Siemens MEM-1 Installation Instructions Manual

Page 1
Installation Instructions
Model MEM-1 MXL Memory Expansion Module
OPERATION
The Model MEM-1 Memory Expansion module kit provides the MXL System with the additional memory required to support MMB firmware revisions 7.0 and higher. If your MXL System is being upgraded to an MMB firmware revision of 7.0 or higher and the MMB-1 does not have a factory installed MEM-1, then you must install the MEM-1.
INSTALLATION
CAUTION:
Remove all system power before
installation, first battery and then AC.
NOTE: If the MKB-1 in your MXL System
straddles the MMB-1 board, remove the MKB-1 before proceeding.
NOTE: If your MXL System has an IEC-1
module, remove it before installing the MEM-1.
The installation kit for the MEM-1 includes the following items:
1. New IC107 (replaces IC107 on MMB-1)
2. MEM-1
3. Nylon standoff
1. Install the new IC107
A new IC107 (20-pin IC) for the MMB-1 is re­quired to support the MEM-1. This new IC107 replaces the existing IC107 which is in a socket just above and to the left of the expansion con­nector P7 (See Figure 1).
a. Remove the old IC107 from the socket
and replace it with the new IC107 in the MEM-1 kit.
b. Be sure that pin 1 of the new IC107 is
pointing down (toward P7).
2. Install the MEM-1
The MEM-1 installs into P7 on the MMB-1. P7 is a 40-position DIP socket labeled Expansion Connector which is located at the bottom center of the MMB-1. The MEM-1 installs into this socket and spans IC101 which is the large square device to the right of P7. The MEM-1 has an adhesive backed nylon standoff that supports the right side of the module. This standoff must be installed.
a. Remove the paper on the standoff to
expose the adhesive.
b. Insert the 40 pin header (P1) into P7 on
the MMB-1 being careful to align all of the pins. You may have to adjust the standoff so that it clears IC101.
c. Once the header is fully inserted, press
down on the right side of the module to adhere the standoff to the MMB-1.
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-093943-5
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
Page 2
4
3
2
1
4
3
2
1
4
3
2
1
P10
D2300CP
F1
F2
20A
P2 BATTERY
P3 POWER TO MOM-4 2 AMP MAX.
TB3
ANALOG LOOP 2
TB2
ANALOG LOOP 1
TB1
NETWORK
P4
1
PRINTER
AC INPUT
BATTERY
PROGRAMMER
1
CB1
CZM-1
NAC 2
NAC 1
SPV
TRBL
ALR
NAC1
CB2 NAC2
CZM-1 POWER
12
11
10
9
8
7
6
5
4
3
2
1
9
8
7
6
5
4
3
2
1
P1
POWER
F5
P8
POWER
1
MMB-1
TO ANN-1, P1
(ON BACK OF MKB)
POLLING
I
I
C
C
1
1
0
0
7
8
1
1
I C 1 1 5
EXPANSION
P7
1
I C 1 1 0
P6
MOM-4
P5
1
C
C
1
1
1
1
2
1
1
11111
C
C
1
1
1
1
4
3
I
I
I
I
IC 101
TAMPER SWITCH
Figure 1
The MMB-1
3. Set the Jumper on the MEM-1
The MEM-1 has a configuration jumper P2 (See Figure 2) that must be set to work with the MSU-1K kit that contains the new firmware. Refer to the MSU-1K Installation Instructions, P/N 315- 092542, for the proper setting of the jumper.
4. Install the EPROM on the MEM-1
Included in the MSU-1K kit is an EPROM labeled U2. This EPROM goes into the U2 socket on the MEM-1. Refer to the MSU-1K Installation Instruc- tions, P/N 315-092542, for the procedure to install the EPROM.
5. Re-install the IEC-1
If the IEC-1 was removed before installing the MEM-1, re-install it now.
Figure 2
The MEM-1
6. Re-install the MKB-1
If the MKB-1 was removed before installing the MEM-1, re-install it now.
P/N 315-093943-5
ELECTRICAL RATINGS
5VDC, 100mA
Loading...