A6V10315038_f_e n_-2016-02-25Siemens Industry, Inc.
Page 2
Legal notice
Building Technologies
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
Legal notice
Technical specifications and availability subject to change without notice.
Transmitt al, reproduction, dissemination and/ or editing of this document as well as
utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of damages. All
rights created by patent grant or registration of a utilit y model or design pat ent are
reserved.
Issued by:
Siemens Industry, Inc.
Building Technologies Div ision
8 Fernwood Road
Florham Park, NJ 07932
Tel. +1 973-593-2600
www.sbt.siemens.com/FIS
2.12 Technical data .................................................................................................42
4 | 46
3FCC Sta te men t ........................................................................................ 4 5
Page 5
Periphery board (250p) FCI2016
Description
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
1Periphery board (250p) FCI2016
1
1.1Description
The periphery board (250p) FCI2016 is used for fire control panels and voice alarm fire
control panels with max. 252 device addresses. The purpose of the periphery board is
to provide means for supervising and controlling various peripheral devices, such as
detectors and not ification devices, and providing power for the entire panel. There is a
detector core on the periphery board, that is isolated from the rest of t he periphery
board. An auxiliary output circuit (1.5 A, 24 V) provides power t o remote devices or
internal modules. The integrated NAC circuit (NAC 1) provides up to 3 A of power for
max. 1 class A circuit or 3 A for each of max. 2 class B circuits. The periphery board
has expansion capabilit ies for leased line / city tie operation, a releasing circuit with 2
zones, and an additional NAC circuit (NAC 2).
The periphery board has a battery charger and battery switchover circuit for AC fail or
brownout. The batter y charger is capable of charging up to 100 Ah batteries.
Building Technologies
5 |
Page 6
Periphery board (250p) FCI2016
Description
1
Building Technologies
A6V10315038_f_en_
--
Siemens Industry,
Inc.
2016-02-25
Properties
●Two different power supplies can be connected:
–Power supply (170 W ) FP2011 only for fire control panels with a m aximum load
of 6.5 A
–Power supply (300 W) FP2012 for fire control panels and voice alarm fire
control panels with a max imum loading of 11.5 A
–Power supply (300 W ) FP2012 for voice alarm fire control panels in housings
(3HU) with a maximum loading of 22 A
●Battery charger capable of charging up to 100 Ah batteries at a maximum of 6 A.
●Power supply (300W) FP2012 must be used for batteries of more than 33 Ah.
●Power supply (170W) FP2011 must be used for batteries of 33 Ah or less
●Ground fault s detected at <1 kΩ to ground
●Ground fault detection for all circuits except the 2 detector c ircuits handled by PMI.
Each detector core has its own ground fault and supervision circuit.
●One integrat ed FDnet/C-NET circuit card for circuits 1 and 2 and EMC surge
protection for four style 4 or two style 6 circuits.
●Maximum of 252 device addresses can be controlled per integrated FDnet/C-NET
circuit card.
●Three relay outputs and one user programmable relay output for common alarm,
common trouble, common supervision, and user programmable.
●The auxiliary output is a regulated DC 24 V output with a max imum of 1.5 A.
●Degraded alarm and trouble m ode functions when either or both CPUs for the
periphery board or PMI are compromised.
●Integrat ed NAC circuit, specified for DC 24 V, configured for either one class A
(style Z) or two class B (style Y) circuits, with a maximum of 3 A for one class A or
max. 3 A for each of the two class B circuits. NACs have integrated
synchronization protocol for audible or visual notification appliances.
–All NAC circuits are supervised and protected for overcurrent and direct short-
circuited output .
●Two slots for optional extensions, one of which is for NAC module (1A/2B) or
releasing module (XCI2001):
–NAC module (1A/2B) FCI2001 for one additional class A circuit or two class B
circuits (sam e data as integrated NAC circuit) (P/N S54400-A54-A1). T he
module connects to X901.
–Releasing module (XCI2001) (P/N S54400-A69-A1) The module connects to
X901.
–Leased line or city t ie module FCI2020 (P/N 54400-A57-A1). The module
connects to X902.
●Additional periph eral data bus connection (X202) for LED or DACT modules.
