SMF121, SMF6120
Radio gateway, radio smoke detector,
manual call point, radio base
Technica l Manual
009865_m_en_-2015-11-06Control Products and Systems
Page 2
Legal notice
Building Technologies
009865_m_en_
--
Fire Safety
Legal notice
Technical specifications and availability subject to change without notice.
Transmitt al, reproduction, dissemination and/or editing of this document as well as
utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of damages.
All rights creat ed by patent grant or registration of a utility model or design patent
are reserved.
Issued by:
Siemens Switzerland Ltd.
Building Technologies Div ision
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies
8.5 Environmental compatibility and disposal ...................................................79
Index ........................................................................................................ 80
Fire Safety
5 | 82
2015-11-06
Page 6
Building Technologies
009865_m_en_
--
Fire Safety
6 | 82
2015-11-06
Page 7
About this document
Applicable documents
82
009865_m_en_
--
Fire Safety
1About this document
The SMF6120 radio base may only be used as a replacement device in fire
Goal and purpose
This document describes the devices
●Radio gateway FDCW221
●DOW1171 radio smoke detector
●Manual call point SMF 121
●Radio base SMF6120
and how to integrate the devices into the fire detection system FDnet.
It contains all the inf ormation you'll need about set up, funct ions, planning,
mounting, and commis sioning.
detection inst allations that were inst alled prior to April 1, 2011!
Target groups
The information in this document is intended for the following target groups:
1
Target groupActivityQualificatio n
Product Manager
●Is responsible for information
passing between the manuf acturer
and regional company.
●Coordinates the flow of information
between the individual groups of
●Has obtained suitable specialist
training for the function and for the
products.
●Has attended the training courses
for Product Managers.
people involved in a project.
Project Manager
Project engineer
●Coordinates the deploym ent of all
persons and resources involved in
the project according to schedule.
●Provides the information required to
run the project.
●Sets parameters for product
depending on specific national
and/or customer requirements.
●Checks operability and appr oves
the product for commissioning at the
●Has obtained suitable specialist
training for the function and for the
products.
●Has attended the training courses
for Project Managers.
●Has obtained suitable specialist
training for the function and for the
products.
●Has attended the training courses
for Product Engineer.
place of installation.
●Is responsible for troubleshooting.
Installation pers onnel
●Assembles and installs the product
components at the place of
installation.
●Has received specialist training in
the area of building installation
technology or electrical installations.
●Carries out a performance check
following installation.
Maintenance personnel●Carries out all maint enance work.
●Checks that the products are in
perfect working order.
●Searches for and corrects
malfunctions.
Building Technologies
●Has obtained suitable specialist
training for the function and for the
products.
7 |
2015-11-06
Page 8
About this document
Applicable documents
1
Building Technologies
009865_m_en_
--
Fire Safety
The 'i'
symbol identifies supplementary information and tips for an easier way of
Source language and reference document
●The source/original language of this document is German (de).
●The reference version of this document is the international version in English.
The international ver sion is not localized.
Document identification
The document ID is structured as follows:
ID codeExamples
ID_Modificat ionIndex_Language_COUN
The date format in the document corresponds to the recommendation of
international standard ISO 8601 (format YYYY-MM-DD).
Conventions for text marking
Markups
Special markups are shown in this document as follows:
⊳Requirement for a behavior instruction
1.
2.
–Version, option, or detailed informat ion for a behavior instruction
⇨Intermediate result of a behavior instruction
⇨End result of a behavior instruction
●
Behavior instruction with at least two operation sequences
Numbered lists and behavior instructions with an operation
sequence
[➙ X]Reference to a page number
'Text'Quotation, reproduced identically
<Key>Identificat ion of keys
>
Relation sign and for ident ification between steps in a sequence,
e.g., 'Menu bar' > ' Help' > 'Help topics'
↑ Te xtIdentif ication of a glossary entry
Supplementary information and tips
working.
8 | 82
2015-11-06
Page 9
About this document
Applica
ble documents
82
009865_m_en_
--
Fire Safety
1.1Applicable documents
You will also find
information about search variants and links to mobile
Docu ment IDTitle
004446Operation instructions Radio test set DZW1171
007227Technical manual D etector ex changer and tester FDUD292
008250Technical Manual Line tester FDUL221
008331List of compatibility (for 'Sinteso™' product line)
009052
009718Technical Manual I ntellige nt detector t ester FDUD 293
009854Installation MCL-USB Adapter FDUZ221
010087
A6V10200368Install ation Radio base SMF6120, Manual call point SMF121
A6V10217915Installation RadioSpy
A6V10229812User-Manual RadioSpy
A6V10336734Installation Radio gateway FDCW221
A6V10336739Installation Radio smoke, detector Base DOW1171, DBW1171
FS20 Fire detection system - Commissioning, Maintenance,
Troubleshooting
Data sheet Radio fire detection system FDCW221, DOW1171,
SMF6120, SMF121
1
1.2Download center
You can download various types of documents, such as data sheets, installation
instructions, and license texts via the following Internet address :
http://siemens.com/bt/download
lEnter t he document ID in the 'Find by keyword' input box.
applications (apps) for various systems on the home page.
Building Technologies
9 |
2015-11-06
Page 10
About this document
Technical terms
1
Building Technologies
009865_m_en_
--
Fire Safety
1.3Technical terms
TermExplanation
AIAlarm indic a tor
dBDecibel: logarithmic relationship between two levels.
DOW1171Radio smoke detector
DZW1171Radio test set
EAIExternal alarm in dicator
EMCElectromagnetic compatibility
ERPEffective Radiated Power
FDnetAddr essed detec tor line
FDUL221Line test er
FDUZ221MCL-USB adapter. Protocol converter fro m USB to MC- Link.
Radio detec torDevices which can communicate with the radio gateway usi ng radio.
Radio cellRadio ra nge, i.e. ran ge of a gateway
GatewayNetwork bridge which links two different systems or networks.
LEDLight-e mitting diod e
MC linkMaintenance and commiss ioning link
PCPersonal computer
RadioSpyTest unit for observing, moni toring and configuring a radio detec tor cell.
SMF121Manual call point
SMF6120Radio base
SPU60xxRadio mod ul e
SRD band
USBUniversal Serial Bus
Reserved frequency band with defined usage rules (Short Range Device
Band)
10 | 82
2015-11-06
Page 11
About this document
Revision history
82
009865_m_en_
--
Fire Safety
1.4Revision history
The first edition of a language version or a country variant may, for
example, be
The reference docum ent's version applies to all languages into which the reference
document is trans lated.
version 'd' inst ead of 'a' if the reference document is already this version.
The table below shows this document's revision history:
VersionEdition da teBrief description
m2015-11-06
l2014-10-17
k2014-09-03
j2014-07-14
i2012-05-15
h2011-08
g2010-12
f2010- 07
e2009-04
d2007-08
c2007-07
b2007-04
a2007-03
●New battery type 'EVE CR9V/P-S ' added to doc ument.
●Editorial changes
Chapter 'Updating the fir mware of radio gatew ay FDCW 21' revised.
External alarm indic ator remove d from 'Structure and function' chapter, sections 'Inter nal view' and
'Connections', 'Mounting / installation', and 'Commissioning'.
Data she et updated in 'Applicable documents' chapter
"External alarm indicators" section in 'Specifications' chapter removed
VdS approvals removed from 'Specifications' chapter for all 3 devices
'Download center' chapter added
Date format changed in line with the requirements of ISO 8601 (f ormat: yyyy-mm-dd), note added to
explai n t hat the SMF6120 may only be used as a replacement d evice in exis ting fire detectio n
installations installed prior to 2 011-04-01.
Editori al changes made, difference betw een FS20/FC20 revis ed; number of batteries for SMF612 0
and DOW1171 corrected; document numbers of mounting instr uctions for FDCW221 and
DOW1171/DBW1171 adapted; new standard, VdS approvals and CPD numbers for FDCW221 and
DOW1171 added to technical data
Editori al changes made
VdS approvals removed
Document title changed
Additional information about the radio smoke detector DOW1171 and the manual call point SMF121
added
Editori al changes made
New safety notes.
Radio gateway, with battery only and which can never be operate d in a 'stub to pology'.
Editori al changes made.
Diagnosis levels chapter: Displays as on the detector exchang er and tester.
Internal view chapter: MC link connection (general).
Hyperlinks in the PDF now function.
Review results incorporated:
- Additional 'SHIELD' spring clip
- Other LEDs in cover
- Only connect detector line later during co mmissioning
- IP40 pro tection category
- DOW117 1: Parameter set 1 is t he default
- DOW117 1: Status indicator rather tha n a larm indicator
- Switch off detector line when replacing the radio detector
Various supplements for DOW1171/SMF6120
Initial edition for VdS
1
Building Technologies
11 |
2015-11-06
Page 12
About this document
Revision history
1
Building Technologies
009865_m_en_
--
Fire Safety
The table below shows the published language versions with the corresponding
modification index:
Modification in dexen_--d e_--fr_--it_--es_--
mXXXXX
lXXXXX
k–X–––
j–X–––
iXXXXX
hXXXXX
g–X–––
fXXXXX
e–X–––
dXX–––
cXX–––
bXXXXX
aXXXXX
X = published
– = no publication with this modification index
12 | 82
2015-11-06
Page 13
Safety
Safety instructions
82
009865_m_en_
--
Fire Safety
2Safety
2.1Safety instructions
The safety notices mus t be observed in order to protect people and property.
The safety notices in this document contain the following elements:
●Symbol for danger
●Signal word
●Nature and origin of the danger
●Consequences if the danger oc curs
●Measures or prohibit ions for danger avoidance
Symbol for danger
This is the symbol for danger. It warns of risks of injury.
Follow all measures ident ified by this symbol to avoid injury or deat h.
Additional dan ger symbols
These symbols indic ate general dangers, the type of danger or poss ible
consequences, measures and prohibitions, examples of which are shown in the
following table:
2
General dangerExplosive atmosphere
Voltage/electric shockLaser light
BatteryHeat
Signal word
The signal word classifies the danger as defined in the following table:
Signal wordDan ger level
DANGER
WARNING
CAUTION
NOTICE
DANGER identifies a dangerous situation, which will result direct ly in death or
serious injury if you do not avoid this situation.
WARNING identifies a dangerous situation, which may result in death or s erious
injury if you do not avoid this situation.
CAUTION identif ies a dangerous situation, which could result in slight to
moderately serious injury if you do not avoid this situation.
NOTICE
observance.
identifies possible damage to property that may result from non-
Building Technologies
13 |
2015-11-06
Page 14
Safety
Safety instructions
2
Building Technologies
009865_m_en_
--
Fire Safety
Nature and origin of the danger
●
Measures / prohibit ions for danger avoidance
Nature and origin of the danger
How risk of injury is presented
Information about the risk of injury is shown as follows:
WARNING
Consequences if the danger oc curs
How possible damage to property is presented
Information about possible damage to property is s hown as follows:
NOTICE
Consequences if the danger oc curs
●Measures / prohibit ions for danger avoidance
14 | 82
2015-11-06
Page 15
Safety
Safety regulations for the method of operation
82
009865_m_en_
--
Fire Safety
2.2Safety regulations for the method of operation
Electrical volt age
regulations.
