Siemens FDOOTC441 Installation Instructions Manual

Page 1
Installation Instructions Model FDOOTC441
Multi-Criteria Fire/CO Detector
Figure 1 FDOOTC441
These instructions are written in accordance with the installation guidelines of NFPA 72, National Fire Alarm Code. The model FDOOTC441 detector (shown in Figure 1) meets the VEWFD (Very Early W arning Fire Detector) classification and sensitivity requirements of NFPA 76 (Standard for the Fire Protection of Telecommunications Facilities) incorporating a programmable “Alert” (Pre-Alarm) sensitivity threshold of 0.2%/ft obscuration and an “Alarm” sensitivity threshold of 1.0%/ft obscuration.
CAUTION
Detection Device Storage
DO NOT install this detection device until all construction is completed.
DO NOT store this detection device where it can be contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Although no specific spacings are set for the detectors used for a clean air application, for multi-criteria fire detection use 30 foot center spacing (900 sq ft) from NFP A S t andard 72 initiating devices chapter, if practical, as a guide or starting point for a detector installation layout. This spacing, however, is based on ideal conditions–smooth ceiling, no air movement, and no physical obstructions. In some applications, therefore, considerably less area is protected adequately by each smoke detector. This is why it is mandatory to closely follow the installation drawings. In all installations place the detector on the ceiling, a minimum of 6 inches from a side wall, or on a wall, 12 inches from the ceiling. For CO gas detection applications, follow detector installation requirements in NFP A 720, S tandard for Installation of Carbon Monoxide Detection and Warning Equipment.
For FM Approved installations, this device has an R TI rating of QUICK. For thermal detection, use the matrix below:
teeF,gnicapS,gnitaRerutarepmeT
05571,561,551,541,531drauGtuohtiWdnahtiW 06571,561,551,541,531drauGtuohtiW 06551,541,5 07541,531drauGtuohtiW 07531drauGhtiW
31drauGhtiW
0
FledoMdrauGtuohtiW/htiW
If you have any questions regarding detector placement, follow the drawings provided or approved by Siemens Industry, Inc., or by its authorized distributors. This is extremely important! The detector placements shown on these drawings were chosen after a careful evaluation of the area that is protected. Such factors as air currents, temperature, humidity , pressure, and the nature of the fire load were carefully considered. Especially noted were the room or area configuration and the type of ceiling (sloped or flat, smooth or beamed). Siemens Industry, Inc.’s extensive experience in the design of the system assures the best detector placement by following these drawings.
TO AVOID NUISANCE ALARMS
Do not locate the detectors where excessive smoke concentrations exist under normal conditions, or in areas of prolonged high relative humidity where condensation occurs.
Do not locate the detectors next to an oil burner, kitchen, or garage where exhaust fumes can trigger an alarm. Other causes of false alarm are dust accumulation, heavy concentrations of steam, heavy pipe or cigar smoke, and certain aerosol sprays.
AIR CURRENTS
Before a detector can sense a fire, the products of combustion or smoke must travel from the fire to the detector. This travel is especially influenced by air currents; therefore, consider air movement when designing the system. While combustion products tend to rise, drafts from hallways, air diffusers, fans, etc., may help or hinder the travel of combustion products to the detector. When positioning a detector at a particular location, give consideration to windows and doors, both open and closed, to ventilating systems, both in and out of operation, and to other factors influencing air movement. Do not install a detector in the air stream of a room air supply diffuser. It is better to position a detector closer to an air return.
The distance that products of combustion or smoke travel from a fire to the detector is not usually the shortest linear route. Combustion products or smoke usually rise to the ceiling, then spread out. Average ceiling heights of 8 to 10 feet do not abnormally affect detector response. High ceilings, located in churches, warehouses, auditoriums, etc., do affect detector response and should be considered.
SPECIAL CEILING CONSTRUCTION FACTORS
Ceiling obstructions change the natural movement of air and combustion products. Depending on the direction of smoke travel, joists and beams can slow the movement of heated air
A6V10324657_en--_f
Building
Siemens Siemens
Siemens
Siemens Siemens
TT
ecec
hnologies Dihnologies Di
T
ec
hnologies Di
TT
ecec
hnologies Dihnologies Di
IndustryIndustry
Industry
IndustryIndustry
visionvision
vision
visionvision
,,
Inc. Inc.
,
Inc.
,,
Inc. Inc.
