Siemens FDA241, FDA221 Technical Manual

A6V10334410_h_en_--
Building Technologies
2015
FDA241, FDA221
Aspirating Smoke Detector
Technical Manual
-09-29 Control Products and Systems
Legal notice
2
Legal notice
Technical specifications and availability subject to change without notice. © Siemens Switzerland Ltd, 2011
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved.
Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724-2424 www.siemens.com/buildingtechnologies
Edition: 2015-09-29 Document ID: A6V10334410_h_en_--
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
3
Table of contents
1 About this document ......................................................................................7
1.1 App l icabl e document s .......................................................................................9
1.2 Downl oad center ...............................................................................................9
1.3 Techn ical ter ms ..............................................................................................10
1.4 Revision history ..............................................................................................11
2 Safety ............................................................................................................13
2.1 Safety instructions ..........................................................................................13
2.2 Safety regu lations for the method of operation ................................................14
2.3 Standards and direct i ves complied with ..........................................................16
2.4 Release Notes ................................................................................................16
3 Structure and function .................................................................................17
3.1 Overview ........................................................................................................17
3.1.1 Details for orderi ng...........................................................................20
3.1.2 Product version ES ..........................................................................21
3.2 Setup..............................................................................................................22
3.2.1 Front indicator ..................................................................................24
3.2.2 Int er nal indicator ..............................................................................28
3.2.3 Interface card ...................................................................................29
3.2.4 External power unit and batteries .....................................................31
3.3 Pipe system ....................................................................................................32
3.3.1 Water trap in the pi pe system ...........................................................33
3.4 Parameter settings..........................................................................................34
3.5 Function .........................................................................................................34
3.5.1 Function during operat ion on detec tor line ........................................34
3.5.1.1 Danger levels ...................................................................................35
3.5.1.2 Interface to service devices ..............................................................35
3.5.1.3 Test m ode........................................................................................36
3.5.1.4 Renov ation mode .............................................................................36
3.5.1.5 Line separ ator ..................................................................................36
3.5.1.6 Line tester FDUL221 ........................................................................36
3.5.2 Standalone oper ation .......................................................................37
3.6 Accessories ....................................................................................................37
3.6.1 Communication transponder FDCC221S..........................................37
3.6.2 Power supply kit A (70 W) FP120-Z1................................................37
3.6.3 Battery FA2003-A1 (12 V, 7 Ah, VdS) ..............................................38
3.6.4 Battery FA2004-A1 (12 V, 12 Ah, VdS).............................................38
3.6.5 Battery FA2005-A1 (12 V, 17 Ah, VdS).............................................38
4 Planning ........................................................................................................39
4.1 Compatibility ...................................................................................................39
4.2 Operating modes ............................................................................................39
4.2.1 Parameter Sets ................................................................................40
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
4
4.3 Power supply .................................................................................................. 41
4.4 Determining the batteries ................................................................................ 42
4.5 Limit s to planning............................................................................................ 43
4.6 Environmental influences ................................................................................ 44
4.7 Blowing-out unit .............................................................................................. 44
5 Mounting / Installation .................................................................................. 45
5.1 Prep arat or y work ............................................................................................ 45
5.1.1 Opening and clos ing the housing cover
when the power supply is switched off.............................................. 45
5.1.2 Opening and clos ing the housing cover
when the power supply is switched on.............................................. 46
5.1.3 Removing and installing the ho usi n g co v er
when the power supply is switched off.............................................. 48
