (P952). Replace test weight with a heavier or lighter weight and try factoring again.
Page 70
message diagnosis action
E101 (run)
E102 (run)
E103 (run)
load cell A mV reading is out
of range
load cell B mV reading is out
of range
combined mV signal from load cell A and B is out of
range
error will appear if:
• mV signal from load cell A or B is out of the 0-50 mV range
• the mV signal from load cell A or B is less than the zero calibration mV level minus one half the span mV level
• A or B mV is greater than 4 times the span mV value
check load cell mV signal and ensure that it is within range
check wiring
error will appear if the com­bined mV signal from load cell A and B is too low
check both load cell signals and ensure that they are greater than 0 mV
check wiring
cycle power and perform mem­ory test (P901)
E104 (run) faulty memory location found
if error reappears, the BW 100 must be repaired or replaced.
OF
no speed signal check speed circuit or run con-
veyor
Error messages are cleared when the condition is remedied.
RUN mode errors are suppressed during PROGRAM mode, zero or span calibration.
Zero and span errors are cleared when zero or span is initiated. Errors that happen
mmmmm
during the calibration require re-starting the procedure.
Program errors are cleared when any key is pressed.
Troubleshooting
The messages E101 through E104 can be turned off (P949).
The load cell errors are detected by certain conditions where it is apparent that the load cell is not functioning or incorrectly wired. It is not a conclusive test, since even with incorrect wiring, the resulting input from the load cell may be within a valid range.
Page 66 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 71
Maintenance
The BW100 requires no maintenance.
The external surface of the enclosure may be cleaned using a vacuum cleaner and a clean dry paint brush. The display window should be cleaned with a moist non-abrasive cloth.
It is a good idea to check the associated load sensing device, according to its instruction manual.
Software Updates
The software can be updated from a floppy disk by use of a PC (IBM Compatible) with Milltronics Dolphin software. It is recommended that a reset (P999) is done after the software update followed by zero and span calibrations.
Direct zero entry (P367) and direct span entry (P368) will suffice in lieu of dynamic zero and span calibrations. Therefore, zero and span counts should be recorded prior to doing the software update.
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 67
Troubleshooting
mmmmm
Page 72
Appendix
Alphabetical Parameter List
Parameter Number
Alarm Dead Band
Baud Rate
Belt Length
Calculator Input 1
Calculator Input 2
Calculator Input 3
Calculator Input 4
Calibration Duration
Calibration Security
Communication Mode
Compensation Point 1
Compensation Point 2
Compensation Point 3
Damping
Design Rate
P117
P751
P016
P291
P292
P293
P294
P360
P350
P760
P392
P394
P396
P080
P011
mmmmm
Appendix
Design Speed
Direct Span
Direct Zero
Display Mode
Factoring
High Alarm
Identification Number
Initial Zero
Initial Span
Linearization
Linearizer Point 1
Linearizer Point 2
Linearizer Point 3
Load Cell A, mV in
Load Cell B, mV in
Load Cell Balance
P014
P368
P367
P081
P359
P101
P761
P377
P388
P390
P391
P393
P395
P940
P941
P295
Lock
Page 68 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
P000
Page 73
Parameter Number
Low Alarm
mA Function
mA Output Damping
ma Output Value
mA Maximum Limit
mA Minimum Limit
mA Range
mA Trim, 20
mA Trim, 4
Manual Span Adjust
Master Reset
Memory
Minimum Speed Frequency
Power Sensor
Programmer Interface
P102
P201
P220
P911
P213
P212
P200
P215
P214
P019
P999
P901
P022
P944
P907
Relay Set Up
Run Time
Software Revision Number
Span Register
Speed Constant
Speed Constant Adjust
Test Load
Totalizer 1 Closure, External
Totalizer 2 Closure, External
Totalizer 1 Resolution, External
Totalizer 2 Resolution, External
Totalizer 1 Resolution, Internal
Totalizer 2 Resolution, Internal
Tot al i z e r D i s p l a y
Tot al i z e r D rop out
P100
P341
P900
P951
P015
P018
P017
P643
P644
P638
P639
P631
P632
P647
P619
Totalizer Reset, Internal
Units
V/F Converter, V in
V/F Converter, f out
Zero Register
Zero Limit
7ML19985DJ01 Milltronics BW100 - INSTRUCTION MANUAL Page 69
P648
P005
P942
P943
P950
P370
