Transmittal, reproduction, dissemination and/or editing of this document as well as
utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of damages.
All rights created by patent grant or registration of a utility model or design patent
are reserved.
Issued by:
Siemens Switzerland Ltd.
Infrastructure & Cities Sector
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies
Edition: 2012-09-07
Document ID: 007016_i_en_--
2
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 3
Table of contents
1 About this document .........................................................................................6
A6V10229261 List of compatibility (for 'Cerberus PRO' product line)
A6V10332811 Mounting/Commissioning Linear smoke detector FDL241-9
1.2 Technical terms
Term Explanation
ABS Acrylonitrile-butadiene-styrene (plastic)
ASA Advanced Signal Analysis
DLR Reflector
FDL Linear smoke detector
FDnet/C-NET Addressed detector line
Collective Unaddressed detector line
MC link Maintenance and commissioning link
PC Polycarbonate (plastic)
9
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 10
About this document
1
History of changes
1.3 History of changes
The reference document's modification index applies to all languages into which
the reference document is translated.
The first edition of a language version or a country variant may for example have
Modification index Edition date Brief description
the modification index 'd' instead of 'a' if the reference document already has this
modification index.
The table below shows this document's history of changes:
i 2012-09-07 Date format changed to meet ISO 8601 specifications (format
h 05.2011 Content and layout revised, history of changes redefined and standardized
g 01.2009 New label for measurements
f 10.2007 Supplements in the technical data: line separator, standard EN 54-17,
e 08.2006 Shielding added in connection diagram
d 05.2005 Compatibility adapted
c 01.2005 Name of division
b 06.2004 Edition with detector heating unit
a 05.2004 First edition
yyyy-mm-dd); reference to standard EN 62471 added; editorial changes
Reference documents adapted
LPCB approvals, information about air humidity
Commissioning of the detector and technical data revised
The language versions and country variants produced by a local company have
the same modification index as the corresponding reference document. They are
not however included in the table below.
10
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 11
About this document
History of changes
1
The table below shows the published language versions and country variants with
the corresponding modification index:
Modification index en_-- de_-- fr_-- it_-- es_--
i X X X X X
h X X X X X
g – X – – –
f X X – – –
e X X – – –
d X X – – –
c X X – – –
b X X X X X
a X X X X X
X = published
– = no publication with this modification index
11
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 12
Safety
2
Safety instructions
2 Safety
2.1 Safety instructions
The safety notices must be observed in order to protect people and property.
The safety notices in this document contain the following elements:
Symbol for danger
Signal word
Nature and origin of the danger
Consequences if the danger occurs
Measures or prohibitions for danger avoidance
Symbol for danger
This is the symbol for danger. It warns of risks of injury.
Additional danger symbols
These symbols indicate general dangers, the type of danger or possible
consequences, measures and prohibitions, examples of which are shown in the
following table:
Follow all measures identified by this symbol to avoid injury or death.
General danger
Explosive atmosphere
Voltage/electric shock
Laser light
Battery
Heat
Signal word
The signal word classifies the danger as defined in the following table:
Signal word Danger level
DANGER DANGER identifies a dangerous situation, which will result directly in death or serious injury
if you do not avoid this situation.
WARNING WARNING identifies a dangerous situation, which may result in death or serious injury if
you do not avoid this situation.
CAUTION CAUTION identifies a dangerous situation, which could result in slight to moderately serious
injury if you do not avoid this situation.
NOTICE
12
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
NOTICE
identifies possible damage to property that may result from non-observance.
Page 13
How risk of injury is presented
Information about the risk of injury is shown as follows:
WARNING
Safety
Safety instructions
2
Nature and origin of the danger
Consequences if the danger occurs
● Measures / prohibitions for danger avoidance
How possible damage to property is presented
Information about possible damage to property is shown as follows:
NOTICE
Nature and origin of the danger
Consequences if the danger occurs
● Measures / prohibitions for danger avoidance
13
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 14
Safety
2
Safety regulations for the method of operation
2.2 Safety regulations for the method of operation
National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant
European and international safety standards. Should additional national or local
safety standards or legislation concerning the planning, assembly, installation,
operation or disposal of the product apply at the place of operation, then these
must also be taken into account together with the safety regulations in the product
documentation.
Electrical installations
WARNING
Electrical voltage
Electric shock
● Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
Lock volt-free areas to prevent them being switched back on again by mistake.
Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
Produce earthing as stated in local safety regulations.
Assembly, installation, commissioning and maintenance
If you require tools such as a ladder, these must be safe and must be intended
for the work in hand.
When starting the fire control panel ensure that unstable conditions cannot
arise.
Ensure that all points listed in the 'Testing the product operability' section below
are observed.
You may only set controls to normal function when the product operability has
been completely tested and the system has been handed over to the customer.
14
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 15
Safety
Safety regulations for the method of operation
2
Testing the product operability
Prevent the remote transmission from triggering erroneously.
If testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
The activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following
instructions must be observed:
– Use the correct potential for activation; this is generally the potential of the
building installation.
– Only check controls up to the interface (relay with blocking option).
– Make sure that only the controls to be tested are activated.
Inform people before testing the alarm devices and allow for possible panic
responses.
Inform people about any noise or mist which may be produced.
Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system design and the products
Modifications to the system and to individual products may lead to faults,
malfunctioning and safety risks. Written confirmation must be obtained from
Siemens and the corresponding safety bodies for modifications or additions.
Modules and spare parts
Components and spare parts must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by
Siemens.
Only use fuses with the specified fuse characteristics.
Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by
Siemens.
Batteries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.
Disregard of the safety regulations
Before they are delivered, Siemens products are tested to ensure they function
correctly when used properly. Siemens disclaims all liability for damage or injuries
caused by the incorrect application of the instructions or the disregard of danger
warnings contained in the documentation. This applies in particular to the following
damage:
Personal injuries or damage to property caused by improper use and incorrect
application
Personal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
Personal injury or damage to property caused by poor maintenance or lack of
maintenance
15
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 16
Safety
2
Standards and directives complied with
2.3 Standards and directives complied with
A list of the standards and directives complied with is available from your Siemens
contact.
2.4 Release Notes
Limitations to the configuration or use of devices in a fire detection installation with
a particular firmware version are possible.
WARNING
Limited or non-existent fire detection
Personal injury and damage to property in the event of a fire.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
NOTICE
Incorrect planning and/or configuration
Important standards and specifications are not satisfied.
Fire detection installation is not accepted for commissioning.
Additional expense resulting from necessary new planning and/or configuration.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
16
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 17
Structure and function
Overview
3
3 Structure and function
3.1 Overview
The linear smoke detector FDL241-9 detects fires according to the principle of light
attenuation by smoke. The linear smoke detector works together with a reflector,
which is installed opposite the detector.
Properties
Communication via FDnet /C-NET detector line or collective detector line
Signal processing with ASAtechnology (ASA = Advanced Signal Analysis)
Detection distance from 5 to100 m
Three sensitivity levels
In accordance with EN 62471, 'Photobiological Safety of Lamps and Lamp
Systems', the linear smoke detector falls into the 'Exempt Group'.
3.1.1 Details for ordering
Type Order no. Designation
FDL241-9 A5Q00002298 Linear smoke detector
3.1.2 Product version ES
The product version ES provides the technical status of a device in terms of
software and hardware. The product version is provided as a two-digit number.
You will find the details of your device's product version:
On the packaging label
On the product label or the type plate
Product version on the packaging label
Details of the product version can be found directly on the packaging label in the
barcode:
ES
Example of a packaging label with details of the product version
17
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 18
Structure and function
3
Setup
Product version on the product label and the type plate
Details of the product version can be found after the device order number:
04
Example of a product label with details of the product version
Depending on the product and various approvals, the product labels may differ in
terms of the information type and layout.
Look for your device's order number on the product label.
You will find the product version after the order number.
3.2 Setup
The linear smoke detector consists of the detector base (1), the terminal block (2),
the detector unit (3) and the hood (4).
ES
3
4
12
Setting up the linear smoke detector
1 Detector base 3 Detector unit
2 Terminal block 4 Hood
18
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 19
Detector unit
Structure and function
Setup
3
12
8
14
13
12
Setting up the detector unit
3
4
5
6
7
8
9
10
11
1 Holder for special filter 8 Safety screws
2 Holder for mirror with visor 9 DIP switch
3 Holder for notch 10 Connection for detector heating
unit
4 Horizontal scale 11 Alarm indicator
5 Receiver lens 12 Connection for adjustment device
6 Knurled screw for horizontal
13 Vertical scale
setting
7 Transmitter lens 14 Knurled screw for vertical setting
19
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 20
Structure and function
3
Function
Labels
In der Haube sind zwei Etiketten beigelegt. Measurements are entered on these
labels when commissioning or checking the linear smoke detector. These
measurements serve as a basis for troubleshooting when periodically checking the
linear smoke detector.
FDL241-9; commissioning & adjustment data
(values displayed on adjustment device)
date &
action
values
distance
[m]
signalvalue
[-]
deviatesignal
[%]
coveredreflector
value
[%]
notes
Label for entering the measurements
3.3 Function
The linear smoke detector smoke detector consists of a transmitter and a receiver
and works according to the principle of light attenuation by smoke. The transmitter
transmits to the reflector a highly focused, pulse-shaped infrared ray. If no smoke is
present, a large part of the infrared ray reaches the reflector and is returned to the
receiver. The incoming light generates an electric signal on the receiver's photo
diode.
12
E
S
3
Function of the linear smoke detector without smoke
1 Detector E Receiver
2 Reflector S Transmitter
3 Measuring section 5…100 m
20
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 21
Structure and function
Function
3
When smoke is present, part of the infrared ray is absorbed when it encounters the
smoke particles, while another part is scattered by smoke particles. The rest
reaches the reflector and is returned to the receiver. The infrared ray is attenuated
further. Only a small part of the infrared ray initially transmitted reaches the
receiver, and the electrical signal becomes weaker.