5.1.4 Removing and installing the housing cover
when the power supply is switched on.............................................. 51
5.1.5 Installation position and space requir ements .................................... 55
5.2 Mounting ........................................................................................................ 58
5.2.1 Ad apting the front indicator to the installation pos i tion ...................... 58
5.2.2 Fastening on a level substructure ..................................................... 59
5.2.3 Connecti ng the pipe s ys tem to the aspir ating smok e detector........... 61
5.2.3.1 Return lin e ....................................................................................... 61
5.2.4 Installi ng communication transponder FDCC2 21S............................ 62
5.3 Installation ...................................................................................................... 64
5.3.1 Connecting the external power unit .................................................. 64
5.3.2 'Smoke 4…20 mA' analog output ..................................................... 66
5.3.3 Configurable 'GPI' input ................................................................... 68
5.3.4 'Purge' relay output for blowing out (with FDA241 only) .................... 68
5.3.5 'Dust' relay output for dust value (with FDA241 only) ........................ 69
5.3.6 'Faul t' relay output for er r or messages.............................................. 69
5.3.7 'Inspect' relay output for early warning (FDA241 only) ...................... 69
5.3.8 'PreAlarm ' relay output for pre-alarm ................................................ 70
5.3.9 'Fire 1' rel ay output for fire al ar m 1 ................................................... 70
5.3.10 'Fire 2' rel ay output for fire al ar m 2 ................................................... 70
5.3.11 Connecti ng to th e detec tor line with the FD CC221S ......................... 71
5.3.12 Connecti on to input/ output module ................................................... 72
6 Configuration ................................................................................................ 77
7 Commissioning............................................................................................. 79
7.1 Oper ation on addressed detec tor line (FDnet/C-NET) ..................................... 79
7.2 Standalone application ................................................................................... 82
7.3 Function al test ing of the syst em ...................................................................... 83
7.3.1 Function al test ing of the syst em with an add r essed detec tor line
(FDnet/C-NET) ................................................................................ 83
7.3.2 Function al test ing of the syst em with the stand alone op tion .............. 84
7.4 Testing the ind i cation of fault s on the front indi cator/ inter nal indic ator.............. 86
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
5
7.5 Testing the airflow...........................................................................................87
7.6 Testing the response time ...............................................................................88
7.7 Checking and testing the power supply units ...................................................89
7.8 LE D and buzzer test .......................................................................................89
7.9 Normalization .................................................................................................90
8 Maintenance / Repair ....................................................................................93
8.1 Visual inspect ion .............................................................................................93
8.2 Checking the pi pe sy s tem ...............................................................................93
8.3 Status quer ies with servic e devic es .................................................................93
8.3.1 Communi cation with the aspirating smoke detector ..........................94
8.4 Resetting status displays and relay outputs (standalone option) ......................96
8.5 Perfo r mance check .........................................................................................97
8.6 Cleaning .........................................................................................................97
8.7 Carrying out water trap maintenance...............................................................97
8.8 Maintenance and cleaning i ntervals ................................................................99
8.9 Event memory .............................................................................................. 100
8.10 Modification memory ..................................................................................... 100
8.11 Faults ........................................................................................................... 101
8.11.1 Table of fau lts ................................................................................ 102
8.11.2 Fault an alysis ................................................................................. 104
9 Specifications ............................................................................................. 105
9.1 Techn ical d ata for FDA241, F DA 221 ............................................................. 105
9.2 Dimensions................................................................................................... 108
9.3 Environmental compatibility and disposal ...................................................... 108
10 Annex .......................................................................................................... 109
10.1 Fault in dication ............................................................................................. 109
Index ..................................................................................................................... 110
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
6
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
About this document
1
Applicable documents
7
Target group
Activity
Qualification