Page 2
and smoke, while pockets between them can contain a reduced level of smoke. Take obstructions created by girders, joists, beams, air conditioning ducts, or architectural design into consideration when determining area protection. Refer to the Initiating Devices chapter of NFPA S tandard 72 for Location and Spacing requirements for specific types of construction; e.g. beam, suspended, level, sloped and peaked ceilings.
(UL268A), heat (UL521) and CO (UL2075) which can be used simultaneously and can be configured and switched on or off individually by the panel. Follow the description and instructions provided in the operation manual of specific control panel used. The FDOOTC441 can be set to the FDOOTC441 Selectable Application Profiles, FDOOTC441 Selectable Fixed Temperature Threshold Profiles and the FDOOTC441 Selectable Alarm Threshold Setting Profiles shown in the tables below and to the
TEMPERA TURE – HUMIDITY – PRESSURE – AIR VELOCITY
The temperature range for the FDOOTC441 detector is 32°F (0°C) to 120°F (49°C). Use the detector in environments where the humidity is 15% to 95% RH continuous and 1% to 99% for short duration (24h to 48h). Normal changes of atmospheric pressure do not affect detector sensitivity . The air velocity range is 0-4000 ft/min for open areas applications. Follow detector spacing and location requirements in NFP A 72 Chapter for High Air Movement Areas and Control of Smoke Spread. The
right. Additionally the detector can have another channel that can be
configured by the panel to have a low or high temperature warning in the range from -4° to 120°F (-20° to 49°C). (Not with FC2005.)
Additionally the detector can be configured by the panel to have a CO gas concentration warning in the range of 30-600ppm. (Not with FC2005.)
detectors can also be installed in duct applications between 0 and 4000 ft/min. For duct installations follow detector installation requirements in NFPA 90A, Chapter for Special Ceiling Construction Factors. When the detectors employ a fixed temperature rating of 165
0
F or less, they are intended for a
maximum installation temperature of 1000F (37.80C). UL listed with STI Mechanical Protection Guard Model: STI-9604
(see www.STI-USA.com for details).
LED INDICATOR OPERATION
The Model FDOOTC441 contains an LED indicator capable of flashing either one of three distinct colors: green, yellow, or red. During each flash interval, the microprocessor-based detector monitors the following:
Smoke in its sensing chamber
Smoke sensitivity is within the range indicated on the nameplate label
Internal sensors and electronics
Based on the results of the monitoring, the LED indicator flashes the following:
hsalF
roloCnoitidnoC
*neerG
wolleY
deRmralA1
oN
*sehsalF
vitisnes
.tnemecalper
tceteD
.dedeensi
.desulenaPeht
ekomS.noitarepoyrosivrepuslamroN
.stimildetarnihtiwsiyti
sdeendnaelbuortnisirotceteD
tnemecalperro,derewoptonsiro
lavretnIhsalF
)sdnoceS(
01
4
­fonoitpircsedgnidnopserrocehtwollofesaelP.ffodenrutebnacDEL*
DETECTOR PROGRAMMING
Each detector must be programmed to respond to a unique system address between 001 - 050 for FC2005.
• To program the detector address, use the Model DPU Device Programming Unit. Refer to the DPU Manual, P/N 315-033260.
• Record the loop and device number (system address) for the detector on the detector label and on the base to prevent installing the detector in the wrong base. The optional DPU label printer can be used for this purpose.
Each detector provides pre-programmed parameter sets which can be selected by the panel. The FDOOTC441 provides three different alarm channels: multi-criteria (UL268) and direct in-duct
Siemens Industry, Inc. Building Technologies Division
ELECTRICAL
For information on electrical characteristics of the detector, refer to the FDOOT441/FDOOTC441 T echnical Manual, A6V10325549 at https://www.buildingtechnologies.siemens.com/extranet/ba-sp/. Refer to the panel Installation, Operation and Maintenance Manual for maximum line impedance of the loop driver.
WIRING
Detector bases for Model FDOOTC441 should be connected as shown in Figure 2.
DETECTOR MOUNTING
The recommended orientation of the detector for wall mounting is shown in Figure 3. T o ensure proper inst allation of the detector head into the base, be sure the wires are properly dressed at installation:
• Position all wires flat against the base.
• Take up all slack in the outlet box
• Route wires away from connector terminals.
TO INSTALL DETECTOR HEAD:
• Rotate detector counterclockwise while gently pressing on it until the detector seats fully into base.
• Then rotate the detector clockwise until it stops and locks in place. Insert optional locking screw (Order Model LK-11).