2
1
5
3
4
2
Function of the linear smoke detector with smoke
1 Absorption 4 Smoke particle
2 Scattering 5 Infrared ray
3 Attenuated infrared ray
The linear smoke detector measures the distance, which enables an exact
alignment of the smoke detector to the reflector when the detector is
commissioned.
Due to distance measuring, the smoke detector recognizes when the measuring
section is crossed by a reflecting object. In this case, the smoke detector sends a
fault signal to the control panel.
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
21
Page 22
Structure and function
3
Function
3.3.1 Infrared ray
Setup of the infrared ray
The infrared ray is scattered, giving it a conical shape. The radiation energy
decreases outwards. The infrared ray is divided into the following three ranges:
Effective range (1): The effective range is the connection between the
transmitter, reflector and receiver.
Core range (2): In the core, enough radiation energy is present to operate the
system.
Scattering range (3): The radiation energy in the scattering range is insufficient
and does not ensure the functionality of the system.
12
FDL
3
DLR
Setup of the infrared ray
1 Effective range 3 Scattering range
2 Core range
1
FDL
0,57°
3
0,57°
2
DLR
d
Diameter of the core
1 Opening angle d Diameter of the core range
depending on the detection
distance
2 Diameter of the core l Detection distance
3 Infrared ray
22
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 23
Structure and function
Function
3
Example of calculating the diameter of the core range depending on the detection
distance:
Known: Detection distance l = 100 m
Wanted: Diameter d of the core range
Adjustment options for the infrared ray
The infrared ray can be adjusted horizontally by a maximum of 10° in either
direction and vertically by a maximum of 5° in either direction. This adjustment
range can be used for an optimum positioning of the devices. In the case of
detection distances greater than 50 m, position the detector and reflector as close
to opposite one another as possible. This makes adjustment easier.
One turn of the knurled screw moves the infrared ray by approx. 0.8 m per 100 m
distance.
1
FDL
10°
DLR
16 m16 m
10°
DLR
100 m
Horizontal adjustment range
1 Diameter of the core
1
FDL
Vertical adjustment range
100 m
5°
5°
DLR
DLR
8 m8 m
1 Diameter of the core
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
23
Page 24
Structure and function
3
Function
3.3.2 Reflectors
Retro-reflectors reflect rays of light that reach them in parallel. The reflector does
not necessarily have to be installed at a right angle to the ray of light. Vibrations
and distortions on the installation surface do not interfere with this. Interfering light
is also reflected in parallel and does not therefore reach the receiver.
The reflectors must be installed at an maximum inclination angle of 20° in all
directions.
max. 20°
11
max. 20°
1
Reflectors with various inclinations
1 Reflector
Reflector for long distance (prism) DLR1191
The reflector for long distance consists of a prism and a housing. The retroreflecting prism has the shape of an even pyramid, the lateral surfaces of which are
made up from isosceles, right-angled triangles. Light rays coming in through the
base surface are completely reflected thrice by the lateral surfaces and are than
scattered back through the base.
The reflector for long distance is fitted with a heating unit and can therefore be
used in environments with a danger of moisture condensation. The heating unit
must be connected to a 24 V supply.
1
Reflector and principle of the reflector
1 Ray of light
24
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 25
Reflector for middle distance (foil) DLR1192 and reflector for short
distance (foil) DLR1193
The reflectors for middle distance and for short distance consist of a foil with microprismatic elements, which are formed in a transparent, synthetic resin, sealed and
mounted on a plastic base. The foil has the same principal effect as the prism.
See also
Accessories [➙ 30]
Detection distance and reflector selection [➙ 40]
3.3.3 Line separator
All FDnet/C-NET devices are equipped with a line separator.
The FDnet/C-NET device is equipped with electronic switches which isolate the
defective part in case of a short-circuit on the detector line. The rest of the detector
line remains serviceable. On a loop line all FDnet/C-NET devices remain fully
functional after a simple error.
Structure and function
Function
3
3.3.4 Danger levels
The detector can transmit the following danger levels to the control panel:
Danger level Meaning Comment
0 No danger Normal condition
11 Check situation You may have to select another
parameter set.
You may have to re-initialize the
detector.
21 Warning Possible danger
3 Alarm Fire
The evaluation of the danger level and the decisions to be taken (e.g. activation of
remote transmission) are configured in the control panel.
1
Danger levels 1 and 2 are only transmitted to FDnet/C-NET detector lines. On a
collective detector line, only danger levels 0 and 3 can be transmitted to the control
panel.
25
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 26
Structure and function
3
Function
3.3.5 Diagnosis levels
Information displayed on the
detector exchanger and tester
For the most part, the linear smoke detector monitors its functionality
autonomously.
The following diagnosis levels are derived from the different control measurements:
Normal
Observe information
Fault
For details, see table below.
When a fatal error (one which impairs the detector's function) occurs, a fault
message is signaled. To correct the cause of the fault, additional information is
available in the detector. This can be displayed by the detector exchanger and
tester FDUD292 or the intelligent detector tester FDUD293, for example.
Meaning Measures
'no deviation' Normal, no fault is present
The detector is fully functional
'maybe excha.' 1 Observe information
Compensation value is too high or too low
Detector is fully functional, reflection or dirt
cannot however be compensated for
'In 1 problem 3' 1 Observe information
Repeated ray interruption
'In 1 trouble 1' 1 Fault
Detection is no longer ensured
Signal interruption: Signal <10 % of the
compensation value
'In 1 trouble 2' 1 Fault
Detection is no longer ensured
Distance interruption: distance measuring
less than 40 % of the detection distance
during initialization
None
In the case of dirt, clean the detector
and reflector and re-initialize them
In the case of reflection, remove or
cover reflecting objects
Prevent interruption or position detector in
another place
Remove obstacle
Clean the detector and reflector and re-
initialize them
Remove obstacle
26
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 27
Structure and function
Function
3
Information displayed on the
detector exchanger and tester
Any fault message 2
Meaning Measures
Invalid parameter settings Set valid parameters
Reflection Remove or cover reflecting objects
Invalid initialization Re-initialize detector
Supply error Check voltage of detector line
Replace detector
Software error (Watchdog error) Replace detector
Memory error Replace detector
Communication error involving detector and
control panel
1
The information displayed on the detector exchanger and tester and intelligent
Remedy cause
detector tester is always in English; no translation into the country language.
2
This status can be displayed together with another status, e.g. 'needed excha.'
(replacement necessary).
You will find more information in documents 007227 and 009718.
See also
Applicable documents [➙ 9]
Repair [➙ 81]
3.3.6 Signal processing
The signal processing of the detector efficiently distinguishes between fire events
and deceptive phenomena. The basis for reaching a danger level is not only given
by measurements below a certain response threshold; moreover, the smoke
density progression is observed over a longer period of time and evaluated with
ASAtechnology (ASA = Advanced Signal Analysis). The detector processes the
signal according to internal diagnoses and reports the result to the control panel.
Correction value
The compensation value is the reference value for the current signal. All response
thresholds and evaluations are based on the current compensation value.
The first compensation value is defined during initialization. The compensation
value is updated approximately every 60 minutes to compensate for any slow
signal drifting. This drift may be caused by dirt on the detector, for example.
The current compensation value is saved in a non-volatile memory every 23 hours
and is not lost in a power cut.
The compensation value can be a minimum of 50 % of the compensation value
during initialization.
Standardized signal value
The standardized signal value is the signal value (as a percentage) of the current
compensation value. If the signal value is the same as the compensation value, the
standardized signal value is 100 %. The standardized signal value is displayed on
the adjustment device.
27
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 28
Structure and function
3
Function
Response threshold
The response threshold corresponds to the standardized signal value for danger
level 3. When the signal drops below the response threshold, algorithms are
activated that trigger an alarm after a certain amount of time. Depending on the
sensitivity level of the parameter set selected, the response threshold may be
higher or lower:
Very sensitive: Response threshold is 30 % below the compensation value.
Sensitive: Response threshold is 50 % below the compensation value.
Standard: Response threshold is 65 % below the compensation value.
Response threshold for various sensitivity settings
1 Signal (typical signal course
during smoke generation)
4 Response threshold for 'Sensitive'
(50 %)
2 Correction value 5 Response threshold for 'Standard'
(65 %)
3 Response threshold for 'Very
sensitive' (30 %)
28
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 29
Structure and function
Function
3
Leveling
The signal is measured four times per second and processed with leveling filters.
Extreme values, which may be caused by signal faults, are thereby leveled out.
Further signal processing is based on the leveled signal.
Leveling characteristics
1 Unleveled signal 2 Leveled signal
Time until alarm activation
The table below shows the time until alarm activation for various internal detector
diagnoses.