●Main CPU and detector core CPUs capable of being updated in the f ield through
the PMI.
6 | 46
Page 7
Periphery board (250p) FCI2016
Installation
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
1.2Installation
The chapter describes how to install periphery board (250p) FCI2016 in the fire control
panel and the voice alarm fire control panel.
1
Figure 1: Installi ng the periphery boar d (250p)
1Threaded standoffs on back box
212x fixing screw
3Periphery board (250p)
w The back box is installed.
w The openings for passing through cables have been broken out.
w The power cable is fed through and is disconnected from the power supply.
w The batteries are not installed or connected.
1. Install the periphery board (500p) (3) on the threaded sleeves (1) of the back box
with the 12 fixing screws (2).
2. Wire the periphery board (250p) according to the pin assignments in the following
chapters.
3. Set the jumpers.
4. Re-install any modules that you m ay have had to remove.
Building Technologies
7 |
Page 8
Periphery board (250p) FCI2016
Views
1
Building Technologies
A6V10315038_f_en_
--
Siemens Industry,
Inc.
2016-02-25
X801
X901
F301
X303
X304
X301
X202
X1101
X1402
X305
1
1111
1
1
X601
X603
X602
X605
X606
X604
F302
1.3Views
X1401
H1301
X1302
S100
X403
X902
X204
11
1
1
1
3
1
16
7
12
8 | 46
X1001
1
11
X201
Figure 2: Printed circuit board view for FCI2016
X302
3
1
Page 9
Periphery board (250p) FCI2016
Views
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
ElementDes.Function
FusesF30130 A fuse for batter y
F302Fuse 20 A for voice alarm DC 24 V output
IndicatorsH1301Status display for circuit card 1 (circuits 1 and 2)
Adjustment elementsS100Reset key for periphery processor (without circuits)
JumpersX403Degraded mode ALARM SILENCEABLE/NON SILENCEABLE
X602Degraded mode ENABLE/DISABLE NAC 1 class A or NAC 1-1 class B
X603Degraded mode ENABLE/DISABLE NAC 1-2 class B
X604NAC 1 class A/B selection
X605NAC 1 class A/B selection
X606NAC 1 class A/B selection
X305Power supply 2 ON/OFF
ConnectorX201Peripheral data bus to the PMI & mainboard
X202Peripheral data bus output
1
X204Future extension (not used)
X301Connector for power supply 1 (PS1)
X302Connector plug for power supply 2 (PS2) in housing (3HU)
X303Battery connection
X304
DC 24 V connection to Card Cage VCA2002 for feed to the voice alarm
modules and associated peripher als
X601NAC1 output
X801BELL follower input
X901NAC 2 extension or releasing module
X902Leased line / city tie module
X1001Output DC 24 V AUX
X1101Plug bloc k for relay connections
X1302F or future application
X1401Det ector circuit circuit card 1, circuit 1
X1402Det ector circuit circuit card 1, circuit 2
Building Technologies
9 |
Page 10
Periphery bo
ard (250p) FCI2016
Configuration input power and battery
1
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry,
Inc.
2016-02-25
1.4Configuration input power and battery
The periphery board has jum pers that are used to configure the system functions. The
jumper settings are described in the following sections.
1.4.1Wiring power supply input and battery
Power supply 1 connection (170 W or 300 W)
Connection X301 must be used for a single power supply.
Jumper X305 must be plugged onto position 1-2.
X301
+
BROO
PSSI2
1
GND
+26V
3
4
Connection for power supply 2 (only 300 W)
Only one power supply (300 W ) may be connected to X302.
A 2nd power supply (300 W) is only allowed in an housing (3HU).
Jumper X305 must be plugged onto position 2-3.
X302
+
BROO
1
PSSI2
GND
+26V
3
4
Battery connection
X303
-
BAT-12
BAT+
+
10 | 46
Page 11
Periphery board (250p) FCI2016
Configuration input power and battery
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
1.4.2X301 Power supply terminal block 1
Terminal X301 must always have a power supply connected.
To power down the system, f irst disconnect the batteries and then the line
supply.
