Siemens IR270CT User Manual

007038_b_- -_-- p1
Installation manual 007038_b_--_-­Edition 07.2003 Supersedes 007038_a_--_-­PN A5Q00003280
IR270CT Passive infrared detector with antimask Passiv-Infrarotmelder mit «Antimask» Détecteur infrarouge passif avec «antimask» Rivelatore passivo a infrarosso con «antimask» Detector a infrarrojos pasivos con «antimask» Passief-infraroddetector met «antimask»
Made in Switzerland
3
Wide angle mirror Weitwinkel-Spiegel
Specchio grandangolare Espejo gran angular BreedhoekspiegelMiroir grand-angle
IRS272 PN 571 733
Miroir rideau
Specchio a tendaCurtain mirror
Vorhang-Spiegel Espejo de cortina
Gordijnspiegel
4
1
BreedhoekspiegelMiroir grand-angle
15m10m5m0
h = 2,2m 7.2ft
max. 2,5m 8.2ft
min. 2,0m 6.5ft
0
0
0,9m
20m
2
15m10m5m0
5m
0
20m
1m
h = 2,2m 7.2ft
max. 3,5m 11.5ft
min. 2,0m 6.5ft
0
0,9m
25m
Wall mounting Wandmontage
Montage sur mur
Montaggio a muro
Montaje en pared
Montage op een mur
Corner mounting
Eckmontage
Montage dans un angle
Montaggio ad angolo
Montaje en esquina
Montage in een hoek
45° mounting 45°-Montage Montage 45°
Montaggio 45°
Montaje 45°
Montage 45°
A
B
5
B
A
Fire & Security Products
Siemens Building Technologies
16ft 32ft 50ft 65ft
3ft
3ft
16ft 32ft 50ft 65ft 80ft
16ft
3.3ft
1m 3.3ft
5m 16ft
5m 16ft
5m 16ft
10m 32ft
10m 32ft
007038_b_- -_-- p2
86
Störungs- & Antimask-Relais
Relay shown in energised (non-alarm) condition Relais in aufgezogenem Zustand (kein Alarm) gezeichnet Le relais est dessiné à l’état activé (pas d’alarme) Il relè è disegnato in stato eccitato (nessun allarme) El relé ha sido dibujado en estado excitado (sin alarma) Relais in aangetrokken toestand (geen alarm) getekend
*
2
1
11
10
8
7
+
-
Relais dérangem. & masquage Relè guasto & mascheramento
*
Dist. & Antimask relay
Rele de avería y antienmascaramiento
Storing & antimask relais
Contact d’autoprotection Contatto del coperchio
Sabotagekontakt
Tamper contact
Contacto de anti-arranque Sabotagecontact
Alimentation Alimentazione
Speisung
Supply
Alimentación Voeding
4
Test de déplacement Test di attraversamento
Gehtest
Walktest
Looptest
Ensayo de desplazam.
5
non amorcé disarmato
+5V
Unscharf
Unset
onscherp
desarmado
13
12
vide riserva
leer
spare
reserva reserve
<45R
30V
8...16V
+5V
7
*
<45R
30V
15
14
Relais d’alarme Relè d’allarme
Alarmrelais
Alarm relay
Rele de alarma Alarm relais
10
Avoid direct or reflected sunlight. Direkte oder reflektierte Sonnenstrahlung vermeiden. Eviter le rayonnement solaire direct ou indirect. Evitare luce solare direttamente o indirettamente. Evite las incidencias directas o indirectas de los rayos solares. Vermijd direct of indirect zonlicht.
Do not install the detector outdoors. Melder nicht im Freien montieren. Ne pas monter le détecteur à l’extérieur. Non montare il rivelatore all’aperto. No montar el detector al aire libre. Uitsluitend voor installatie binnenshuis.
Avoid looking directly at air conditioning or heat sources. Zonen nicht direkt auf Kälte- bzw. Wärmequellen richten. Ne pas diriger les zones sur radiateurs ou climatiseurs. Non indirizze le zone su radiatori o condizionari d’aria. No dirigir las zonas encima de calefactores o aparatos de aire
acondicionado. Richt de zones nooit op verwarmde oppervlakten of
airconditioners.