National standards, regulations and legislation
Siemens products ar e developed and produced in compliance with the relevant
European and international safety standards . Should additional national or local
safety standards or legislation concerning the planning, mounting, installation,
operation or disposal of the product apply at the place of operation, then these
must also be taken into account together with the safety regulations in the product
documentation.
Electrical installations
WARNING
Electric shock
●Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordanc e with the electrotechnic al
2
●Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
●Lock volt-free areas to prevent them being switched back on again by mistake.
●Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
●Route mains connect ions to products separately and fuse them with their own,
clearly marked fuse.
●Fit an easily accessible disconnecting device in acc ordance wit h IEC 60950-1
outside the installation.
●Produce earthing as stated in local safety regulations.
Mounting, installation, commissioning and maintenance
●If you require tools such as a ladder, these must be safe and must be intended
for the work in hand.
●When starting the fire control panel ensure that unstable conditions cannot
arise.
●Ensure that all point s listed in the 'Testing the product operability' section below
are observed.
●You may only set controls to normal function when the product operability has
been completely tested and the system has been handed over to the customer.
Building Technologies
15 |
2015-11-06
Page 16
Saf
ety
Safety regulations for the method of operation
2
Building Technologies
009865_m_en_
--
Fire Safety
Testing the product operability
●Prevent the remote transmission from triggering erroneously.
●If testing building installations or activating devices from third- party companies,
you must collaborate with the people appointed.
●The activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following
instructions m ust be observed:
–Use the correct potential for activation; this is generally the potential of the
building installation.
–Only check controls up to the interface (relay with blocking option).
–Make sure that only the controls to be tested are activated.
●Inform people before testing the alarm devices and allow for pos sible panic
responses.
●Inform people about any noise or mist which may be produced.
●Before testing t he remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system design and the products
Modifications to the system and to individual products m ay lead to faults,
malfunctioning and safety risks. Written confirmation must be obtained from
Siemens and the corresponding safety bodies for m odifications or additions.
Modules and spare parts
●Components and spare part s must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by
Siemens.
●Only use fuses with the specified fuse characteristics.
●Wrong battery ty pes and impr oper battery changing lead to a ris k of explosion.
Only use the same battery type or an equivalent battery t ype recommended by
Siemens.
●Batteries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.
Disregard of the safety regulations
Before they ar e delivered, Siemens products are tested to ensure they function
correctly when used properly. Siemens disclaims all liability for damage or injuries
caused by the incorrec t application of the instructions or the disregard of danger
warnings contained in the documentation. This applies in particular to the following
damage:
●Personal injuries or damage to property caused by improper use and incorrect
application
●Personal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
●Personal injury or damage to property caused by poor maintenance or lack of
maintenance
16 | 82
2015-11-06
Page 17
Safety
Standards and directives complied with
82
009865_m_en_
--
Fire Safety
2.3Standards and directives complied with
Limited or non
-
existent fire detection
detection installation.
Incorrect planning and/or configurat ion
detection installation.
A list of the standards and directives complied wit h is available from your Siemens
contact.
2.4Release Notes
Limitations t o the configuration or use of devices in a fire detection inst allation with
a particular firmware version are possible.
WARNING
Personal injury and damage to property in the event of a fire.
●Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
●Read the 'Release Notes' before you carry out a firmware update to a fire
2
NOTICE
Important st andards and specifications are not satisfied.
Fire detection installation is not accepted f or commissioning.
Additional expense result ing from necessary new planning and/ or configuration.
●Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
●Read the 'Release Notes' before you carry out a firmware update to a fire
Building Technologies
17 |
2015-11-06
Page 18
Structure and function
Release Notes
3
Building Technologies
009865_m_en_
--
Fire Safety
3Structure and functio n
The radio gateway F DCW221 is used to monitor signals from radio detectors and
to transfer them via the FDnet to a fire control panel.
The radio gateway is operated on the FDnet. All devices which can be monitored
by the radio gateway are collectively known as a 'radio detectors'.
The FDCW221 radio gateway c an communicate with the following radio detectors:
●DOW1171 radio smoke detector
●Manual call point SMF121 with radio base SMF6120
The unit, comprising radio gateway and the radio detectors logged onto it, forms a
radio cell.
The following diagram shows how the radio gateway is integrated in the fire
detection via the FDnet.
Radio gateway on FDnet with radio detec tors
Features of the radio gateway FDCW221
●Compatible with the FDnet-compatible fire detection systems FS20, AlgoRex
and Sigmasys
●Simultaneous operat ion of wired fire detectors on FDnet and wireless radio
detectors on radio gateway
●High signaling securit y
–Automatic definition of optimum basic and deviating radio channels
–Automatic channel change in the event of radio problems
●Individual addressing for simple site identificat ion
●Up to 16 radio gateways can be operated with radio cell overlapping
●Up to 30 radio detectors can be activated per radio gateway
●Low current consumption, battery only needs replacing every 5 years
18 | 82
2015-11-06
Page 19
Structure and function
Release Notes
3
82
009865_m_en_
--
Fire Safety
Features of the radio smoke detector DOW1171
●Consistent response to different fires
●Dynamic analysis of the sensor signal in the radio smoke detector itself
●Built-in diagnosis algorithms with automatic selftest
●High degree of immunit y towards false alarms and environmental influences
●High-quality, opto-electronic sensor system
●Automatic compensation for soiling
●Supply via two 9 V lithium bat teries
●Low current consumption, battery only needs replacing every 5 years
●Separate monitoring of each individual battery : Even when a battery fails,
detector operat ion is still guaranteed for up to 30 days
●Built-in alarm indicat or
●Mounting with detector base DBW1171 (accessories)
Features of the manual call point SMF121 and radio base SMF6120
●Radio module is integrated in the radio base SMF6120
●Radio base supply via two 3. 6 V lithium batteries
●Manual call point with indirect alarm activation: To trigger, drive in the washer
and press the knob
Applications
●For rooms of a high historical value, e.g. museums, churches, libraries.
●For rooms where cabling is not desired for esthetic reasons.
●For rooms where changes are alway s taking place, e.g. exhibition rooms.
Building Technologies
19 |
2015-11-06
Page 20
Structure and function
Structure of the radio gateway FDCW221
3
Building Technologies
009865_m_en_
--
Fire Safety
2
354
3.1Structure of the radio gateway FDCW221
3.1.1Overview
1
Overall view of radio gateway
1 LED red/green4 Magnet movement for Reed
contact
2 Housing cover5 Unlocking for housing cover
3 Back box
20 | 82
2015-11-06
Page 21
Structur
e and function
Structure of the radio gateway FDCW221
82
009865_m_en_
--
Fire Safety
3.1.2Internal view
5
6
778
9
3
1
Internal view of radio gatew ay
234
19 V battery with clip6
2Battery cable connection7
3MC link connection8
'LINE' spring clips for the FDnet
detector line
Brackets for cable strain relief
using cable ties
'SHIELD' shield connection
terminal blocks for detector line
cables
4Button for settings9Reed contact
5Radio module SPU60xx
See also
2 Connections [➙ 22]
Building Technologies
21 |
2015-11-06
Page 22
Structure and function
Structure of the radio gateway FDCW221
3
Building Technologies
009865_m_en_
--
Fire Safety
2
3.1.3Connections
The radio gateway FDCW221 has connections for:
●The FDnet detector line
●The shieldings of the detector line cables
The two 'SHIELD' connection terminals are internally linked to one another.
1
SHIELD
_
+
Connections on FDCW221 radio gateway
1
Shield connection terminal blocks
for detector lines
LINE
__
++
2
Spring clips for the FDnet detector
line
MC link
The MC link connection in the radio gateway is mainly used to connect the detector
exchanger and tester FDUD292 and the intelligent detector tester FDUD293 (as of
software V2.1). These devices allow informat ion to be read from the radio gateway
for commissioning, maintenance and troubleshooting.
You will find more information in documents 007227 and 009718.
The MC link is also used to update the radio gateway firmware. The MCL-USB
adapter FDUZ221 is used to lead the firmware from the PC to the radio gateway.
You will find a descript ion of firmware update in chapter 'Updating t he firmware of
radio gateway FDCW 221 [➙ 73]'.
For details, see document 009854.
22 | 82
3.1.4Radio transmission
The radio module SPU60xx consists of a printed circuit board with two integrated
aerials.
The radio module is a module which allows for bidirectional data trans mission in
the 868...870 MHz frequency range.
The radio module has a complete send and receive unit and a microcontroller
control unit for all radio transmission funct ions.
Radio transmission takes place in the SRD band (Short Range Devic e), a reserved
frequency band with defined usage rules. The SRD band is free from amateur
users. The SRD band provides 80 channels with a channel width of 25 kHz.
Characteristics of the SRD band:
●Defined low maximum transmitting powers and duty cycle (ratio between
send/idle time)
●Sub-bands for various uses and applications
●High availability
2015-11-06
Page 23
Structure and function
Structure of the radio gateway FDCW221
82
009865_m_en_
--
Fire Safety
Characteristics of the radio module:
Batteries are not included in the scope of delivery. Batteries are always needed to
●4 alternative channels ar e assigned to each of the 16 basic channels
(5 x 16 = 80 different channels)
–If there is a problem with the basic channel, this is detected right away. If
this happens, t he frequency automatically changes channel up to four
times.
●Communication faults between the gateway and the detectors are detected and
displayed within 300 s. Alarms are transferr ed immediately.
●If a detector cannot directly reach the gateway and the contact is interrupted, a
diversion mechanism is activated. The bidirec tional contact between the
detector and t he gateway then takes place via a neighboring detector of the
same radio cell.
If the problem persists for a long time, the diversion is displayed as a fault
within 300 s, like other communication faults.
3.1.5Reed contact and button
The Reed contact is an extra operating element which can be used to perform
some of the functions of the button when the housing cover is closed.
Generally when commis sioning, the Reed contact can also be activated with a
magnet rather than the button. Activation of the Reed contact then equates to
briefly pressing the button.
The Reed contact is act ivated by slowly pulling (approx. one second) along the
length of the Reed cont act with a magnet.
3
See also
2 Internal view [➙ 21]
2 Status dis play on the radio gateway FDCW221 [➙ 39]
2 Overview [➙ 20]
3.1.6Scope of delivery
The radio gateway is supplied with the following accessories :
●1x battery connect ion cable (with 9 V battery clip and PCB plug)
●2x cable ties (3.7 x 208 mm) for cable strain relief
commission and operate the radio gateway.
See also
2 Details for or dering [➙ 29]
2 9 V lithium manganese dioxide battery [➙ 30]
Building Technologies
23 |
2015-11-06
Page 24
Structure and function
Structure of the radio smoke detector DOW1171
3
Building Technologies
009865_m_en_
--
Fire Safety
1
2
3
4
3.2Structure of the radio smoke detector DOW1171
Radio smoke detector DOW1171 with base DBW1171
1 DBW1171 base2 DOW1171 radio smoke detector
The radio smoke det ector DOW1171 works in line with the scattered light principle.
