Siemens ICP-B6 Installation Instructions Manual

Installation Instructions
MODEL ICP-B6 Intelligent Control Point
The Model ICP-B6 Intelligent Control Point from Siemens Industry, Inc. can be used as an independent, remotely located telephone zone, a speaker zone (25V or 70.7V RMS), or notification appliance circuit (NAC), depending on how it is configured. It communicates through the analog loop of the MXL/MXLV System.
OPERATION
Up to 12 ICP-B6s can connect to each analog loop of the MXL/MXLV. These modules must be connected to the first 12 address locations on the analog loop.
The 24 VDC power input for each ICP-B6 comes from either the MMB, the PSR, or from an auxiliary power supply which is power limited and UL listed for fire protective signal­ing use and is rated between 24 and 27.3 VDC. Each ICP-B6 can be assigned a 32­character, custom alphanumeric message.
Each module uses one address on either the analog loop of the ALD-2I module or the analog loop of the MMB board. (See Figure 1) The ICP-B6 is programmable for different usages.
To Set the ICP-B6 Module Address:
1. Plug the programming cable of the DPU or FPI-32 Programmer/Tester (SensorLINK) into the two-pin receptacle on the ICP-B6. (See Figure 2 for location only.)
2. Set the system address for the ICP-B6 by following the instructions in the FPI-32
(SensorLINK) Programmer/Tester Manual, P/N 315-090077, or the DPU User's Manual, P/N 315-033260, as applicable.
Remove all system power before installa­tion, first battery and then AC. (To power
up, connect the AC first, then the battery.)
All wiring must comply with
national and local codes.
The ICP-B6 should be installed in a UL
listed electrical box. (See Figure 10.)
For additional information on the MXL/MXLV System, refer to the MXL/MXLVManual, P/N 315-092036.
Addressing and Testing
Use the DPU Device Programming Unit or the FPI-32 Programmer/Tester (SensorLINK) to program and test the module.
NOTE: With FPI-32 Rev. 1.3 software, only
1=MXL mode should be used when programming a device.
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-095306-10
Analog Loop
The ICP-B6 communicates with the MXL through its analog addressable loops. These loops are on either the MMB or on the op­tional ALD-2I module of the MOM-4. They may be wired for Class A (Style 6) or Class B (Style 4). Figure 1 shows both wiring types and the connections to either the MMB or to the MOM-4 when the ALD-2I module is used. The table on the following page lists the maximum output currents allowed.
Siemens Building Technologies, Ltd. Fire Safety & Security Products 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
The ICP-B6 module can be used in four different ways:
1. Using the ICP-B6 as an NAC Module
This notification appliance application uses the principle of polarity reversal when there is an alarm. Figure 2 shows the polarity connection in a supervisory condition. When using the ICP-B6 as a supervised NAC output module with notification appliance devices, cut jumper JP2. Refer to Figure 2 for additional connec­tion and jumper information, and to P/N 315­096363 for a list of compatible devices.
MAXIMUM ALLOWABLE I CP-B6 OUTPUT CIRCUIT LINE RESISTANCE
FOR SPECIFIED DC RISER CURRENT AND LINE RESISTANCE
MAXIMUM DC RISER CURRENT (in Amps)
8 2.46 1.67 .33
7 2.53 1.83 .66
6 2.60 2.00 1.00
0.1 Ohm 0.25 Ohm 0.5 Ohm 0.75 Ohm 1 Ohm 1.5 Ohms
DC RISER RESISTANCE (in Ohms)
When used as an NAC module, the output circuit is power limited. The ICP-B6 maximum current is 1.5A at 24 VDC. If the 24 VDC is lost or the NAC line is broken or shorted, the trouble condition INPUT DEVICE RESPONSE TOO LOW displays at the MXL/MXLV control panel. Refer to Figures 3 and 4 for the con­nections used with the TRI-60/B6 module and the PSR-1 module, respectively. See the
Line
Resistance chart for the allowable line
resistance for each ICP-B6 output circuit.
