• Building maintenance companies, facility management.
• Real estate agencies.
• District heating companies, installers, end customers.
Functions
Basic functions Basic functions of the central communication unit OZW775:
• Monitor KNX network member devices and acquire fault statuses in HVAC plants via
digital and universal inputs.
• Signal faults via direct connection to local operator station and/or via modem to
operator stations, SMS recipients, pagers, fax machines, email recipients.
• Central communication unit V2.0 with web server: Send faults to web browser via
Ethernet and/or direct connection or modem.
• Operate HVAC plants and equipment with operator stations and/or web browser, and
display process values on operator stations and/or web browser.
• Function "Clock time master" for default system time (date and time) to KNX network
member devices.
• Function "System clock" with adjustable time zone and daylight saving/standard time
changeover.
Faults
Fault sources
• "System" fault source
The central communication unit detects device failures and faults on the KNX
network listed in the unit’s device list.
• "Local" fault source
The central communication unit identifies internal faults and fault states at the digital
and universal inputs configured as fault inputs (fault source "Local"). Typical faults at
digital and universal inputs:
− Overload signals from thermal cutouts.
− Error states signaled by switches or monitors.
− Limit value violations.
− Fault states of aggregates and plants.
− Common messages from external plants.
Fault indication Depending on the fault's source, the central communication unit indicates faults either
via "Local" or "System" LED. The "Local" LED also indicates state "Hours run for
service reached".
Fault relays
You can configure two relay outputs as fault relays. As a result, faults can be indicated
by optical or acoustic alarm equipment in addition to LEDs.
Fault status message
Faults can also be sent as text messages via PC or modem interface. For messages
via modem, both the number of repetitions and the modem message interval can be
parameterized.
2/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 3
Fault acknowledgement
A
The "Local" LED blinks to indicate that a fault is unacknowledged. The LED continues
to be lit until the fault is no longer pending even after the fault is acknowledged with the
"Ack" button. "Ack" resets the fault relay if a fault relay is configured.
The same applies to unacknowledged "System" faults in the event of a configured fault
relay. Without fault relay, a "System" fault is acknowledged automatically, i.e. the
"System" LED is lit immediately (no blinking until acknowledged).
External fault acknowledgement is possible via digital input, provided the input is
connected to input "Ack" on function block "Faults".
System report The central communication unit can generate system reports and periodically send the
system operating state to different types of message receivers.
History The history includes the last 500 events on faults, fault messages, and system reports.
The events are entered in the circular message buffer of the central communication
unit. The history data can be read via web browser and the ACS software.
Offline trend "Offline trend" allows logging values for selected data points of the central
communication unit and for Synco devices listed in the device list. The ACS7 software
is necessary to define trends and trend displays on an operator station as well as to
specify data exports (e.g. to Excel).
5 offline trends can be defined and run at the same time. One trend may contain 10,000
values (number of data points x number of samplings).
Central communication unit memory to log for each trend: Examples
• 1 data point at 30 second intervals for 83 hours.
• 6 data points at 30 second intervals for 27 hours.
• 10 data points at 5 minute intervals for 7 days.
The number of values that can be logged is reduced if text information (e.g. input
names, aggregate names for runtime totalization) is also recorded.
Ordering and delivery
When ordering, provide both name and product number (ASN):
• Central communication unit OZW775
The central communication unit is delivered in a box. The following are inserted in the
package:
• Installation instructions G5663 (multilingual).
• CD with ACS700 software.
Commissioning instructions C5663 saved as a PDF file on the CD.
ccessories
Order the following accessories separately:
• Ethernet card OZZ7E5
• CF card (Compact flash card) OZZ7CF
Note
The CF card contains the latest firmware version and web server data. See document
G5663 on firmware updates and preparing web server data.
3/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 4
Product documentation
A
Central communication
unit OZW775
Document typeDocument no.