An infrared LED sends short, intense light pulses t o the scattering volume. The
orifices shield the light receiver from direct rays of light and reflexes. Penetrating
smoke particles scatter the light on the light receiver. The signal of the light
receiver is evaluated by the electronics.
Algorithms evaluate the smoke density and the probabilit ies of alarms are
forwarded by the mic roprocessor.
24 | 82
5
Cross-section through a radio smoke detector DOW1171
Battery compartment and log-on bu tton on the DOW117 1
3
1
Battery compartment for two 9 V
lithium manganese dioxide
batteries
See also
2 DBW1171 base [➙ 32]
2 Structure of the radio smoke detector DOW1171 [➙ 24]
2 'New' log-on button
Building Technologies
25 |
2015-11-06
Page 26
Structure and function
Structure of the radio smoke detector DOW1171
3
Building Technologies
009865_m_en_
--
Fire Safety
3.2.1Parameter sets for the radio smoke detector DOW1 171
The radio smoke detector DOW1171 has efficient detection algorithms to
distinguish between fire events and deceptive phenomena. Measured values
above a response thres hold are not the only basis for reaching a danger level. The
smoke density progression is also observed over a longer period of time and
evaluated using algorithms.
The algorithms contain among other things filters to suppress short-t erm
disturbances. Slow signal changes as a result of soiling are compensated for by
automatic digit al compensation. The extremely slow compensation ensures that
very slowly developing fires can be detected too.
The sensitivit y of alarm activation by radio smoke detectors DOW1171 can be set
per detector point .
The table below contains lists of possible parameter s ets and the average
response times using test gas:
Parameter set no.Parameter set nameAverage response t ime using test gas
Response sensitivity D1 of the radio smoke detector: D1 = 3.3…4.0 %/m
Environmental influences
The smoke sensitivity of the radio smoke detector DOW1171 typically changes
±10 % over the entire operating temperature range.
The radio smoke det ector DOW1171 is resistant to ambient light, air flows and
other changes within t he specified data.
3.2.2Scope of delivery
The radio smoke det ector is supplied as 'DOW1171/DBW1171 radio smoke
detector under the order number S24218-F62-A7. The following are included in the
scope of delivery:
●1x radio smoke detector DOW1171
●1x base DBW1171
●2x 9 V lithium manganese dioxide batteries
See also
2 Details for or dering [➙ 29]
2 9 V lithium manganese dioxide battery [➙ 32]
26 | 82
2015-11-06
Page 27
Structure and function
Structure of the manual call point SMF121 and radio base SMF6120
82
009865_m_en_
--
Fire Safety
3.3Structure of the manual call point SMF121 and
Batteries are not
included in the scope of delivery. Batteries are always needed to
1
1
radio base SMF6120
2
Figure 1: Manual call point SMF121 and radio base SMF612 0
1 Manual call point SMF 1212 Radio base SMF6120
3
The manual call point SMF121 can only be used together with the radio base
SMF6120.
The radio electronic s are integrated with the two aerials in the radio base
SMF6120.
The radio base is batt ery-operated and is supplied by two 3.6 V lithium batteries.
Figure 2: View ins ide radio base SMF6120
1 3.6 V lithium batteries
3.3.1Scope of delivery
The manual call point SMF121 and the radio base SMF6120 must be ordered
separately.
commission and operate the radio manual call point.
See also
2 Details for or dering [➙ 29]
2 3.6 V lithium battery [➙ 34]
Building Technologies
27 |
2015-11-06
Page 28
Structure and fun
ction
Product version ES
3
Building Technologies
009865_m_en_
--
Fire Safety
Depending on the product and various approvals, the product labels may differ in
ES
3.4Product version ES
The product version ES provides the technical status of a device in terms of
software and hardware. The product version is provided as a two-digit number.
You will find the det ails of your device's product version:
●On the packaging label
●On the product label or the type plate
Product version on the packaging label
Details of the product version can be found directly on the packaging label in the
barcode:
Example of a packaging label with details of the product version
Product version on the product label and t he type plate
Details of the product version can be found after the device order number:
04
ES
Example of a product label with details of t he product ver sion
terms of the informat ion type and layout.
Look for your device' s order number on the product label.
You will find the produc t version after the order number.
28 | 82
2015-11-06
Page 29
Structure and function
Details for ordering
82
009865_m_en_
--
Fire Safety
3.5Details for ordering
The SMF6120
radio base may only be used as a replacement device in fire
SMF121V24217-C1218-W200 International manual call point (Siemens)
SMF121V24217-C1218-W100 Neutral manual call point
SMF6120S24218-F72-A1Radio base for SMF121
detection inst allations that were inst alled prior to April 1, 2011!
S24218-F62-A7
3
Complete radio smoke detector, including base
DBW117 1 and two 9 V lithi um mangan es e dioxide
batteries
Radio smoke detector (without base, without
batteries)
3.6RadioSpy
RadioSpy is an optional tool for installing radio cells and analysis in the event of
problems.
The following modules form part of RadioSpy:
●RadioSpy software ( installation on PC)
●RadioSpy hardware (radio module in hous ing + cable kit)
The RadioSpy can perform the following functions:
●Observing radio cell ( recording and analysis)
●Signing radio detectors on and off
●Replacing radio detector or radio gateway
See also: A6V10229812 and A6V10217915 documents.
Building Technologies
29 |
2015-11-06
Page 30
Structure and function
Accessories for the FDCW221 radio gateway
3
Building Technologies
009865_m_en_
--
Fire Safety
3.7Accessories for the FDCW221 radio gateway
3.7.19 V lithium manganese dioxide battery
●For supplying radio detectors, radio gateways and service
devices with power
●EVE lithium manganese dioxide type CR9V/P-S Li/MnO2
9 V, 1.2 Ah battery with pin cover
●Compatible with:
●Order no.: A 5Q000041 42
3.7.2Micro terminal DBZ1190-AA
●Auxiliary terminal for connecting cables
●For T-branches of additional cabling e.g. for detector
heating u nits, sounder base, external alarm indicators etc.
●For wire d iameters of 0.28…0.5 mm
●4-pin
●Order no.: B PZ:46770 80 00 1
2
3.7.3Connection termi nal DBZ1190-AB
●Auxiliary terminal for connecting cables
●For T-branches of additional cabling, e.g., for cable
shieldi ng, detector heati ng units, sounder base, external
alarm indicators, etc.
●For wire diameters of 1…2.5 mm²
●3 poles
●Order no.: B PZ:49423 40 00 1
3.7.4MCL-USB adapter FDUZ221
●For connecting FDnet devices to a personal computer
●Interface converter for USB on MC link
●Compatible with:
●For details, see document 009854 (mounting instructions)
●No longer available, replaced by MCL-USB adapter
(radio) FDUZ227
30 | 82
2015-11-06
Page 31
Structure and function
Accessories for the FDCW221 radio gateway
82
009865_m_en_
--
Fire Safety
3.7.5Radio test set DZW1171
●For measuring the field stren gth in buildings
●Planning tool when setting up radio networks
●Two-part test unit:
●For details, see doc ument 004446
●Order no.: B PZ:57622 00 00 1
See also
2 Radio test set DZW1171 [➙ 47]
3.7.6RadioSpy
●To assis t with inst alling radio cells an d analysis in the
s
●Components:
●Compatible with:
●For details, see A6V1022 9812 document
●Order no.: S 2 42 18-F65-A 1
3
event of problems
3.7.7Cable ties 2.4 x 137
●For strain relief on the connection wires or generally for
attachment
●Made from polyamide
●Compatible with:
●Order no.: B PZ:18253 30 00 1
Building Technologies
31 |
2015-11-06
Page 32
Structure and function
Accessories for radio s
moke detector DOW1171
3
Building Technologies
009865_m_en_
--
Fire Safety
3.8Accessories for radio smoke detector DOW1171
3.8.1DBW11 71 bas e
●For inst alling radio smoke detectors
●Compatible with:
●Order no.: S 2 42 18-F316-A1
3.8.29 V lithium manganese dioxide battery
●For supplying radio detectors, radio gateways and service
devices with power
●EVE lithium manganese dioxide type CR9V/P-S Li/MnO2
9 V, 1.2 Ah battery with pin cover
●Break-out points f or M20 x 1.5 m etal cable glands
●Compatible with:
●Order no.: B PZ:45881 40 00 1
32 | 82
2015-11-06
Page 33
Structure and function
Accessories for radio smoke detector DOW1171
82
009865_m_en_
--
Fire Safety
3.8.5Protective cage DBZ1194
●To protect the devices against mec hanical d amage
●Can only be used i n conjunction with the following
accessories:
●Order no.: BPZ:46771 10 00 1
3.8.6Desig nation plate D BZ1193A
●To identify the location
●Compatible with:
●Order no.: B PZ:48643 30 00 1
3
Building Technologies
33 |
2015-11-06
Page 34
Structure and function
Accessories for manual call point SMF121 with radio base SMF6120
3
Building Technologies
009865_m_en_
--
Fire Safety
3.9Accessories for manual call point SMF121 with
radio base SMF6120
3.9.13.6 V lithium battery
●For supplying radio detectors with power
●TADIRAN SL-760 lithium battery (3.6 V, 2.2 Ah)
●Battery with connection cables and plugs
●Compatible with:
●Order no.: V 2 40 69-Z112-A1
3.6 V
3.9.2Key
3.9.3Glass insert
●For openin g doors on ma nual call points
●Compatible with:
●Order no.: S 2 42 17-G34-A1
●For alarm activation and protection against soiling
●Compatible with:
●Order no.: S 2 42 17-G41-A1
See also
2 Replacing the glass plat e on the manual call point SMF121
34 | 82
[➙ 72]
2015-11-06
Page 35
Structure and function
Function
82
009865_m_en_
--
Fire Safety
3.10Function
The radio
gateway may only be operat ed on a loop in the
FDnet
. Since the radio
The FDCW221 communicat es with the control panel via the FDnetdetector line.
The range of the radio s ignal in buildings is up to 40 m and is heavily dependent on
materials and equipment .
If the radio cells overlap, the maximum number of radio gateways is limited to 16
radio gateways or radio cells because of the limited number of channels available.
If there is no radio cell overlapping, the maximum address connection factor for the
FDnet detect or line limits the number of devices connected (r adio gateways,
detectors).
A maximum of 30 radio detectors can be connected to a radio gateway. Each radio
detector has its own address. The radio gateway itself has two addresses.
gateway and connected radio detectors form a stub, t his configuration must never
be used in stub operations. If it is, an impermissible 'stub-on-stub' topology will
result.
3
Two radio cells on the FDnet
Building Technologies
1
FDnet–compat ible control panel
(FC20xx, AlgoRex, Sigmasys)
2 FDnet detect or line
3 Radio cells
35 |
2015-11-06
Page 36
Structure and function
Function
3
Building Technologies
009865_m_en_
--
Fire Safety
The status 'Any fault message' can be displayed together wit h another status, e.g.
3.10.1Radio gateway FDCW22 1 diagnosis levels
The radio gateway monit ors its operation largely autonomous ly.
The following diagnosis levels are derived from the different control measurement s:
●Normal
●Replacement recomm ended
●Replacement necessary
●Fault
For details, see table below.