Internal detector diagnosis Time until alarm activation (typical value)
Normal or slow fire 6 s
Background noise or repeated open lines 16 s
Alarm test filter 10 s
29
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 30
Structure and function
A
3
ccessories
3.4 Accessories
3.4.1 Base for linear smoke detector FDLB291
For installing the linear smoke detector
Compatible with:
– Linear smoke detector FDL241-9
Order no.: A5Q00003941
See also
Installing the detector base [➙ 54]
3.4.2 Reflector for long distance (prism) DLR1191
For reflecting the infrared ray of the linear smoke
detector
Prism-shaped
Reflection distance: 20…100 m
With a built-in heating unit
Compatible with:
– Linear smoke detector FDL241-9
Order no.: BPZ:4787710001
See also
Installing the reflector for lo
ng distance (prism) [➙ 61]
30
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 31
Structure and function
A
ccessories
3
3.4.3 Reflector for middle distance (foil) DLR1192
For reflecting the infrared ray of the linear smoke
detector
Micro-prismatic foil
Reflection distance: 30 … 65 m
Dimensions: 200 x 200 x 2.5 mm
Hole diameter: 4 mm
Compatible with:
– Linear smoke detector FDL241-9
Order no.: BPZ:4788490001
See also
Installing the reflectors for middle distance and short
tance (foil) [➙ 62]
dis
3.4.4 Reflector for short distance (foil) DLR1193
For reflecting the infrared ray of the linear smoke
detector
Micro-prismatic foil
Reflection distance: 10 … 30 m
Dimensions: 100 x 100 x 2.5 mm
Hole diameter: 4 mm
Compatible with:
– Linear smoke detector FDL241-9
Order no.: BPZ:4787840001
See also
Installing the reflectors for middle distance and short
tance (foil) [➙ 62]
dis
3.4.5 Short distance filter DLF1191-AA
For toning down the infrared ray over short
distances
Distance: 7…10 m
Compatible with:
– Linear smoke detector FDL241-9
Order no.: BPZ:4933030001
Building Technologies
Fire Safety 2012-09-07
31
007016_i_en_--
Page 32
Structure and function
A
3
ccessories
3.4.6 Short distance filter DLF1191-AB
For toning down the infrared ray over short
distances
Distance: 5…8 m
Compatible with:
– Linear smoke detector FDL241-9
Order no.: BPZ:4933160001
3.4.7 Extraneous light filter DLF1191-AC
For filtering extraneous light during a high level of
extraneous light
Compatible with:
– Linear smoke detector FDL241-9
Order no.: BPZ:5221480001
3.4.8 Detector heating unit DLH1191A
For applications where there is danger of moisture
condensation or icing
Incl. terminal block for the connection
Compatible with:
– Linear smoke detector FDL241-9
Order no.: BPZ:4787970001
See also
Installing the detector heating unit (optional) [➙ 66]
32
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 33
A
3.4.9 Adjustment kit FDLU291
For commissioning the linear smoke detector
Components: Adjustment device, alarm test filter,
Compatible with:
Order no.: A5Q00004905
Structure and function
ccessories
visor, magnet, spiral cable, MC link cable, 9 V
battery, suspension fixture with cable gripper and
chain, case
– Linear smoke detector FDL241-9
3
3.4.10 Detector tester for linear smoke detector RE10
For undertaking a performance check on the linear
smoke detector
Compatible with:
– Linear smoke detector FDL241-9
Order no.: BPZ:3685190001
3.4.11 Alarm test filter TF04
Alarm test filter for detector tester for linear smoke
detector RE10
Absorption: 77 %
Dimensions: approx. 170 x 85 mm
Compatible with:
– Linear smoke detector FDL241-9
– Detector tester for linear smoke detector RE10
– Adjustment kit FDLU291
Order no.: BPZ:4931090001
3.4.12 M20 x 1.5 metal cable gland
For introducing a cable into a housing
Allows for increased IP protection
Compatible with:
– M20 x 1.5 metal counter nut
Building Technologies
Fire Safety 2012-09-07
– Manual call point FDM223
– Manual call point FDM224
– Manual call point FDM223H
– Manual call point FDM224H
Order no.: A5Q00004478
33
007016_i_en_--
Page 34
Planning
4
Fields of application
4 Planning
4.1 Fields of application
Typical fields of application of the linear smoke detector
Application area Reason
Buildings with historically valuable ceilings Fire detector installation on ceilings is not
Atriums, detection on multiple levels Point detector unaccessible due to height
Large rooms and high halls Lower investment costs
Churches No impairment of the ceiling by installation
Long corridors, cable and energy ducts with
a room height of more than 3 m
Airplane hangars with stable building
construction, in which flame detectors alone
do not suffice
Saw-tooth roofs, where point detectors must
be suspended lower
desirable or possible.
Smoldering fire detection not possible with
point detectors
or point detectors
Lower investment costs
Lower investment costs
Lower investment costs
Examples of fields of application of the linear smoke detector
4.2 General planning information
Between the detector and the reflector therer must be permanent, undisturbed
visual contact.
– The infrared ray must not be interrupted by moving objects, e.g. cranes,
ladders, transportable objects, cobwebs.
– Vision impaired by dust, vapor or smoke generated as a result of operation
may impair the system.
The detector's installation location must be absolutely statically stable, as the
admissible deviation of the infrared ray is max. 0.1°. Examples:
– Concrete and brick walls are suitable.
– Wood and steel girder constructions are unsuitable, as temperature and
humidity fluctuations, wind or snow pressure influence on such
constructions.
The detector and reflector must be securely installed on the installation surface.
In the case of detection distances greater than 50 m, position the detector and
reflector as close to opposite one another as possible. This makes adjustment
easier.
Position the detector near the ceiling, as the smoke is generally only sufficiently
think to trigger an alarm in the mushroom cloud.
Avoid bringing the detector into direct contact with sunlight, halogen lights etc.
34
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 35
Planning
Planning in rooms with flat ceilings
The infrared ray must be at least 30 cm away from ceilings, walls, fittings and
4
goods in stock to avoid unwanted reflections. You can use the adjustment
device to check for unwanted reflections. Instructions for this can be found in
the chapter 'Testing detectors [➙ 77]', in the 'Testing detection distance'
section. If the standardi
zed signal value is greater than 5 %, you must increase
the distance by the infrared ray.
Ensure there is sufficient space around the detector such that the infrared ray's
entire adjustment range can be used.
If you use covers or enclosures for the detector, you must ensure sufficient
space around the detector such that e.g. the following work can be carried out
efficiently and without hindrance:
– Connect the adjustment device
– Set the detector optics
– Mount hood
After commissioning for the first time, the service personnel must be able to
access the detector safely and with ease, e.g. for maintenance and adjustment
work.
See also
Testing detectors [➙ 77]
4.3 Planning in rooms with flat ceilings
Please note the following points if you are installing detectors in rooms with flat
ceilings. More information about the individual points can be found on the specified
pages.
8
7
6
5
1 Detection distance 5 Minimum distances to ceilings,
2 Room height 6 Distance between detector and
3 Installation height 7 Minimum distance between two
1
2
3
4
walls etc.
ceiling
detectors
Detection distance (1): Define the distance to be monitored. Depending on this,
define the type and number of reflectors. See [➙ 40]
4 Width of monitoring area 8 Detector or reflector
Room height (2) and installation height (3): Define the installation height. In
high rooms, you must install detectors at different levels. See [➙ 42]
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
35
Page 36
Planning
4
Planning in rooms with flat ceilings
Width of monitoring area (4): Define the width of the monitoring area and,
depending on this, the number of detectors. See [➙ 43]
Minimum distances (5): The infrared ray must be at least 30 cm away from
ceilings, walls, fittings and goods in stock to avoid unwanted reflections.
Distance between detector and ceiling (6): Define the distance between the
detector and the ceiling depending on the room height. See [➙ 43]
Installation surface: Define the installation surface given the architectural
circumstances. The installation surface must be stable and vibration-free.
See [➙ 45]
If the room has
one or more of the following circumstances, you must also observe
further information.
Narrow spatial circumstances: Maintain the minimum distance (7) between two
detectors. See [➙ 47]
Girders: The detector can be installed in the ceiling panel between the girders
or below the girders. See [➙ 47]
Glass panes: Detection through glass panes and installation on glass panes
are only possible under certain circumstances. See [➙ 49]
Danger of moisture condensation: Use the detector heating unit if there is a
danger of moisture condensation. See [➙ 50]
Extraneous light: Use the extraneous light filter in the case of extremely strong
extraneous light. See [➙ 51]
36
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 37
Planning
Planning in rooms with inclined ceilings
4
4.4 Planning in rooms with inclined ceilings
A ceiling is inclined if the incline n is at least 0.2. This corresponds to an inclination
angle of 11°.
Calculation of the inclination n:
n
a
b
Please note the following points if you are installing detectors in rooms with inclined
ceilings. More information about the individual points can be found on the specified
pages.
1
8
n =
3
a
b
4
2
7
5
6
Planning in rooms with inclined ceilings
1 Detector or reflector 5 Detection distance
2 Minimum distance between two
6 Width of monitoring area
detectors
3 Distance between detector and
7 Installation height
ceiling
4 Room height 8 Minimum distances to ceilings,
walls etc.
Detection distance (5): Define the distance to be monitored. Depending on this,
define the type and number of reflectors. See [➙ 40]
Room height (4) and installation height (7): Define the installation height. In
high rooms, you must install detectors at different levels. See [➙ 42]
Width of monitoring area (6): Define the width of the monitoring area and,
depending on this, the number of detectors. See [➙ 43]
Minimum distances (8): The infrared ray must be at least 30 cm away from
ceilings, walls, fittings and goods in stock to avoid unwanted reflections.
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
37
Page 38
Planning
4
Planning in rooms with inclined ceilings
Distance between detector and ceiling (3): Define the distance between the
Installation surface: Define the installation surface given the architectural
If the room has
further information.
Ceiling with uneven inclines: The detector must be slid sideways to the flatter
Narrow spatial circumstances: Maintain the minimum distance (2) between two
Girders: The detector can be installed in the ceiling panel between the girders
Glass panes: Detection through glass panes and installation on glass panes
Danger of moisture condensation: Use the detector heating unit if there is a
Extraneous light: Use the extraneous light filter in the case of extremely strong
detector and the ceiling depending on the room height. See [➙ 43]
circumstances. The installation surface must be stable and vibration-free. See
[➙ 45]
one or more of the following circumstances, you must also observe
roof incline. See [➙ 39]
detectors. See [➙ 47]
or below the girders. See [➙ 47]
are only possible under restricted circumstances. See [➙ 49]
danger of moisture condensation. See [➙ 50]
extraneous light. See [➙ 51]
Infrared ray in the gable
In the case of ceilings with an inclination of n > 0.5, you must always install an
infrared ray in the gable. In the case of ceilings with an inclination of n < 0.5, the
infrared ray is not necessary in the gable.
Left: Ceiling with inclination of n > 0.5. Right: Ceiling with inclination of n < 0.5
38
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 39
Planning in rooms with inclined ceilings
4.4.1 Ceilings with uneven inclines
In the case of ceilings with uneven inclines, the detector must be slid sideways to
the flatter roof incline. Define the distance between the detector and the ceiling (2)
using the room height (1).