Data sheet
Installation instructions (package insert)
Commissioning instructions
Ethernet card OZZ7E5
Mounting instructions (package insert)
Information on OZZ7E5: See this document and Æ
CF card OZZ7CF
Operating instructions (package insert)
Information on OZZ7CF: See this document and Æ
KNX bus
Data sheet
Basic documentation
CS7… software
Data sheet
Service tool OCI700.1
Data sheet
Synco products The following Synco products can be integrated in a KNX network:
Synco 700 devices
ProductData sheet no.
Universal controller RMU7x0, RMU7x0B
Heating controller RMH760, RMH760B
Boiler sequence controller RMK770
Central control unit RMB795
Switching & monitoring device RMS705
Bus operator unit RMZ792
Room unit QAW740
Central communication unit OZW771
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 5
Mechanical design
Basic design
The central communication unit consists of the housing lower section with printed circuit
boards and connection terminals. The upper housing section contains the printed circuit
boards. The LEDs, operating buttons, interfaces, and slots for the CF cards (compact
flash memory cards) are integrated in the upper housing section. These elements and
the connection terminals are labeled on the front of the housing. The shape and dimensions of the housing sections conform to DIN 43880 (size 2).
12
Q
11 12 21 22
Q
QQ QQQQ
18 19 20 21
34567
OZW775OZW775
OZW775
040601A001001
XXXXXXXXXXXX HEX
8
XX:XX:XX:XX:XX:XX
9
10
11 12 1314 15
161718
19
20 21
22232425 2627
Position Labeling Element
1 PCUSB interface
2 D1...D8 M Connection terminal digital inputs (M = ground)
3 X1...X8 M Connection terminals universal inputs (M = ground)
4 Upper housing section
5 Modem RS-232 interface
6 KNX LED (green/red) Bus voltage, data exchange via KNX (green) / unit in addressing mode (red)
7 CE- CE+KNX (Konnex) connection terminals
8 EthernetEthernet plug RJ45 on Ethernet card OZZ7E5 (order card separately)
9 XX:XX:XX:XX:XX:XXMAC address (Media Access Control address, 48 bits)
10 RunLED (green) Operating voltage applied (lit), communicating with ACS (flashing)
11 LocalLED (red) Central unit faults or faults at fault inputs, or "Hours run for service reached"
12 SystemLED (red) Device faults in the KNX network
13 CF cardsLED (green) CF card integrated (lit), CF card being integrated or removed (flashing)
14 G G0Connection terminals for AC 24 V operating voltage
15 ConfigButton Integrate or remove CF card
16 AckButton Acknowledgement of "Local" fault, fault relay "System"
17 CF card memorySlot for CF card (web server data)
18 CF Card Config/ReportSlot for CF card (firmware update)
19 Q11,Q12 Q21,Q22
Q31,Q32 Q41,Q42
20 ReportButton For function, see “Button combinations“
21 ModemButton initializes modem, checks connection to the modem (short) / sends system report (long)
22 Q73,Q74 Q83,Q84Connection terminals for 2 relays with NO contact
23 Lug for cable tie (cable strain relief)
24 Fastening spring to mount the central communication unit to a standard rail TH 35-7.5
25 Snap cover
26 Cover (can be opened without tools if Ethernet card OZZ7E5 needs to be inserted)
27 Lower housing section
Connection terminals for 4 relays with NC contacts
5663Z01
5/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 6
Technical design
Inputs and outputs
Digital inputs
Universal inputs
Relay outputs
The central communication unit contains various function blocks (FB). The functionality
of the unit can be extended by connecting (binding) the digital inputs N.D1…N.D8 and
the universal inputs N.X1…N.X8 to the FB inputs "d", "x", and "i" (see figure and
function block description).
The digital inputs N.D1…N.D8 help connect potential-free status contacts. They act as
fault inputs when connecting digital inputs to FB "Faults". When connected to FB
"Operating hours", the number of operating hours of aggregates (burners, pumps, fans,
etc.), can be counted.
The universal inputs N.X1…N.X8 can be configured for potential-free status and
counting impulse contacts and analog signals from sensors and transmitters.