Make sure AC is disconnected. Wire power supply (300 W or 170 W) connection to
X301. Check whether jum per X305 is in position 1-2 before a single power supply is
connected.
Do not connect AC or batteries until all jumpers and modules are configured and
connected in the system. Once everything is installed and connect ed, first AC, then the
batteries must be connected.
PinDesignationDescription
1
1BROO
(White) AC low signal. Signals when the supply system
connection drops below AC 102 V.
2PSSI
(Green) Power supply status indication. Used by the
periphery board to know t he health of the power supply.
3GND(Black) Return ( ground)
4+24 V(Red) DC +24 V system supply
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
Building Technologies
11 |
Page 12
Periphery board (250p) FCI2016
Configuration input power and battery
1
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry,
Inc.
2016-02-25
Terminal block X302 may only be used for an additional PS300 when the system
Terminal X301 must always have a power supply
connected. When a single power
1
2
3
1
2
3
1.4.3X302 Power supply 2 terminal block
requirements exceed 300 W. The housing (3HU) is the only housing that is capable of
having two PS300 supplies connected at the same time. No power supply (170 W)
may be connected to term inal block X302.
supply is used, it must be c onnected to terminal X301.
Check whether jumper X305 is in position 2-3 before PS300 #1 is connect ed to X301
or #2 to X302. Make s ure line voltage is not present on the system, and that the
breaker in the panel is off. Both power supplies need to be connected before line
voltage is switched on at t he panel. X301 and X302 should never be
connected/disconnect with line voltage present. Batteries may only be connected after
the system is brought up on line voltage power.
PinDesignationDescript ion
1BROO
(White) AC low signal. Signals when the supply system
connection drops below AC 102 V.
2PSSI
(Green) Power supply status indication. Used by the
periphery board to know t he health of the power supply.
3GND(Black) Return ( ground)
4+24 V(Red) DC +24 V system supply
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
1.4.4X305 jumper – Power supply 2 on/off
This jumper is used to configure the periphery board for one or two power supplies.
The factory setting m ay only be changed when a second power supply (300 W) in an
housing (3HU) is supported.
X305Jumper positionFunctionMeaning
1 - 2
2 - 3
Deactivated
PS 2 300 W
Activated
PS 2 300 W
Default sett ing; for power supply (170 W) and a single power
supply (300 W).
For a second power supply (300 W) in an housing (3HU).
The power supply is activated and is monitored by the system.
12 | 46
Page 13
Periphery board (250p) FCI2016
NAC circuits
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
1.4.5X304 Voice supply +24 V
The battery
connection is only made once the whole system has been configured
The hardware required to connect the batteries to the periphery board is in the battery
The NAC circuit can be configured such that, when degraded mode is active,
the
The X304 connector on the periphery board provides the power for all Voice option
modules inside the VCA2002 Card Cage and for the connected peripherals. The cable
that connects X304 on the Periphery Board to X101 on the Card Cage is inc luded in
the VCA2002's scope of supply.
1.4.6X303 Battery terminal
A cable harness is required to connect batteries to the periphery board. The battery
connector end that goes on the periphery board at X303 can only connect one way
because it is keyed.
through jumpers and modules , and after AC has been applied.
PinDesignationDescription
1BAT (+)DC 24 V feed for battery (RED WIRE)
2BAT (-)Return (Ground) feed for battery (BLUE WIRE)
1
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
kit.
1.5NAC circuits
The periphery board has an NAC circuit that can be configured for 1 class A (style Z)
or 2 class B (style Y) circuits. Configuration is done via 3 jumpers (X 604, X605 and
X606).
NAC circuit is activ ated by an alarm in the case of a CPU error on the periphery
board.
For the status of degraded mode during an active alarm, NAC activation is set by the
jumpers X602 and X603.
The outputs are power limit ed and are supervised for short-circuit and open cir cuit.
They are protected against direct short-circ uit of the output terminals.
The synchronization protocol is built into the panel, so no module is needed.
The NAC is configured in the Engineering tool set. This includes the output pattern and
class A/B selection. Please note that the periphery board also has three jumpers (X 604,
X605 and X606) that must m atch the settings in the Engineering tool set. If they do not
match, a trouble will post on the system.