TO REMOVE DETECTOR HEAD:
• Loosen locking screw, if installed. Then rot ate the detector counterclockwise until stop is reached.
• Pull detector out of base.
erutarepmeTdexiFelbatceleS144CTOODF
seliforPdlohserhT
0
531erutarepmetdexiF
F
0
F
541erutarepmetdexiF
0
F
551erutarepmetdexiF
0
F
561erutarepmetdexiF
0
F
0
531erutarepmetdexiF
0
571erutarepmetdexiF
0
531erutarepmetdexiF
0
571erutarepmetdexiF
571erutarepmetdexiF
0
51)RoR(esiRfoetaR+F
F
0
51)RoR(esiRfoetaR+F
F
0
02)RoR(esiRfoetaR+F
F
0
02)RoR(esiRfoetaR+F
F
seliforPgnitteSdlohserhTmralAelbatceleS144CTOODF
dlohserhTtf/%05.2 dlohserhTtf/%00.3
f/%05.2
deifirev,dlohserhTt deifirev,dlohserhTtf/%00.3
A6V10324657_en--_f2
Page 3
seliforPnoitacilppAelbatceleS144CTOODF
noitacinummoceleT tnempiuqegnissecorplangiseulavhgih,detalugeryl
eriFemitnwodtneverpotmralA-erP)DFWEV(noitceteD .ytiunitnocssenisublacitircniatnia
tneipicnI .mralanoitcetedgninrawylraesedivorP.detalugerylesolcerutarepmet,naelc,tnemnorivnedellort
tnelaviuqenoI .selcitraperutangiserifllamsdnaserifgnimalfotevitisneS.rotcetednoitazinoIotevitan
nocyreV
retlanasadesU
esolcerutarepmet,naelc,tnemnorivnedellortnocyreV
mdna
.stnemeriuqernoisserppusgninozssorcrofdesuebnaC
retneCataD netfo,yticolevriahgih,tnempiuqe
ocleTrodnaelbac,gnissecorpatadgniniatnoctnemnorivnedellortnoC
.sroolf-bussniatnoc
mooRretupmoC gnissecor
.snoitidnocyticolevriahgihdnagnitarepotnempiuqe
egarotSsuoicerP .derisedgninrawtseilrae,tnemnorivneeerf-tsudnaelc,egarotstn
noitareneGrewoP emoS.tneserpgnicralacirtcele,gnidlew,FR,gniwserutarepmetonro
empiuqeroslairetamevtisneS
ronim,tnemnorivnedellortnoC
.tneserptnanimatnoc)anemonehpevitpeced(enrobria
latipsoH oterusopxE.tnempiuq
egnitarenegFRerusopxeemoS.ksirlevelhgiH.tnemnorivnenaelcdellortnoC
.stnevlosgninaelc
eraChtlaeH .erusopx
yrotimroD .maetsdnagn
mooRytilitU .tnempiuqegninnurmorfta
ybboL .etalucitrapedistuoemos,senohpralullec,segnah
cerutarepmet,aeranaelcylevitaleR
eh,tnemnorivneytridtahwemosotlamron,moorremrofsnarT
ikoms,semufgnikooC.sretrauqgnivil,segnahcerutarepmetdnatsudenrobriA
eciffO.erehpsomtadellortnocetamilc,naelcylbanosaeR letoH .elbissopgnikoo
loohcS .stnanimatnocenrobriadnasgniwserutarepmetemos
,ytefasefiL
cdnagnikoms,maets,sgniwserutarepmetemos,ytefasefiL
esuoheraW .semuftsuahxednaaerakcodmuidemotthgildnatfilkrof,tnempiuqe,tsudenrobriA
naMedulcninactnemnorivnedellortnoc-imeS stnanimatnocenrobria,gnidlew,gniredloslacimehcgnidulcni
gnirutcafu
.erusopxeropav
egaraGgnikraP .sgniwserutarepmetegral,semufleseiddnaraC.tsudenrobriA
tnemnorivnEnepO semufmorfanemo
.elbissop
esionIME latnemnorivner
.lamronerasnoitidnoc
el
itsoH .sgniwserutarepmetediw,tneserpFR,tnempiuqegnitarepo,dimuh,ytsud,ytriD
OC/wretneCataD netfo,yticole
.sroolf-bussniatnoc
OC/
wletoH gnikoms,maets,sgniwserutarepmetemos,ecnadiovamralaecnasiungnitroppusrosnesOCsedivorP
.elbissopgnikoocdna
OC/welitsoH .anemonehpevitpecedmorfsmralaecnasiungnidiovarofnoitcetedekomstsuborotrosnesOCsddA
.sgniwserutarepmetediw,tneserpFR,tnempiuqegnitarepo,dimuh,ytsud,ytriD
OC/wtcuD .sgniwserutarepmetediw,d
imuh,ytsud,ytrid,yticolevriahgiH.troppusOChtiwtcudninoitcetedekomS
fostnemeriuqernoitcetedehtsteeM.sgniliechgihsahnetfO.snoitidnocyticolevriahgihdnagnitarepo