2
Planning
4
1
Position on ceilings with uneven inclination
1 Room height 2 Distance between detector and
ceiling
Example: In the case of a room height of 10 m, the distance between the detector
and ceiling is 40 to 90 cm.
See also
Distance between detector and ceiling [➙ 43]
39
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 40
Planning
4
Detection distance and reflector selection
4.5 Detection distance and reflector selection
The detection distance between the detector and reflector is 5 to 100 m. Select the
reflectors depending on the detection distance.
The table below shows guidelines for the type and number of reflectors depending
on the detection distance.
Detection distance Type and number of reflectors
5 … 10 m 1 reflector for short distance (foil) DLR1193
+ filter for short distance DLF1191
10 … 30 m 1 reflector for short distance (foil) DLR1193
30 … 50 m 1 reflector for middle distance (foil)
50 … 65 m 4 reflectors for middle distance (foil)
20 … 100 m 1 reflector for long distance (prism)
Type and number of reflectors depending on the detection distance
If you are using more than one reflector, always position them close together and in
a square shape. The detection distance details are guidelines. They depend on
detector and reflector tolerances and may vary by a few meters. It is important that
a sufficiently high signal intensity is reached.
If there is a danger of moisture condensation, always use the reflector for long
distance and the built-in heating unit, even for short distances. You may not use
the reflectors for middle distance and short distance if there is a danger of moisture
condensation.
DLR1192
DLR1192
DLR1191
See also
Accessories [➙ 30]
40
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 41
Detection distance and reflector selection
4.5.1 Measures for long distances
Long distances can be split into smaller ones for monitoring. Detectors positioned
opposite one another can however have a negative influence on one another. In
such a position, install a sufficiently large plate between the reflectors, such that it
is not possible for detectors to influence those opposite them.
Planning
4
FDL
DLR
FDL
Subdivision of a longer distance
To check whether two detectors are influencing one another, proceed as follows:
1. Commission the first detector and use the adjustment device to measure the
standardized signal value.
2. Commission the second detector.
3. Use the adjustment device to once again measure the standardized signal
value of the first detector.
- If the standardized signal value has not changed since the first
measurement, the two detectors are not influencing one another.
- If the standardized signal value has changed since the first measurement,
the two detectors are influencing one another. Install a larger plate between
the reflectors or take other suitable measures.
4. Completely cover the reflector and for each detector use the adjustment device
to measure the standardized signal value. Measure the signal value once when
the the detector opposite is switched on and once when it is switched off. The
two signal values measured must not differ.
4.5.2 Measures for short distances
In the case of a short detection distance between 5 and 10 m, you must also use a
short distance filter. The following filters are available:
Detection distance Filter
5…8 m DLF1191-AB
7…10 m DLF1191-AA
Short distance filter
See also
Accessories [➙ 30]
41
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 42
Planning
4
Room height and installation height
4.6 Room height and installation height
In rooms with a height greater than 6 m, a second and, if necessary, third infrared
ray must be used such that smoldering fires or smaller fires are detected.
1
2
Detection of smoldering fires in high rooms on different levels
1 Detector 2 Reflectors
The table below shows examples of the installation height for different room
heights.
The higher the room, the greater the width of the monitoring area. To cover
heightened risks, you can also select a smaller width of monitoring area.
The figure below shows the maximum widths of monitoring area depending on the
room height. If the infrared ray is positioned at a lower level to detect smoldering
fires, the distance from the floor to the detector applies instead of the room height.
Planning
Width of monitoring area
4
Maximum widths of monitoring area depending on the room height
4.8 Distance between detector and ceiling
In order that the detector can detect smoke, the infrared ray must be positioned
immediately below the heat accumulation. Detectors and reflectors must therefore
be positioned at an ever-greater distance from the ceiling as the room height
increases. The steeper the angle of a gable roof, the greater the distance must be
between gable and infrared ray positioned in gable.
The figures below show the distance between the infrared ray and the ceiling
depending on the room height.
Flat ceilings
Flat ceilings: Distance between infrared ray and ceiling
43
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 44
Planning
4
Distance between detector and ceiling
Inclined ceilings
Inclined ceilings: Distance between infrared ray and ceiling
44
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 45
4.9 Installation surface
The detector must be installed on a stable and vibration-free surface. Remember
that large fluctuations in temperature (e.g. between day and night) can cause slight
deformations to iron girders etc. If the detector is installed on an unstable surface,
the infrared ray may not reach the reflector and therefore causes an alarm or fault.
The following are examples of unstable installation locations:
Walls of non-insulated rooms with steel constructions. These move due to the
lengthwise expansion of steel.
Bricked walls, on which a steel roof construction is placed.
In such cases, the detector must be installed on a stable surface, while the reflector
can be installed on the unstable wall.
Example
The example below illustrates how the infrared ray is deflected by the influence of
heat on a hall roof's steel construction.
Planning
Installation surface
4
l
Δl
c
DLRFDL
β
h
Incorrect installation: The infrared ray no longer reaches the reflector as a result of
deflection.
c Deflection of the infrared ray Δl Lengthwise expansion
l Length of the roof h Room height
Wanted: Deflection of the infrared ray c
Known:
l Length of the roof 80 m
α Expansion coefficient of steel 12 x 10-6 K
ΔT Difference in temperature 40 K
h Room height 4 m
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
-1
45
Page 46
Planning
Δ
4
Installation surface
Calculating the lengthwise expansion of the roof Δl:
l = l ××ΔT
α = 80000 mm
Calculating the angle β:
β = arctan
Δl
h
= arctan
Calculating the deflection c:
= β ctan ×l
= tan (0.55)
The deflection c is 0.77 m.
40 K
×
×
38.4 mm
4000 mm
80 m = 0.77 m
×
= 0.55°
DLRFDL
-1
= 38.4 mm0.000012
K
Possible solution: Install the detector on the stable surface and install the reflector on the
unstable wall
46
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 47
Minimum distance between two detectors
4.10 Minimum distance between two detectors
The greater the detection distance, the greater the distance between two detectors
must be. This prevents the detectors from influencing one another.
The figure below illustrates the minimum distance between two parallel infrared
rays.
Planning
4
Minimum distance between two parallel infrared rays
4.11 Arrangement with girders
The detector can be positioned in the ceiling panel between the girders or below
the girders.
Girders include building elements (e.g. air conditioning ducts) installed at a
distance of at maximum 15 cm below the ceiling.
Position in the ceiling panel between girders
The detector must be positioned in the ceiling panel between the girders if the
height of the girders is more than 20 % of the total room height. In this case, the
girders are considered as partition elements, and each ceiling panel must be
considered as a separate room.
> 20%
100%
Position in the ceiling panel between girders
47
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 48
Planning
A
4
rrangement with girders
Position below girders
The detector can be installed below girders if the following points apply:
The height of the girders is less than 20 % of the total room height.
The width of the ceiling panel is at most 50 % of the maximum width of
monitoring area.
The ceiling panel surface is a maximum of 200 m
Only the room height h up to the girder is relevant when calculating the width of
monitoring area.
< 20%
h
100%
2
.
min. 30cm
Position below girders
See also
Width of monitoring area [➙ 43]
48
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 49
4.12 Position on glass panes
Detection through glass panes
Detection through glass panes is only possible under certain circumstances.
Please observe the following points:
Glass panes must be smooth, clear, and stably fitted.
A maximum of two glass panes, each max. 5 mm thick, may be penetrated. It is
however better to only penetrate one glass pane.
The detection distance is reduced by 20 m per glass pane.
Detection is faultless when the standardized signal value is less than 5 % when
the reflector is covered.
Glass panes may never be at a right angle to the infrared ray (see example
below).
Glass panes must never be installed at an angle to the infrared ray, in which
the glass pane acts as a mirror and can reflect the infrared ray to the receiver
(impact angle = angle of reflection).
Planning
Position on glass panes
4
FDLDLR
1
E
S
2
min. 5-10°
2
FDL
E
S
Detection through glass panes. Left: Correct use. Right: Incorrect use.
1 Glass pane E Receiver
2 Light scatter S Transmitter
1
DLR
49
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 50
Planning
4
Measures against moisture condensation
Example:
1
DLR
2
FDL
DLR
3
Detection through one glass pane
1 Correct position 3 Glass pane
2 Incorrect position
Mounting reflectors on glass plates
When reflectors are installed on glass panes, there is danger of the glass panes,
not the reflector, reflecting the infrared ray. This may even occur after
commissioning, when the glass plate is slightly shifted. However, this is not the
case when the infrared ray does not hit the glass pane at a right angle, but at a
slight angle.
Recommendation: The infrared ray should reach the reflector at an angle of 5 to
10° to avoid unwanted reflection.
4.13 Measures against moisture condensation
Moisture condensation on the detector or reflector can cause faults and false
alarms. Moisture condensation can occur e.g. when the detector or reflector is
installed in a room with cool outer walls, where high air humidity and rapid
temperature increases can be expected as a result of sunshine on a non-insulated
roof, for example.
Use the detector heating unit DLH1191A for the linear smoke detector if there
is a danger of moisture condensation.
If there is a danger of moisture condensation, always use the reflector for long
distance and the built-in heating unit, even for short distances. You may not
use the reflectors for middle distance and short distance if there is a danger of
moisture condensation.
See also
Detector heating unit DLH1191A [➙ 32]
50
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 51
Measures for strong extraneous light
4.14 Measures for strong extraneous light
Interferences of the detector by extraneous light are rather rare. If faults occur
when there is strong extraneous light, use the extraneous light filter DLF1191-AC.
See also
Extraneous light filter DLF1191-AC [➙ 32]
4.15 Determine parameter set
A parameter set can be used to set the linear smoke detector perfectly to the
ambient features.