When a fatal error occurs, which impairs the funct ion of the radio gateway, a fault
message is reported and displayed on the control panel.
To remedy the cause, additional information is available in the radio gateway. This
can be displayed by the detector exchanger and tester FDUD292 or the intelligent
detector tester FDUD293 (as of software V2.1) for example.
You will find more information in documents 007227 and 009718.
Display on the test deviceMeaningMeasures
'no deviation'Normal, no fault is present
Radio gateway is fully functi onal
'advice excha.'
'needed excha.'
Any faul t messageFault pres ent
1
1
Replacement recommended
Radio gateway is still functional in spite of the battery
voltage being too low:
●FDCW221
Replacement necessary
Radio gateway is only being supplied with power via
the detector line:
●FDCW221
Alarming no longer guaranteed:
●FDCW221
Supply error●Check detector li ne voltage
Software error (Watchdo g error)Replace radio gateway
Memory errorReplace radio gateway
Communication error between radio gateway and
control pa ne l
None
Replace battery
Replace or insert battery
●Configure radio cell
●Replace radio gateway
●Replace radio gateway
Remedy cause
1
The information displayed on the detector exchanger and tester is always in
English; no translation into the corresponding language.
'needed excha.' (replac ement necessary).
36 | 82
2015-11-06
Page 37
Structure and function
Function
82
009865_m_en_
--
Fire Safety
3.10.2Behavior in degraded mode
Applicable for the FDnet:
When the main processor of the fire control panel fails, the control panel works in
degraded mode operation. Depending on the control panel type, the fire control
panel can continue to perform the most important alarming and signaling functions
in degraded mode operation.
Behavior of control panels that support degraded mode operation:
Alarming is still ensured in degraded mode operation. However, in degraded mode
only collective alarming is possible. This means that in the event of an alarm, it is
possible to identif y the FDnet detector line but not the exact location of the detector
triggering the alarm.
Degraded mode operation on the FDnet is not supported in the same way by all
control panels. T he information in the 'List of compatibilit y' and in the corresponding
control panel document ation must be taken into acc ount during project planning.
3.10.3O peration mod es of the radio gateway
The radio gateway FDCW221 has the following operation modes:
●Normal operation
●Start-up operation
●Configuration operation
3
3.10.3.1Normal op er ation
The radio gateway is in intended operation. All of the radio detect ors within the
radio cell are monitored.
3.10.3.2Start-up operation
As soon as the radio gateway is energized, it goes into start-up operation. In startup operation, the radio gateway checks whether radio detectors are logged on.
If the radio detectors of the radio cell are logged on, the radio gateway goes from
start-up to normal operation.
Otherwise the radio gateway goes from start-up operation to configuration
operation.
See also
2 Starting up the radio gateway [➙ 58]
3.10.3.3Configuration operation
When in configuration operation, radio links are established with all radio detectors.
Free radio channels are s earched for and the radio detectors logged on in the radio
gateway.
The radio gateway also goes into configuration operat ion when a radio detector is
removed or added.
The radio gateway is t aken into configuration operation by pr essing the button in
the radio gateway as f ollows:
●Long: for removing a radio detector
●Short: for adding a radio detector
If the radio gateway is not touched for a maximum of 15 minutes, it switches from
configuration operation to normal operation.
Building Technologies
37 |
2015-11-06
Page 38
Structure and function
Function
3
Building Technologies
009865_m_en_
--
Fire Safety
The radio gateway may only be operated on a loop in the
FDnet
. Since the radio
3.10.4Line separator in the radio gateway FDCW221
All FDnet devices are equipped with a line separator.
The FDnet device is equipped with electronic switches which isolate the defective
part in case of a short-circuit on the FDnet detector line. The rest of the detector
line remains serviceable. On a loop line all FDnet devices remain fully functional
after a simple error.
FDCL221 line separator
In terms of topology, the radio detectors logged onto the radio gateway are in a
stub. The st ub branches off on the FDnet detector line between the FDCW221 and
the integrated line separator FDCL221 of the radio gateway (see figure below).
Figure 3: Topology of radio gateway on FDnet
Gateway Radio gateway housingM1 Radio detect or 1 on stub
FDnet FDnet spring clips on radio gatewayM2 Radio detector 2 on st ub
gateway and connected radio detectors form a stub, t his configuration must never
be used in stub operations. If it is, an impermissible 'stub-on-stub' topology will
result.
38 | 82
2015-11-06
Page 39
Structure and function
Function
82
009865_m_en_
--
Fire Safety
3.10.5Status display on the radio gateway FDCW221
The flash sequences of
the amber LED inside the radio gat eway cannot be
The radio gateway has t hree internal LEDs (amber, red, green) and a red/green
LED in the cover.
The flash sequences are displayed in parallel on the two green LEDs or t he two
red LEDs.
displayed by the LED in the housing cover. The amber LED only displays f lash
sequences if radio detectors are to be removed.
1
2
3
4
3
LEDs for status display
1 Internal LED amber H33 Internal LED red H4
2 Internal LED green H24 LED in cover red/green H1
Building Technologies
39 |
2015-11-06
Page 40
Structure and function
Function
3
Building Technologies
009865_m_en_
--
Fire Safety
Oper ati o n mo deLEDs red
H1, H4
Normal operationOffOffOffNormal, intended operati on
Start-up operation Flashes twiceOffOffNo battery voltage or insufficient battery voltage
Off
Configuration
operation
Flashes once
briefly
Off
Flashes slowlyFlashes slowlyOffChannel search underway
OffFlashes slowlyOffChannel found
Flashes slowlyOffOffNo free channel found
Flashes rapidlyFlashes rapidlyOffLog oth er radio detectors on t o gateway
Off
Flashes rapidlyOffOff
OffOffFlashes slowlyRadio gateway ready to log off a radio detec tor
OffFlashes slowlyFlashes slowly
Flashes rapidlyOffFlashes rapidly
LEDs gree n
H1, H2
Flashes quickly
for 10 s
OffOff
Flashes once
briefly
Flashes quickly
for 3 s
LED amb er
H3
Off
Off
OffRadio detector log ged on to g ateway
Meaning
The radio gateway can be reset to its delivery status
(deleting internal configuration)
The butt on has been briefly pres sed or the R eed
contac t has been ac tivated with a magnet
Release the button after holding down for a long
period
Radio detector could not be logged on to gateway
(30 radi o d etectors already logged on)
A radio detector has already been detected for logging
off
(Note: The radio detector can be logged off using the
button)
Several radio detec tors have already been detec ted
for logging off
(Note: RadioSpy must be used to log off radio
detectors)
Status of radio gateway FDCW221
Legend
LEDs:Flashes slowly1x / second
Flashes rapidly4x / second
Flashes twice1x twice / second
Flashes once brieflyaround 0.3 of a second
Button:Press briefly<1…2 seconds
Press for long period>3 seconds
See also
2 Resetting the radio gateway to delivery stat us [➙ 62]
40 | 82
2015-11-06
Page 41
Structure and function
Function
3
82
009865_m_en_
--
Fire Safety
3.10.6Status display on the radio smoke detector DOW1171 and
on the radio base SMF6120
The radio smoke detector DOW1171 and the radio base SMF6120 have a status
indicator.
In configuration operation, the status indicator displays flash sequences to indicate
the field strength.
The status displays are listed in the following table:
Flashing cycle of status indicator
(red LED) / s (second)
OffNormal operation
1x / sALARM (AI only with DOW1171)
1x / 2 sNew lo g-on
3x / 2 sRe-log-on
1x long / 2 s
1
4x / s
1
3x / s
2x / s
1x / s
Continuous flashing (5x / s)Error
Meaning of flas hing cycle
System search: Attempt to establish a radio link to a radio
gateway
Field strength following successful radio detector log-on to radio
gateway:
●High receive field strength
Field strength following successful radio detector log-on to radio
gateway:
●Average receive field strength
Field strength following successful radio detector log-on to radio
gateway:
●Low receive field strength
Field strength following successful radio detector log-on to radio
gateway:
●Very low receive field strength
Building Technologies
Status of the radio smoke detector DOW1171 and the radio base SMF6120
1
Only the field strengths which are displayed with the 3x/s or 4x/s flashing cycle are acceptable link
qualities for the radio gateway.
41 |
2015-11-06
Page 42
Structure and function
Function
3
Building Technologies
009865_m_en_
--
Fire Safety
3.10.7Power supply
Radio gateway FDCW221
The radio gateway is normally powered via the FDnet detect or line.
Should the mains volt age fail, the radio gateway is powered via the battery in the
control panel.
Brief open lines (<5 hours) on the detector line can be bridged by the 9 V lithium
manganese dioxide batteries .
DOW1171 radio smoke detector
Power is supplied to the power supply via two 9 V lithium manganese dioxide
batteries.
Manual call point SMF121 and radio base SMF6120
Power is supplied to the manual call point and the radio base via two 3.6 V lithium
batteries. The battery compartment is located in the radio base.
See also
2 9 V lithium manganese dioxide battery [➙ 30]
2 3.6 V lithium battery [➙ 34]
42 | 82
2015-11-06
Page 43
Planning
Compatibility
82
009865_m_en_
--
Fire Safety
4Planning
The radio gateway may only be operated on a loop in the
FDnet
. Since the radio
Control panel
FC20xx
FC72x
SIGMASYS
AlgoRex
When planning a project, proceed as follows:
●Use a suitable radio test set to measure the local radio wave propagation (field
strength measurement) in the building.
●Plan how to split t he radio cover age into individual radio cells.
You will need this information for the number and posit ioning of the radio
gateways.
Note requirements in standards (e.g. fire sectors according to EN 54, local
specifications etc.).
gateway and connected radio detectors form a stub, t his configuration must never
be used in stub operations. If it is, an impermissible 'stub-on-stub' topology will
result.
See also
2 Radio test set DZW1171 [➙ 47]
2 Defining the place of mounting [➙ 47]
2 Transmission field [➙ 45]
4
4.1Compatibility
Compatible with control panels that support the FDnet detector line.
You will find detailed information in the 'List of compatibility'.
The table below shows the compatibility of the devices with various control panels:
Detector line
FDnetX–XX
C-NET––––
X = compatible
– = not compatible
Building Technologies
43 |
2015-11-06
Page 44
Planning
Usage cond
itions
4
Building Technologies
009865_m_en_
--
Fire Safety
Incorrect planning of usage
conditions
'Transmission field' chapters.
4.2Usage conditions
WARNING
Faults occur and are display ed on the control panel.
●Measure the field strength in advance.
●Note the usage conditions and the 'Defining the place of mount ing' and
The following usage condit ions apply to the radio gateway FDCW221 and the radio
detectors:
●The radio gateway and the radio detectors must be easily accessible f or the
service staff at all times:
–Accessing operating elements (plug connection for MC link, button, Reed
contact for the radio gateway)
–Replacing battery
●All devices, even the radio gateway, must always be operated with a bat tery
●The distance between the radio gateway and radio detector m ust be noted
(max. 40 m, depending on field strength measurement )
●The building construc tion will have a major impact on the radio range
–Steel
–Concrete
–Thick or damp walls
●Transmission f ield damping and reflection
–Doors must be closed when measuring the f ield strength
–Mirrors in the room will have a negative im pact on damping
Limitations
The following application may be unsuitable:
●Rooms with a high level of transmission field damping, for example those with
a framework of met al bars used as a partition or metallic storage racks.