Detector breakage/removal monitoring
Abreißüberwachung
Contrôle d’arrachement
Controllo dello strappo
Control de ruptura Afbreekbeveiliging
Back tamper contact
Abreißkontakt
Contact d’arrachement
Contatto di strappo
Contacto anti-arranque
Afbreekcontact
4
9
Changing the mirror
Spiegel wechseln
Remplacement du miroir
Sostituzione dello specchio
Cambio del espejo Spiegel vervangen
IRUM20, IRUM30 Mounting brackets
Montagehalter IRUM20, IRUM30
Supports de montage IRUM20, IRUM30
Supporti IRUM20, IRUM30
Soportes de montaje IRUM20, IRUM30
Montagehouders IRUM20, IRUM30
TOP
Cable knock-out
Kabeldurchführung
Passage de câble
Foro per il cavo
Orificio para cable
Kabelpassage
Cable attachment
Kabel-Befestigung
Fixation du câble
Fissaggio per cavo
Fijación del cable Kabelbevestiging
IRUM20
IRUM30
PN 562 247
PN 562 250
007038_b_- -_-- p3
IR270CT Instruction for use
H The detector reacts most sensitively to movement which proceed at right
angles to the coverage zones (the direction of the arrow in figures 1 and 2).
H The detector’s coverage area is limited by any solid objects. H The detector is designed to achieve optimal response sensitivity and a high
level of false alarm suppression. Nevertheless, you are recommended to take note of the following points (see also figure 10):
- Do not direct the zones at sources of heat or cold, nor at points subject to strong sunlight.
- Direct the zones towards uniform references. Zones which are directed towards heaters (including floor heating equipment) can reduce the prob­ability of detection of movement.
- If it is impossible to avoid positioning the detector above heaters, you must keep them at a minimum distance of 1.50m / 5ft away!
H The integrated breakage/removal contact and the «real time» antimask sur-
veillance system mean that security against tampering satisfies the highest requirements. What is more, all the functions of the entire detector (includ­ing the detection sensors) are constantly monitored.
Anti-masking and alarm memory features are not verified by UL.
Installation
The detector is intended for use in inside rooms. Do not remove the printed circuit board from the detector. There is a dan-
ger that it may be damaged!
1. Open the detector (figure 3).
2. Mount the detector on a stable vertical surface.
- Select the height (h) above the floor according to figure 1 or 2.
- Corner mounting and 45° installation (right / left) are possible without any accessories (see figure 4A).
- Detector must be inclined at an angle of 2° when mounting above 3m / 10ft in order to detect crawling intruders and to ensure the detection range (see figure 4B).
- The cable is introduced through one of the knock-out points A (see figure 5).
3. Wire the connections as shown in figure 7.
4. For strain relief on the connection cable, pierce the lug B (figure 5) and fix
the cable with a cable cleat.
5. Select the desired settings as shown in the section on ”Programming”.
6. Replace the cover, screw it down with the screw provided, and close the
screw cover (figure 3). Detector breakage/removal monitoring Figure 6
If the detector is forcibly removed from the mounting surface, a sabotage alarm is triggered.
For this, the detector base must be secured with an additional screw.
This feature is not verified by UL.
Control inputs Figure 7
Walktest remote control Terminal 4
Remote control of the walktest indicator. Use switch DIP1 to select the polarity of the control signal.
Walk test remote control is not verified by UL.
Set/unset remote control Terminal 5 Remote control of the set/unset state. Use switch DIP4 to select the polarity of the control signal.
An open control input is HIGH (internal pull-up); for control with active HIGH, a resistor (t y p . 2 k Ω, max. 47k/detector) must be switched to 0V.
Programming
You can use switches DIP1 to DIP8 to select the following functions:
DIP ON OFF (default) Function
1 LOW (0V) HIGH (+12V)
Potential for walktest ON at termi­nal 4
2 3
see ”Detection sensitivity” tableSensitivity of motion detection
4 LOW (0V) HIGH (+12V) Potential for unset at terminal 5
5
To distur­bance and alarm relay
To disturbance relay only
Detector function monitoring, dis­turbance (DIST) and antimask (AM)
6 High Standard Antimask sensitivity (AM) 7 Latch Real time Antimask function (AM) 8 - - -
For installations with intrusion detection control units without distur­bance input, set DIP5 to ON.