Two types of parameter set, each with three sensitivity levels, exist. The parameter
sets with open line and with British Standard Alarm differ in the way the smoke
detector responds to a signal interruption.
Parameter sets with interruption Parameter sets with British Standard Alarm
Planning
4
In the case of a signal interruption (signal
less than 10 % of the compensation value),
the 'Signal interruption' fault occurs. An
alarm is suppressed.
In the case of a distance interruption (signal
less than 40 % of the compensation value),
the 'Distance interruption' fault occurs. An
alarm is suppressed.
After canceling the fault, any possible alarm
is delayed for 40 s.
With distances of less than 7 m, the distance
is not evaluated.
The table below shows the parameter sets in three sensitivity levels and sample
applications of the parameter sets.
Parameter set
No. Name
01 Standard with open line
02 Standard with British
Standard Alarm
03 Sensitive with open line
04 Sensitive with British
Standard Alarm
05 Very sensitive with open line
06 Very sensitive with British
Standard Alarm
In case of a signal interruption (signal below
alarm threshold), an alarm is actuated.
In the case of a distance interruption
(distance measuring less than 40 % of the
initialization distance), the 'Distance
interruption' fault occurs. An alarm is
suppressed. When the signal drops below
the alarm threshold during the fault, an
alarm is actuated after 40 s.
-
With distances of less than 7 m, the distance
is not evaluated.
Properties of the monitored room Examples of application
Offices, warehouses, electric vehicle
traffic, congress centers
Low danger to life
No smoking ban necessary
High concentration of valuable
property
Medium danger to life
Smoking ban
Clean warehouses, museums, archives,
EDP and telecommunication systems in
clean environments, high level of air
change
51
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 52
Mounting / Installation
5
Determine parameter set
5 Mounting / Installation
Prerequisites
The installation locations for the detector and reflector are defined according to
the planning information.
The supply network is produced, connected and checked in line with the
country-specific installation guidelines.
Sequence
1. Switch detector over to collective operation (optional)
2. Installing the detector base
3. Electrical connection
4. Installing the reflector for long distance (prism)
5. Installing the reflectors for middle distance and short distance (foil)
Information on the individual steps can be found in the following chapters.
The detector is only installed on the detector base during commissioning.
See also
Planning [➙ 34]
52
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 53
Mounting / Installation
+
Switching detector over to collective operation
5.1 Switching detector over to collective operation
When supplied, the detector is set for operation on an FDnet/C-NET detector line.
When operating a collective detector line, the control panel normally switches the
detector to collective operation automatically.
Some collective control panels do not however automatically switch from FDnet/CNET operation to collective operation. In these cases, you must switch the detector
over manually. If you are not certain whether the detector is switched over
automatically, switch it manually to collective operation before installing.
The detector always switches automatically from collective operation to FDnet/CNET operation.
Procedure
Note the positive and negative poles.
The detector base must not be connected to the detector line.
5
1. Connect the detector base to a DC 12 V to 28 V source of DC voltage, e.g. a
battery, according to the connection diagram shown below. Use a screwdriver
to remove the load from the spring clip so you can slide in the wire.
2. Insert the detector unit into the detector base.
3. Wait around 15 seconds and then remove the detector unit and source of DC
voltage.
The detector is switched over to collective operation and can be connected to a
collective detector line.
-
Connection diagram for the source of DC voltage
53
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 54
Mounting / Installation
5
Installing the detector base
5.2 Installing the detector base
WARNING
Danger of falling
Bodily injury
● When installing, use a secured ladder or work platform.
CAUTION
Using the device in a damp and/or corrosive environment
Device function is impaired.
● Use the M20 x 1.5 metal cable gland in damp and/or corrosive environments.
1
2
Installation and electrical connection
1 Detector base 2 Terminal block
1. Break open the plastic parts in the detector base (1) at the openings you
require for cable entry. Note the arrows in the detector base indicating which
side should be at the top.
2. If necessary screw the M20 x 1.5 metal cable gland into the openings.
3. Install the detector base on a stable, vibration-free surface with two screws.
4. Guide the cables from the detector line and external alarm indicator into the
detector base. You will also need a 24 V supply if you are using the detector
heating unit DLH1191A.
5. Mount the terminal block (2) with two screws into the detector base. The arrows
in the terminal block indicate which side should be at the top.
6. If you are using the detector heating unit DLH1191A, insert the terminal block
supplied into the terminal block with the detector heating unit.
The detector base is installed.
54
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 55
5.3 Electrical connection
The electrical connection depends on the following factors:
Connection to an FDnet/C-NET detector line or collective detector line
Use of unshielded cables or shielded cables
The general process is described below. The connection diagrams and more
information on the various connection variants can be found in the following
chapters.
Note the following with regard to the electrical connection:
CAUTION
Mounting / Installation
Electrical connection
5
Using the device in a damp and/or corrosive environment
Device function is impaired.
● Use the M20 x 1.5 metal cable gland in damp and/or corrosive environments.
Note the positive and negative poles.
Only connect one wire per terminal. This is the only way of ensuring a problemfree connection over the device's entire service life.
Wherever possible use twisted, unshielded cables. Shielded cables are only
required in special cases, such as strong high-frequency fields. This also
applies to connecting the external alarm indicators.
Only use cables with a wire diameter of 0.2…1.5 mm
2
.
General procedure
The detector base and terminal block are installed.
1. Connect the wires as shown in the corresponding connection diagram. Use a
screwdriver to remove the load from the spring clip so you can slide in the wire.
2. If you are using the detector heating unit, connect the wires of the 24 V supply
according to the connection diagram shown below.
+
-
Connection diagram for the detector heating unit
Building Technologies
Fire Safety 2012-09-07
+
-
55
007016_i_en_--
Page 56
Mounting / Installation
5
Electrical connection
5.3.1 Connection to an addressed detector line
The following applies to FDnet/C-NET detector lines:
Loops, stubs and T-branches are possible.
You may only connect external alarm indicators to one detector.
Permissible cables for detectors with more than one external alarm indicator
according to the collective connection diagram may be migrated to the
FDnet/C-NET without any changes.
Note document 001508 for installation (calculation of the capacity layer).
5.3.1.1 Use of unshielded cables
The connection is established from base to base using twisted or non-twisted wire
pairs.
-
+
LINE
1
+
-
__
++
2
_
+
LINE
3
LINE
__
++
+
_
+
LINE
__
++
4
_
+
LINE
+
__
++
_
+
4
LINE
__
++
2
_
+
Connection diagram for addressed detector line with and without external alarm indicators
(without shielded cables)
1 Control panel 3 Auxiliary terminals DBZ1190-xx
2 Detector 4 External alarm indicator
56
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 57
5.3.1.2 Use of shielded cables
A
The detector line shielding must be connected through in the detector base with
auxiliary terminals DBZ1190-xx.
There are two ways of connecting external alarm indicators:
Mounting / Installation
Electrical connection
5
LINE
1
__
++
3
2
_
+
3
LINE
LINE
++
LINE
__
++
+
__
_
+
_
+
LINE
++
LINE
__
++
4
__
2
_
+
_
+
3
+
4
Connection diagram for addressed detector line with and without external alarm indicators
(with shielded cables)
1 Control panel 3 Auxiliary terminals DBZ1190-xx
2 Detector 4 External alarm indicator
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
B
57
Page 58
Mounting / Installation
5
Electrical connection
Variant A
1. Connect the positive pole of the external alarm indicator to the positive pole for
the external alarm indicator on the detector.
2. Connect the negative pole of the external alarm indicator to the negative pole
for the external alarm indicator on the detector.
3. Connect the shielding of the connection cable between the external alarm
indicator and detector on the detector side to the positive pole for the external
alarm indicator via an auxiliary terminal DBZ1190-xx.
Variant B
1. Connect the positive pole of the external alarm indicator to the positive pole for
the external alarm indicator on the detector.
2. Leave the negative pole for the external alarm indicator on the detector
unoccupied.
3. Connect each of the two negative poles of the external alarm indicator
separately to both negative poles of the detector line.
The two negative connections of the external alarm indicator are decoupled
externally in the alarm indicator by diodes.
4. Connect the shielding of the detector line with the shielding of the connection
cable to the external alarm indicator with an auxiliary terminal DBZ1190-xx.
5.3.2 Connection to a collective detector line
Connect a control panel-specific end-of-line to the end of the collective detector
line.
58
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 59
5.3.2.1 Use of unshielded cables
The connection is established from base to base using twisted or non-twisted wire
pairs.
LINE
__
++
+
1
-
2
_
+
LINE
LINE
B
Mounting / Installation
Electrical connection
LINE
__
++
_
+
5
__
++
_
+
C
+
A
3
4
Connection diagram for collective detector line with and without external alarm indicators
(without shielded cables)
1 Control panel 3 External alarm indicator
2 Detector 4 End-of-line depending on control
panel
Standard circuitry
With standard circuitry, the external alarm indicator is connected to the positive and
negative poles of each detector.
Wire-saving cabling
NOTICE
Cabling for new sites
Wire-saving cabling in external alarm indicators is prohibited for new sites.
With wire-saving cabling, the external alarm indicator is connected as follows:
The external alarm indicator must be connected to the positive and negative
poles of at least one detector (A).
The external alarm indicator must be connected to the positive pole of every
other detector (B).
The external alarm indicator need not be connected to the negative pole of
every other detector (C).
59
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 60
Mounting / Installation
A
_
_
5
Electrical connection
5.3.2.2 Use of shielded cables
The detector line shielding must be connected through in the detector base with
auxiliary terminals DBZ1190-xx.
There are two ways of connecting external alarm indicators:
LINE
++
1
3
2
__
_
+
LINE
LINE
__
_
++
+
++
4
4
LINE
LINE
__
++
+
B
__
++
+
5
Connection diagram for collective detector line with and without external alarm indicators
(with shielded cables)
1 Control panel 4 External alarm indicator
2 Detector 5 End-of-line depending on control
panel
3 Auxiliary terminals DBZ1190-xx
Variant A
1. Connect the positive pole of the external alarm indicator to the positive pole for
the external alarm indicator on the detector.