gninraWylraEyreVagnidivorpybtnempiuqEnoitacinummoceleTfonoitcetorPehtrofdradnatS67APFN
plangisnaelceulavhgih,detalugerylesolcerutarepmet,naelc,tnemnorivnedellortnocyreV
eropavgninaelcdnalacimehcemoS.tnempiuqecinortcele,naelcylevitaler,ksirlevelrehgiH
nehpevitpeced,sgniwserutarepmeT.smuidats,sanera,smuirta,saeranepoegraL
ehtO.langislacirtcelegnitarenegtnempiuqedezilaicepsruodnaFR,ecafretnilacirtcelE
vriahgih,tnempiuqeocleTrodnaelbac,gnissecorpatadgniniatnoctnemnorivnedellortnoC
*1SUdecnalaB dna4302LUmorfstnemeriuqerytivitisnesslliflufdna5702LUsteemtesret
.1-91.6ASC
5002CFhtiwdesutoN*
DETECTOR TESTING
Only qualified service personnel should test. To assure proper operation of the detector, both the Sensitivity and Functional Test should be conducted. The minimum test schedule may be found in the current edition of NFPA 72.
The CO sensor of the FDOOTC441 has a 5-year lifetime from the date of installation.
Siemens Industry, Inc. Building Technologies Division
eliforPytefaSefiLOCCTOODF
emarap1SUdecnalaBehT
SENSITIVITY MEASUREMENT
The sensitivity of FDOOTC441 detectors can be tested individually using the DPU. Refer to the DPU Manual, P/N 315-
033260. The sensitivity can be measured by the panel. Follow the instructions of the panel used.
A6V10324657_en--_f3
Page 4
T
LINE 1**
T
TO INITIATING CIRCUIT OF SIEMENS INDUSTRY,INC. COMPATIBLE CONTROL UNIT
LINE 2**
Figure 2 Installation and Wiring Diagram
TB1
TB2
TB3
REMOTE RELAY BASE MODEL DB2-HR***
5
NO
C
6
NC
RELAY* CONTACTS 3A, 120 VAC 3A, 30 VDC
561a
1b
DETECTOR BASE MODEL DB-11/DB-11E
561a
SUPERVISED AND POWER LIMITED
*The relay contacts are shown after System reset, which represents the non-alarm condition.
**FDOOTC441 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.
***FDOOTC441 is NOT compatible with the DB-HR base.
1b
OPTIONAL REMOTE ALARM INDICATOR MODELS RL-HW/RL-HC
TO NEXT BASE
5
NO
C
6
NC
TO NEXT BASE
DO NO USE AN END OF LINE DEVICE
DO NO USE AN END OF LINE DEVICE
Figure 3
1.
MOUNT BOX ON
WALL WITH
EXTERIOR
MOUNTING HOLES
IN UPPER LEFT
AND LOWER
RIGHT POSITIONS
WALL
4-INCH SQUARE BOX 2 1/8-INCHES DEEP
DB-11 BASE
LOCKING HOLE
2.
D
O
N
O
T
P
A
I
N
T
MOUNT DETECTOR BASE TO 4-INCH SQUARE BOX AS SHOWN WITH LOCKING HOLE ON LEFT TOP IN POSITION SHOWN
Recommended Detector Wall Mounting / Detector Guard Orientation
SMOKE DETECTOR FUNCTIONAL TEST (SMOKE TEST GAS)
The fire control panel
must be programmed to test mode prior
to performing a functional (*Go-No-Go) smoke entry test. Failure to do so may result in a test failure. Refer to the specific control panel installation operations manual for proper “test mode” programming instructions. To determine how to put the control panel in “test mode”, specific programming instructions are located in the following documents: XLS IOM, P/N 315-033744, FC2005 Installation Instructions, P/N A6V10333722, and FC2025/FC2050 Installation Instructions, P/N A6V10315023. T o activate the detector with test gas, only use SmokeCheck™ test gas manufactured by HSI Fire & Safety Group, P/N HO-25S (see www.homesafeguard.com for product and ordering details). Strictly follow the testing instructions provided on the gas canister label.
