Siemens FDT181C, FDB181C Product Manual

Page 1
Building Technologies
Fire safety and security products
FDT181C Collective Heat Detector Product Manual
Overview
The heat detector FDT181C is a collective detector. It is used for fire detection inside a building.
Characteristics
– Operation modes: A2 (Rate-of-rise and fixed temperature) – Collective detector, no address setting, polarity free connection – 360° visible alarm indicator – Resistant to environment and interference factors such as humidity, corrosive and
vibration, with immunity against electro-magnetic interference.
Application
– Communication with FC18 controller via FDCI183 transponder, each FDCI183 can
connect max. 32 collective detectors.
– Communication with BC80 controller via BDS161 transponder, each BDS161 can
connect max. 10 collective detectors.
Page 2
2
Building Technologies
A6V10361100_b_en_--
Fire safety and security products 07.2012
Indicator
The detector is provided with an internal alarm indicator to show its operating status.
Status
Indicator
Normal
Off
Alarm
Steady on
Installation
Easy and time-saving mounting
Install the base and finish the wiring during the construction phase.
1. Insert detector into base and turn it clockwisely until positioning pointer on base
align with positioning pointer on detector.(see below)
Uninstallation:
1. Turn it counterclockwisely and pull the detector out of base.
After all the construction is finished, the dust cap must be taken away! No painting!
Dimensions
In:mm(with base)
Detector
Positioning pointer
Base
Positioning pointer
Page 3
3
Building Technologies
A6V10361100_b_en_--
Fire safety and security products 07.2012
Connection diagram
5
1a61b
Connect to collective input module
FDB181C
5
1a61b
FDB181C
5
1a61b
FDB181C
EOL1.5KE20CA
Maintenance
Performance test
Recommendation: – Submit all detectors to an annual visual check. Detectors that are strongly soiled or
mechanically damaged must be replaced. – Long term backup detectors should be stored with plastic bag. – Carry out heat test each year.
Technical data
Operating voltage
10 … 28 VDC
Operating current (quiescent)
0.1 mA
Activation current
60.0 mA
Alarm temperature
61 °C±3
Operating temperature
–10 ... +50 °C
Storage temperature
–20 ... +70 °C
Humidity
96% (40
Color
White, RAL 9010
Protection category GB4208-93
IP40
Details for ordering
Type
Material No.
Part No.
Designation
Weight
FDT181C
S54320-F12-A2
101190983
Collective heat detector
0.065Kg
FDB181C
S54320-F9-A2
101190980
Collective detector base
0.038Kg
Page 4
Beijing Siemens Cerberus Electronics Limited No.1,Fengzhidonglu, Xibeiwang, HaiDian District, Beijing, 100094, China Tel: +10 6476 8806 Fax: +10 6476 8899
© Data and design subject to change without notice.
Doc No.
A6V10361100_b_en_-- Manual FD18
Edition
07.2012
101190971
Loading...