Universal inputs configured for status contacts (digital) or limit values (analog) and
connected to FB "Faults" act as fault inputs.
When universal inputs are configured for operating status contacts of aggregates and
connected to FB "Operating hours", the operating hours can be acquired.
When universal inputs are configured for counting pulses and connected to FB
"Meters", consumption values (heat, gas, electricity, etc.) can be acquired.
The outputs of relays N.Q1…N.Q4 have NC contacts, those of relays N.Q7, N.Q8 have
NO contacts. To signal faults (e.g. with signal lamps, horns), relay 1 and/or relay 2 of
FB "Faults" are connected to one of the relays N.Q_.
If one of the relays N.Q_ is connected to an FB "7-day time switch with control switch",
relay N.Q_ in "Auto" position operates as per the time switch program, else per the
control switch position "Off" or "On".
N.D1N.D2N.D3N.D4N.D5N.D6N.D7N.D8
dddd
d
Ack
Faults
Relay 1 Relay 2
Q
On/Off
1
N.Q1N.Q2
Inputs, outputs and function blocks of the OZW775 central communication unit.
1234567891011
Q
QQ
Q
Input identifier
xxxxxxxx x xx xxx
On/OffOn/OffOn/Off
Q
N.Q3
Q
N.Q4
ddd d
xxxxxx
12
32
QQ
131415
N.Q7
171819
16
4
Q
20
QQ
N.Q8
N.X1N.X2N.X3N.X4N.X5N.X6N.X7N.X8
System
Intern
Message receivers
System report
xxxxxxxx
d
dddd
1
234
Operat ing hoursMe t er s
Ein/Aus
Receiv e r 1
1
d
iiiiiiii
5
Receiv e r 2
On/Off
a
d
r
e
a
n
l
C
ccc
cc
PC USB
1
On/Off
2
d
e
a
n
l
C
2345 6
Receiv er 3
On/Off
a
r
c
ModemEthernet
d
e
n
a
l
C
a
r
78
Receiv e r 4
On/Off
43
e
a
l
C
c
a
d
r
n
5663B01en
6/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 7
Function blocks
FB "Faults"
FB "Operating hours"
FB "Meters"
FB "7-day time switch
with operation selector"
FB "System report"
FB "Message receivers"
FB "Faults" is designed for 20 fault inputs. Inputs N.D1…N.D8 (digital) and N.X1…N.X8
(digital/analog) are connected to FB inputs "x". "Relay 1" and/or "Relay 2" is activated
depending on fault priority and source.
FB "Faults" handles faults and failures of the Synco devices (“System“ faults) listed in
the device list as well as faults at the fault inputs and faults of the central
communication unit ("Local" faults)..
To facilitate external fault acknowledgement, a digital input must be connected to input
"Ack". External fault acknowledgement acts like pressing the "Ack" button.
FB "Operating hours" can handle up to 5 runtime totalizers. The operational status
contacts of the aggregates are connected to FB inputs "d" via the digital inputs
N.D1...N.D8 or N.X1...N.X8 (configured as digital inputs).
If a service interval is defined, the “Local“ LED indicates when the number of operating
hours is reached and, if configured, a service alarm is issued.
FB "Meters" can handle up to 8 counting values. The universal inputs N.X1…N.X8
(configured as counting pulses) are connected to the FB inputs "i". The acquired
counting pulses from heat, water, gas, electricity meters are converted to consumption
values, e.g. energy in Wh, kWh or volume in m
3
. The 15 monthly values along with
readout dates are stored.
The 4 FB "7-day time switch with control switch" allow for switching various consumers
in dependence of time via the relays N.Q_. Each 7-day time switch allows for programming up to 6 switching points (3 "On", 3 "Off". Additionally, a configurable operation
selector with positions "Auto" / "Off" / "On" is integrated.
If a time switch output "Q" is connected to a relay input, position "Auto" ensures that the
relay is energized and deenergized as per the time program, or the relay is constantly
deenergized or energized.