1 About this document

Goal and purpose
This document contains all the information you'll need about the following aspirating smoke detectors:
FDA241 FDA221
Following the instructions consistently will ensure that the product can be used safely and without any problems.
Intended use
Aspirating smoke detectors FDA241 and FDA221 may only be used for fire detection and fire control purposes.
Target groups
The information in this document is intended for the following target groups:
Product Manager Is responsible for information passing
between the manufacturer and regional company.
Coordinates the flow of information
between the individual groups of people involved in a project.
Project Manager Coordinates the deployment of all
persons and resources involved in the project according to schedule.
Provides the information required to run
the project.
Project engineer Sets parameters for product depending
on specific national and/or customer requirements.
Checks operability and approves the
product for commissioning at the place of installation.
Is responsible for trouble-shooting.
Installation personnel Assembles and installs the product
components at the place of installation.
Carries out a performance check
following installation.
Commissioning personnel Configure the product at the place of
installation according to customer­specific requirements.
Check the product operability and
release the product for use by the operator.
Searches for and corrects malfunctions.
Maintenance personnel Carries out all maintenance work.
Checks that the products are in perfect
working order.
Searches for and corrects malfunctions.
Has obtained suitable specialist training
for the function and for the products.
Has attended the training courses for
Product Managers.
Has obtained suitable specialist training
for the function and for the products.
Has attended the training courses for
Project Managers.
Has obtained suitable specialist training
for the function and for the products.
Has attended the training courses for
Product Engineer.
Has received specialist training in the
area of building installation technology or electrical installations.
Has obtained suitable specialist training
for the function and for the products.
Has attended the training courses for
commissioning personnel.
Has obtained suitable specialist training
for the function and for the products.
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
1
About this document
Applicable documents
8
Source language and reference document
ID code
Examples
on symbols and for identification between steps
The 'i' symbol identifies supplementary information and tips for an easier way of
The source/original language of this document is German (de). The reference version of this document is the international version in English.
The international version is not localized.
Document identification
The document ID is structured as follows:
ID_ModificationIndex_Language_COUNTRY
-- = multilingual or international
A6V10215123_a_de_DE A6V10215123_a_en_-­A6V10315123_a_--_--
Date format
The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD).
Conventions for text marking
Markups Special markups are shown in this document as follows:
Requirement for a behavior instruction
1.
2.
Version, option, or detailed information for a behavior instruction
Intermediate result of a behavior instruction
End result of a behavior instruction
Numbered lists and behavior instructions with an operation
Behavior instruction with at least two operation sequences
sequence
[➙ X] Reference to a page number
'Text' Quotation, reproduced identically
<Key> Identification of keys
> In addition to relati
in a sequence, e.g., 'Menu bar' > 'Help' > 'Help topics'
Text Identification of a glossary entry
Supplementary information and tips
working.
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
About this document
1
Applicable documents
9

1.1 Applicable documents

Document ID
Title
You will also find information about search variants and links to mobile
001508 Guidelines Connection factors, line resistances and
capacitances for fire detection systems collective, AnalogPLUS, interactive, FDnet
007023 Technical manual Input module, input/output module FDCI222,
FDCIO222, FDCIO224
007227 Technical manual Detector exchanger and tester FDUD292
008250 Technical Manual Line tester FDUL221
008331 List of compatibility (for 'Sinteso™' product line)
009052 FS20 Fire detection system - Commissioning, Maintenance,
Troubleshooting
009078 FS20 Fire detection system - Configuration
009718 Technical Manual Intelligent detector tester FDUD293
A6V10210416 FS720 Fire detection system - Commissioning, Maintenance,
Troubleshooting
A6V10210424 FS720 Fire detection system - Configuration
A6V10229261 List of compatibility (for 'Cerberus™ PRO' product line)
A6V10331032 Data sheet Aspirating Smoke Detectors FDA221, FDA241
A6V10332759 Installation, Operation Manual, Configuration 'ASD
Configuration Tool FXS2051'
A6V10334435 Planning, Installation ASD Pipe system
A6V10340094 User Manual 'ASD Asyst Tool FXS2055'
A6V10344957 Installation Manual for 'FXS2055 ASD Asyst Tool'
A6V10345654 Installiotion, Mounting Aspirating Smoke Detectors FDA241,
FDA221
A6V10348930 Driver Installer and Uninstaller for TUSB3410 based devices
A6V10367668 Open-Source Software (OSS) Licenses ASD
A6V10387338 Open-Source Software (OSS) Licenses ASD
A6V10388922 Open-Source Software (OSS) Licenses TUSB3410
A6V10393194 Technical manual Power supply kit A 70 W FP120-Z1
A6V10448753 Data sheet Remote test system for aspirating smoke detectors
(ASD)

