Siemens FDOOT441 Installation Instructions Manual

Installation Instructions Model FDOOT441
Multi-Criteria Fire Detector
Figure 1 FDOOT441
These instructions are written in accordance with the installation guidelines of NFPA 72, National Fire Alarm Code. The model FDOOT441 detector (shown in Figure 1) meets the VEWFD (Very Early Warning Fire Detector) classification and sensitivity requirements of NFPA 76 (Standard for the Fire Protection of Telecommunications Facilities) incorporating a programmable “Alert” (Pre-Alarm) sensitivity threshold of 0.2%/ft obscuration and an “Alarm” sensitivity threshold of 1.0%/ft obscuration.
CAUTION
Detection Device Storage
DO NOT install this detection device until all construction is completed.
DO NOT store this detection device where it can be contaminated by dirt, dust, or humidity.
DETECTOR PLACEMENT
Although no specific spacings are set for the detectors used for a clean air application, for multi-criteria fire detection use 30 foot center spacing (900 sq ft) from NFP A S tandard 72 initiating devices chapter, if practical, as a guide or starting point for a detector installation layout. This spacing, however, is based on ideal conditions–smooth ceiling, no air movement, and no physical obstructions. In some applications, therefore, considerably less area is protected adequately by each smoke detector. This is why it is mandatory to closely follow the installation drawings. In all installations place the detector on the ceiling, a minimum of 6 inches from a side wall, or on a wall, 12 inches from the ceiling.
For FM Approved installations, this device has an R TI rating of QUICK. For thermal detection, use the matrix below:
teeF,gnicapS,gnitaRerutarepmeT
05571,561,551,541,531drauGtuohtiWdnahtiW 06571,561,551,541,531drauGtuohtiW 06551,541,5 07541,531drauGtuohtiW 07531drauGhtiW
31drauGhtiW
0
FledoMdrauGtuohtiW/htiW
If you have any questions regarding detector placement, follow the drawings provided or approved by Siemens Industry, Inc., or by its authorized distributors. This is extremely important! The detector placements shown on these drawings were chosen after a careful evaluation of the area that is protected. Such factors as air currents, temperature, humidity , pressure, and the nature of the fire load were carefully considered. Especially noted were the room or area configuration and the type of ceiling (sloped or flat, smooth or beamed). Siemens Industry, Inc.’s extensive experience in the design of the system assures the best detector placement by following these drawings.
TO AVOID NUISANCE ALARMS
Do not locate the detectors where excessive smoke concentrations exist under normal conditions, or in areas of prolonged high relative humidity where condensation occurs.
Do not locate the detectors next to an oil burner, kitchen, or garage where exhaust fumes can trigger an alarm. Other causes of false alarm are dust accumulation, heavy concentrations of steam, heavy pipe or cigar smoke, and certain aerosol sprays.
AIR CURRENTS
Before a detector can sense a fire, the products of combustion or smoke must travel from the fire to the detector. This travel is especially influenced by air currents; therefore, consider air movement when designing the system. While combustion products tend to rise, drafts from hallways, air diffusers, fans, etc., may help or hinder the travel of combustion products to the detector. When positioning a detector at a particular location, give consideration to windows and doors, both open and closed, to ventilating systems, both in and out of operation, and to other factors influencing air movement. Do not install a detector in the air stream of a room air supply diffuser. It is better to position a detector closer to an air return.
The distance that products of combustion or smoke travel from a fire to the detector is not usually the shortest linear route. Combustion products or smoke usually rise to the ceiling, then spread out. Average ceiling heights of 8 to 10 feet do not abnormally affect detector response. High ceilings, located in churches, warehouses, auditoriums, etc., do affect detector response and should be considered.
A6V10324655_en--_e
Building
Siemens Siemens
Siemens
Siemens Siemens
TT
ecec
hnologies Dihnologies Di
T
ec
hnologies Di
TT
ecec
hnologies Dihnologies Di
IndustryIndustry
Industry
IndustryIndustry
visionvision
vision
visionvision
,,
Inc. Inc.
,
Inc.
,,
Inc. Inc.
SPECIAL CEILING CONSTRUCTION FACTORS
Ceiling obstructions change the natural movement of air and combustion products. Depending on the direction of smoke travel, joists and beams can slow the movement of heated air and smoke, while pockets between them can contain a reduced level of smoke. Take obstructions created by girders, joists, beams, air conditioning ducts, or architectural design into consideration when determining area protection. Refer to the Initiating Devices chapter of NFPA S tandard 72 for Location and Spacing requirements for specific types of construction; e.g. beam, suspended, level, sloped and peaked ceilings.