2. Connect the negative pole of the external alarm indicator to the negative pole
for the external alarm indicator on the detector.
3. Connect the shielding of the connection cable between the external alarm
indicator and detector on the detector side to the positive pole for the external
alarm indicator via an auxiliary terminal DBZ1190-xx.
Variant B
1. Connect the positive pole of the external alarm indicator to the positive pole for
the external alarm indicator on the detector.
2. Leave the negative pole for the external alarm indicator on the detector
unoccupied.
3. Connect the negative pole of the external alarm indicator with the negative pole
on the input side of the detector line on the detector via an auxiliary terminal
DBZ1190-xx.
4. Connect the shielding of the detector line with the shielding of the connection
cable to the external alarm indicator via an auxiliary terminal DBZ1190-xx.
60
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 61
Mounting / Installation
Installing the reflector for long distance (prism)
5.4 Installing the reflector for long distance (prism)
WARNING
5
Danger of falling
Bodily injury
● When installing, use a secured ladder or work platform.
2
3
+
-
1
+
-
Installing the reflector
1 Base 3 Terminals for heating unit
2 Prism unit
Installation without heating unit
The installation location of the reflector is defined according to the planning
information.
1. Install the base (1) with two screws on a level surface.
2. Install the prism unit (2) on the base with four screws.
The reflector is installed.
Installation with heating unit
Note the positive and negative poles.
Only connect one wire per terminal. This is the only way of ensuring a problemfree connection over the device's entire service life.
The installation location of the reflector is defined according to the planning
information.
You need a 24 V supply for the heating. Only use cables with a wire diameter
2
of 0.2…1.5 mm
.
1. Break open the plastic parts in the base (1) at the openings you require for
cable entry.
61
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 62
Mounting / Installation
5
Installing the reflectors for middle distance and short distance (foil)
2. If necessary screw the M20 x 1.5 metal cable gland into the openings.
3. Install the base with two screws on a level surface.
4. Insert the cable for the 24 V supply into the base.
5. Connect the wires to the terminals for the heating unit (3) according to the
connection diagram.
6. Install the prism unit (2) on the base with four screws.
See also
Planning [➙ 34]
5.5 Installing the reflectors for middle distance and
short distance (foil)
WARNING
Danger of falling
Bodily injury
● When installing, use a secured ladder or work platform.
The installation location of the reflector is defined according to the planning
information.
Install the reflector with one screw on a level surface. The diameter of the hole
is 4 mm.
62
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 63
Commissioning
Installing the reflectors for middle distance and short distance (foil)
6
6 Commissioning
Sequence
1. Set parameter set
2. Install detector unit
3. Install detector heating unit (optional)
4. Insert filter in detector (optional)
5. Commissioning the adjustment device
6. Checking the signal level and distance
7. Preliminary setting of the detector optics (optional)
8. Fine-tuning of the detector optics
9. Initializing the detector
10. Testing detectors
The types are described in the following chapters.
63
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 64
Commissioning
6
Set parameter set
6.1 Set parameter set
Setting the parameter set depends on the detector line.
FDnet/C-NET detector line
The parameter set is set using control panel.
The procedure for setting the parameter set via the control panel is described in the
control panel documentation.
Collective detector line
The parameters are set with the DIP switches in the detector unit.
Use DIP switches (1) to set the parameter set you want (see table below).
1
Detector unit with DIP switches
Parameter set DIP switch
No. Name Alarm for n %
1 2 3 4 5 6
attenuation
01 Standard with open line 65 %
02 Standard with British
65 %
Standard Alarm
03 Sensitive with open line 50 %
04 Sensitive with British
50 %
Standard Alarm
05 Very sensitive with open
30 %
line
06 Very sensitive with British
Standard Alarm
30 %
ON
OFF OFF OFF OFF OFF
ON
OFF
ONON
OFF OFF
ON
OFF
OFF OFF OFF OFF
OFF OFF OFF OFF
ON
OFF
ON ON
OFF OFF OFF
ON
OFF OFF OFF
OFF OFF OFF
Set parameter set
See also
Determine parameter set [➙ 51]
64
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 65
6.2 Installing the detector unit
WARNING
Commissioning
Installing the detector unit
6
Danger of falling
Bodily injury
● When installing, use a secured ladder or work platform.
The terminal block is installed in the detector base.
1. Insert the detector unit (1) in the base with the terminal block (2) with the LED
pointing downwards.
2. Fasten the detector unit with four screws (3). Ensure that the screws are
tightened.
1
3
2
Installing the detector unit
1 Detector unit 3 Screws
2 Detector base with terminal block
65
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 66
Commissioning
6
Installing the detector heating unit (optional)
6.3 Installing the detector heating unit (optional)
You must install the detector heating unit DLH1191A if there is a danger of
moisture condensation. To do this, you need a 24 V supply.
1. Insert the detector heating unit in the detector.
2. Connect the detector heating unit to the printed circuit board.
Installation of the detector heating unit
See also
Accessories [➙ 30]
66
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 67
Commissioning
Inserting the filter in detector (optional)
6.4 Inserting the filter in detector (optional)
For short detection distances and strong extraneous light, you may have to use a
filter.
1. Select the filter according to the planning information:
- Short distance filter DLF1191-AA
- Short distance filter DLF1191-AB
- Extraneous light filter DLF1191-AC
2. Insert the filter (1) in the detector.
1
6
Inserting the filter
See also
Accessories [➙ 30]
Measures for short distances [➙ 41]
Measures for strong extraneous light [➙ 51]
67
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 68
Commissioning
6
Commissioning the adjustment device
6.5 Commissioning the adjustment device
Securing the adjustment device to the detector
1. From the adjustment set, take the chain with the two cable grippers and the
2. Screw one cable gripper into a free opening for the cable entry (1) on the
3. Secure the snap hook on the suspension chain of the adjustment device (3).
The adjustment device hangs on the detector. You therefore have your hands
Connecting the adjustment device
The detector line is switched on.
snap hook.
detector base. Cable grippers are available in two different sizes:
- PG16
- M20 x 1.5
free to undertake commissioning work.
1. Connect the adjustment device (3) electrically to the detector. To do so, use the
MC-Link cable enclosed in the delivery and the connecting sockets (2) on the
detector and on the adjustment device.
2. Switch on the adjustment device with the button on the right (4). With the same
button, it is possible to switch between 'Adjust' and 'Initialization'.
1
2
43
Detector with adjustment device
1 Opening for cable entry 3 Adjustment device
2 Connection sockets 4 Button
68
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 69
Commissioning
A
Commissioning the adjustment device
Indication on the adjustment device
The indication before the initialization differs from that after initialization. The
indication is described in the table below.
Indication location Example Meaning
6
Top left
555 Signal level before initialization
Must be between 255 and 1195 for
initialization. Otherwise initialization is not
possible.
100% Standardized signal value as % of the
current compensation value
During initialization, the signal level is
equalized to the compensation value 100 %.
Bottom left 50m Distance in meters between detector and
reflector
Top right Adjust Detector not yet initialized
Bottom right OK Last initialization successfully completed
Indication before initialization:
555
50m
djust
Indication after initialization:
100%
50m
OK
69
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 70
Commissioning
6
Checking the signal level and distance
6.6 Checking the signal level and distance
The detector line is switched on.
1. Loosen the two safety screws (3).
2. Make sure that the vertical scale (7) and the horizontal scale (1) are centered
3. Set the 'Adjust' menu with the button (4) on the adjustment device.
4. Read the indicators for the signal level and the distance from the adjustment
(factory setting). Otherwise the scales must be re-adjusted with the knurled
screws:
- the vertical scale (7) with the knurled screw (8)
- the horizontal scale (1) with the knurled screw (2).
device:
- If the signal level is over 100 and the distance indication matches the
detection distance, continue fine-tuning the detector optics.
- If the signal level is below 100 and/or the distance indicator does not match
the detection distance, continue with preliminary setting of the detector
optics.
70
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 71
Commissioning
A
Checking the signal level and distance
Possible reasons for the signal level and distance indication deviating:
The detector and the reflector are not positioned on the same horizontal or
vertical axis.
The detector is not mounted on an even surface.
1
3
2
9
6
8
3
7
6
5
4
Checking the signal level and distance
1 Horizontal scale 6 Connection sockets
2 Knurled screw for horizontal
7 Vertical scale
adjustment
3 Safety screws 8 Knurled screw for vertical
adjustment
4 Button 9 Opening for cable entry
5 Adjustment device
Example: Signal level and distance indication in the 'Adjust' menu:
555
50m
djust
See also
Preliminary setting of the detector optics (optional) [➙ 72]
Fine-tuning of the detector optics [➙ 73]
71
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 72
Commissioning
6
Preliminary setting of the detector optics (optional)
6.7 Preliminary setting of the detector optics (optional)
Preliminary setting of the detector optics must only undertaken when the signal
level was below 100 and/or the distance indication was incorrect.
The detector line is switched on.
The adjustment device is connected to the detector and must be set to 'Adjust'.
The signal level is below 100 and/or the distance indication does not match the
detection distance.
1. Mount the sighting system on the detector. The mirror (1) and the front sight (2)
must be free from clearance.
2. Ensure that the two safety screws (5) are loosened.
3. Align the detector optics to the reflector using the knurled screws (3):
- knurled screw (6) for vertical setting
- knurled screw (4) for horizontal setting
- The reflector (3) and the front sight (2) must be on the axis of the circular
mark on the mirror.
4. Simultaneously check the signal level and the distance indication on the
adjustment device.
Following successful alignment of the detector optics, the signal level must
be over 100 and the distance indication match the detection distance with
an accuracy of 10 %.