1.2 Download center

You can download various types of documents, such as data sheets, installation instructions, and license texts via the following Internet address:
http://siemens.com/bt/download
Enter the document ID in the 'Find by keyword' input box.
applications (apps) for various systems on the home page.
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
1
About this document
Technical terms
10

1.3 Technical terms

Term
Explanation
P
ABS Acrylonitrile-butadiene-styrene (plastic)
ASD Aspirating smoke detector
FDnet/C-NET Addressed detector line
GPI General Purpose Input, connection for an external switch
MC link Maintenance and commissioning link
n.c. normally closed (standard state of connection is closed)
n.o. normally open (standard state of connection is open)
PC Personal computer
PC Polycarbonate (plastic)
PSU
SRC1 Optical detection channel in the FDnet/C-NET
SRC3 Channel for monitoring the airflow in the FDnet/C-NET
ower supply unit
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
About this document
1
Revision history
11

1.4 Revision history

The first edition of a language version or a country variant may, for example, be
Modification index
Edition date
Brief description
New firmware version 3.10 taken into account New chapters:
Amended chapters:
The language versions and country variants produced by a local company have
me modification index as the corresponding reference document. They are
The reference document's version applies to all languages into which the reference document is translated.
version 'd' instead of 'a' if the reference document is already this version.
The table below shows this document's revision history:
h 2015-09-29
'Connection to input/output module'
'About this document' ('Intended use' section added); 'Applicable documents'; 'Operation on addressed detector line' ('Selection of settings' > 'Smoke alarm delay time'); 'Testing the airflow' ('Large deviations in the airflow'); 'Power supply'; 'Normalization'; 'Table of faults'; ' 'Dust' relay output for dust value (FDA241 only)'; 'Technical data FDA241, FDA221'
g 2015-03-03 Data sheet 'Remote test system for aspirating smoke detectors' added in
'Applicable documents' chapter. 'Technical data FDA241, FDA221' chapter amended and supplemented. Power supply kit FP120-Z1 added. Battery FA2003­A1 added. Detector can also be installed horizontally. Editorial changes
f 2014-06-25 Data sheet updated in 'Applicable documents' chapter.
Editorial changes New chapter with reference to download center added
e 2013-07-02 Change of function when opening housing cover.
d 2012-11-02 Planning limits adapted. Additional references to license document and
commissioning on the detector line. Information added about commissioning and maintenance. Change to date format in line with ISO 8601 specifications (yyyy-mm-dd format).
c 2012-03 Document adapted to the following type designation: communication transponder
FDCC221S. Additional information on blowing-out unit. Technical data and mounting notes added. Additional notes on test mode and about commissioning on the detector line.
b 2011-12 Revised version
a 2011-10 First edition
the sa not however included in the table below.
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
1
About this document
Revision history
12
The table below shows the published language versions and country variants with
Modification index
en_--
de_--
fr_--
it_--
es_--
the corresponding modification index:
h X X X X X
g X X X X X
f X
e X X X X X
d X X
c - X
b - X
a X X
X = published – = no publication with this modification index
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
Safety
2
Safety instructions
13
risks of injury
Signal word
Danger level
DANGER
will result directly in death or
serious injury
WARNING
may result in death or serious
injury
CAUTION
slight to
moderately serious injury