Appendix
mmmmm
Page 74
Program Record
Parameter Value
P005 Units
P011 Design Rate
P014 Design Speed
P015 Speed Constant
P016 Belt Length
P017 Test Load
P018 Speed Constant Adjust
P019 Manual Span Adjust
P022 Minimum speed Frequency
P080 Damping
PO81 Display Mode
P100 Relay Set Up
Program Record
P101 High Alarm
P102 Low Alarm
P117 Alarm Dead Band
P200 mA Range
P201 mA Function
P212 mA Min Limit
P213 mA Max Limit
P220 mA Output Damping
P341 Run Time
P350 Calibration Security
P360Calibration Duration
P367 Direct Zero
P368 Direct Span
P370 Zero Limit
P390 Linearization
P391 Linearizer, Point 1
P392 Compensation, Point 1
P393 Linearizer, Point 2
P394 Compensation, Point 2
mmmmm
P395 Linearizer, Point 3
Appendix
P396 Compensation, Point 3
Page 70 Milltronics BW100 - INSTRUCTION MANUAL 7ML19985DJ01
Page 75
Parameter Value
P396 Compensation, Point 3
P619 Totalizer Dropout
P631 Total 1 Resolution, Int
P632 Total 2 Resolution, Int
P638 Total 1 Resolution, Ext
P639 Total 2 Resolution, Ext
P643 Total 1 Closure, Ext
P644 Total 2 Closure, Ext
P647 Totalizer Display
P648 Totalizer Reset, Int
P751 Baud Rate
P760 Communication Mode
P761 Identification Number
Program Record
P900 Software Rev.#
P949 Diagnostic Errors
P950 Zero Register
P951 Span Register
P952 Design Load
7ML19985DJ01 Milltronics BW100 – INSTRUCTION MANUAL Page 71
Page 76
Index
A
alarm
condition 44
B
belt
speed compensation
belt scale 3
C
controller
45
logic
D
damping
value 52
Dolphin
E
EEPROM 3
F
factoring 38 function
I
inearizer 58
L
linearization 39
load cell
M
mA
Master
P
parameter
1, 3, 47
43
alarm output 43
rate 1
21
analog 1
54
input
64
P000 security lock 50, 56 P005 design rate units P011 design rate P014 design speed 51 P015 speed constant P016 belt length P017 test rate 51, 56 P018 speed adjust P019 manual span adjust P022 minimum speed frequency P080 damping display P081 display scroll mode
43, 45, 50
51
52
29
50
51
30, 52
43, 52
60
52
P101 high alarm/deviation alarm P102 low alarm 53 P117 alarm dead band 53 P200 mA output range P200 mA range 54 P201 mA function 54 P212 mA output minimum P213 mA output maximum 43, 54 P214 mA output trim 43, 54 P215 20 mA output trim P220 mA damping 43, 54 P291 calculator input 1 55 P292 calculator input 2 P293 calculator input 3 55 P295 load cell balancing 55 P341 run time P350 calibration security 56 P359 factoring 56 P360 calibration duration P367 direct zero entry 34, 56 P368 direct span entry 37, 56 P370 zero limit deviation P377 initial zero 57 P388 initial span 57 P390 linearizer P391 linearizer, point 1 57 P392 compensation, point 1 57 P393 linearizer, point 2 P394 compensation, point 2 58 P395 linearizer, point 3 58 P396 compensation, point 3 P619 totalling dropout P631 totalizer resolution P632 totalizer 2 resolution, internal P638 external totalizer resolution
P639 totalizer 2 resolution, external 59 P643 external contact closure P643 totalizer 1 contact closure, exter-
P644 totalizer 2 contact closure, exter-
P647 totalizer display 46, 60 P648 totalizer reset, internal P648 totalzier reset, internal P751 baud rate P760 communication mode
55
39, 57
59, 60
60
nal
60
nal
61
43
43, 54
54
55
56
56, 57
58
45, 58
45, 59
53
58
59 45,
45
45 61
61
7ML19985DJ01 Milltronics BW100 – INSTRUCTION MANUAL Page 72
Page 77
P761 identification number 61 P900 software revision P901 memory test P907 programmer interface 62 P940 load cell ’A’, mVin P941 load cell ’B’, mVin 63 P942 V/F converter, Vin 63 P943 V/F converter, fout P944 power sensor 63 P949 diagnostic errors 63 P999 master reset relay set up 53
paramter
P396 linearizer compensation %
62
45
R
relay
44
alarm
reset
master 45
S
span 37, 56
adjust 30, 31 calibration 27, 30, 39
37
direct initial 33, 37, 57 manual 30 routine
35
T
test
load 30, 56 material weight 27, 35 weights 26, 32
totalizer
functions master 45 remote
30
45
45
1
Z
zero
auto 4 calibration direct initial 33, 34, 57
26, 38
34
62
62
63
39
Page 73 Milltronics BW100 7ML19985DJ01
Page 78
www.siemens-milltronics.com
Siemens Milltronics Process Instruments Inc. 1954Technology Drive, P.O. Box 4225 Peterborough, ON, Canada K9J 7B1 Tel: (705) 745-2431 Fax: (705) 741-0466 Email: techpubs@siemens-milltronics.com
Siemens Milltronics Process Instruments Inc. 2004
Subject to change without prior notice
Rev. 1.1
*7ml19985dj01*
Printed in Canada
Loading...