Siemens IP Control Center N152, 5WG1 152-1AB01 Technical Product Information

GAMMA instabus
Technical Product Information
December 2014
IP Control Center N152 5WG1 152-1AB01
Siemens AG N 152, 4 Pages Technical Manual Infrastructure & Cities Sector, Building T echnologies Control Products and Systems ã Siemens AG 2014 Update: http://www.siem ens.com/gamma
Product and function description
The IP Control Center N152 is a device for DIN-rail mounting.
It offers the following functions:
· A web server for operating and observing KNX sys­tems is incorporated in this device.
· A standard web browser displays the operating pages, (tested browsers, see application program description)
· A graphics web editor projects a fully graphic view with control and display elements in various styles.
· Application modules:
- Time switch schedules with up to 300 time switch
commands per week
- Scenes module with up to 5000 scenes or events
- Full graphic Logic module with up to 1000 Logic
functions
- Alarm functi on with up to 250 different alarm mes-
sages
- Email function with up to 20 contacts are configured via a graphics web editor.
· An additional smart editor allows the intuitive and quick preparation of simple visualisations for smart­phones with mobile browser or for room control units.
· It provides an interface to KNX installations via data networks, using the Internet Protocol (IP). Concur­rently, this device provides communication f rom KNX devices with PCs or other data processing equipment (KNXnet/IP tunnelling).
The device is configured with the settings using ETS 3/4. It defines the data types for the 250 available KNX communications objects and provides basic information for the device and for network settings.
The following data types can be chosen at the parameter setting of the communication objects:
· 1 bit
· 1 Byte (0…100%)
· 1 Byte unsigned
· 1 Byte signed
· 2 Byte unsigned
· 2 Byte signed
· 2 Byte float
· 4 Byte unsigned
· 4 Byte signed
· 4 Byte float
· 14 Byte text
Further 1000 group addresses can be linked together di­rectly with the visualisation components.
The following default settings can be placed on the de­vice:
· The IP address of the device is assigned by ETS con­figuration or automatically by a DHCP service in the IP network. Assigning of the IP address by a DHCP ser­vice allows changes to the IP address without config­uring the device with the ETS.
· When configuring the device with a fixed IP address and subnet mask, a standard gateway or router can also be defined. This gives subscribers the opportunity to access the Internet or another network. If you have queries on setting the parameters IP ad­dress of the device and subnet masks, as well as DHCP, you should contact your local network adminis­trator.
· You can set the port number of the integrated web server.
· Web pages for viewing and the web editor can be pro­tected separately with different passwords.
· The device can be set both as a time master (syn­chronisation by time server via I P) and as a time slave (synchronisation by KNX telegrams).
· A further parameter sets a read r equirement. This will send an update to the object values after a restart/bus reset.
The device is delivered with a preset IP setti ng:
Delivery status: IP address: 192.168.1.133
Additional Information
http://www.siemens.com/gamma
GAMMA instabus
Technical Product Information
Decem ber 2014
IP Control Center N152 5WG1 152-1AB01
Technical Manual N 152, 4 Pages Siemens AG
Infrastructure & Cities Sector, Building T echnologies
Update: http://www.siem ens.com/gamma ã Siemens AG 2014 Control Products and Systems
Subject to change without further notice. P. O. Box 10 09 53, D-93009 Rege nsburg
2.11.1.15/2
Installation Instructions
The device can be used for permanent interior installa­tions in dry locations within distribution boards or small casings with DIN rail EN 60715-TH35-7.5.
Υ
WARNING
· The device may only be installed and commissioned by a licensed electri cian.
· Exposed sections of rail with integrated data rails are to be covered with the cover 5WG1 192-8AA01.
· The relevant safety and accident prevention rules are to be obeyed.
· The device must not be opened.
· When planning and installing electrical systems, the
relevant national directives, rules and regulations of the country in question are to be obeyed.
Technical Specifications
Power supply
· Bus voltage: supplied via the KNX bus line
· Operating voltage:
from an external SELV power supply DC 24 V nominal,
permissible input voltage range: DC 12 ... 30 V, (for class 2 only),
· Power consumption: max. 1,2 W @ 24 V DC
· Recommended power supplies:
LOGO! Power 24 V / 1,3 A, (class 2),
Rated input voltage AC 100…240 V wide range, Input voltage range AC 85…264 V,
Constant current supply DC 24 V / 1,3 A, Rated output voltage: DC 24 V,
Width: 3 SU
LOGO! Power 24 V / 2,5 A, Rated input voltage AC 100…240 V wide range, Input voltage range AC 85…264 V,
Constant current supply DC 24 V / 2,5 A, Rated output voltage: DC 24 V, Width: 4 SU
LOGO! Power 24 V / 4 A, Rated input voltage AC 100…240 V wide range, Input voltage range AC 85…264 V,
Constant current supply DC 24 V / 4 A, Rated output voltage: DC 24 V, Width: 5 SU
Network communication
· IP-connection via Ethernet, speed 100 Mbit / second
· IP address allocation via DHCP service or fixed IP ad-
dress
Connections
· Bus line: Bus terminal (black-red), without screws 0,6...0,8 mm Ø single core Insulation st rip length 5 mm
· Ethernet 10/100 Mbps, connection: RJ45 socket
· Power supply:
Bus terminal (yellow-white), without screws 0,6...0,8 mm Ø single core Insulation st rip length 5 mm
Control elements
· 1 learning button: to change between normal and addressing modes
Display elements
· 1 red LED: ERR-LED signals fault status
· 1 yellow LED: LK-LED signals device Ethernet readi-
ness
· 1 red LED: to indicate normal mode / addressing mode
Mechanical specifications
· Dimensions: DIN-rail mounted device, Width 4 SU (1 SU = 18 mm), height 55 mm
· Fire load: approx. 3.300 kJ
· Weight: approx. 150 g
Electrical safety
· Degree of contamination: 2
· Type of protection (to EN 60529): IP 20
· Protection class: (to IEC 1140) III
· Overvoltage category: III
· Bus: Safety Extremely Low Voltage SELV DC 24 V
Reliability
Failure rate: 795 fit according SN29500
EMC criteria
· Meets EN 50428:2005 + A1:2007 + A2:2009 and
EN 61000-6-2:2005, EN 61000-6-3:2007 + A1:2011