See also
2 Defining the place of mounting [➙ 47]
2 Transmission field [➙ 45]
4.2.1Environmental influences
If the devices are used in industrial applications, consultation with the project
manager is required, since plastics do not withstand cert ain environmental
conditions.
The following factors must be taken into consideration:
●Chemicals
●Temperature
●Moisture
44 | 82
2015-11-06
Page 45
Planning
Transmissio n field
82
009865_m_en_
--
Fire Safety
4.3Transmission field
The transmis sion field in the building is affected by walls and obstacles. These
In the open, the field strength falls with a factor of 1/r², i.e. a doubling of distance in
the open equates to a 6 dB increase in damping. In buildings, the factor in a first
approximation is 1/r5, i.e. a doubling of distance means that damping increases by
around 6 to 17 dB.
The table below illustrates the relationship bet ween distance and damping for the
line of sight in the building:
constructions (walls, ceilings etc.) must be analyzed in detail to obtain a
statement on damping.
Radio da mping when passing through obstacles
The approximate values listed in the table should be added together for
constructions encountered along the radio link in order to determine the actual
damping at the receiver location.
ConstructionAdditional damping
Room divi der<1 dB
Dry bricksaround 6 dB
Dry concretearound 6 dB
Lime sand brickaround 8 dB
Planar lime sand brick el ementsaround 8 dB
Timber frame wallaround 8 dB
Timbe r panel wallaround 8 d B
Building Technologies
45 |
2015-11-06
Page 46
Planning
Transmissio n field
4
Building Technologies
009865_m_en_
--
Fire Safety
ConstructionAdditional damping
Damp bricksaround 10 dB
Coated plasterboard (double wall)around 15 dB
Armored concretearound 30 dB
Thick, damp brick wall>40 dB
Sample calculation:
A radio gateway is fitted under an armored concrete ceiling. The partition walls are
made from concrete.
A
B
C
Radio gateway with radio links A, B, C
Path A:5 mFree space+armored concrete ceiling≈40 + 30 = 70 dB
Path B:15 m
Path C:10 m Free space+concrete wall≈57 + 6 = 63 dB
Free space+armored concrete ceiling+concrete
wall
≈67 + 30 + 6 = 103 dB
Result:
●Paths A and C can be used.
●The radio detect or will not be reached with path B.
46 | 82
2015-11-06
Page 47
Planning
Defining the place of mounting
82
009865_m_en_
--
Fire Safety
4.4Defining the place of mounting
Several radio gat eways using the same basic channel
●
Start up radio gateways one after in the same transmission field.
Measure the distances between the radio gateway and radio detector on the
General restrictions/system limits
Maximum number of radio detectors per radio gateway30
Maximum distance between radio gateway and radio detector40 m or 90 dB
WARNING
Faults or malfunctions will arise.
If you want to start up several radio gateways, they have to be started up one after
another in the same transmission field such that every radio gateway can establish
its own basic channel in configuration operation and logged on radio detectors
each communicate with just one radio gateway.
You can then also fit the radio gateways at a greater distance.
This will also ensure that temporary changes to the transmission fields do not
result in malfunctions as a result of the same basic channels being occupied
several times over.
4
building plan in advance and calculate the damping.
For reliable planning, you will have to measure the field strength in the building.
More than 16 radio gateways
If a project consists of more than 16 radio gateways (max. utilization), additional
radio gateways (>16) have to be fitted in a remote transmission field without radio
cell overlapping.
The 16 basic channels can t hen be used again.
4.5Radio test set DZW1171
For reliable planning, field strength measurements must be taken in the building.
You can take field strength measurements with the radio test set DZW1171.
For details, see document 004446.
See also
2 Radio test set DZW1171 [➙ 31]
Building Technologies
47 |
2015-11-06
Page 48
Mounting/Installation
Installing and connecting the radio gateway FDCW221
5
Building Technologies
009865_m_en_
--
Fire Safety
Damage to spring clips or contact problems
sections. The t erminal can be positioned inside t he housing.
Fit the radio gateway such that it is easily acces sible for battery changes and for
Note the positive and negative poles.
5Mounting/Installation
5.1Installing and connecting the radio gateway
FDCW221
NOTICE
If the cable cross-sections you want to connect to the radio gateway are larger
than 1.5 mm2, the spring clips may be damaged or contact problems may arise.
●Use the connection t erminal DBZ1190-AB for cables with a diameter of
1.5…2.5 mm2.
●Obtain a corresponding terminal from the customer for even larger cross-
the following operating elements: MC link plug connect ion, button and Reed
contact.
Ensure suitable position so that the LEDs are visible.
Only connect one wire per terminal. This is the only way to ensure the connection
is failure-free for the entire service life of the device.
SHIELD
_
+
+
_
Connection diagram with detector line not yet connected
LINE
++
__
+
LINELINE
_
48 | 82
2015-11-06
Page 49
Mounting/Installation
Installing and connecting the radio gatewa
y FDCW221
82
009865_m_en_
--
Fire Safety
Procedure:
Short
-
circuit as a result of incorrectly inserting batteries
●
When inserting battery, note polarity.
The shielding must not touch any other potentials or metal parts in the device.
WARNING
Warming of batteries and risk of fire
w The detector line is switched off.
1. Remove the two stickers featuring the serial number from t he back box.
2. NOTICE! Do not stick any stickers on the radio module! The stickers may
impair the send and r eceive properties of the radio module.
3. Stick one sticker in the battery compartment of the radio gateway so t hat you
can identify the radio gateway even when it is screwed down.
The other sticker is intended for sticking in the building plan.
4. Break out the cable entries according to the cable supply.
Recess-mounted cable entry:
Break out openings in supporting surface of back box.
Surface-mount ed cable entry:
Break open openings in face end of back box.
5
5. Guide cables through back box and use two s crews (max. diameter 4.3 mm) to
fit back box on a level surf ace.
6. Prepare the detector line wires s uch that they can be connected to the 'LINE'
spring clip later on.
7. Connect negative and positive poles of the detector line with a micro term inal
or connection terminal (order separately) . To test the detector line, these must
not be interrupted.
8. If the detector line cables are shielded, connect the shieldings of the two
detector line cables (coming and going) to the 'SHIELD' spring clips. Use a
screwdriver to remove the load from the spring clip so you can slide in t he wire.
9. Connect clip to 9 V battery contacts and insert battery in back box's battery
compartment. Only connect battery cable to connector on PCB when
commissioning.
10. Snap housing cover onto back box.
See also
2 Connections [➙ 22]
Building Technologies
49 |
2015-11-06
Page 50
Mounting/Installation
Installing the radio smoke detector DOW1171
5
Building Technologies
009865_m_en_
--
Fire Safety
2
3
5.2Installing the radio smoke detector DOW1171
w Ensure that the radio smoke detector DOW1171 is connected to the radio
gateway FDCW221 from its intended location.
1. Define the mounting location of the base such that the alarm indicator of the
radio smoke detector DOW1171 is clearly visible from the investigation route.
2. Install the base with two screws on a level surface.
–Note the minimum distances to be complied wit h.
3. Install a designation plate DBZ 1193A (accessory) if necessary.
4. Install the radio smoke detect or DOW1171 on t he base DBW1171.
1
Mounting location of the radio smoke detector
20 mm
500 mm
1 DOW1171 radio smoke detector3 Investigation route
2 Alarm indicator
Base DBW1171 with designation plate DBZ1193A
50 | 82
2015-11-06
Page 51
Mounting/Installation
Installing the radio smoke detector DOW1171
82
009865_m_en_
--
Fire Safety
Inserting the batteries
Short
-
circuit as a result of incorrectly inserting batteries
●
When inserting battery, note polarity.
Insert the batteries in the devices just before commissioning the fire detection
1
WARNING
Warming of batteries and risk of fire
installation.
w The radio smoke detector DOW1171 is inst alled on the base DBW1171.
1. Remove the radio smoke det ector DOW1171 from the radio base DBW1171.
2. WARNING! Device does not work! Only use the battery type intended for
the device!
3. Connect clip to 9 V lithium manganese dioxide battery contacts and insert
battery in back box's battery compartment.
5
–Repeat this step for the second battery.
4. Install the radio smoke detect or in the base.
a The radio smoke detector is ready for commissioning.
2
Battery compartment and log-on bu tton on the DOW117 1
1
Battery compartment for two 9 V
lithium manganese dioxide
batteries
Building Technologies
2 'New' log-on button
51 |
2015-11-06
Page 52
Mounting/Installation
Installing the radio smoke detector DOW1171
5
Building Technologies
009865_m_en_
--
Fire Safety
If you use
the detector locking device DBZ1190, you can only unlock radio smoke
Installing the detector locking device
lInstall a det ector locking device DBZ1190 (acces sory) if necessary
2
1
Installing the de tector locking dev ice DBZ1190
1 DBW1171 base2 DBZ1190 detector locking device
detectors inserted in the base DBW1171 using a screwdriver.
See also
2 DBZ1190 detect or locking device [➙ 32]
2 9 V lithium manganese dioxide battery [➙ 30]
52 | 82
2015-11-06
Page 53
Mounting/Installation
Installing the
radio base SMF6120 and manual call point SMF121
5
82
009865_m_en_
--
Fire Safety
Note the word 'TOP' on the radio base housing.
1
5.3Installing the radio base SMF6120 and manual call
point SMF121
Installing the radio base SMF6120
w Ensure that the radio base SMF6120 is connected to the radio gateway
FDCW221 from its intended location.
lSecure t he radio base at a height of 1.3…1.6 m on a level surface us ing
suitable screws. Use the mounting openings (1).
1
Mounting openings in the radio base SMF6120
1 Mounting openings
Building Technologies
53 |
2015-11-06
Page 54
Mounting/Installation
Installing the radio base SMF6120 and manual call point SMF121
5
Building Technologies
009865_m_en_
--
Fire Safety
Deactivating the manual call points prevents alarms from being forwarded.
with the notice 'NOT IN USE'!
bab
a
2
Installing the manual call point SMF121
w The radio base SMF6120 is already installed.
1. Open the door of the manual call point using a suitable key.
2. Break out the opening (2) on the rear of the manual call point's housing.
3. Guide the radio base's two connection cables through the opening (2) in the
manual call point.
4. WARNING! The manual call point does not work if the terminal assignment
deviates! Use only t erminals 'b▼' and 'b▲'.
5. Clip one connection cable each to terminals 'b▼' and 'b▲' in the terminal strip.
6. Secure the manual call point t o the radio base using the screws supplied.
7. Stick on the 'ATTENTION!' sign. If the feed lines are interrupted, 'Alarm
triggered' is display ed on the inside of the door of the manual call point.
8. Close the door of the manual call point.
View inside manual call point SMF121
2 Opening for cable feedthrough
WARNING
The alarm is not triggered.