TEMPERA TURE – HUMIDITY – PRESSURE – AIR VELOCITY
The temperature range for the FDOOT441 detector is 32°F (0°C) to 120°F (49°C). Use the detector in environments where the humidity does not exceed 95% (non-condensing). Normal changes of atmospheric pressure do not affect detector sensitivity. The air velocity range is 0-4000 f t/min for open areas applications. Follow detector spacing and location requirements
prevent installing the detector in the wrong base. The optional DPU label printer can be used for this purpose.
Each detector provides pre-programmed parameter sets which can be selected by the panel. The FDOOT441 provides two different alarm channels: multi-criteria (UL268) and direct in­duct (UL268A), and heat (UL521) which can be used simultaneously and can be configured and switched on or off individually by the panel. Follow the description and instructions provided in the operation manual of specific control panel used. The FDOOT441 can be set to the FDOOT441 Selectable Application Profiles, the FDOOT441 Selectable Fixed T emperature Threshold Profiles and the FDOOT441 Selectable Alarm Threshold Setting Profiles shown in the tables below and to the right.
Additionally the detector can have another channel that can be configured by the panel to have a low or high temperature warning in the range from -4° to 120°F (-20° to 49°C). (Not with
FC2005.) in NFPA 72 Chapter for High Air Movement Areas and Control of Smoke Spread. The detectors can also be installed in duct applications between 0 and 4000 ft/min. For duct installations follow detector installation requirements in NFPA 90A, Chapter for Special Ceiling Construction Factors. When the detectors employ a fixed temperature rating of 1650F or less, they are intended for a maximum installation temperature of 1000F (37.80C).
UL listed with STI Mechanical Protection Guard Model: STI-9604 (see www.STI-USA.com for details).
LED INDICATOR OPERATION
The Model FDOOT441 contains an LED indicator capable of flashing either one of three distinct colors: green, yellow, or red. During each flash interval, the microprocessor-based detector monitors the following:
Smoke in its sensing chamber
Smoke sensitivity is within the range indicated on the
nameplate label
Internal sensors and electronics Based on the results of the monitoring, the LED indicator flashes
the following:
hsalF
roloCnoitidnoC
*neerG
wolleY
deRmralA1
oN
*sehsalF
vitisnes
.tnemecalper
tceteD
.dedeensi
.desulenaPeht
ekomS.noitarepoyrosivrepuslamroN
.stimildetarnihtiwsiyti
sdeendnaelbuortnisirotceteD
tnemecalperro,derewoptonsiro
lavretnIhsalF
)sdnoceS(
01
4
­fonoitpircsedgnidnopserrocehtwollofesaelP.ffodenrutebnacDEL*
DETECTOR PROGRAMMING
Each detector must be programmed to respond to a unique system address between 001 - 050 for FC2005.
• To program the detector address, use the Model DPU Device Programming Unit. Refer to the DPU Manual, P/N 315-033260.
• Record the loop and device number (system address) for the detector on the detector label and on the base to
ELECTRICAL
For information on electrical characteristics of the detector, refer to the FDOOT441/FDOOTC441 T echnical Manual, A6V10325549 at https://www.buildingtechnologies.siemens.com/extranet/ba-sp/. Refer to the panel Installation, Operation and Maintenance Manual for maximum line impedance of the loop driver.
WIRING
Detector bases for Model FDOOT441 should be connected as shown in Figure 2.
DETECTOR MOUNTING
The recommended orientation of the detector for wall mounting is shown in Figure 3. T o ensure proper inst allation of the detector head into the base, be sure the wires are properly dressed at installation:
• Position all wires flat against the base.
• Take up all slack in the outlet box
• Route wires away from connector terminals.
TO INSTALL DETECTOR HEAD:
• Rotate detector counterclockwise while gently pressing on it until the detector seats fully into base.
• Then rotate the detector clockwise until it stops and locks in place. Insert optional locking screw (Order Model LK-11).
erutarepmeTdexiFelbatceleS144TOODF
seliforPdlohserhT
0
531erutarepmetdexiF
F
0
F
541erutarepmetdexiF
0
F
551erutarepmetdexiF
0
F
561erutarepmetdexiF
0
F
0
531erutarepmetdexiF
0
571erutarepmetdexiF
0
531erutarepmetdexiF
0
571erutarepmetdexiF
571erutarepmetdexiF
0
51)RoR(esiRfoetaR+F
F
0
51)RoR(esiRfoetaR+F
F
0
02)RoR(esiRfoetaR+F
F
0
02)RoR(esiRfoetaR+F
F
seliforPgnitteSdlohserhTmralAelbatceleS144TOODF
dlohserhTtf/%05.2 dlohserhTtf/%00.3
/%05.2
deifirev,dlohserhTtf deifirev,dlohserhTtf/%00.3
Siemens Industry, Inc. Building Technologies Division
A6V10324655_en--_e2
Loading...
+ 2 hidden pages