Detection sensitivity
DIP2 DIP3 Sensitivity /
Range
Application
ON ON
High values 18m 60ft
Stricter detection requirements
OFF OFF
Standard (default) 18m 60ft
Residential, offices
ON OFF
Increased stability 18m 60ft
Rooms with low sources of in­terference
OFF ON
Harsh environment 12m 40ft Not approved for ANPI, CNMIS, IMQ, UL, SKAFOR
Rooms with considerable inter­ference effects
Setting note
If the longest wall in the room is less than 5m / 16ft, do not use the «High val­ues» sensitivity setting!
Functions
Detector function monitoring (self-test) DIP5
A self-test is always carried out when the supply voltage is applied. The detec­tor is also equipped with a periodic self-test.
A malfunction (such as a sensor failure) is indicated as a disturbance by the continuously red LED, and also at the disturbance output (terminals 7+8); and if DIP5 = ON, it is also outputted to the alarm relay in the unset mode.
Antimask surveillance
When masking is performed which restrict the motion detection, an antimask signal is outputted via output DIST. & AM (terminals 7+8), and during walktest, the masking indicator (LED lights green) is activated.
To ensure reliability of operation, detector covers must be replaced if they have been sprayed. Cleaning them is not enough.
Sensitivity of antimasking surveillance DIP6
- Standard Recommended setting to detect masking.
- High This setting enables faster and more sensitive masking detection for very high risks.
Depending on the masking material, the range of the antimask surveil­lance is approximately 0.20m / 0.7ft.
Antimask surveillance function DIP7
- Real time The antimask signal follows the state of the detector. Masking will only be indicated as long as the detector is masked. This is the setting recom­mended by the manufacturer.
- Latch Once the antimask signal is activated, it is retained (stored) on self-hold until it is reset by carrying out an antimask surveillance reset.
Antimask surveillance reset
- Variant1 With masking present, switch over to walktest ON:
- Remove the masking and trigger the motion alarm;
- Switch back to unset, and the antimask surveillance will then be re-initial-
ised.
- Variant 2 Restart due to voltage cut.
The detection area must be checked after every reset or restart.
LED displays
Control line state Detector state LED
Arming, terminal 5
Walktest, terminal 4
red green
Change to set
Memory reset - -
Set
any
Memory set - ­Alarm stored -
Walktest OFF
Masking stored (AM) -
Self-test at start-up
-
Unset
Walktest alarm -
Walktest ON
Masking -
Disturbance (DIST)
-
lit
flashing
constantly
lit for 2.5s
slow flashing
Memory displays
Set memories are shown in the unset with walktest OFF state. The alarm memory (LED flashes red) shows the result of the last set period.
This memory is always reset when the system is next in the set state. The masking memory (LED flashes green) is set when an event of the rele-
vant type has been continuously or temporarily present during the previous set period. This memory is reset when the system is next in the set state, pro­vided that the masking is no longer present.
Commissioning
1. Switch on the supply voltage.
During the self-test and the start-up phase with walktest ON, the LED flashes red slowly for about 1 minute.
- When the LED goes out, the detector is ready.
- If the LED lights red continuously, there is a fault in the detector.
2. Carry out the walk test, i.e. check the complete monitoring area to make
sure the alarm triggers: Walk upright across the active area at a rate of about 1 step per second in the
direction shown by the arrows (fig. 1 or 2) and pause. An alarm should be trig­gered in approx. 2 to 3 seconds!
The detector must also trigger an alarm if the active area is crossed near to its edges.
Sealing the detector Figure 3
If sealing of the detector is prescribed, apply an adhesive seal over the gap between the base of the detector and the cover.
Maintenance
Check the function of the detector regularly (at least once per year) - carry out a walktest, check for dirt and inspect the fixture.
Troubleshooting
Detector does not react
- Check whether the mirror is inserted.
- Check the supply voltage and polarity.
No alarm display on the detector
- Check programming, control signals and polarities.
No alarm
- Check the alarm relay.
- Check the alarm line.
Continuous or intermittent alarm
- Check the sensitivity setting.