2 Safety

2.1 Safety instructions

The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements:
Symbol for danger Signal word Nature and origin of the danger Consequences if the danger occurs Measures or prohibitions for danger avoidance
Symbol for danger
This is the symbol for danger. It warns of Follow all measures identified by this symbol to avoid injury or death.
Additional danger symbols These symbols indicate general dangers, the type of danger or possible
consequences, measures and prohibitions, examples of which are shown in the following table:
General danger
Explosive atmosphere
.
NOTICE
Voltage/electric shock
Battery
Laser light
Heat
Signal word
The signal word classifies the danger as defined in the following table:
DANGER identifies a dangerous situation, which
if you do not avoid this situation.
WARNING identifies a dangerous situation, which
if you do not avoid this situation.
CAUTION identifies a dangerous situation, which could result in
if you do not avoid this situation.
NOTICE
identifies possible damage to property that may result from non-
observance.
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
2
Safety
Safety regulations for the method of operation
14
How risk of injury is presented
WARNING
Nature and origin of the danger
Measures / prohibitions for danger avoidance
NOTICE
Nature and origin of the danger
Measures / prohibitions for danger avoidance
WARNING
Electrical voltage
regulations.
Information about the risk of injury is shown as follows:
Consequences if the danger occurs
How possible damage to property is presented
Information about possible damage to property is shown as follows:
Consequences if the danger occurs

2.2 Safety regulations for the method of operation

National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation, operation or disposal of the product apply at the place of operation, then these must also be taken into account together with the safety regulations in the product documentation.
Electrical installations
Electric shock
Work on electrical installations may only be carried out by qualified electricians or by instructed persons working under the guidance and supervision of a qualified electrician, in accordance with the electrotechnical
Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
Lock volt-free areas to prevent them being switched back on again by mistake. Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
Produce earthing as stated in local safety regulations.
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
Safety
2
Safety regulations for the method of operation
15
Mounting, installation, commissioning and maintenance
If you require tools such as a ladder, these must be safe and must be intended
for the work in hand.
When starting the fire control panel ensure that unstable conditions cannot
arise.
Ensure that all points listed in the 'Testing the product operability' section below
are observed.
You may only set controls to normal function when the product operability has
been completely tested and the system has been handed over to the customer.
Testing the product operability
Prevent the remote transmission from triggering erroneously. If testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
The activation of fire control installations for test purposes must not cause
injury to anyone or damage to the building installations. The following instructions must be observed:
– Use the correct potential for activation; this is generally the potential of the
building installation. – Only check controls up to the interface (relay with blocking option). – Make sure that only the controls to be tested are activated.
Inform people before testing the alarm devices and allow for possible panic
responses.
Inform people about any noise or mist which may be produced. Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system design and the products
Modifications to the system and to individual products may lead to faults, malfunctioning and safety risks. Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions.
Modules and spare parts
Components and spare parts must comply with the technical specifications
defined by Siemens. Only use products specified or recommended by Siemens.
Only use fuses with the specified fuse characteristics. Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by Siemens.
Batteries must be disposed of in an environmentally friendly manner. Observe
national guidelines and regulations.
Disregard of the safety regulations
Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation. This applies in particular to the following damage:
Personal injuries or damage to property caused by improper use and incorrect
application
Personal injuries or damage to property caused by disregarding safety
instructions in the documentation or on the product
Personal injury or damage to property caused by poor maintenance or lack of
maintenance
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
2
Safety
Standards and directives complied with
16

2.3 Standards and directives complied with

WARNING
Limited or non-existent fire detection
detection installation.
NOTICE
Incorrect planning and/or configuration
Additional expense resulting from necessary new planning and/or configuration.
detection installation.
A list of the standards and directives complied with is available from your Siemens contact.