After applying the test gas for 1-2 seconds, the
smoke alarm will occur within 4-10 seconds. If not, check the Test Mode and repeat the test. Do not repeat the test multiple times or apply the test gas too long – this will cause CO-troubles.
CAUTION: DO NOT USE AT DISTANCES SMALLER THAN 2 FEET (0.6m) FROM DETECTOR. SPRA Y THE TEST GAS FOR A PERIOD OF 1-2 SECONDS. EXCESSIVE SPRAYING MAY AFFECT THE DETECTOR’S SENSITIVITY AND CAUSE CO SENSOR TROUBLES.
*This test is simply used to ensure that smoke can enter the
sensing chamber and alarm the control panel when the detector reaches the programmed obscuration (concentration) level.
CAUTION: DO NOT USE ANY TEST GAS OTHER THAN THE ONE MENTIONED ABOVE AS COMPATIBILITY TO THE CO SENSOR CANNOT BE ASSURED.
Test by activating the detector using the approved CO test gas, Siemens P/N 500-650053, following the instructions with product and provided on the CO gas canister label. Spray the CO gas stream into the detector opening from the opposite side of the alarm indicator LED from the CO sensor to the straw of the test gas can is required. Use only short (approx. 1-2 seconds, BUT NOT LONGER THAN 2 seconds) activation of the gas can. Af ter applying the test gas for 1-2s, the CO alarm will occur within 4-10 seconds. If not please check the Test Mode again and repeat the test. Do not repeat the test multiple times or apply the test gas too long – this will cause CO-troubles.
*This test is simply used to ensure that a CO gas can enter the sensing chamber and alarm the control panel when the detector reaches the programmed obscuration (concentration) level.
The FDOOTC441 detectors can also be tested individually using the DPU. Refer to the DPU manual, P/N 315-033260.
MAINTENANCE
The control unit automatically indicates the trouble message for the FDOOTC441 detector whose smoke chamber changes to the level where the set sensitivity cannot be maintained. In such circumstances, the detector may require replacement.
CAUTION: UNDER NO CIRCUMSTANCES IS THE DETECTOR HEAD TO BE DISASSEMBLED. NO REPAIRS SHOULD BE ATTEMPTED.
DO NOT PAINT
The detector/base plastic is marked DO NOT PAINT. This is intended to prohibit painting during routine maintenance of the occupancy which can affect proper operation of the detector.
CO DETECTOR FUNCTIONAL TEST (CO TEST GAS)
The fire control panel must be programmed to test mode prior to performing a functional (*Go-No-Go) CO gas entry test. Failure to do so may result in test failure. Refer to the specific control panel installation operations manual for proper “test mode” programming instructions. To determine how to put the control panel in “test mode”, specific programming instructions are located in the following documents; XLS IOM, P/N 315-033744, FC2005 Installation Instructions, P/N A6V10333722, and FC2025/FC2050 Installation Instructions, P/N A6V10315023.
3.
WHEN 4-INCH SQUARE BOX AND DETECTOR BASE ARE MOUNTED AS SHOWN,
DETECTOR
DETECTOR LED WILL BE IN RECOMMENDED 0 POSITION WITH DETECTOR INSERTED IN BASE.
STI-9604
WHEN MOUNTING THE STI-9604 MECHANICAL GUARD (BOTH POSITIONS: WALL OR CEILING), USE ORIENTATIONINDICATED IN THIS DRAWING.
0
a distance of approximately 2 inches (5cm)
TNEMPIUQELORTNOCELBITAPMOC
reifitnedIytilibitapmoCtnempiuqEsnoitcurtsnIgniriW/noitallatsnI
2R-/2U-5002CF4 2R-/2U-5202CF83051301V6A 2R-/2U-0502CF83051301V6A
)CLD(SLX-redniFeriF090330-513
2733301V6A
.reifitnediytilibitapmocehtsirebmunledomrotcetedehT
Siemens Industry, Inc. 8 Fernwood Road Building Technologies Division
Florham Park, NJ 07932
Siemens Canada Limited Building Technologies Division 2 Kenview Boulevard Brampton, Ontario L6T 5E4 Canada
P/N A5Q00044197
Document ID A6V10324657_en--_f
Loading...