Siemens FDCIO422 Installation Instructions Manual

SIEMENS
Industry, Inc.
A6V10324662_g_en_US 2016-01-20 Building Technologies Division
Model FDCIO422
Installation Instruction s
Download link
Desigo:
https://www.buildingtechnolog ies.s iemens .com/extranet/ba-sp/
Download link Cerberus PRO:
http://iknow.us009.siemens.net/infolink
INTRODUCTION
The FDCIO422 is used for the connection of up to 2 inde pendent Cl ass A or 4 independent Class B dry N/O configurable contacts. Input lines can be supervised for op en, short and ground fa ult conditions (depending on EOL termination resistor and class configuration).
Inputs can be independently configured via the fire control panel for alarm, trou ble, status or supervisory zones.
The FDCIO422 has 4 programmable outputs with 4 potential-free latching type form A relay contacts for fire control installations.
Status indication per LED for each input and output pl us 1 LED for general stat us of the device. Power su pply via FDnet (supervised power limited).
· Including 4 EOL devices (470 Ω)
· 3 separators to separate the power limited
wiring from the non-power limited. Separators are delivered in 3 different sizes for standard 411/16-inch box, 411/16-inch extension ring and 5-inch box (RANDL).
CAUTION
Electric shock!
High voltages may occur on the terminals. Always use a faceplate and the separator(s).
Figure 1 FDCIO422 cage and car rier
CAUTION
This device is not intended for
applications in explosive environments.
Class A is equivalent to DCLA (Canada) Class B is equivalent to DCLB (Canada)
For complete configuration and commissioning of the FDCIO422 also refer to the user documentation of your panel, especially for the software tool used for configuration.
Figure 2 Removing the cage and the terminal strips fr om the carrier
2
Siemens Industry, Inc.
Building Technologies Division
A6V10324662_g_en_US
2016-01-20
PROGRAMMING INSTRUCTIONS
Refer to Fi gure 3 to locate the opening on the cage cover that allows access to the programming holes which are on the FDCIO422 printed circuit board. To connect the FDCIO4 22 to the DPU or 8720 Programmer/Tes ter, insert t he plug from the DPU/8720 cable provided with the Programmer/Tester into the opening on the front of the FDC IO422. Be sure to insert the locating tab on the plug into the slot for the locating tab as shown in Figure 3. Minimum Firmware revision of the DPU must be 9.00.0004, for 8720 must be
5.02.0002.
NOTICE
To prevent potential damage to the DPU (refer to manual P/N 315-033260) or to the 8720 (refer to manual P/N 315­033260FA) DO NOT connect a FDCIO422 to the DPU or 8720 until the cage is removed from the carrier (Figure 2).
Figure 3 Connecting t he DPU/8720 plug to the cage
Modul Status LED
Flash Color
Condition
Flash Intervals
(Seconds)
Green
*
Normal s upervisory oper ation.
10
Amber
Device is in troubl e
4
Red
Locate
/
Alarm1Input/Output active
10
No Flashes
Device is n ot powere d, or
replace ment is needed.
-*LED can be turned off. Please follow the corresponding
description of the P anel used.
WIRING
Refer to Figure 11. Refer to the appropriate wiring diagram and wire the addressable input/output module accordingly.
Recommended wire size: 18 AWG minimum and 14 AWG maximum
Wire larger than 14 AWG can damage the connector.
(Refer to Figures 2 and 3). Follow the instructions in the DPU manual or 8720 manual to program the FDCIO422 to the desired address. Record the device address on the label located on the front of the module. The FDCIO422 can now be installed and wired to the system.
Figure 4 Wiring multiple switches
INPUT NOTES:
1. There can be any number of normally open dry contact switches.
2. The end of line device must be located at the last switch.
3. Do not wire a normally closed switch across the end of line device in a normally open wiring.
4. Multiple switches: for open wiring supervision only.
INPUT ACTIVE LED,
red
INPUT TROUBLE LED,
yellow
PLUG FROM DPU/8720
PROGRAMMER/TESTER
LOCATING
TAB
OUT A OUT B OUT C OUT D
IN 1 IN 2 IN 3 IN 4
IN 1 trouble IN 2 trouble IN 3 trouble IN 4 trouble
SLOT FOR LOCATING T AB
PROGRA M M I NG HOLES
OUTPUT ACTIVE LED,
red
1)
1)
Command for the activation
of the output received by the
control unit
PROGRAMMABLE SWITCHES (SEE NOTES 1, 2 AND 3)
PROGRAMMABLE SWITCHES (SEE NOTES 1 AND 3)
Rp ½ W470 Ω
EOL
UL 864 CLASS STYLE
BB
UL 864 CLASS STYLE
AD
IN 1-4
IN1/IN2
IN3/IN4
3
Siemens Industry, Inc.
Building Technologies Division
A6V10324662_g_en_US
2016-01-20
Power limite d wir ing
In compliance with NEC Article 760, all power limited fire protective signaling conductors must be separated a minimum of ¼ inch from all of the following items located within an outlet box:
· Electric light
· Power
· Class 1 or non-power limited fire protective
signaling conductors To meet the above requirements, the foll owing guidelines must be observed when ins talling this input/output module.
If non-power limited wiring is not used within this outlet box, then these guidelines do not apply. In that case, be sure to follow standard wiring practices.
Wiring entering outlet box
All power limited wiring must enter the outlet box separately from the electric l ight, power, class 1, or non-power limited fire protection signaling conductors. For the FDCIO422, wiring to the terminal block for li ne and inputs must enter the outlet box separately from the ter minals for outputs. For the output terminals, protection with a fuse is recommended. Refer to Figures 6 and 9.
WIRING AT THE TERMINAL BLOCKS
Minimize the length of wire entering the outlet box.
Figure 6 Power Limited Wiring
Separators
The separators must be used when the relay contacts are connected to non-power limited lines. Mount the correct separator in the box used (411/16-inch box and 5-inch box). If an extension ring is used in connection with a 411/16-inch square box an additional separator has to be mounted in the extension ring. The separators create two compartments to separate the wires as shown in Figure 5.
Figure 5 Mounting the separat ors in the boxes
P
N
N
P
DO NOT USE!
P = POWER LIMITED
N = NON-POWER LIMITED
11
16
1
8
11
16
ADAPTER PLATE
11
16
4 INCH SQ UARE BOX
WITH EXTENSION RING
INCHES DEEP (29.5 in³)
Loading...
+ 5 hidden pages