The end-of-line resistor is 2.4 kΩ, 1/2 W.
These circuits are for NAC circuits NFPA 72 Local only. For NFPA 72 Municipal Tie or
NFPA 72 Leased Line, use the leased line/city tie module FCI2020. The module
connects to X902.
Building Technologies
13 |
Page 14
Periphery board (250p) FCI2016
NAC circuits
1
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry,
Inc.
2016-02-25
To ensure proper f unctioning, the jumpers must be set correctly
for class A/B
+
+
-
-
+
-
EOL
You will find information on the installation in the followi ng documents:
●A6V10315015 for Desigo
●A6V10333409 for Cerberus PRO
You will find information on the configuration in the following documents:
●A6V10315023 for Desigo
●A6V10333423 for Cerberus PRO
1.5.1Wiring the NAC circuits
The following wiring diagrams show how to connect notification devices to the circuit,
either as class A (style Z) or class B (style Y) circuit. For class A, no end-of-line resistor
is needed. It is built int o t he circuit.
selection.
In the diagrams below, polarity is shown in activated condition.
Notification appliance c ircuit supervised and power limited.
X601
+
NAC1-1
NAC1-1
NAC1-2
NAC1-2
4
-
3
+
2
-
1
Figure 3: X601: Class A (style Z) supervised output connection
X601
+
NAC1-1
NAC1-1
NAC1-2
NAC1-2
Figure 4: X601: Class B (style Y) supervised output connection
4
-
3
+
2
-
1
+
*
EOL
* EOL resistance must be connec ted during non-use.
EOL resistance: 2.4 kΩ, 0.5 W
1.5.2X601 te rminal block – NAC 1 class A / NAC 1-1 class B /
NAC 1-2 class B
PinDesignationDescription
4NAC1-1 (+)Positive feed f or notification appliances for NAC 1 class A or NAC 1-1 class B
3NAC1-1 (-)Return feed for notification appliances for NAC 1 class A or NAC 1-1 class B
2NAC1-2 (+)Positive feed f or notification appliances for NAC 1 class A or NAC 1-2 class B
1NAC1-2 (-)Return feed for notification appliances for NAC 1 class A or NAC 1-2 class B
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
14 | 46
Page 15
Periphery board (250p) FCI2016
NAC circuits
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
1.5.3X602 jumper – ENABLE/DISABLE DEGRADED MODE for
1
2
3
123
123
NAC 1 class A or NAC 1-1 class B
Errors of the power P C are displayed on the PMI & mainboard when degraded mode is
activated.
X602Jumper positionFunctionMeaning
3 - 2Enable degradeEnable degraded mode for NAC 1 class A or NAC 1-1 class B.
Circuit will activate the notification appliances if degraded
mode is activated and an alarm is present.
1 - 2Disable degradeDisable degraded mode for NAC 1 class A or NAC 1-1 class B.
Circuit will not activate the notification appliances if degraded
mode is activated and an alarm is present.
1.5.4X603 jumper – ENABLE/DISABLE DEGRADED MODE for
NAC 1-2 class B
Errors of the power P C are displayed on the PMI & mainboard when degraded mode is
activated.
1
X603Jumper positionFunctionMeaning
3 - 2Enable degrade
Enable degraded mode for NAC 1-2 c lass B. Circuit will not
activate the notification appliances if degraded mode is
activated and an alarm is present.
1 - 2Disable degrade
Disable degraded mode for NAC 1-2 class B. Circuit will not
activate the notification appliances if degraded mode is
activated and an alarm is present.
1.5.5X604, X605, X606 Jumper – NAC 1 class A/B
Class A/B setting of the onboard NAC circuit
X604
X605
X606
Jumper positionFunctionMeaning
3 - 2Class AConfigures periphery board NAC 1 for class A wiring
1 - 2Class B
Configures periphery board NAC 1-1 and NAC 1-2 for class B
wiring
The class A/B configuration of the jumpers on the periphery board must be transferred
in the Engineering tool set. An error is generated if the configurations do not match.
Building Technologies
15 |
Page 16
Periphery board (250p) FCI2016
Bell follower input
1
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry,
Inc.