- Check DIP5 (masking signal to alarm relay).
Switch the detector to walk test, mask the detector window with a sheet of cardboard and wait 30 seconds:
- If the LED is red constantly, the detector is defective.
- If the alarm indication disappears:
- ascertain the sources of alarm in the active area,
- remove the cause of the alarm,
- check the evaluation mode,
- reposition the detector or tilt it through 2°.
Insufficient range
- Check the mounting height and inclination (fig. 1 or 2).
- Walk at right angles to the active area!
- Check the IR window for soiling.
- Check the detection sensitivity setting.
Antimask signal, temporary or permanent
- Check for possible masking of the detector in the close range up to approx.
0.4m (curtains, sides of windows, doors, etc.).
- Carry out an antimask surveillance reset and check the coverage area.
- Select «Real time» instead of «Latch» (DIP7).
- Check the Dist. & AM line.
- Is the mirror optic inserted?
- Exchange the detector.
Options
Curtain mirror IRS272 Figure 2
The IRS272 curtain mirror has overlapping active zones forming a monitored area to provide secure monitoring against intrusion. At installation heights above 3m / 10ft, mount the detector with a downward inclination of 2°.
Changing the mirror: Remove the wide-angle mirror from the cover using a No. 1 screwdriver (Fig.
8) and replace it with an IRS272 curtain mirror.
Use the sensitivity settings «High values», «Standard» or «Increased stability».
Check the mirror for soiling and damage. Do not touch the pyrosensor!
Mounting bracket IRUM20, IRUM30 Figure 9 The mounting brackets IRUM20 (wall-mounting) and IRUM30 (ceiling mount­ing) enable the detector to be rotated through ±45° and tilted through +10°/–15°.
The monitored zone can differ from that shown in Fig. 1 or 2, depending on local conditions and the setting of the mounting bracket.
Approvals
ANPI, CNMIS, IMQ, UL, SKAFOR applied for. . . . . . . . . . . . . . . . . . . . . . . . .
It is essential to comply with national approval conditions which relate to the use of the product.
Technical data
Supply voltage 8.0 to 16.0VDC (12V nom.). . . . . . . . . . . . . . . . . . . . . . . . . . . .
- max. ripple (0...100Hz) 2.0Vpp. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
- voltage monitoring alarm at <5.5...7.5V. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current consumption (at 8...16VDC):
- quiescent 3.2mA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
- max. (with LED on) 12mA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm output:
- semiconductor relay opens at alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
- alarm holding time 2...3s. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
- contact load rating 30VDC / 100mA (ohmic load)). . . . . . . . . . . . . . . . . . . .
- series resistance <45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Disturbance & antimask output:
- semicond. relay opens at masking / disturbance. . . . . . . . . . . . . . . . . . . . .
- contact load rating 30VDC / 100mA (ohmic load)). . . . . . . . . . . . . . . . . . . .
- series resistance <45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tamper contact 30VDC / 100mA (ohmic load). . . . . . . . . . . . . . . . . . . . . . . . .
Control inputs LOW 1.5V / HIGH ≥3.5V. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Walking speeds:
- wide angle mirror (standard) 0.1...4.0m/s. . . . . . . . . . . . . . . . . . . . . . . . . . . .
- curtain mirror IRS272 (option) 0.1...4.0m/s. . . . . . . . . . . . . . . . . . . . . . . . . .
Ambient conditions:
- operating temperature 32°F to +120°F. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
0°C to +49°C
- storage temperature -4°F to +140°F. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-20°C to +60°C
- air humidity 85% at 86°F. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
85% at 30°C
- EMC resistance up to 2GHz 30V/m. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
- housing protection EN60529, EN50102 IP41 / IK02. . . . . . . . . . . . . . . . . .
Details for ordering
IR270CT Passive infrared detector A5Q00003273. . . . . . . . . . . . . . . . . . .
IRS272 Curtain mirror (4 pcs) 571 733. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IRUM20 Mounting bracket, wall 562 247. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IRUM30 Mounting bracket, ceiling 562 250. . . . . . . . . . . . . . . . . . . . . . . . . . .
Anti-tamper seal 503 251. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Loading...
+ 5 hidden pages