2.4 Release Notes

Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.
Personal injury and damage to property in the event of a fire.
Read the 'Release Notes' before you plan and/or configure a fire detection installation.
Read the 'Release Notes' before you carry out a firmware update to a fire
Important standards and specifications are not satisfied. Fire detection installation is not accepted for commissioning.
Read the 'Release Notes' before you plan and/or configure a fire detection installation.
Read the 'Release Notes' before you carry out a firmware update to a fire
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
Structure and function
3
Overview
17

3 Structure and function

3.1 Overview

Aspirating smoke detectors are used for early detection of smoke-generating fires in rooms and equipment. They are especially suited to applications in which point detectors are pushed to their limits, cannot be used or can only be used with restrictions.
The aspirating smoke detector continually takes air from the monitored room using a connected pipe system with defined aspirating holes. The air is supplied to the detection chamber and is analyzed for smoke particles using the detector installed there. The sensitivity of the detector can be adjusted.
The position and size of the aspirating holes are calculated with the 'FXS2055 ASD Asyst Tool' software. The calculation ensures that the air passes from the aspirating hole to the detector in the time specified and with the required calculated sensitivity.
Examples of application
Cavities such as false ceilings or false floors Rooms with polluted air, in which the pollution has impaired the performance of
optical point detectors
Clean rooms Rooms the height of which is greater than that permitted for point detectors Rooms with electromagnetic fields which influence the function of point
detectors
Large rooms up to 800 m² Separate monitoring of control cabinets and electronics cabinets Data centers Telecommunication centers Mounting lines Cable tunnels Conveyor belts
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
3
Structure and function
Overview
18
The aspirating smoke detector can be operated on an FDnet/C-NET detector line.
1
7
2
3
4
4
56
8
4
8
8
8
When the aspirating smoke detector is operated on a FDnet/C-NET detector line,
For this purpose, communication transponder FDCC221S is also required:
Aspirating smoke detector on addressed detector line
1
Aspirating smoke detector with communication transponder FDCC221S
2 External power unit with batte ry 6 Fire control panel FC20xx /FC72x
3 Blowin g-out unit (optional) 7 FDnet/C-NET detector line
4 Pipe system 8 FDnet/C-NET peripheral device
the relay outputs are inactive.
5 Return line (optional)
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
Structure and function
3
Overview
19
Alternatively, various external devices can be connected to the aspirating smoke
1
7
2
3
4
4
5
6
4
8
9
10
detector in standalone operation [➙ 37]:
Aspirating smoke detector in standalone operation
1 Aspirating s moke det ector 6
2 External power unit with batte ry 7 External control/indicator (optional)
3 Blow ing-out un it (optional)
4 Pipe system
5 Return line (optional)
PC with 'FXS2051 ASD Configuration Tool' software
8 External button (optional)
9
External acoust ic signa l equipment (optional)
10
External optical signa l equipment (optional)
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
3
Structure and function
Overview
20
Properties
Type
Order no.
Designation
Patented technology Can be used with Siemens FDnet/C-NET loop (with optional FDCC221S
installed)
Extended optical detection thanks to dual wavelengths (blue and infrared) Configuration via USB or FDCC221S (option) 'Out-of-the-box' installation and commissioning Early detection of a wider spectrum of particle sizes in the air Software 'FXS2055 ASD Asyst Tool' and pipe configuration supported Programmable alarm thresholds Unique dust-resistant detection chamber Intuitive front indicator for airflow and smoke value Normalization of the smoke value Normalization of the airflow Access to service functions Different event protocols Offline/online configuration supported FDA241, monitoring area of up to 800 m² FDA221, monitoring area of up to 500 m² 4…20 mA output Cleaning function (with FDA241 only) Firmware can be updated locally

3.1.1 Details for ordering

FDA241 S54333-F17-A1 Aspirating smoke detector (8H)
FDA221 S54333-F15-A1 Aspirating smoke detector (5S)
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
Structure and function
3
Overview
21

3.1.2 Product version ES

ES
ES
04
Depending on the product and various approvals, the product labels may differ in
The product version ES provides the technical status of a device in terms of software and hardware. The product version is provided as a two-digit number.
You will find the details of your device's product version:
On the packaging label On the product label or the type plate
Product version on the packaging label
Details of the product version can be found directly on the packaging label in the barcode:
Example of a packaging label with details of the product version
Product version on the product label and the type plate
Details of the product version can be found after the device order number:
Example of a product label with details of the product version
terms of the information type and layout. Look for your device's order number on the product label. You will find the product version after the order number.
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
3
Structure and function
Setup
22