2016-02-25
123
1.5.6X403 jumper – DEGRADE ALARM SILENCEABLE
Degraded mode behavior of the NAC ci rcuit during an alarm
X403Jumper positionFunctionMeaning
3 - 2NONSILENCEABLE
1 - 2SILENCEABLE
1.6Bell follower input
The periphery board has an input designed to connect to an external f ire alarm control
unit's NAC circuit so that the periphery board's NAC circuits can follow t he activation of
the NAC circuits from an external source.
1.6.1Wiring
NAC is active.
*1) Fire detect ion device or bell extender.
When degrade mode is active in the system, and an alarm is
present, this setting prevents the user from turning off the
notification appliances .
When degrade mode is active in the system, and an alarm is
present, this setting allows the user to turn off the notification
appliances. The notification devices remain switched off in the
event of a further alarm.
X801
-
BF1
+
BF
2
+
*1
16 | 46
1.6.2X801 Bell follower terminal block
PinDesignationDescription
1BF (-)
2BF (+)
Admissible cable cros s-section: 1 x 12-18 AWG or 2 x 16-18 AWG
Input from external fire control panel and voice alarm fire
control panel.
The return feed of the external fire control panel's NAC
circuit connect s here.
Input from external fire control panel and voice alarm fire
control panel.
The active positive output signal of the external fire control
panel's NAC circuit connects here.
Page 17
Periphery board (250p) FCI2016
Auxiliary DC 24 V output
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
1.7Auxiliary DC 24 V output
Auxiliary output DC 24 V with a maximum output current of 1.5 A. The output can be
used for devices such as door holders, DACT, or RDT. The circuit is power limit ed and
is protected against a direct shorted output. The out put is power limited and supervised
for overcurrent. To configure the output to shut down during AC loss to conserve the
battery, you must configure the system with the Engineering tool set.
If the output is configured to turn off on battery, then the output is used for
supplementary purposes only.
1.7.1Wiring
X1001
+
AUX
AUX
AUX
AUX
1
-
2
+
3
-
4
1
1.7.2X1001 Au xiliary output termi nal block
PinDesignationDescription
1AUX (+)Positive feed for Aux circuit (DC +24 V)
2AUX (-)Return feed Aux circuit
3AUX (+)Positive feed for Aux circuit (DC +24 V)
4AUX (-)Return feed Aux circuit
Admissible cable cros s-section: 1 x 12-18 AWG or 2 x 16-18 AWG
1.8Relays
Common alarm relay
The alarm relay changes state whenever a fire alarm is detected. In degrade mode, the
alarm relay will still activate in case of a fire, without processor control.
Common trouble relay
The trouble relay c hanges state whenever a system trouble is detected. In degrade
mode, the trouble relay will still activate without processor control.
Common supervisory relay
The supervisory relay changes state whenever a supervisory trouble is detected. In
degrade mode, the supervisory relay will not function.
Building Technologies
Programmable user relay
The user programmable relay changes state depending on the configurat ion set in the
Engineering tool set.
In degrade mode, the user relay will not activate.
17 |
Page 18
Periphery board (250p) FCI2016
Detector circuits,
circuit driver 1 (circuits 1 and 2)
1
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry,
Inc.
2016-02-25
C
1.8.1Wiring
Supervisory
C NCNO
1
7
C NCNO C NCNO
NC NO
TroubleAlarm
6
12
1.8.2X1101 Relay terminal block
PinDesignationDescription
1CCommon contact common alarm relay
2NCNormally closed contact common alarm relay
3NONormally open contact common alarm relay
4CCommon contact common trouble relay
5NCNormally closed contact common trouble relay
6NONormally open contact common trouble relay
7CCommon contact common supervisory relay
8NCNormally closed contact common supervisory relay
User
9NONormally open contact common supervisory relay
10CCommon contact programmable relay
11NCNormally closed contact programmable relay
12NONormally open contact programmable relay
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
NO/NC (normally open / normally closed) relates to the fire detection system's normal
status.
1.9Detector circuits, circuit driver 1 (circuits 1 and 2)
The periphery board (250p) has one independent integrated circuit card. This
integrated card is a driver that has 2 circuits that can handle a maximum of 252
devices. Circuit driver 1 supports circuits 1 and 2 and can be configured for two circuits
(style 6) or four circuit s (style 4).
