Siemens LCM-OAVS 570-804PA Installation Instructions Manual

Installation Instructions
Document No. 570-114
October 26, 2016
BACnet LCM-OAVS with HW Reheat and Two Venturi Air Valves One Exhaust, One Supply Applications 6750 (RTS) 6756 (BTU)
This controller requires Offboard Air Module(s) (ordered and shipped separately
570-804PA
Generic Controller I/O Layout. See Wiring Diagram for application specific details.
Control Applications
6750, 6756
Product Description
The Siemens Venturi Air Valve is a pre-packaged, easy to install airflow measurement and control solution. It provides stable and precise airflow control of room supply, room general exhaust or fume hood exhaust.
These instructions explain how to field install or replace the BACnet Laboratory Controller Module LCM.
This BACnet LCM-OAVS VAV Room Pressurization Controller with HW Reheat and Two Fast-acting Venturi Air Valves One Exhaust, One Supply features VAV control of a laboratory room with one supply duct, one exhaust duct, and up to six Fume Hoods. It uses fast-acting electronic actuators (shipped separately) to control the supply and
exhaust Venturi air valves.
Item No. 570-114 Rev. CA Page 1 of 8
This controller is built on a BACnet Programmable TEC (PTEC) platform that supports up to two Offboard AVS signals; however, Onboard AVS transducers are not supported. Offboard Air Module(s) (OAM) house AVS transducers and send signals to the AVS input(s) on the LCM OAVS board.
The LCM can operate stand-alone, with a field panel, or as part of a network.
Product Numbers
See the
Technical Specification Sheet Configuration and Sizing
section of InfoLink.
Venturi Air Valve for Critical Environments
(149-425) or
in the Critical Environments
Document No. 570-114
Offboard Air Module – two required, order separately
550-819B
Siemens fast-acting Lab Electronic Actuator(s) – order and ship separately)
GNP191.1U
CAUTION
Keep the unit in its static-proof bag until installation.
Otherwise, you run the risk of damage to the printed circuit board from electrostatic discharge.
Low cost temporary temperature sensor, 10K Ω thermistor with
RJ11 (1” long), that enables space
control if the permanent room or duct sensor is not installed (pack of
25).
540-658P25
Duct Temperature Sensor, NTC
10K Ω Type 2, 3" Probe for
Commissioning only.
QAM1030.008P50
WARNING
Personal injury/loss of life may occur if you do not follow the procedures as specified.
CAUTION
Equipment damage or loss of data may occur if you do not follow the procedures as specified.
NOTE: A low-cost temporary RTS (540-658P25) is available that plugs into the RTS port on the controller, providing temperature input and actual space control until a permanent RTS is installed.
NOTE: All wiring must conform to national and local codes and regulations (NEC, CE, and so on).
Installation Instructions October 26, 2016
Shipping carton includes a controller assembly, a mounting rail, and two self-tapping/drilling screws.
Accessories
Prerequisites
Wiring conforms to NEC and local codes and
regulations. For further information, see the
Wiring Guidelines Manual
(Optional)
24 Vac Class 2 power available. Supply power to the unit is OFF. Any application specific hardware or devices
Room temperature sensor installed.
installed.
(125-3002).
Warning/Caution Notation
Required Tools and Equipment
Small flat blade screwdriver 3/8-inch open end wrench
Expected Installation Time
30 minutes
Installation Instructions
1. Secure the mounting rail in the controller’s desired location.
2. Place the ESD wrist strap on your wrist and attach it to a good earth ground.
3. Remove the controller from the static proof bag and snap it into place on the mounting rail.
4. If the controller will be used with a field panel, disconnect the field level network (FLN) trunk from the field panel.
5. Wire the FLN trunk to the controller. After all controllers are connected to the FLN, reconnect the FLN trunk to the field panel.
Needle nose pliers 1/4-inch poly tubing
Page 2 of 8 Siemens Industry, Inc.
Document No. 570-114
CAUTION
DO Wiring – Each DO provides a Normally Open (NO) terminal and a Common (C) terminal.
To reduce noise and the potential for ground loops, both connections of a 24 Vac load must be wired directly to the DO terminal on the controller board.
CAUTION
The fume hood flow module, the FHC, any 0 to 10 Vdc actuator used by the LCM, and the LCM cannot share a single power trunk.
The preferred configuration for shared power trunks is to use one trunk for the FFM and FHC and another trunk for the actuator(s) and LCM.
8.
For each Fast Acting Lab Electronic Actuator, verify that the switches are set as shown in Figure
Switch Settings for the Fast Acting
Lab Electronic Actuator
.
Supply
Exhaust
Switch Settings for the Fast Acting Lab Electronic
Actuator.
CAUTION
This actuator requires a maximum of 20 VA, 24 Vac source.
DO NOT connect any other non­isolated devices to the transformer that powers the electronic actuator or the hot water valve actuator.
9.
Plug the room temperature sensor cable into the RTS port.
10.
Connect the power trunk. DO NOT apply power to the controller without first consulting the specialist.
CAUTION
It is important that the neutral that supplies the TEC must be earth grounded at the source of the 24 Vac power.
Possible erratic equipment operation or damage if neutral is not grounded.
Installation Instructions
October 26, 2016
6. If the controller requires Offboard Air Modules, install them now following the appropriate Installation Instructions (see
7. Connect the point wiring (see
Product Numbers
Wiring Diagram
).
s).
Siemens Industry, Inc. Page 3 of 8
The installation is complete.
Dimensions.
Loading...
+ 5 hidden pages