In FB "System report", the time the message is sent (hh:mm) and the message cycle
interval (1...255 days) for sending system reports can be programmed. A system report
is sent to one or several message receivers depending on fault priority (urgent/not
urgent).
FB "Message receivers" is subdivided into 4 receivers. Message suppression via input
"d" acts on all receivers. You can set both receiver type and fault priority individually for
each receiver. Each receiver has a "Time switch with calendar" to program three
sending times per day and holidays/special days.
Example: All fault messages from Monday through Friday 08:00 - 18:00 are sent to
receiver "Service business receiver", e.g. to a fax machine. Outside these hours, the
fault status messages are sent to receiver "24-hour service", e.g. SMS to mobile phone.
The outputs "c" of FB "Message receivers" are connected to inputs "c" of the PC USB,
modem, or Ethernet interfaces. The PC USB interface is designed for local commissioning, operation and monitoring (alarming).
Remote operation and monitoring are possible via modem (dial-up) and, at the same
time, via Ethernet (Internet/intranet) to one (or several) web browsers.
7/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 8
Interfaces The central communication unit has three interfaces to communicate between unit and
user, and the interface or connection for the KNX bus.
PC
The "PC" interface is intended to directly connect a central communication unit to a
local operator station. A USB cable, type A-B, is required to this end.
Modem
The "Modem" interface is intended to connect a modem via RS-232. When communicating via modem, the following message recipients are supported: Operator stations
(PC/laptop with ACS software), SMS recipients, pagers, fax machines.
Ethernet
The interface labeled "Ethernet" corresponds to a RJ45 plug on the Ethernet card
OZZ7E5. Order the card separately and insert in the central communication unit. A
network cable Cat-5 is required to connect to the Ethernet (Ethernet category 5 cable).
KNX
The"KNX" labeled connection terminals CE+ and CE- are intended for the KNX bus.
For more information on the KNX bus, see data sheet N3127.
Parallel operation
We speak of parallel operation if one central communication unit is operated with two or
multiple operator stations. Also, e.g. with one operator station via USB, and/or via
modem, and/or via Ethernet.
Operation
Communication connections for local operation (USB), and for remote operation via
modem and Ethernet.
8/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 9
Monitoring,
alarming
Communication connections for local monitoring and alarming (USB), and for remote
operation via modem and Ethernet.
Parameter settings for
message receivers
The following table lists all parameters for the communication connections that can be
set in each message receiver.
Receiver type Interface Modem type Transmission protocol
--- (Default) - - Email Ethernet xx SMTP
ACS alarm
Mobile phone
Fax machine
Pager
USB xx
Modem Analog/ISDN
GSM
Ethernet xx
Modem Analog/ISDN TAP
UCP
GSM
Modem Analog Fax protocol
GSM Fax protocol
SMS GSM service
Modem Analog/ISDN TAP
GSM TAP
SMS GSM service
ACS protocol
SMS GSM
No other selection
- Value cannot be set or not value entry required
xx No modem required
Bold/Italics Default value
Example: Receiver type = EmailInterface = Ethernet (Default if receiver type = Email)
Transmission protocol = SMTP (Default if receiver type = Email)
9/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 10
Mounting notes
Installation notes
You must mount the central communication unit in a cabinet or control panel. Make
sure service can easily access the unit.
• Standard mounting On standard rail TH 35-7.5
• Screwed-on mounting Screwed to rear wall
• Mounting position Horizontal only
• Mounting and dimensions See "Dimensions"
Important notes
Observe the following important notes for mounting and installation:
• The central communication unit must
be mounted in a cabinet or control panel,
as when mounted on a freely accessible wall, the relay output terminals
carrying mains voltage (bottom of the unit, terminals not covered) are not
protected against electric shock hazard.
• Run fuses, switches, wiring and earthing as per local regulations for electrical
installations.
• The relay contacts of the central communication unit can switch either mains
voltage or
low-voltage. Applying both mains and low voltage is not permitted.
