Siemens FDBZ492-PR Installation Instructions Manual

Global Air Duct Monitoring Housing
Installat ion Instructions Model FDBZ492-PR
INTRODUCTION Model FDBZ492-PR from Siemens Industry, Inc., is a RoHS
compliant air duct monitoring housing containing sampling tubes. When used with a Siemens conventional smoke detector, smoke and combustion products are detected for shutdown of the duct system and/or operation of supplementary equipment as provided by the system control panel. The duct unit supports two sets of Form C alarm contacts, one Form A alarm contact and one Form C trouble contact. The trouble contact supervises the presence of the input power, removal of the detector cover and the removal of the smoke detector head.
TECHNICAL DATA AIR DUCT CONDITIONS
Temperature Range:
With PE-11, 8854, PE-11C: 0
O
C (32OF) - 38OC (100OF)
With OP121: 0
O
C (32OF) - 49OC (120OF)
Altitude Range:
No altitude limitations
Relative Humidity:
Up to 95% RH (non-condensing/non-freezing)
Air Duct Velocity Range:
100-4000 ft/min
Sampling and Exhaust Tube Pressure Differential Range:
Greater than 0.01 and less than 1.2 inches of water column
These airThese air
These airThese air
These air
duct det duct det
duct det duct det
duct det
ectors are designed forectors are designed for
ectors are designed forectors are designed for
ectors are designed for
det det
det det
det
ectect
ectect
ect
ion andion and
ion andion and
ion and
control of products of combustcontrol of products of combust
control of products of combustcontrol of products of combust
control of products of combust
ion in a duct syion in a duct sy
ion in a duct syion in a duct sy
ion in a duct sy
stst
stst
st
em.em.
em.em.
em.
They areThey are
They areThey are
They are
not to be used as a substnot to be used as a subst
not to be used as a substnot to be used as a subst
not to be used as a subst
itit
itit
it
utut
utut
ut
ion forion for
ion forion for
ion for
open area prot open area prot
open area prot open area prot
open area prot
ectect
ectect
ect
ion.ion.
ion.ion.
ion.
DO NODO NO
DO NODO NO
DO NO
T USE air
T USE air
T USE airT USE air
T USE air
duct det duct det
duct det duct det
duct det
ectors with ectors with
ectors with ectors with
ectors with
Alarm Alarm
Alarm Alarm
Alarm
VV
VV
V
erificaterificat
erificaterificat
erificat
ion.ion.
ion.ion.
ion.
ASSEMBLY This detector has a cover tamper (removal) switch. Care should
be taken when installing the cover. Squarely place the cover on the unit to aviod possible damage to the switch.
DO NODO NO
DO NODO NO
DO NO
T SLIDE COT SLIDE CO
T SLIDE COT SLIDE CO
T SLIDE CO
VER INVER IN
VER INVER IN
VER IN
TT
TT
T
O POSITION.O POSITION.
O POSITION.O POSITION.
O POSITION.
Siemens Siemens
Siemens Siemens
Siemens
IndustryIndustry
IndustryIndustry
Industry
,,
,,
,
Inc. Inc.
Inc. Inc.
Inc.
Building Building
Building Building
Building
TT
TT
T
ecec
ecec
ec
hnologies Dihnologies Di
hnologies Dihnologies Di
hnologies Di
visionvision
visionvision
vision
P/N A6V10330327_a_en
P/N A6V10330327_a_en
Siemens Industry, Inc. Building Technologies Division
2
APPLICATION The FDBZ492-PR duct smoke detectors provide early detection
of smoke and products of combustion present in air moving through an HVAC duct supply, return, or both. These devices are designed to prevent the recirculation of smoke in areas by the air handling system’s fans and blowers and may be used with fire alarm systems that shut down complete air handling system in the event of smoke detection.
FF
FF
F
oror
oror
or
the cor the cor
the cor the cor
the cor
rect instrect inst
rect instrect inst
rect inst
allatallat
allatallat
allat
ion of a duct smokion of a duct smok
ion of a duct smokion of a duct smok
ion of a duct smok
e unit please refere unit please refer
e unit please refere unit please refer
e unit please refer
to NFPto NFP
to NFPto NFP
to NFP
A 72 (NatA 72 (Nat
A 72 (NatA 72 (Nat
A 72 (Nat
ional Fire ional Fire
ional Fire ional Fire
ional Fire
Alarm Code),Alarm Code),
Alarm Code),Alarm Code),
Alarm Code),
NFP NFP
NFP NFP
NFP
A 90A (StA 90A (St
A 90A (StA 90A (St
A 90A (St
andardandard
andardandard
andard
forfor
forfor
for
Inst Inst
Inst Inst
Inst
allatallat
allatallat
allat
ion of ion of
ion of ion of
ion of
AirAir
AirAir
Air
Condit Condit
Condit Condit
Condit
ioning and
ioning and
ioning and ioning and
ioning and
VV
VV
V
entent
entent
ent
ilatilat
ilatilat
ilat
ion Sion S
ion Sion S
ion S
yy
yy
y
stst
stst
st
ems),ems),
ems),ems),
ems),
and NFPand NFP
and NFPand NFP
and NFP
A 92A (RA 92A (R
A 92A (RA 92A (R
A 92A (R
ecommended Pecommended P
ecommended Pecommended P
ecommended P
ractract
ractract
ract
ice forice for
ice forice for
ice for
Smok Smok
Smok Smok
Smok
e Controle Control
e Controle Control
e Control
SS
SS
S
yy
yy
y
stst
stst
st
ems).ems).
ems).ems).
ems).