5. Remove the sighting system.
12
3
5
6
5
4
Preliminary setting
1 Mirror 4 Knurled screw for horizontal
setting
2 Notch 5 Safety screws
3 Reflector 6 Knurled screw for vertical setting
72
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 73
Fine-tuning of the detector optics
A
S
6.8 Fine-tuning of the detector optics
1
2
9
2
Commissioning
3
6
8
7
5
6
4
Fine-tuning with the adjustment device
1 Knurled screw for horizontal
6 Adjustment device
setting
2 Safety screws 7 Connection sockets
3 Hood 8 Knurled screw for vertical setting
4 Alarm indicator 9 Opening for cable entry
5 Button
When you change the setting, the course of the signal is trapezoidal (see figure
below). For optimum setting of the detector optics, the setting must be in the middle
of the trapezoid (point D). If the detector optics is not optimally set, e.g. between
points B and A, problems and faults may occur during operation, e.g. greater
susceptibility to mechanical changes.
y
B
D
C
ignal level
Signal course
Impermissible
x The course of the signal level
when changing the setting
Building Technologies
Fire Safety 2012-09-07
Sub-optimum
Sub-optimumOptimum
y Signal level (display on the
adjustment device)
007016_i_en_--
x
73
Page 74
Commissioning
6
Fine-tuning of the detector optics
To optimally set the detector optics, proceed as follows:
The detector line is switched on.
The adjustment device is connected to the detector and must be set to 'Adjust'.
The two safety screws (2) are loosened.
1. Turn the knurled screws (1, 8) until the standardized signal value on the
adjustment device is as high and constant as possible (point A in the figure
above).
2. Turn the knurled screws back until the standardized signal value decreases
considerably (point B).
3. Note point B. Count e.g. the number of knurled screw turns or mark the scale.
4. Turn the knurled screws forwards again until the standardized signal value is
as high and constant as possible. Continue turning until the standardized signal
value decreases considerably (point C).
5. Note point C. Count e.g. the number of knurled screw turns or mark the scale.
6. Turn the knurled screws back until you reach the middle between points B and
C (point D).
The detector optics are optimally set.
The detector indication matches the detection distance with an accuracy of
10 %.
7. Carefully tighten the two safety screws (2). The values indicated on the
adjustment device must not change significantly.
8. Pull the MC-Link cable from the detector.
9. Fix the hood (3) on the detector with four screws. The alarm indicator (4) must
point downwards.
74
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 75
6.9 Initializing the detector
After the fine-tuning of the detector optics, the detector must be initialized with the
hood screwed on.
Commissioning
Initializing the detector
6
12
3
Initializing the detector
1 End plug 3 Button
2 Connection sockets
The detector line is switched on.
Setting of the detector optics is complete.
1. Remove the sealing plug (1) from the hood.
2. Connect the MC link cable to the connection socket (2) of the detector.
The standardized signal value and the detection distance are displayed in
the 'Adjust' menu on the adjustment device. Example:
1133
Adjust
50m
FDL241-9; commissioning & adjustment data
(values displayed on adjustment device)
values
date &
action
distance
[m]
signalvalue
[-]
deviatesignal
[%]
coveredreflector
value
[%]
50 1133
3. Copy the two display values onto the two labels.
75
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 76
Commissioning
6
Initializing the detector
4. Activate the initialization procedure by pressing the button (3). The detection
distance must not be interrupted during initialization!
During initialization, the following is displayed on the adjustment device:
Initialization
....................
Following successful initialization, 100 % ±3 % and the effective detection
distance is displayed on the adjustment device. Example:
100%
50m
OK
5. Copy the standardized signal value onto the two labels.
100%
50m
FDL241-9; commissioning & adjustment data
(values displayed on adjustment device)
values
distance
date &
action
[m]
signalvalue
[-]
OK
deviatesignal
[%]
coveredreflector
value
[%]
50 1133 100
The detector is initialized.
Troubleshooting during initialization
If the standardized signal value is not within 100 % ±3 % or if the detection
indication displayed deviates by more than 10 % from the effective detection
distance, repeat the initialization process from step 4.
If initialization fails, the following is displayed:
Initialization
failed
Remedy the error and repeat the initialization process. Possible causes for
failed initialization:
Signal Possible cause
Not stable Moving obstacle
Too high Strong reflection
Too low Detection distance too large
Reflector too small
Reflector aligned incorrectly
76
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Reflector covered
Page 77
6.10 Testing detectors
Undertake a performance check following initialization.
Checking the detection distance
The detector is connected to the adjustment device.
1. Cover the reflector completely, using an appropriate object.
The standardized signal value on the adjustment device must be <5 %; the
distance display is frozen.
2. Enter the read-in standardized signal value on the two labels.
Commissioning
Testing detectors
6
2%
50m
FDL241-9; commissioning & adjustment data
(values displayed on adjustment device)
values
distance
date &
action
[m]
50 1133 100
signalvalue
[-]
OK
deviatesignal
[%]
coveredreflector
value
[%]
2
3. Stick a label on the hood, at the top or side. The other label is intended for
system documentation.
Activating the test alarm
1. On the control panel, switch off the remote transmission of alarms. To do this
set the 'Detector test' operating mode on the control panel.
2. Hold the alarm test filter TF04 in front of the hood, such that it covers the
detector optics.
The detector activates an alarm after around 10 seconds.
3. Pull the MC-Link cable from the detector and remove the adjustment device.
4. Re-insert the end plug in the hood.
5. On the control panel, switch the remote transmission of alarms back on.
The detector is ready for operation.
If the alarm doesn’t sound:
Check whether the standardized signal value is attenuated enough to reach the
alarm threshold. Otherwise rotate the alarm test filter a little or turn it round.
77
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 78
Maintenance / Repair
7
Performance check
7 Maintenance / Repair
7.1 Performance check
Due to the built-in operating monitoring function, the detector is automatically
subjected to a performance check. However, an additional performance check
should be carried out once a year. To do so, proceed as follows:
Activating the test alarm
1. On the control panel, switch off the remote transmission of alarms. To do this
set the 'Detector test' operating mode on the control panel.
2. Hold the alarm test filter TF04 in front of the hood, such that it covers the
detector optics.
The detector activates an alarm after around 10 seconds.
3. On the control panel, switch the remote transmission of alarms back on.
4. Check the detector for mechanical damage.
5. Replace detectors that do not respond or are mechanically damaged.
If the alarm doesn’t sound:
Check whether the standardized signal value is attenuated enough to reach the
alarm threshold. Otherwise rotate the alarm test filter a little or turn it round.
78
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 79
Checking the standardized signal value and detection distance
Checking steps Criteria Measures
Maintenance / Repair
Performance check
7
Use the adjustment device to check
the standardized signal value and
the detection distance.
Compare the values with those of
the last commissioning session.
Enter the values on the label in the
hood and in the system
documentation.
Cover the reflector and use the
adjustment device to check the
standardized signal value.
The standardized signal value
must be 100 % ±3 %.
The distance indication must
not deviate by more than
±10 % from the effective
detection distance.
The signal value on the adjustment
device must not deviate by more
than ±10 % from the value entered
under 'Signal value' on the label.
The standardized signal value on
the adjustment device must not
deviate by more than ±3 % from the
value entered under 'Deviate signal'
on the label.
The distance indication on the
adjustment device must not deviate
by more than ±5 % from the value
entered under 'Distance' on the
label.
The standardized signal value must
be less than 5 %.
Repeat initialization.
Check the coverage area for changes, e.g.
obstacles, reflections, structural
adaptations.
Check the signal value during initialization.
Check the coverage area for changes.
Ensure that the detector and reflector are
secure.
Check the coverage area for short-term
changes, e.g. dirt, smoke, vapor, insecure
installation or installation surface. It is
possible that the compensation value has
not yet been updated.
Check the coverage area for changes, e.g.
obstacles, reflections, structural
adaptations.
Check the coverage area for extraneous
light.
Remove or cover reflecting objects.
If necessary use the extraneous light filter
DLF1191-AC.
Check whether the detector is aligned
correctly.
See also
Initializing the detector [➙ 75]
Extraneous light filter DLF1191-AC [➙ 32]
79
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 80
Maintenance / Repair
7
Cleaning
7.2 Cleaning
WARNING
Danger of falling
Bodily injury
● When cleaning, use a secured ladder or work platform.
NOTICE
Damage caused by solvents and/or steam blasters
Detector can be damaged.
● Never use solvents or steam blasters!
Clean the protective hood and the reflector on a regular basis. The interval
depends on the ambient conditions (e.g. degree of soiling). Use either a dry, soft
cloth or a damp cloth, together with window cleaner or a mild soap solution.
After cleaning, check the detector's function according to the information provided
in the chapter 'Performance check [➙ 78]'. In case of strong soiling, re-initiali
zation
is required.
See also
Performance check [➙ 78]
Initializing the detector [➙ 75]
80
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 81
7.3 Repair
When false alarms or faults occur sporadically, it is important to know the cause.
Use the adjustment device and observe the signal strength over a longer period of
time. Compare the values with those on the label. The table below provides you
with an overview of possible faults and there remedy.
Perform an initialization after troubleshooting.
Fault Possible cause Remedy
Maintenance / Repair
Repair
7
The detector sporadically
triggers false alarms or faults
(depending on the selected
parameter set).
The detector sporadically
triggers false alarms.
The detector sporadically
triggers faults.
No alarm is triggered with the
alarm test filter.
Initialization has not been performed
Repeat initialization.
correctly.
Fine-tuning of the detector optics was
not performed correctly.
Repeat fine-tuning. Make sure that the signal is
set to the maximum value. At the end, perform
the initialization with the hood fitted.
The ray is temporarily interrupted by
obstacles (cranes, decoration, work
Avoid interruptions to the infrared ray, or install
the detector in a different position.
within the detection distance etc.).
The building may warp due to solar
radiation. The ray is deflected and no
Mount the detector base on a solid, stable
surface.
longer reflected.
The detector or the detector unit has
been dislocated, e.g. due to an impact.
Moisture condensation of the detector or
Ensure that the detector is fixed and the screws
are tightened.