• You must connect circuits with relay contacts Q11, Q12 through Q41, 42 to the
same mains phase.
• You must connect circuits with relay contacts Q73, Q74 and Q83, Q84 to the
same mains phase.
• Connect only potential-free contacts to digital inputs D1…D8 and universal
inputs X1…X8 (configured for digital inputs signals).
• We do not recommend plant monitoring via PC interface in environments with
strong electromagnetic interference (e.g. in industrial environments with
electrical welding equipment).
Operating voltage The central communication unit operates on AC 24 V and must meet requirements for
SELV/ PELV (safety extra low-voltage / protective extra low-voltage).
Use only safety isolating transformers suited for 100 % duty (as per
EN 61558-2-6).
Wiring Plan sufficient space around the unit for easy wiring. The unit’s terminals are arranged
to eliminate cross-wiring of input and output lines to prevent faulty wiring to the greatest
extent possible.
The terminals for digital inputs, universal inputs, and the KNX bus are located at the top
of the unit (low-voltage side). The terminals for AC 24 V operating voltage and relay
outputs carrying mains voltage are located at the bottom (mains voltage side).
Connecting terminals
The terminals are designed for wire diameters of min. 0.8 mm or cross-sections of
0.5...2.5 mm
2
. See "Technical data".
10/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 11
Commissioning notes
A
A
uthorized staff Only authorized staff may commission and parameterize the central communication
unit as well as start the web server.
Select telephone service
provider and modem
You must select the telephone service provider and modem depending on the message
receiver type prior to commissioning. If you use a GSM modem, make sure that the
SIM card allows for data communication and that it is not protected by a PIN code.
IP address Before activating the web server via the web browser on Ethernet, the network system
administrator must assign the IP address for the central communication unit.
Commissioning
Commission the central communication unit locally via PC interface using a PC/laptop.
The service tool ACS must be installed on the PC/laptop.
You need a USB cable, type A-B, to locally connect the PC interface of the
communication unit to the PC/laptop.
The installation instructions G5663xx (enclosed with unit), topic “Commissioning“ also
point out important commissioning issues.
Parameterization Parameterize the central communication unit locally via PC interface using a PC/laptop
and service tool ACS.
Read the commissioning instructions C5663 for the associated procedure. The commissioning instructions PDF file is saved to the CD supplied with the unit. You can also
download the PDF file from www.siemens.com/synco
Web server
Local activation
Locally activate the web server following
commissioning and parameterization of the
central communication unit.
You need a USB cable, type A-B, to locally connect the PC interface of the communication unit to the PC/laptop.
The installation instructions G5663xx (enclosed with unit) stress the following issues:
• Insert Ethernet card.
• Update firmware.
• Prepare web server data.
• Start web browser with IP address 192.168.250.1 and login.
ctivate via
Ethernet connection
See the commissioning instructions C5663 for information on how to activate the web
server via Ethernet connection (Ethernet card OZZ7E5). The PDF file of the commissioning instructions are saved on the CD supplied with the unit. You can also download
the PDF file from www.siemens.com/synco
11/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 12
LED displays
A
A
Run (green) Dark No operating voltage AC 24 V or unit is starting.
Lit Unit ready to operate.
Flashing Communicating with ACS.
Local (red)
Dark No fault (normal operating state).
Lit Central communication unit faults and/or signal at fault inputs "Hours run for
service reached".
Flashing Fault unacknowledged.
System (red)
Without configured fault relay "System" in the OZW775:
Dark No fault (normal operating state).
Lit Device fault in KNX network.
With configured fault relay "System" in the OZW775:
Dark No fault (normal operating state).
Lit Device fault in KNX network, fault relay acknowledged.
Flashing Device fault in KNX network, fault relay unacknowledged.
CF cards (green)
Dark No CF card integrated.
Lit CF card integrated.
Flashing CF card is being integrated or removed
(after pressing button "long" on "Config").
KNX (green/red)
Dark No bus power supply.
Steady green Bus power supply available.
