Siemens MICROMASTER Vector 6SE32, MIDIMASTER Vector 6SE32 Getting Started

Page 1
Press this green button (RUN button) to start the motor.
This is the STOP button.
When the inverter reaches 50Hz output, press this DOWN button and watch the motor speed and display value decrease.
P
Jog
Forward/ reverse
MICROMASTER Vector 6SE32 MIDIMASTER Vector 6SE32
Getting Started
Caution: Before installing and putting this equipment into operation, please read the Operating Instructions Manual for Safety Precautions and Warnings
SIEMENS MICROMASTER
Step 1 Connecting up the MMV and MDV
230V Single Phase 400V Three Phase
The MICROMASTER Vector (MMV) and the MIDIMASTER Vector (MDV) are a range of frequency inverters for controlling the speed of three phase AC induction motors.
Note: Motors above 11kW are usually configured 400V Delta / 690V Star. In this case the motor should be connected in Delta.
Star connection for 400V 3 phase
Delta connection for 230V 3 phase
MIDIMASTER Vector (MDV)
The MDV electrical installation section of the Operator Instructions Manual shows the position of the terminals used to connect the power and the motor.
At any time, press the 'STOP' button and watch the motor stop.
Step 3 Changing the speed of the motor
The default output frequency of the drive is 5Hz (see Hints and Tips to convert this to RPM). This speed will probably be too low for most applications and a speed change may be required. The following steps will allow you to change the preset value of the inverter output to the required speed.
Step / Action
Press the 'P' button to access the parameter settings.
P000
P005
005.0
035.0
P005
P000
000.0
035.0
Press the button 5 times until the display reads P005.
Display
Press the 'P' button to display the current parameter value.
Press the button to change the value to 35Hz. (This number can be any number between 0 and 50Hz - default.)
Press the 'P' button to store the new value.
Press the button until the display reads P000.
Press the 'P' button to exit the parameterisation procedure. The display will alternate between the output frequency and the frequency set point.
The required speed has now been stored.
This method is used to access all parameters.
The drive can now be started by pressing the 'RUN' button. It will ramp up to the frequency held in parameter P005 and remain there. To stop the drive press the 'STOP' button, the drive will then ramp down to 0Hz output.
Default Parameters:
Digital input
ParameterTerminal Default
1 2 3 4 5 6
5 6 7 8 16 17
P051 = 1 P052 = 2 P053 = 6 P054 = 6 P055 = 6 P356 = 6
ON right ON left Fixed frequency 3 Fixed frequency 2 Fixed frequency 1 Fixed frequency 6
Output Relays
1 2
18/19/20 21/22
P061 = 6 P062 = 8
Fault identification Warning active
Fault Codes:
Motor overtemperature by I²t calculation
Other faults, see manual
F001 F002 F003
F005
F074
Overvoltage Overcurrent Overload
Inverter overtemperature (internal PTC)
http://www.con.siemens.co.uk
For further Technical Support Information, and to submit your suggestions for improvements, see our Web Site:
Siemens plc Automation and Drives Varey Road Congleton Cheshire CW12 1PH Great Britain
May 1999 English Order Number: 6SE3286-4BA86
G85139-H1751-U568-D1
F004 Overheating of motor (PTC)
This is the STOP button''
STOP''
'DOWN' button
Hz
Page 2
3_ Mot IEC 56 IM B3
1LA7053-2AA10
Nr. ED510 3053 IP54 Rot KL 16
12 022 I.CI.F
60 Hz 440V Y
0.34A
0.14kW
3360 /min
VDE 0530 S.F. – 1.15
P081 P084
Cos 0.81
P085P082
P083
P080
0.61 0.35A
50Hz
230 400
0.12kW
2800 /min
Cos .810
/Y
/
/
Step 4 Controlling the motor speed with a potentiometer
A potentiometer can be used to control the running speed of the inverter. This is achieved by varying the voltage applied to the analogue input. Connect the potentiometer to the control terminals shown below. Starting and stopping of the motor may be achieved by connecting a switch to the digital input terminals shown.
P006 Set to 1 to allow analogue input P007 Set to 0 to enable control via digital input
The following parameter settings are required
To get the best performance from your drive, you should enter information from your motor ratings plate into certain parameters. The following diagram indicates the location of the information and the parameters which should be entered.
Telling the drive about your motor
Commissioning MICROMASTER Vector / MIDIMASTER Vector
Display parameters
Basic parameters
Motor parameters
Frequently used parameters
Select display
via P001
Display frequency, motor current and motor speed P001 0 = output frequency
1 = frequency setpoint 2 = motor current 5 = motor speed (RPM)
Ramp-up time
P002 0-650 sec.
Ramp-down time
P003 0-650 sec.
Frequency setpoint P006 0 = digital
1 = analog 2 = fixed frequency 3 = digital setpoint addition
Keypad control
P007
0 = disable 1 = enable
Parameter protection P009 0 = only P001-P009 can be
altered 2, 3 = all can be altered.
Nominal rating plate
motor power factor
P080 0.00-1.00
Nominal rating plate frequency for motor
P081 0-650Hz
Nominal rating plate
speed for motor
P082 0-9999 RPM
Nominal rating plate
current for motor
P083 0.1-300.0A
Nominal rating plate
voltage for motor
P084 0-1000V
Nominal rating plate
power for motor
P085
0-250kW
Motor current limit
P086 0-250%
Automatic calibration
P088
Minimum motor frequency
P012
0-650Hz
Maximum motor frequency
P013
0-650Hz
Automatic restart after mains
failure
P015
0 = disable 1 = enable
Start on the fly
P016
0 = disable 2 = enable
Analogue input P023
0 = 0-10V/0-20mA, 1 = 2-10V/4-20mA, 3 = -10V to +10V
Fixed frequency operation
P041-044 P046-049
0-650Hz
Input terminal function
P051-055, 356
Selection relay output
P061, 062
DC injection braking
P073 0-200%
Pulse frequency
P076
See Operator Manual
Control mode
P077
See Operator Manual
Continuous Boost
P078 0-250%
See Operator Manual for other
parameters
Hints and Tips
The direction of rotation of the motor can be reversed during commissioning by changing over two of the output connections on the inverter, or by pressing the Forward/Reverse button.
Parameters P000 to P009 can always be read or set. Access to all other parameters is controlled by the contents of P009. The factory default value is '0' which only allows access to P000 to P009. Changing its value to ‘3' allows all parameters to be accessed permanently. See Operator Manual for the function of other values of P009.
In case there are problems with the parameter settings and you wish to start again, change P944 to '1'. This will reset to the default settings.
The value displayed in P000 is the output frequency of the inverter, this is the default setting but it can be changed by altering the value in P001. For example, changing P001 to a value of '5' will cause the inverter to display the RPM of the motor in P000. See the Operator Manual for other settings of P001.
The default value (0) of parameter P006 ensures that the drive runs at the frequency set in P005. In order to control the output frequency by an analogue input signal, the value of P006 should be set to '1'. For other methods of control using P006, see the Operator Manual.
DIP selection switches are used to select a range of 0-10V or 0-20mA for the analogue input. See the Operator Manual for more information.
An F002 fault is often caused by either too short a ramp time or too much voltage boost. An increase in the values in P002 will increase the ramp time. Alternatively lower the values in P078 and P079 to reduce the voltage boost. Please note that if P078 falls below '100' (default value for MMV) then the motor may under-perform at low frequencies.
An F001 fault is often caused by attempting to stop the motor too quickly - increasing the value in P003 (ramp-down time) will reduce this possibility.
If the display flashes during operation, the drive is registering a warning. Check P931 for the cause.
Loading...