●Mark deactivated manual call points or those which are not fully functional
54 | 82
2015-11-06
Page 55
Mounting/Installation
Installing the radio base SMF6120 and manual call point SMF121
5
82
009865_m_en_
--
Fire Safety
Short
-
circuit as a result of incorrectly inserting batteries
●
When inserting battery, note polarity.
Insert the batteries in the devices just before commissioning the fire
detection
Inserting batteries
WARNING
Warming of batteries and risk of fire
installation.
w The manual call point SMF121 is installed on the radio base SMF6120.
1. Open the door of the manual call point using a suitable key.
2. Remove the fixing screws in the manual call point and lift the manual call point
off the radio base.
3. Press the alarm button (2).
4. WARNING! Device does not work! Only use the battery type intended for
the device!
5. Insert two 3.6 V lithium AA batteries into the radio base.
6. Connect the batteries' plug connections to the two bushes on the PCB in the
radio base.
7. Secure the manual call point t o the radio base again using the screws.
8. Press the reset slider (1).
a The alarm button (2) jumps out.
9. Close the door of the manual call point.
a The manual call point is ready for commissioning.
Building Technologies
55 |
2015-11-06
Page 56
Mounting/Installation
Instal
ling the radio base SMF6120 and manual call point SMF121
5
Building Technologies
009865_m_en_
--
Fire Safety
1
View inside manual call point SMF121
2
1 Reset slider2 Alarm button
See also
2 3.6 V lithium battery [➙ 34]
56 | 82
2015-11-06
Page 57
Commissioning
Basic rules for commissioning
82
009865_m_en_
--
Fire Safety
6Commissioning
Insert the batteries in the devices just before commissioning the fire detection
The RadioSpy can be used to assist with configuration.
Before commissioning the FDnet detector line, the radio cell of the radio gateway
must be fully started up.
installation.
The device is commissioned via the control panel. The exact procedure is
described in the control panel documentation.
Conduct a performance check once commissioning is complete.
The flashing pattern of the LEDs and the length of time for which the button must
be pressed (briefly/long time) are described in the 'S tatus display on radio
gateway' chapter.
Generally when commis sioning, the Reed contact can also be activated with a
magnet rather than using the button.
6
Starting up radio cell
A radio cell must be commissioned as described below following some basic rules:
1. Start up radio gateway.
2. Log radio detector on to radio gateway.
3. Start up radio gateway on detector line.
See also
2 RadioSpy [➙ 29]
2 Status dis play on the radio gateway FDCW221 [➙ 39]
2 Starting up the radio gateway [➙ 58]
2 Logging radio detectors on to the radio gateway [➙ 59]
2 Starting up the radio gateway on the detector line [➙ 60]
2 Basic rules for commissioning [➙ 57]
6.1Basic rules for commissioning
You must comply with the following basic rules:
●One radio detector must be correctly logged on to its radio gateway before
starting t o commission another radio detector.
●One radio cell must be fully started up before commissioning of another radio
cell begins.
Only one radio gateway may be in configuration operation.
●All the radio cells m ust be completely started up before starting up the detector
line.
Building Technologies
57 |
2015-11-06
Page 58
Commissioning
Starting up the radio gateway
6
Building Technologies
009865_m_en_
--
Fire Safety
Several radio gat eways using the same basic channel
●
Start up radio gateways one after in
the same transmission field.
If the red LED flashes twice
once the battery has been inserted, the battery
If a basic channel isn't found, you will find assist ance in the 'Maintenance
6.2Starting up the radio gateway
Before radio detectors can be logged on to the radio gateway, the radio gateway
must be started up.
WARNING
The radio detectors communicate using sev eral radio gateways. Faults or
malfunctions will arise.
If you want to start up several radio gateways, they have to be started up one after
another in the same transmission field such that every radio gateway can establish
its own basic channel in configuration operation and logged on radio detectors
each communicate with just one radio gateway.
You can then also fit the radio gateways at a greater distance.
This will also ensure that temporary changes to the transmission fields do not
result in malfunctions as a result of the same basic channels being occupied
several times over.
Procedure:
w The FDnet detector line must be switched off.
w The radio gateway is in its delivery status.
w Several radio gateways must not be started up at the same time.
w There is a new battery ready for the radio gateway.
1. Unlock the housing cover of the radio gateway on the face side using a pin.
2. Remove the housing cover.
3. Insert a new battery.
a Radio gateway switches f rom start-up operation to configuration operation
for basic channel
a Red and green LEDs flash slowly in t urn
a Radio gateway searches for free basic channel and signals result
– channel found: Green LED flashing slowly
– no channel found: Red LED flashing slowly
a Radio gateway is ready for configuration operation
voltage is too low.
Insert a new battery.
/ troubleshooting' chapter.
See also
2 Logging radio detectors on to the radio gateway [➙ 59]
2 Resetting the radio gateway to delivery stat us [➙ 62]
2 Maintenance / troubleshooting [➙ 67]
58 | 82
2015-11-06
Page 59
Commissioning
Logging radio detectors on to the radio gateway
82
009865_m_en_
--
Fire Safety
6.3Logging radio detectors on to the radio gateway
The RadioSpy can be used to assist with configuration.
If the radio detector is not in its delivery status, f irst do this as described in the
Note the serial number or log
-
on sequence and location of the radio detector.
Radio detectors can log on to a radio gateway which has just started up or also be
added to the existing configuration of a radio cell.
In each case, the button in t he radio gateway has to be pressed briefly to either
change from the exited 'Scan mode for the basic channel' or from normal operation
to configuration operation.
The Reed contact can be act ivated instead of pressing the butt on.
Procedure:
w FDnet detector line is switched off.
w Radio gateway is in configuration operat ion.
– green/red LEDs flash quickly in turn.
w Number of radio detectors logged on to radio gateway <30.
w Radio detector is in its delivery st at us.
6
'Resetting DOW1171 t o delivery status' or 'Resetting SMF6120 to delivery status'
chapters.
1. Insert batteries into the radio detector. Press the alarm button on the SMF6120
too.
2. Screw the radio smoke detector DOW1171 int o the base and the manual call
point SMF121 into the radio base SMF6120.
3. Press the reset slider for the alarm button on the manual call point .
a The radio detector is autom atically logged on to the radio gateway.
a Successful log-on: Green LED on radio gateway flashes quickly for
5 seconds
a Unsuccessful log-on: rapid continuous flashing of red LED on radio
gateway
a The radio gateway automatically returns to configuration operation.
a Green/red LEDs flash quickly in turn.
a Once the radio detector has logged on to the radio gateway, the radio
detector's status indicator (LED) display s the field strength for two minutes as
follows:
Flashing cycle / s (second)Field strength
4x/sHigh
3x/sMedium
2x/sLow
1x/sVery low
Only the field strengths which are displayed with the 3x/s or 4x/s flashing cycle are
acceptable link qualities for the radio gateway.
Building Technologies
59 |
2015-11-06
Page 60
Commissioning
Starting up the radio g
ateway on the detector line
6
Building Technologies
009865_m_en_
--
Fire Safety
Assignment of the detector serial number to
FC20xx
:
In terms of topology, the radio detectors logged onto the radio gateway are in a
Logging on more radio detectors
1. Repeat the process for all other radio detectors on the same radio gateway.
2. When the field strength flashing has stopped, exit the radio gateway's
configuration mode by briefly pressing the button.
a The radio gateway is then in normal operation and all LEDs are off.
●After 15 minutes without any action, the radio gateway automatically switches
from configuration operation to normal operation.
●After 30 radio detectors have logged on, the radio gateway aut omatically
switches to norm al operation.
See also
2 Resetting the DOW1171 to delivery status [➙ 63]
2 Resetting the SMF6120 to delivery status [➙ 65]
2 RadioSpy [➙ 29]
2 Reed contact and button [➙ 23]
6.4Starting up the radio gateway on the detector line
Once all the radio detectors of a radio cell have been logged on to the radio
gateway in battery mode, the FDnet detector line can be started up.
SHIELD
_
+
Connection diagram for FDnet detector line
LINE
__
++
Procedure:
1. Connect the FDnet detector line cable to the 'LINE' spring clips.
2. Start the FDnet detect or line up again. You will find instruct ions on
commissioning the detector line in the corresponding system and control panel
documentation.
For FS20: Document 009052
The last three digits match. If e.g., the serial number of the detector is '80840349',
the ID on the FC20xx control panel is defined as follows:
..........349
stub. The st ub passes through the FDnet detector line between the FDCW221
and the integrated line separator FDCL221 of the radio gateway. The order in
which the radio detectors log on determines the order on the st ub.
60 | 82
2015-11-06
Page 61
Commissioning
Logging radio detectors off the radio gateway
82
009865_m_en_
--
Fire Safety
6.5Logging radio detectors off the radio gateway
If radio detectors are defective or more than one radi o
detector is det ected for
Radio detectors logged on to a radio gateway can be logged off. This can be done
with or without RadioSpy .
Below you will find a description for the procedure without RadioSpy.
Procedure:
w The radio gat eway is in normal operation.
w The radio detector to be logged off is in nor mal operation.
1. Press the button in the radio gateway for more than three seconds:
a Amber LED flashes slowly
2. Unscrew the radio detector DOW1171 from the base or remove the radio
detector SMF6120 bat tery.
a The radio gateway detect s the radio detector to be removed (with
SMF6120, detection will take up to four minutes)
a Amber and green LEDs in radio gateway flash slowly in turn
3. Press the button in the radio gateway for more than three seconds
a LEDs go out
a Log-off is confirm ed
a The radio detector is logged of f and the radio gateway switches to normal
operation (the DOW1171 als o signals correct logging off , i.e. its status
indicator flashes continuously)
or
6
Aborting the log-off process before confirmation
lBriefly press the button in the radio gateway
a The radio detector remains logged on and the radio gateway switches to
normal operation.
removal, the red and amber LEDs flash quickly in turn. RadioSpy must then be
used for logging off.
See also
2 RadioSpy [➙ 29]
2 Status dis play on the radio gateway FDCW221 [➙ 39]
Building Technologies
61 |
2015-11-06
Page 62
Commissioning
Resetting the radio gateway to delivery status
6
Building Technologies
009865_m_en_
--
Fire Safety
Resetting the radio gateway to delivery status
can be deleted.
6.6Resetting the radio gateway to delivery status
The radio gateway is res et to the delivery status if the existing conf iguration is to be
deleted. For example, if the radio gateway is to occupy another basic channel.
NOTICE
An existing configuration is deleted.
●Only reset the radio gateway to its delivery status if the existing configuration
Procedure:
w The FDnet detector line is switched off.
1. Unlock the housing cover of the radio gateway on the face side using a pin.
2. Remove the housing cover.
3. Unplug the battery plug connection for at least 10 seconds.
4. Then re-insert the batt ery plug connection.
a Wait for green LED to flash quickly.
5. Briefly press the butt on in the radio gateway while the green LED is f lashing.
a The radio gateway is init ialized and returns to configuration operation. This
is indicated by the red and green LEDs flashing slowly in turn.
a A free basic channel is automatically looked for and the result displayed:
– channel found: Green LED flashing slowly
– no channel found: Red LED flashing slowly
6. Now log the radio detector on to the radio gateway.
See also
2 Logging radio detectors on to the radio gateway [➙ 59]
62 | 82
2015-11-06
Page 63
Commissioning
Resetting the DOW1171 to delivery status
82
009865_m_en_
--
Fire Safety
6.7Resetting the DOW1171 to delivery status
Resetting the radio s moke detector to delivery status
immediately.