Flashing green Data exchange via KNX.
Steady red Unit in addressing mode.
Operating buttons
Pressing the button briefly ("short") means <2 seconds, "long" >4 seconds.
Config Short No function.
Long Integrate or remove CF card (or both CF cards).
ck
Short Acknowledge "Local" fault, fault relay "System".
Long See “Button combinations“.
Report
Short No function.
Long See “Button combinations“.
Short Initializes modem, checks modem connection. Modem
Long Initializes modem, sends system report to configured receivers.
Button combinations For button combinations, always press "long" (>4 seconds).
ddressing mode
Simultaneously press "Modem" and "Report" (programming mode).
Restart central unit
Simultaneously press "Modem" and "Ack".
Default state
Simultaneously press "Modem", "Ack", and "Config".
Note: All configuration data and settings are reset. The device list and all unsent
messages are deleted. History data is not deleted.
12/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 13
General notes
Maintenance The OZW775 central communication unit requires no maintenance (no battery
changes, no fuses). Clean the housing only with a dry cloth.
Repair
The central communication unit OZW775 cannot be repaired in the field. If faulty, return
to the Repair Center of the relevant Siemens Regional Company.
Disposal
The central communication unit is subject to directive 2002/96/EEC (WEEE, Waste of
Electrical and Electronic Equipment).
"Dispose of the device as electronic waste in compliance with European directive
2002/96/EEC (WEEE) and not as municipal waste. Observe all relevant national
regulations and dispose of the unit correctly. Comply with all local and currently valid
legislation".
Technical data
Power supply G, G0
Functional data
Digital inputs D1...D8
Universal inputs X1...X8
Operating voltage
Rated voltage as per EN 60950-1
Safety extra low-voltage (SELV) / protective extra low-voltage
(PELV) as per
Requirements for external safety isolating transformer
(100 % duty, max. 320 VA)
Frequency 50 / 60 Hz
Power consumption OZW77520 VA
Supply line fusing
Clock reserve
OZW775 device listUp to 250 Synco devices
Number
Contact sensing
Voltage
Current
Requirements for status / fault contacts
Signal coupling
Type of contact
Insulating strength against mains potential
Permissible resistance
Contact closed
Contact open
Number
Sensors
Passive
Active
Transmitter
Active
Contact sensing status / impulse contacts
Voltage
Current
Requirements for status contacts
Signal coupling
Type of contact
Insulating strength against mains potential
46 h typical, min. 12 h
AC 24 V ± 20 %
AC 24 V
HD 384
EN 61558-2-6
Max. 10 A, transformer on primary
side
8 (terminals D1...D8 and 1 ground
connection for 2 terminals each)
DC 16.5 V
Typically 8 mA
Potential-free
Maintained contact
AC 3750 V as per EN 60950-1
Max. 200 Ω
Min. 50 kΩ
8 (terminals X1...X8 and 1 ground
connection for 2 terminals each)
LG-Ni1000, T1, Pt1000
DC 0...10 V
DC 0...10 V
DC 16.5 V
Typically 1 mA, max. 6 mA
Potential-free
Maintained contact
AC 3750 V as per EN 60950-1
13/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 14
Universal inputs
continued
Relay outputs
Q1_,Q2_,Q3_,Q4_,Q7_,Q8_
AC 230 V
Connecting terminals
Inputs and outputs
PC interface
Modem interface
Requirements for pulse inputs
Signal cables
Signal coupling
Type of contact
Mechanical signal source (Reed contact)
Max. pulse frequency
Min. pulse duration
Electronic signal source
Max. pulse frequency
Min. pulse duration
Insulating strength against mains potential
Line length for:
Passive sensor signals LG-Ni 1000, T1, Pt 1000
Active signals DC 0…10 V
Status and impulse contacts
Number
Relay with NC contact
Relay with NO contact
External supply line fusing
NC contact, non-renewable fuse (slow)
NO contact, non-renewable fuse (slow)
Automatic line cutout
Release characteristic
Line lengthMax. 300 m
Relay contact data
Switching voltage
AC current (NC)
AC current (NO)
At 250 V
At 19 V
Switch-on current
Contact life at AC 250 V
At 0.1 A ohm.