3.2 Setup

Position
Part
Function
Components
Overview
1 Housing cover -
2 Front indicator Operating indicators and fault indicators,
connected to the interface card by a cable
3 Opening Cable entry
4 Back box Wall mounting with screws
5 Interface card Connections to external devices and signal
equipment. Depending on the version of the aspirating smoke detector, not all connections are available. If the aspirating smoke detector is operated on a FDnet/C-NET detector line, certain outputs are not active. See the chapter 'Function [➙ 34]'.
6 Air inlet Pipe system connection
7 Detection chamber Smoke sensor with flow monitoring
8 Internal indicator Alarm indicator, activate normalization
9 Aspiration unit Fan for aspirating the air.
10 Type plate Relevant identification and detector data
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
Structure and function
3
Setup
23
Position
Part
Function
11 Mini USB connection for
PC
Interface for configuring the aspirating smoke detector using the 'FXS2051 ASD Configuration Tool' software
12 Air outlet Air outlet in the room or return line connection
13 Cables Connection to the front indicator
14 Contact pins Connection for communication transponder
FDCC221S
15 Buzzer Signal tone output
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
3
Structure and function
Setup
24

3.2.1 Front indicator

The front indicator can be rotated 180° in the housing cover if necessary. See
The front indicator on the housing cover provides a quick overview of the aspirating smoke detector's current status using LED indicators. The buzzer can be switched off and a function test for LEDs and buzzers activated using a button.
Front indicator FDA241
Front indicator FDA221
'Adapting the front indicator to the installation position [➙ 58]'.
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
Structure and function
3
Setup
25
Display
Designation
Function
Operating indication The green LED lights up permanently:
When the power supply is con nected
1
Blowin g-out indicator
The yellow LED lights up permanently:
When the blowing-out process is activated
The yellow LED flashes:
Once the blowing-out process has been act ivated until the normal operating status
is achieved (lasts up to 2 minutes)
Indication of faults The yellow LED flashes:
When there is a technical fa ult
Airflow indicator The current airf low is indicated by an LED in the airflow indicator (b ar graph ind icator).
When the housing cover is opened
a) LED yellow
b) LED green
If a yellow LED lights up, the airflow has increased.
As the deviation increases, the light moves upwards.
If the topmost LED flashes, the airf low has exceeded the upper limit an d the a larm de lay time has expired.
Example: There may be a leak in the pipe system.
One of the green LEDs lights up.
The airflow is normal.
c) LED yellow
If a yellow LED lights up, the airflow is too low.
As the deviation increases, the indicator moves downwards.
If the bottommost LED flashes, the airflow has fallen below the lower limit and the alarm delay time has expired.
Example: Some of the as pirating holes in the pipe sy stem may be blocked.
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
3
Structure and function
Setup
26
Alarming indicator
Number of LEDs lighting up and their meaning
The aspirating smoke detector's current alarm status is ind icated by LEDs in the s moke indicator (bar grap h indicator).
Yellow LED
Green LED
Smoke indicator
Alarm level
1
Alarm level
Inspect
1…5 'Smoke low'
6…9 ' Inspect'
10…12 'Prealarm'
13…14 'Fire 1'
15 'Fire 2'
The green LED lights up if the level of smoke is minimal.
At the same time, the bottommost 1 to 5 yellow LEDs may indicate minor dev iations.
The red LED lights up at the 'I nspect' alarm lev e l.
At the same time, the bottommost 6 to 9 yellow LEDs light up.
Red LED
Red LED
Red LED
Red LED
Alarm level
Prealarm
Alarm level
Fire 1
Ala rm le vel
Fire 2
The red LED lights up at the 'Prealarm' alarm level.
At the same time, the bottommost 10 to 12 yellow LEDs light up.
The red LED lights up at the ' Fire 1' a lar m level.
At the same time, the bottommost 13 to 14 yellow LEDs light up.
The red LED lights up at the ' Fire 2' a lar m leve l.
At the same time, the 15 yellow LEDs light up.
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
Structure and function
3
Setup
27
Button
Actio n
Consequence
LED status
Meaning
Press the button br ief ly The buzzer sw itches off
Press and hold the button
A signal test/fault analysis is activated.
(approx. 5 s)
When the housing cover is open , the button takes on the function of the reset button and the alarm outputs are deactivated. See t he chapter 'Int ernal indicato r [➙ 28]'.
Press the button briefly The buzzer sw itche s off.
The relay outputs are deactivated.
The 4…20 mA analog out put re mains on fault.
Dust indicato r 1 Flashing becomes more frequent as the dust d ensity increases.
Off Normal operation
Slow flashing Low dust v alue
Fast flashing Medium dust va lue
Permanently on High dust value
1
FDA241 only
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
3
Structure and function
Setup
28