-- -- --
-- -- --
-- -- --
5 2.67 2.16 1.33 .5
4 2.73 2.33 1.67 1.00 .33
3 2.80 2.50 2.00 1.50 1.00
2 2.86 2.67 2.33 2.00 1.67 1.00
1 2.93 2.83 2.67 2.50 2.33 2.00
.5 2.96 2.92 2.83 2.75 2.67 2.50
MAXIMUM LOOP RESISTANCE FOR EACH ICP-B6 ON RISER
NOTES:
1. Resistances specified are for both wires.
2. If higher currents are required, Siemens Industry, Inc. recommends using a local auxiliary supply which is UL listed for fire protection signaling use. The supply should be rated between 24 and 27.3 VDC.
ELECTRICAL RATINGS
tnerruCeludoMCDV5evitcAAm0
-- --
--
--
tnerruCeludoMCDV42evitcAAm01
tnerruCeludoMCDV42ybdnatSAm01
2
ALD-2I ALD-2I
MOM-4
TB2
LOOP 1 LOOP 2 LOOP 1 LOOP 2 LOOP 1 LOOP 2
4
3
2
1
4
3
2
1
8
7
6
5
8
7
6
5
4
3
2
1
4
3
2
1
MOM-4
TB1
MMB
TB2
8
7
6
5
8
7
6
5
MMB
TB3
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
ANALOG LOOP CONNECTION
OPERATES IN FULL CONFORMANCE WITH STYLE 4 (CLASS B)
*
(T-TAPPINGALLOWED)
100 OHMS MAX
*
SUPERVISED, POWER LIMITED PER NEC 760
ALL WIRING MUST CONFORM TO NATI ONAL AND
SUPERVISED
DC INPUT RATED
24 - 27.3 VDC FWR
SUPV: 12mA
ACTIVATED: 1.5A MAX
MODULE INPUT SUPPLY
FROM PS-35, PSR-1, OR
UL LISTED POWER SUPPLY
ALARM-SAF (Model BN4-002-UL)
MANUFACTURED BY
ELECTRICAL:
INPUT DC SUPPLY:
SUPERVISORY OUTPUT:
ACTIVATED:
LOOP RESISTANCE 100 OHMS MAX
18 AWG MINIMUM WIRE
NO EOL DEVICE REQUIRED
LOCAL ELECTRICAL CODES
-
ANALOG
LOOP
CONNECTION
+
TB1 TB1
TB2
EARTH
SHIELD
SUPERVISED STROBE ACTIVATION - SPECIAL APPLICATION SUPV: 9VDC, .5mA ACTIVATED: 16-32V UNFILTERED FULL WAVE RECTIFIED, 1.5A MAX POLARITY SHOWN IN SUPV. CONDITION
1 1
3 3
2 2
----
++++
ICP-B6 ICP-B6
PROGRAM PLUG
6
5
4
-
+
24-27.3 VDC, 18mA MAX 9 VDC, 0.5mA SPECIAL APPLICATION 16-32V UNFILTERED FULL WAVE RECTIFIED
1.5A, POWER LIMITED
ICP-B6 MODULE IS USED FOR
NAC SUPERVISION AND ACTIVATION
12 12 12
TB1 TB1 TB1
ICP-B6 ICP-B6 ICP-B6
*JUMPERS CAN BE REMOVED FROM MMB-3 WITH CSGM CONFIGURATION
Figure 1
Analog Loop Connections
STYLE Y
POWER LIMITED
6 6
5 5
4 4
-
JP2 JP2
+
JP1 JP1
+
+--
1
3
2
15K, 1/2W, 5% EOL RESISTOR P/N 140-820400
16-32 VDC
NAC UNITS
SEE TABLE 1
NOTES:
1. ALL WIRING MUST COMPLY WITH NATIONAL AND LOCAL CODES.
2. POSITIVE AND NEGATIVE GROUND FAULT DETECTED AT <5K OHMS FOR TERMINALS 3-6.
3. FOR SYNCHRONIZATION OF NOTIFICATIONAPPLIANCES USE EITHER DSC, DSC-W, OR PAD-3.
EARTH
SHIELD
NAC SUPERVISION AND ACTIVATION
PROGRAM PLUG
TB2
6
5
ICP-B6 MODULE IS USED FOR
STYLE Z
15K, 1/2W, 5% EOL RESISTOR P/N 140-820400
-
++
--
+
+
+--
1
3
2
4
Figure 2
ICP-B6 Used as a Strobe Module
3
Loading...
+ 5 hidden pages