At 0.5 A ohm.
At 2 A ohm.
At 4 A ohm.
Red. fact. at ind. (cos φ = 0.6)
Insulating strength between:
Relay contacts and system electronics (reinforced insulation)
Neighboring relay contacts (operational insulation)
Screw terminals for:
Solid / stranded wire (twisted or with ferrule)
1 solid / stranded wire per terminal
2 solid / stranded wires per terminal (max. 2)
Interface
Standard
Device class
Baud rate
Connecting cable for operator station
Cable length
Cable type for connection to PC/laptop
Cable type for connection to OZW775
Max. 300 m
See data for signal-sending device
300 m
4 (terminals Q11,Q12 Q21,Q22,
2 (terminals Q73,Q74 Q83,Q84)
Max. 3.15 A
Max. 5 A
Max. 13 A
B, C, D as per EN 60898
Max. AC 250 V, min. AC 19 V
Max. 2 A ohm., 2 A ind. (cos φ = 0.6)
Max. 4 A ohm., 3 A ind. (cos φ = 0.6)
Min. 5 mA
Min. 20 mA
Max. 10 A (1 s)
Guide values:
2 x 10
2 x 10
4 x 10
3 x 10
6 x 10
3 x 10
0.85 (NC and NO)
AC 3750 V, as per EN 60950-1
AC 1250 V, as per EN 60950-1
Min. Ø 0.8 mm
0.5...2.5 mm
0.5...1.5 mm
USB V1.1 (universal serial bus)
RNDIS (remote network device
Interface specification)
Max. 12 Mbps (full speed)
Max. 5 m
USB type A
USB type B
RS-232, V.24 / EIA 232D
Max. 115 kbaud
Max. 15 m
D-sub 9-pin, plugs
Q31,Q32 Q41,Q42)
7
switchings (NC and NO)
6
switchings (NC)
6
switchings (NO)
5
switchings (NC)
5
switchings (NO)
5
switchings (NO only)
2
2
14/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 15
Protocols to send
messages
KNX bus
Ethernet
Ethernet card OZZ7E5
Ambient conditions
Degree of protection
Standards
Materials and colors
Dimensions
Protocol support for connection via
Leased line telephone service provider
GSM telephone service provider, additional
Interface type
2-wire bus
Bus load number OZW775
Decentralized bus power supply, can be switched off
Permissible line length and cable typesSee data sheet N3127
Interface type
Bit rate
Protocol
Connection
Cable type
Cable length
Ethernet cable for:
Point-to-point connection
Multi-connection (e.g. to switchbox)
Operation to
Climatic conditions
Temperature (housing and electronics)
Humidity
Mechanical conditions
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Degree of protection when mounting:
Rear wall in cabinet or control panel
Front panel cutout for display and operation
Safety classII as per EN 60950-1
Product safety
For information technology equipment
Electromagnetic compatibility
Immunity OZW775
Immunity PC interface
Emissions
Home and Building Electronic System (HBES)
conformity
EMC directive
Low voltage directive
-conformity
Australian EMC Framework
Radio Interference Emission Standard
Environmental compatibility
The environmental product declaration CE1E5663en
contains data on environmentally compatible product design
and assessments (RoHS compliance, materials composition,
packaging, environmental benefit, disposal)
Housing lower and upper section
Length x width x height (max. dimensions) 298 mm x 128 mm x 77 mm
Size 2 as per DIN 43880
Polycarbonate, RAL 7035 (light-gray)
UCP (universal computer protocol)
TAP (telocator alphanum. protocol)
FAX protocol (fax class 2 or 2.0)
AT+ (extended AT command set)
TP1 (twisted pair, 1 cable pair)
CE+, CE- (non exchangeable)
E 0.3
DC 30 V / 25 mA
100BaseTX, IEEE 802.3 compatible
10 Mbps
TCP/IP
RJ45 plug (screened)
Standard Cat-5, UTP or STP
Max. 100 m
Crossed cable
Straight cable
IEC 60 721-3-3
Class 3K5
0 ...50 °C
5...95 % r. h. (non-condensing)
Class 3M2
IEC 60 721-3-2
Class 2K3
− 25...+ 70 °C
< 95 % r. h.