3.2.2 Internal indicator

Indication
Designation
Function
Button
Designation
Function
The 'Normalize Flow' and 'Normalize Smoke' buttons can only be actuated using
When the housing cover [➙ 46] is open, the internal indicator is accessible. The internal indicator performs the following functions:
Status display for airflow, smoke value, and alarm using 3 LEDs Activate or stop normalization of the airflow using a button Activate or stop normalization of the smoke value using a button Reset self-retaining status displays and relay outputs using a button
Internal indicator
Flow ok The green LED flashes when the airflow is normal.
Smoke ok The green LED flashes when the smoke value is low.
Alarm The red LED flashes during an alarm.
Normalize Flow Button for activating or stopping normalization of the
Normalize Smoke Button for activating or stopping normalization of the
airflow.
smoke value.
Reset Button for resetting the self-retaining status displays
and relay outputs. The current detector status is reset.
a suitable, thin tool, e.g. a pen or a paper clip.
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
Structure and function
3
Setup
29

3.2.3 Interface card

The interface card in the back box is accessible once the housing cover has been removed.
You can do the following on the interface card:
Establish the cable connection to the front display in the housing cover Connect the external power supply for the aspirating smoke detector Control various external functions via relays Install communication transponder FDCC221S (accessory) Establish a connection to a PC using the mini USB interface
The graphic below provides an overview of the connections together with the associated symbols and labels.
Building Tec hnologies A6V10334410_h_en_ --
Fire Safety 2015-09-29
3
Structure and function
Setup
30
The connection terminals are combined in functional units.
'Smoke 4…20 mA'
'GPI'
'Purge'
'Dust
'Fault'
'Inspect'
'Prealarm'
'Fire 1'
'Fire 2'
'FDNet
'USB'
Power supply
You will find details on page [➙ 64].
analog output. You will find details on p age [➙ 66].
Configurable
You will find details on page [➙ 68].
relay output f or blowing out (with FDA24 1 only)
You will find details on page [➙ 68].
' relay output for dust value (with FDA24 1 only). You w ill find details on page [➙ 69].
relay output for error messages. You will find details on page [➙ 69].
relay output for Ins pect (with FDA241 only)
You will find details on page [➙ 69].
You will find details on page [➙ 70].
relay output for Fire 1
You will find details on page [➙ 70].
relay output for Fire 2
You will find details on page [➙ 70].
' relay connection w ith FDCC 221S (optional)
You will find details on page [➙ 66].
Mini USB port for connecting to a PC
You will find details on page [➙ 94].
input
relay output f or Prealarm
Building Tec hnologies A6V10334410_h_en_--
Fire Safety 2015 -09-29
See also
Communication transponder FDCC221S [➙ 37]  External power unit and batteries [➙ 31]  Removing and installing the housing cover when the power
supply is switched on [➙ 51]
Loading...
+ 84 hidden pages