Install a detector heating unit DLH1191A.
the reflector.
Detection distance influenced by dust,
Select a less sensitive parameter set.
vapor or mist.
The sun or other strong sources of light
directly shine on the detector.
The ray is reflected not only by the
reflector, but also by other objects (e.g.
ventilation ducts). This results in too high
a standardized signal value.
Avoid direct contact with sunlight or use an
extraneous light filter DLF1191-AC.
Cover the reflector and check the standardized
signal value on the adjustment device. This value
must be <5 %. If the standardized signal value is
greater than 5 %, remove the reflecting objects or
cover them with a non-reflecting material.
Radiant heaters cause air flickering and
thus have an influence on the detection
Install the detector and reflector in a different
position.
distance.
Strong soiling of the detector or reflector. Clean the detector and the reflector, then perform
initialization.
Aging of the transmitter diode. Initialize the detector again. If this does not
remedy the fault, replace the detector.
Fault on the detector line. Check the line voltage. The detector does not react
Detector defective. Replace the detector.
Incorrect handling of the alarm test filter. Place the alarm test filter directly on the
detector.
Rotate or turn the alarm test filter.
The alarm test filter does not attenuate
the signal enough.
Check the signal attenuation with the adjustment
device.
Detector defective. Replace the detector.
See also
Accessories [➙ 30]
Initializing the detector [➙ 75]
Cleaning [➙ 80]
81
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 82
Specifications
8
Technical data
8 Specifications
8.1 Technical data
FDnet/C-NET-detector line Operating voltage DC 12…33 V
Operating current (quiescent) 0.8 mA
Maximum current connection factor 4
Quiescent current connection factor 4
Address connection factor 1
Separator connector factor 1
Protocol FDnet/C-NET
Compatibility See 'List of compatibility'
Collective detector line Operating voltage DC 14…28 V
Operating current (quiescent) 0.7 mA
Making current Max. 1.5 mA
Connection factor 10
Alarm voltage at alarm current:
1 … 15 mA DC 5…10 V
35 mA DC 18…22 V
50 mA DC 26…28 V
Alarm current at operating voltage DC 5 … 28 V 4 … 50 mA
Reset voltage DC 2…4 V
Reset time at reset voltage DC 2 V 1…2 s
Protocol Collective (with and without current
Compatibility See 'List of compatibility'
Line separator Line voltage:
Nominal DC 32 V (= V
Minimum DC 12 V (= V
Maximum DC 33 V (= V
Voltage at which the separator opens:
Minimum DC 7.5 V (= V
Maximum DC 10.5 V (= V
Permanent current when switches are closed: Max. 0.5 A (= I
Switching current (e.g., in the event of a short-
Leakage current when switches are open: Max. 1 mA (= I
Serial impedance when switches are closed: Max. 0.5 Ω (= Z
circuit)
limitation)
Max. 1 A (= I
nom
min
max
SO min
C max
S max
L max
)
)
)
SO max
)
C max
)
)
)
)
)
82
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 83
Specifications
Technical data
8
External alarm indicators Number of external alarm indicators that can be
2
connected
Voltage DC 6 … 17 V
Current 9…15 mA
Length of line Max. 30 m with unshielded cables
(recommended) or if the shielding on the
detector is connected to the positive pole
for the external alarm indicator
Max. 5 m, if the shielding is connected to
earth
Flashing interval times on FDnet/C-NET detector
line:
Bright 15 ms
Dark 1 s
Flashing interval times on collective detector line Control panel-specific
Device characteristics Infrared transmitter:
Wavelength 950 nm
Pulse frequency 4 Hz
Compensation (if the ray attenuates)
2.3 %/h
Compensation speed
Alarm integration 6 … 16 s
Detection distance:
Without filter 10 … 100 m
With filter for short distance DLF1191-AA 8 … 12 m
With filter for short distance DLF1191-AB 5 … 10 m
Detector heating unit
Operating voltage DC 20 … 30 V
DLH1191A
Operating current 30 … 50 mA
Resistance 600 Ω
Heating unit in reflector for
Operating voltage DC 20 … 30 V
long distance (prism)
DLR1191
Operating current 30 … 50 mA
Resistance 600 Ω
Connections Detector line, detector heating unit and external
alarm indicator:
Design Spring clips
Cable cross section 0.2…1.5 mm
MC link Plug-type connection
2
83
Building Technologies
007016_i_en_--
Fire Safety 2012-09-07
Page 84
Specifications
8
Technical data
Ambient conditions Operating temperature -25 … +60 °C
Storage temperature -30 … +75 °C
Air humidity ≤ 95 % rel.
Protection categories according to
IP65
EN 60529 / IEC 60529
Electromagnetic compatibility:
1 MHz … 1 GHz 50 V/m
1 GHz … 2 GHz 30 V/m
Mechanical data Dimensions (L x W x H) 135 x 135 x 115 mm
Material
Detector base ABS/PC-Blend
Hood ABS/PC-Blend
Color ∼RAL 9010 pure white
Standards European standards EN 54-12
EN 54-17
EN 62471
International standards IEC 60529
ISO 9001
ISO 9004
Siemens standards SN 36350
Approvals EC Certificate of Conformity (construction products):
FDL241-9 0786-CPD-20014
VdS approvals: G204063
LPCB approvals: 126ag/01
84
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 85
8.2 Dimensions
Base for linear smoke detector FDLB291
Specifications
Dimensions
8
4,5
153
135
135
Base for linear smoke detector FDLB291 with linear smoke detector
FDL241-9
M20 x 1.5
45
115
Reflector for long distance (prism) DLR1191
M20 x 1.5
45
65
Reflector for middle distance (foil) DLR1192 and reflector for short
distance (foil) DLR1193
100 / 200
2.5
4.0
100 / 200
85
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 86
Specifications
8
Environmental compatibility and disposal
8.3 Environmental compatibility and disposal
This device is manufactured using materials and procedures which
comply with current environmental protection standards as best as
possible. More specifically, the following measures have been
undertaken:
Use of reusable materials
Use of halogen-free plastics
Electronic parts and synthetic materials can be separated
Larger plastic parts are labeled according to ISO 11469 and ISO 1043.
The plastics can be separated and recycled on this basis.
Electronic parts and batteries must not be disposed of with domestic
waste.
Take electronic parts and batteries to local collection points or
recycling centers.
Contact local authorities for more information.
Observe national requirements for disposing of electronic parts
and batteries.
86
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 87
Index
Index
A
Adjustment device
Commissioning, 68
nce indication, 70
Dista
Signal level, 70
Alarm test filter, 78
A, 9
AS
B
British Standard Alarm, 51
C
Cleaning, 80
Collective operation
Switching over to collective operation, 53
ction, 55
Conne
ssed detector line, 56, 56, 57, 58
Addre
Collective det
ction diagram
Conne
Addressed detector line with shielding, 57
ssed detector line without shielding, 56
Addre
ctive detector line with shielding, 60
Colle
ctive detector line without shielding, 59
Colle
Correction
ector line, 58, 59, 60, 60
value, 27
D
Danger levels, 25
Detection distance, 40
Detector h
Detec
Fine-tuning, 74
Preliminary setting, 72
Detec
Diagno
Difference in temperature, 45
imensions, 85
D
Disp
Dist
Detector - ceiling, 43
Detec
Dist
eating unit, 50, 66
tor optics
tor unit, 19
sis levels, 26
osal, 86
ance
tor - detector, 47
ance measuring, 21
E
Electrical connection, 55
End-of-line, 58, 59, 60
Environm
ES
ternal alarm indicator, 55, 56, 57
Ex
Extraneo
Extraneo
ental compatibility, 86
ct version, 17
Produ
us light, 51
us light filter, 51, 67
F
False alarm, 81
Fault, 81
Fields of appl
Film, 25
Flat ceilings, 35
ication, 34
G
Girders, 47
Glass pane, 49
I
Inclination, 37
Inclined ceilings, 37
frared ray, 22
In
tion, 45
Deflec
tialization, 75
Ini
tallation, 52, 52
Ins
tor base, 54
Detec
ctor heating unit, 66
Dete
ctor unit, 65
Dete
ctor for long distance (prism), 61
Refle
tor for middle distance (foil), 62
Reflec
tor for short distance (foil), 62
Reflec
Terminal block, 54
Installation height, 42
tallation site, 45
Ins
Installation su
rface, 45
87
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 88
Index
L
Label, 20, 75
Lengthwise expansion, 45
Levelin
Line sepa
List of com
g, 29
rator
Function, 25
patibility, 9
M
Moisture condensation, 50
P
Packaging label
Product version, 17
Parameter s
Performan
m, 24
Pris
Product label
Produ
et, 51, 64
ce check, 78
ct version, 17
T
Test alarm, 77
Transmitter, 20
Trouble
Type plate
shooting, 81
ct version, 17
Produ
W
Width of monitoring area, 43
R
Receiver, 20
Recycling, 86
tor, 24, 40
Reflec
ctor for long distance (prism), 24
Refle
tor for middle distance (foil), 25
Reflec
tor for short distance (foil), 25
Reflec
Reflector for l
Reflector for
tor for short distance (foil), 25, 62
Reflec
Remed
r, 81
Repai
Respon
Room heig
ong distance (prism), 24, 61
middle distance (foil), 25, 62
ying faults, 81
se threshold, 28
ht, 42
S
Sensitivity, 28, 51
Short distance filter, 67
Short-ci
S
Signal processing, 27
Signal value
Smoldering fire detection, 42
Standa
Switching over to collective operation, 53
rcuit
Line separator, 25
ighting system, 72
Standardized, 27
rdized signal value, 27
88
Building Technologies 007016_i_en_--
Fire Safety 2012-09-07
Page 89
Index
89
Building Technologies
Fire Safety 2012-09-07
007016_i_en_--
Page 90
Issued by
Siemens Switzerland Ltd
Technical specifications and availability subject to change without notice.