Class 2M2
IP 20 as per EN 60529
IP 30 as per EN 60529
EN 60950-1
EN 61000-6-2
EN 61000-6-1
EN 61000-6-3
EN 50090-2-2
2004/108/EC
2006/ 95/ EC
Radio communication act 1992
AS/ NZS 3548
ISO 14001 (Environment)
ISO 9001 (Quality)
SN 36350 (Environmentally
compatible products)
2002/95/EC (RoHS)
15/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 16
Weight OZW775
Weight OZZ7E5
Weight OZZ7CF
Terms and abbreviations
Central communication unit OZW775
With packaging, installation instructions and CD
Packaging Cardboard box
Ethernet card OZZ7E5
With packaging, mounting instructions
Packaging Cardboard box
CF card OZZ7CF
With packaging, operating instructions
Packaging Plastic bag
Extended command language for modems: Attention+
Global system for mobile communicationGSM
Integrated services digital networks ISDN
Internet protocol IP
Shielded twisted pair STP
Simple mail transfer protocol SMTP
Short message service SMS
Telocator alphanumeric protocol TAP
Transmission control protocol TCP
Universal computer protocol UCP
Universal serial bus USB
Unshielded twisted pair UTP
AT+
0.825 kg
1.185 kg
0.018 kg
0.044 Kg
0.010 kg
0.022 Kg
16/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008
Page 17
Connection diagrams
Connection diagram
Connection diagram
G
D2MD3D4
Q11
Q12
Q21
MD5
D6D8MMD1
Q22 Q31
D7
Q32G0
X1 M
Q41 Q42
X2
X3 M X4 X5 M X6 X7 M X8CE- CE+
Q73
Q74
Q83 Q84
D1…D8 Digital inputs
X1…X8 Universal inputs
M Ground for digital inputs, measuring ground for universal inputs
CE-KNX bus connection (negative)
CE+ KNX bus connection (positive)
G, G0 Operating voltage AC 24 V
Q… Relay outputs
G
AC 24 V
G
G0
F1
F2
Q11
Q12
Q21
Q22
Q31
B1
B2N2
0...10 V
RS-232
X3.......X8X1D3.......D8D2MD1
Q32
Q41
Q42
Q73
Q74
CE-X2M
Q83
Q84
RJ45Modem
Ethernet
5662G02
N3
KNX
Ethernet
RJ45CE+Modem
Ethernet
N1
Pin assignment
Ethernet card OZZ7E5
Modem connection,
central communication
unit
G0
5663A02
K1
L
NN
K2
L
K3
N1 Central communication unit OZW775
N2, N3 Synco device in KNX network
F1, F2 Device with potential-free contact output
B1 Sensor with passive signal
B2 Transmitter with active signal
K1, K2 Contactor (control by relay with NC contact)
K3 Contactor (control by relay with NO contact)
RJ45 plug (screened), standard assignment as per AT&T256.
1
2345678
1 Tx + 5 Not used
2 Tx – 6 Rx –
3 Rx + 7
3206Z01
5663Z21
4 Not used 8
Not used
Not used
Modem connection (D-pins, 9-pin), interface definition as per RS-232.
6789
23
45
1
1 DCD Data carrier detect 6 DSR Data set ready
2 RXD Received data 7 RTS Request to send
3 TXD Transmit data 8 CTS Clear to send
4 DTR Data terminal ready 9 NC Not connected
5663Z22
5 GND Signal ground
17/18
Building Technologies Central communication unit OZW775 V2.0 CE1N5663en
HVAC Products 29.10.2008