The 'New' log
-
on button (1) can be actuated using a size 0 screwdriver or similar
2
NOTICE
All existing configurations are deleted.
●Only reset the radio smoke detector to its delivery status if the existing
configurations can be deleted.
●Ensure that no gateway is in configuration mode during the reset process.
Exception: T he reset radio device should be logged back on to the gateway
1. Unscrew the radio smoke detector DOW1171 from the base.
2. Remove both batteries from the bracket and pull the clips out off the battery
contacts.
3. Wait 10 seconds for the batteries to discharge.
4. Plug the clips back on to the two batteries and insert the batteries into the
brackets.
a The status indicator flashes three times repeatedly.
5. Press the 'New' log-on button until the status indicator only f lashes once.
6. Screw the radio smoke detector into the base and wait until the status indicator
displays 'System search'.
a The configuration data has been deleted from the radio smoke detector
DOW1171.
a The radio smoke detector is ready to log on to a radio gateway again.
See also
2 Logging radio detectors on to the radio gateway [➙ 59]
64 | 82
2015-11-06
Page 65
Commissioning
Resetting the SMF6120 to delivery status
82
009865_m_en_
--
Fire Safety
6.8Resetting the SMF6120 to delivery status
Resetting the manual c all point with radio base to delivery status
immediately.
NOTICE
All existing configurations are deleted.
●Only reset the radio smoke detector to its delivery status if the existing
configurations can be deleted.
●Ensure that no gateway is in configuration mode during the reset process.
Exception: T he reset radio device should be logged back on to the gateway
6
1
Figure 5: View inside manual call point SMF121
2
1 Reset slider2 Alarm button
Building Technologies
65 |
2015-11-06
Page 66
Commissioning
Resetting the SMF6120 to delivery status
6
Building Technologies
009865_m_en_
--
Fire Safety
4
1
Figure 6: View ins ide radio base SMF6120
32
1 'New' log-on button3 Status indicator
2 Battery plug connec tions4 3.6 V lithium AA batteries
Procedure:
1. Unscrew the manual call point SMF121 from the radio base SMF6120.
2. Pull both plugs of the battery connection cable out of the printed cir cuit board in
the radio base.
3. Wait 10 seconds for the batteries to discharge.
4. Press the alarm button on the manual call point SMF121.
5. Plug both plugs of the battery connection cable back into of the printed circuit
board in the radio base.
a The status indicator flashes three times repeatedly.
6. Press the 'New' log-on button in the radio base until the status indicator only
flashes once.
7. Reset the alarm button using the res et slider on the manual call point SMF121
and wait until the st atus indic ator displays 'System search' .
66 | 82
a The configuration data is deleted from the manual call point with radio bas e
SMF6120.
a The manual call point with radio base is ready to log back on to a radio
gateway.
See also
2 Logging radio detectors on to the radio gateway [➙ 59]
2015-11-06
Page 67
Maintenance / troubleshooting
Changing batteries on the FDCW221
82
009865_m_en_
--
Fire Safety
7Maintenance / troubleshooting
Short
-
circuit as a result of incorrectly inserting batteries
●
When inserting battery, note polarity.
The
battery may only be replaced by technical personnel.
It may take up to 30
minutes for the battery fault
message to disappear f rom the
Dispose of batteries in an environmentally friendly manner and observe national
7.1Changing batteries on the FDCW221
The battery in the radio gateway must be replaced when a battery fault for the
radio gateway appears on the control panel. The detector line must not be
switched off during the battery fault otherwise the service life of the radio detector
batteries will be reduced significantly!
WARNING
Warming of batteries and risk of fire
7
Procedure:
w The FDnet detector line is operating.
w The radio gateway is in normal operat ion and is being powered by the FDnet
detector line without any interruptions.
w The new battery is ready to be inserted.
1. Unlock the cover of the radio gateway on the face side using a pin.
2. Pull off the cover of the radio gateway.
3. Replace the battery.
4. Snap the cover of the radio gateway back into the back box.
control panel because the battery is only checked ev ery 30 m inutes. The fault
message only disappears if the newly inserted battery has sufficient voltage.
All fault messages are updated if you do the following:
1. Switch the detector line off.
2. Remove the battery.
3. Insert the battery.
4. Switch the detector line on.
guidelines and regulations.
See also
2 Status dis play on the radio gateway FDCW221 [➙ 39]
2 9 V lithium manganese dioxide battery [➙ 30]
Building Technologies
67 |
2015-11-06
Page 68
Maintenance / troubleshooting
Changing batteries on the
DOW1171
7
Building Technologies
009865_m_en_
--
Fire Safety
Short
-
circuit as a result of incorrectly inserting batteries
●
When inserting battery, note polarity.
The batteries may only be replaced by technical personnel.
The batteries in the radio smoke detector must be replaced one after another.
Dispose of batteries in an environmentally friendly manner and observe
national
7.2Changing batteries on the DOW1171
The two batteries in the radio smoke detector must be replaced when a battery
fault for the radio gateway appears on the control panel.
WARNING
Warming of batteries and risk of fire
Always change the two batteries together.
Only one radio smoke det ector per radio cell may be briefly without batteries.
Procedure:
w The FDnet detector line or detector zone is s witched off.
w The radio gateway is in normal operation.
w The new 9 V batteries for the DOW1171 are ready f or inserting.
1. Unscrew the radio smoke detector DOW1171 from the base.
2. Remove the old batteries from the DOW1171.
3. Wait 10 seconds for the batteries to discharge.
4. Insert the new batteries into the DOW1171.
5. Screw the radio smoke detect or DOW1171 back into the base.
a The status indicator indicates the corresponding field strength by flashing
for 2 minutes.
guidelines and regulations.
See also
2 Status display on the radio smoke detector DOW1171 and
on the radio base SMF6120 [➙ 41]
2 9 V lithium manganese dioxide battery [➙ 32]
68 | 82
2015-11-06
Page 69
Maintenance / troubleshooting
Changing batteries on the SMF6120
82
009865_m_en_
--
Fire Safety
7.3Changing batteries on the SMF6120
Short
-
circuit as a result of incorrectly inserting batteries
●
When inserting
battery, note polarity.
The batteries may only be replaced by technical personnel.
The batteries in the manual call points with radio base must be replaced one after
Dispose of batteries in an environmentally friendly manner and observe national
The two batteries in the manual call point with radio base must be replaced when a
battery fault for the manual call point with radio base appears on the control panel.
WARNING
Warming of batteries and risk of fire
Always change the two batteries together.
another.
Only one manual call point per radio cell may be briefly without bat teries.
7
Procedure:
w The FDnet detector line or detector zone is s witched off.
w The radio gateway is in normal operation.
w The new 3.6 V lithium batteries for t he SMF6120 are ready for inserting.
1. Open the manual call point with radio base SMF 6120.
2. Remove the old batteries from the SMF6120.
3. Wait 10 seconds for the batteries to discharge.
4. Insert the new batteries into the SMF6120 and close the SMF6120 again.
a The status indicator indicates the corresponding field strength by flashing
for two minutes.
For more information see document 010087.
guidelines and regulations.
See also
2 Status display on the radio smoke detector DOW1171 and
on the radio base SMF6120 [➙ 41]
2 3.6 V lithium battery [➙ 34]
Building Technologies
69 |
2015-11-06
Page 70
Maintenance / troubleshooting
Status query
7
Building Technologies
009865_m_en_
--
Fire Safety
7.4Status query
The radio gateway is equipped with the MC link (Maintenance and Commissioning
Link). This interface can be used to query the following data using the detect or
exchanger and test er FDUD292 or intelligent detect or tester FDUD293 (as of
software V2. 1):
●Impermissible c onfiguration
●Status of radio links
●Error list
●Status regist er
You will find more information in documents 007227 and 009718.
7.5Perf ormance check
Recommendation:
●Check the devices every year.
●Replace heavily soiled or damaged devices.
You will find more detailed information in the fire detection system documentation.
Other than battery changes, no particular maintenance is needed.
7.6Remedy ing faults
The following problems may arise:
A radio detector cannot be logged on in configuration operation
There are already 30 radio detectors logged on to the radio gateway. The radio
gateway can still be put into configuration operation with the 31st radio detect or,
but the radio detector cannot log on.
Remedy:
Use another radio gateway.
Control panel not correctly displaying the fire detection topology or
display taking 10 minutes
It may take up to 10 minutes for the fire detection topology to again be displayed
on the control panel or f or the data to be synchronized in the following cases:
●The radio gateway had no power supply for a couple of seconds, i.e. the FDnet
detector line was switched off or interrupted and also had no battery voltage.
●You have updated the radio gat eway firmware.
●You have replaced the radio gateway.
Remedy:
The first case can be avoided by only ever changing the battery when the FDnet
detector line is switched on.
lRestart the FDnet detector line.
70 | 82
2015-11-06
Page 71
Maintenance / troubleshooting
Replace radio gateway
82
009865_m_en_
--
Fire Safety
7.7Replace radio gateway
Note the connection assignment of the line cables
when replacing the radio
Replace the radio detectors one after another.
Using RadioSpy is the preferred way of replacing a radio gateway. All radio
detector configurations can then be transferred.
gateway.
Mixing up the line cables will produc e a topology error.
Procedure with RadioSpy:
w The FDnet detector line is switched off.
1. For the steps required, see document A6V10229812.
2. The radio gateway automatically synchronizes its dat a with the radio detectors.
Follow the entire pr ocess with RadioSpy or wait 10 minutes until the data is
fully synchronized.
3. Switch the FDnet detector line back on.
7
4. Select 'Accept replaced devices' on the control panel.
Procedure without RadioSpy
The radio gateway must be f ully reconfigured after replacement.
See also
2 Starting up the radio gateway [➙ 58]
7.8Replacing radio detectors
You will find points 2 and 4 listed below in relation to replacing a radio detector in
the corresponding chapt er.
Procedure:
1. Switch the FDnet detector line off.
2. Log the existing radio detector off the radio gateway.
3. Replace the radio detector.
4. Log the new radio detector on to the radio gateway.
5. Switch the FDnet detector line back on.
6. Select 'Accept replaced devices' on the control panel.
Building Technologies
See also
2 Logging radio detectors on to the radio gateway [➙ 59]
2 Logging radio detectors off the radio gateway [➙ 61]
71 |
2015-11-06
Page 72
Maintenance / troubleshooting
Replacing the glass plate on the manual call point SMF121
7
Building Technologies
009865_m_en_
--
Fire Safety
7.9Replacing the glass plate on the manual call point
SMF121
w A new glass plate is ready.
w The manual call point SMF121 is installed on the radio base SMF6120.
1. Open the door using a suitable key. NOTICE! Keep the key in a safe place.
2. Remove the old glass pane.
3. Push the retainer (1) to the right.
4. Place the glass pane under the guide (2) and under the retainer (1). The glass
pane is square-shaped and can be inser ted in any direction.
