5/22
Building Technologies CC1N7435en
HVAC Products 11.01.2007
Mechanical design
The housing is made of impact-proof, heat-resistant and flame-retarding plastic.
It is of plug-in design (measuring 91 x 62 x 63 mm, including the base) and engages
audibly in the base.
The housing accommodates the
- programming mechanism with the synchronous motor
- electronic flame signal amplifier (ionization) with the flame relay and the other
switching devices
- lockout reset button with its integrated fault indication lamp
Type summary
The type references given below apply to LGB... burner controls without plug-in base
and without flame detector. For ordering information on plug-in bases and other accessories, refer to «Mechanical design», «Ordering», «Flame supervision ...» and «Technical data».
Flame detector Type reference Approved in: tw/s t1/s TSA/s t3n/s t3/s t4/s t9/s t10/s t11/s t12/s t20/s
6) 3) 3)
ca. min. max. ca. ca. ca. max. min. max. max. ca.
Burner controls for 2-stage burners without contr ol of act uator
Ionization probe (ION)
LGB21.130A27 4)7)
CH, EU, S, SF 8 7 3 2.4 2 8 --- 5 --- --- 6
LGB21.230A27 5)
CH, EU, S, SF 8 15 3 2.4 2 8 --- 5 --- --- 38 or UV detector QRA...
with AGQ1...A27
LGB21.330A27 5)
CH, EU, H, S, SF 8 30 3 2.4 2 8 --- 5 --- --- 23
LGB21.350A27 5)7)
CH, EU, H, S, SF 8 30 5 4 2 10 --- 5 --- --- 21
LGB21.550A27 5)
AUS, CH, EU 8 50 5 4 2 10 --- 5 --- --- 2
Burner controls for 2-stage burners with control of actuator
Ionization probe (ION)
LGB22.130A27 4)
CH, EU, N, S 9 7 3 2.4 3 8 --- 4 12 12 21
or UV detector QRA...
LGB22.230B27 5)
CH, EU, N, S, SF 9 20 3 2.4 3 8 --- 4 16.5 16.5 2
with AGQ1...A27
LGB22.330A27 5)7)
AUS, CH, EU, H, N, S, SF 9 30 3 2.4 3 8 --- 4 12 11 2
LGB22.330A270 5)8)
EU 9 30 3 2.4 3 8 --- 4 12 11 2
Blue-flame detector
LGB32.130A27 4)1)
CH, EU 9 7 3 2.4 3 8 --- 4 12 12 21
QRC1...
LGB32.230A27 5)1)
CH, EU 9 20 3 2.4 3 8 --- 4 12 12 2
LGB32.330A27 5)
CH, EU 9 30 3 2.4 3 8 --- 4 12 11 2
LGB32.350A27 5)
CH, EU 9 30 5 4.4 1 10 --- 4 12 9 2
Burner controls for atmospheric burners
Ionization probe (ION)
LGB41.255A27
EU 18 --- 5 4 2 10 5 --- --- --- 10
or UV detector QRA...
with AGQ1...A27
LGB41.258A27 2)5)7)
CH, EU, H, SF 18 --- 5 4 2 10 8 --- --- --- 10
Legend
tw Waiting time 1) On request
t1 Prepurge time 2) For atmospheric burners up to 120 kW
TSA Ignition safety time 3) Maximum running time available for actuator
t3 Preignitio n time 4) Also suited for flash steam generators
t3n Postignition time 5) Also suited for stationary direct-fired air heaters
t4 Interval «BV1-BV2» or «BV1-LR» 6) «t9» + reaction time of flame relay
t9 Second safety time 7) Also available for AC 100...110 V; in that case, the last 2
t10 Specified time for air pressure signal digits read ...17 in place of ...27
t11 Programmed opening time for actuator «SA» 8) Without internal microfuse; must only be used in connection
t12 Programmed closing time for actuator «SA» with external microfuse 6.3 A (slow)!
t20 Interval up to self-shutdown of programming mechanism