This unit is not intended for open area protection nor should it be used for early warning detection or to replace a regular fire detection system.
OPERATION When the Model FDBZ492-PR is operating, a sample of air is
drawn from the duct and passed through the sampling chamber by means of the input sampling tube. The air sample passes through the smoke detector mounted in the duct housing and is exhausted back into the duct through the outlet tube.
The FDBZ492-PR supports two sets of Form C alarm contacts, one Form A alarm contact and one Form C trouble contact. The trouble contact supervises the presence of the input power, removal of the detector cover and the removal of the smoke detector head.
The FDBZ492-PR contains a green power on LED, red alarm LED and yellow trouble LED which are visible through the housing cover.
The trouble LED is activated when either the housing cover or smoke detector is removed from the unit.
When the trouble LED is activated, the power LED turns off.
A reset/test switch is located on the housing cover and is used to reset the unit after an alarm and the smoke condition is cleared. When not in alarm, the reset/test switch can be used to test that the unit will operate properly when an alarm condition exists.
The trouble contacts will not operate in the event of a smoke alarm. The FDBZ492-PR duct detector will operate from various input voltage sources; namely 24VAC, 24VDC, 115VAC and 230VAC.
Siemens Industry, Inc. Building Technologies Division
3 P/N A6V10330327_a_en
Detector LED The FDBZ492-PR contains an LED indicator (located on the
smoke detector) capable of flashing either one of three distinct colors: green, yellow, or red. During each flash interval, the microprocessor based detector checks the following:
for smoke in its sensing chamber
that its critical smoke sensing electronics are operating.
Based on the results of these checks, the LED indicator flashes as follows:
rotceteD
hsalF
roloCnoitidnoC
hsalF
lavretnI
)sdnoceS(
11-EP
4588
C11-EP
neerG.noitarepoyrosivrepuslamroN7
121POnee
rG.noitarepoyrosivrepuslamroN01
11-EP
4588
C11-EP
wolleY
siro)riaperrogninaelc(ecivresseriuqerrotceteD
.snoit
acificepslatnemnorivnestidnoyebgnitarepo
03-7
121POwolleY.tnemecalpersdeendnaelbuortnisirotceteD5
11-EP
4588
C11-EP
121PO
deRmralA½2
11-EP
4588
C11-EP
sehsalFoN.riaperseriuqerroderewoptonsirotceteD__
121POsehsalFoNroderewop
tonsirotceteDdedeensitnemecalper.__
MOUNTING THE AIR DUCT HOUSING
Location on Duct System
This guideline contains general information on duct smoke detector installation, but does not preclude the NFPA docu­ments listed. Siemens Industry, Inc. assumes no responsibility for improperly installed duct detectors. To determine the correct installation position for an FDBZ492-PR duct smoke detector, the following factors must be considered.
1) A uniform non-turbulent (laminar) airflow between 100 ft/ min. to 5,000 ft/min. must be present in the HVAC duct. To determine duct velocities, examine the engineering specifications that define the expected velocities or use an Alnor model 6000AP velocity meter (or equivalent).
2) To minimize the impact of air turbulence and stratification on performance, a duct smoke detector should be located as far as possible downstream from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In all situations,
P/N A6V10330327_a_en
Siemens Industry, Inc. Building Technologies Division
4
confirmation of velocity and pressure differential within specifications is required.
The pressure differential between the input sampling (high pressure) tube and outlet (low pressure) tube for the FDBZ492-PR smoke duct detector should be greater than
0.01 inches of water and less than 1.2 inches of water.
3) Identify a code compliant location (supply or return side, or both) for the installation of the duct unit that will permit easy access for viewing and serviceability.
4) When installing on the return side, install duct units prior to the air being exhausted from the building or diluted with outside “fresh” air.
5) When installing duct smoke units downstream of filters, fires occurring in the filters will be detected, but if the filters become blocked, insufficient air flow through the duct unit will prevent the correct operation of the duct detector. Duct units installed in the supply air side may monitor upstream equipment and/or filters.
Figure 2 Recommended Locations in Duct Systems
RETURN
AIR
SUPPLY
AIR
AIR DUCT HOUSING
AIR DUCT HOUSING
DAMPER
BLOWER
FILTER
PLENUM
FRESH AIR INTAKE
DAMPER
TYPE A: CLOSED SYSTEM - NO EXHAUST
D D
TYPE B: PROVISION FOR EXHAUSTING
SOME PERCENTAGE OF RETURN AIR
RETURN
AIR
SUPPLY
AIR
AIR DUCT HOUSING
AIR DUCT HOUSING
DAMPER
DAMPER
BLOWER
FILTER
PLENUM
FRESH AIR INTAKE
DAMPER
D D
EXHAUST AIR
OUTPUT
DAMPER
TYPE C: RETURN AIR UNDER POSITIVE PRESSURE
FROM SEPARATE BLOWER
EXHAUST AIR
OUTPUT
DAMPER
RETURN
AIR
SUPPLY
AIR
AIR DUCT HOUSING
RETURN AIR
BLOWER
AIR DUCT
HOUSING
DAMPER
DAMPER
BLOWER
FILTER
PLENUM
FRESH AIR INTAKE
DAMPER
D D
Figure 1 Typical Mounting of Duct Housing
OUTLET
TUBE
INPUT
SAMPLING
TUBE
CENTER
LINE
OF DUCT
C
L
Loading...
+ 8 hidden pages