5. Release the retainer (1).
6. Close the door.
Figure 7: Replacing the glass plate on the SMF121
1 Retainer2 Guide
See also
2 Glass insert [➙ 34]
72 | 82
2015-11-06
Page 73
Maintenance / troubleshooting
Updating the firmware of radio gateway FDCW221
7
82
009865_m_en_
--
Fire Safety
Read the 'Release Notes' before you carry out a firmware update. O bserve the
7.10Updating the firmware of radio gateway FDCW221
information about the update routine displayed on the screen.
1. Disconnect the detect or line connected to the radio gateway FDCW221
completely from the control panel.
2. Connect the detector line as a loop to the line tester FDUL221.
3. Start the detector line.
–Note the number of devices on the detector line for the check after the
update; see step 12.
4. Connect the radio gateway FDCW221 to the PC via the MC link cable and an
FDUZ221/227.
5. Ensure that radio gateway FDCW221 is supplied with power via the line tester
FDUL221.
6. Start the update routine.
a The firmware update is carried out.
a The separators for the radio gateway FDCW221 are open.
7. Remove the MC link cable from the radio gateway FDCW221 once the update
routine is complete.
8. Restart the detector line on the l ine tester FDUL221.
a The separators for the radio gateway FDCW221 are closed.
9. If necessary: Update the firmware of additional radio gateways FDCW221 on
this detect or line; see steps 4 to 8.
10. After updating the firm ware of the last radio gateway on the detector line: Wait
at least 10 minutes.
a The data for all radio detectors is synchronized.
a The supply of the detector line is ensured by the line tester FDUL221.
11. Restart the detector line on the line tester FDUL221.
12. Check the number of devices on the detect or line and compare the number
with the result from step 3.
13. Disconnect the detector line from the line tester FDUL221.
14. Reconnect the detect or line to the control panel.
15. Wait for the detector line reading before you carry out further activities on the
detector line or control panel.
a The firmware update is complete.
Building Technologies
73 |
2015-11-06
Page 74
Specifications
Technical data for the radio gateway FDCW221
8
Building Technologies
009865_m_en_
--
Fire Safety
8Specifications
8.1Technical data for the radio gateway FDCW221
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapt er:
●Document 010087
Detector lineOperating voltageDC 12…33 V
Operating currentTyp. 1 mA
Maximum current connection factor5 + n*1 (n=number of radio detectors)
Quiescent current connection factor4 + n*1 (n = number of radio devices)
Address connection factor2 + n*1 (n = number of radio detectors)
Separator connector fact or1
ProtocolFDnet
Compati bilitySee 'List of compatibility'
Design●Inherently short-circuit-proof
●Protected against polarity reversal
●Protected against overvoltage
Line separatorLine voltage:
●NominalDC 32 V (= V
●MinimumDC 12 V (= V
●MaximumDC 33 V (= V
Voltage at which t he separa tor opens:
●MinimumDC 7.5 V (= V
●Maxim umDC 10.5 V (= V
Permanent current when switches are closedMax. 0.5 A (= I
Max. 1 A (= I
Max. 16
Radio
Switching current (e.g., in the event of a shortcircuit)
Leakage current when switches are openMax. 1 mA (= I
Serial impedance when switches are closedMax. 0.5 Ω (= Z
Number of radio gateways with radio cell
overlapping
Number o f radio detectors per radio gatewayMax. 30
Sending /r ec e iv in g aerials2 (aerial diversity)
Radio tra ns m is s ion :
●Frequency range868…870 MHz, SRD band (S hort Range Device)
●Channel grid25 kHz
●Number of channels80
●Transmitting power<5 mW ERP
●Range:
– In build ingMax. 40 m
– OutdoorsMax. 200 m
●DampingMax. 90 dB
nom
min
max
SO min
C max
S max
L max
)
)
)
SO max
)
C max
)
)
)
)
)
74 | 82
2015-11-06
Page 75
Specifications
Technical data for the radio gateway
FDCW221
82
009865_m_en_
--
Fire Safety
BatteryNumber of batteries1
VoltageDC 9 V
Type:
●Capacitance1200 mAh
●Service lif e>5 years
Battery voltage monitoredYes
ConnectionsDetector line:
●DesignSpring clips
●Cable cross section0.2…1.5 m m
MC lin k:
●DesignPlug connection
Ambient conditionsOperating temperature-10…+55 °C
Storage temperature-30…+65 °C
Air humidity≤95 % rel.
Protection category (IEC 60 529)IP40
Elect romagnetic compatibi lity:
●1 MHz…2 GHz30 V/m
Mecha nic al dataDimensions (L x W x H)214 x 58 x 33 mm
Weight not including battery0.190 kg
MaterialPolycarbo nate (PC) Makrolon 9125
Color~RAL 9002 gray white
CombustibilityUL94 V-1
StandardsEuropean standards●EN 54-17
Block / Li/MnO2
ULTRALIFE U9VL-J or EVE CR9V/P-S
2
●EN 54-18
●EN 54-25
8
Building Technologies
75 |
2015-11-06
Page 76
Specifications
Technical data for radio smoke detector DOW1171
8
Building Technologies
009865_m_en_
--
Fire Safety
8.2Technical data for radio smoke detector DOW1171
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapt er:
●Document 010087
RadioNumber of radio detectors p er radio gatewayMax. 30
Sending /r ec e iv in g aerials2 (aerial diversity)
Radio tra ns m is s ion :
●Frequency range868…870 MHz, SRD band (S hort Range Device)
●Channel grid25 kHz
●Transmitting power<5 mW ERP
●Range:
– In build ingMax. 40 m
– OutdoorsMax. 200 m
BatteryNumber of batteries2
VoltageDC 9 V
Type:
●Capacitance1200 mAh
●Service lif e>5 years
Battery voltage monitoredYes
Ambient conditionsOperating temperature-10…+55 °C
Storage temperature-30…+65 °C
Air humidity≤95 % rel.
Protection category (IEC 60 529)IP44
Mecha nic al dataDimensions (diame ter x H) with base DBW1171 119 x 73 mm
Color~RAL 9010 pure white
StandardsEuropean standards:●EN 54-7
Block / Li/MnO2
ULTRALIFE U9VL-J or EVE CR9V/P-S
●EN 54-25
76 | 82
2015-11-06
Page 77
Specifications
Technical data for manual call point SMF121 and radio base SMF6120
82
009865_m_en_
--
Fire Safety
8.3Technical data for manual call point SMF121 and
The SMF6120 radio base may only be used as a replacement device in fire
radio base SMF6120
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapt er:
●Document 010087
detection inst allations that were inst alled prior to April 1, 2011!
RadioNumber of radio detectors per radio gateway Max. 30
Sending /r ec e iv in g aerials2 (aerial diversity)
Radio tra ns m is s ion :
●Frequency range868…870 MHz, SRD band (Short Range Device)
●Channel grid25 kHz
●Transmitting power<5 mW ERP
●Range:
– In build ingMax. 40 m
– OutdoorsMax. 200 m
BatteryNumber of batteries2
VoltageDC 3.6 V
Type:TA D IRAN SL-760 lithium
●Capacitance2.2 Ah
●Service lif e>5 years
Battery voltage monitoredYes
Ambient conditionsOperating temperature-10…+5 5 °C
Storage temperature-30…+65 °C
Air humidity≤95 % rel.
Protection category according to
EN 60529 / IEC 60529
Mecha nic al dataDimensions (L x W x D)125 x 125 x 57 mm
Color~RAL 3000 flame r ed
StandardsEuropean standardsEN 54 -11
IP43
8
Building Technologies
77 |
2015-11-06
Page 78
Specifications
Dimensions
8
Building Technologies
009865_m_en_
--
Fire Safety
213.5
73
Ø 119
Ø 115
8.4Dimensions
Radio gateway FDCW221
58
33.4
Radio smoke detector DOW1171 with base DBW1171
Manual call point SMF121 with radio base SMF6120
125
125
78 | 82
57
2015-11-06
Page 79
Specifications
Environmental compatibility and disposal
82
009865_m_en_
--
Fire Safety
8.5Environmental compatibility and disposal
This equipment is manufactured using materials and procedures whic h
comply with current environmental protection standards as best as
possible. More specifically, the following measures have been
undertaken:
●Use of reusable materials
●Use of halogen-free plas tics
●Electronic parts and synthetic materials c an be separated
Larger plastic part s are labeled according to ISO 11469 and ISO 1043.
The plastics can be separated and recycled on this basis.
Electronic parts and batteries must not be disposed of with domestic
waste.
●Take electronic parts and batteries to local collection points or
recycling centers.
●Contact local authorities for more information.
●Observe national requirements for disposing of electronic parts
and batteries.
8
Building Technologies
79 |
2015-11-06
Page 80
Index
Building Technologies
009865_m_en_
--
Fire Safety
Index
A
Application area
Ambient conditions 44
Approvals 74, 76, 77
C
Cable with shield ing 49
CE marking 74, 76, 77
Collective behavior
Degraded mode operation 37
Commissioning
Overview 57
Radio gateway 58
Compatibility 43
Compatibility with control panels 43
Control panel 57
D
Damping
Distance 45
Sample calculation 46
Degraded mode operation
Collective behavior 37
Fire control panel f ailure 37
Delivery status
DOW1171 64
Radio gateway 62
SMF6120 66
Diagnosis levels
Radio gateway 36
Disposal 79
Distance
Damping 45
Download center
URL 9
E
Environmenta l compatibility 79
Environmenta l influences 26, 44
ES
Product version 28
EU directives 74, 76, 77
F
Field strength
Link quality 59
Field strength measurements 47
Fire control panel f ailure
Degraded mode operation 37
Firmware
Update 22, 73
Frequency range 22
I
Impact
Chemicals 44
Moisture 44
Temperature 44
L
Line separator
FDCL221 38
Function 38
Link quality
Field strength 59
List of compatibility 9, 37, 43, 74
M
Magnet
Reed contact 23
Maintenance int ervals 70
MC link 22
O
Original langu age
Source language 8
P
Packaging label
Product version 28
Parameter set s
Radio smoke detector 26
Product label
Product version 28
Protocol 22
80 | 82
2015-11-06
Page 81
Index
82
009865_m_en_
--
Fire Safety
R
Radio base
Status indicat or 41
Radio cell 18
Radio detector
Logging on to the radio gateway 59
Radio module
SPU60xx 22
Radio smoke detector
Parameter sets 26
Smoke sensitivity 26
Status indicat or 41
Radio test set 43
RadioSpy
Tool 29
Recycling 79
Reed contact
Magnet 23
S
Short-circuit
Line separator 38
Smoke sensitivity 26
Source language 8
Standards 75, 76, 77
Status indicat or 41
Field strength 41
T
Tool
RadioSpy 29
Topology 38
Type plate
Product version 28
81 |
Building Technologies
2015-11-06
Page 82
Issued by
Siemens S witzerland Ltd
Building Technologies Division
International Headquarters
Gubel strasse 22
CH-6301 Zug
+41 41-724 24 24
www.siemens.com/buildingtechnologies
Docume nt ID: 0098 65_m_en_--Manual FD20
Edition: 2015-11-06Register 5
Technical specifications and availability s ubject to change without notice.