The detector circuits are isolated from the periphery board's main circuit. The circuit
card has its own microprocessor for supervising ground fault, short-circuit, open circuit,
and line capacity.
18 | 46
Page 19
Periphery board (250p) FCI2016
Detector circuits, circuit driver 1 (circuits 1 and 2)
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
1.9.1Wiring
X1402
No EOL required
X1402
No EOL required
132
4
Initiating
device
1
No EOL required
2+
1324
2-1+ 1-
X1401
Figure 5: Style 6 wiring
Both circuits are supervised and power limited.
No EOL required
Initiating
device
X1401
2+
2-1+1-
2+
2+
1324
2-1+ 1-
1324
2-1+1-
Figure 6: Style 4 wiring
Both circuits are supervised and power limited.
Building Technologies
19 |
Page 20
Periphery board (250p) FCI2016
Indicators
1
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry,
Inc.
2016-02-25
1.9.2X1401 terminal block – detector circuit 1
PinDesignationDescription
12-Return feed for circuit 1-2
22+Positive feed f or circuit 1-2
31-Return feed for circuit 1-1
41+Positive feed f or circuit 1-1
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
1.9.3X1402 terminal block – detector circuit 2
PinDesignationDescription
12-Return feed for circuit 2-2
22+Positive feed f or circuit 2-2
31-Return feed for circuit 2-1
41+Positive feed f or circuit 2-1
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
1.10Indicators
LED indicators on the FDnet/C-NET detector circuit
ONStartup problem s on integrated circuit card 1
1 x flash per secondFail-safe active (no communication to the PMI)
2 x flash per secondFail-safe active and local alarm
1 x flash every 2 secondsFail-safe active and signalization (local alarm)
1 x flash per second and 2 x rapid
flash every 2 seconds
Fail-safe act ive and local alarm and signalization
1.11Reset Buttons
1.11.1S100 RESET periphery board
ButtonFunctionPositionMeaning
S100
20 | 46
Reset main microproc essor on
periphery board
Not pressedNormal
Pressed
Resets only the main
microprocessor on the periphery
board.
Page 21
Periphery board (250p) FCI2016
Technical data
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
1.12Technical data
Supply inputPlug stripX301/302
Operating voltageDC 24 V nominal, filtered
Operating current (standby)120 mA
Max. operating cur rent.136 mA
1
Input current (active)
Design
●PS170W (only f ire detection systems) 6.5 A at
●1 x PS300W 11.5 A
●2 x PS300W 20 A
Not power limited
Battery out putPlug stripX303
Voltage
DC 20.4 V…DC 26.4 V
(DC 24 V nominal)
CurentMax. 11.5 A
NAC circuitPlug stripX601
VoltageDC 24 V
Special Application for strobe loads
Regulated for non-pulsing loads
Standby operating cur rentMax. 10 mA
Active operating currentMax. 1x class A circuit or 2x class B circuits
Max. 3 A for 1x class A circuit
Max. 3 A per class B circuit
2x 3 A = 6 A for 2x class B circuits
Max. circuit resistance1.4 Ω @ 3.0 A
Supervised for●Open circuit
●Short circuit
●Ground fault
AUX outputPlug stripX1001
Building Technologies
Design●Short-circuit protection
●Voltage surge protection
●Power limited
VoltageDC 24 V nominal "Special Application"
For use with: FN2006/FN2007, HZM, HCP,
FCA2018, FT2014/FT2015, FTI2001
CurentMax. 1.5 A
Design●Short-circuit protection
●Voltage surge protection
●Power limited
21 |
Page 22
Periphery board (250p) FCI2016
Tec
hnical data
1
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry,
Inc.
2016-02-25
Bell follower inputPlug stripX1001
VoltageDC 24 V filtered or full wave
CurentMax. 4 mA
DesignVoltage surge protection
Detector circ uitsTerminal stripsX1401 c ircuit card 1, circuit 1
X1402 circuit card 1, circuit 2
Output voltageDC 24 V, filtered
Number of integrat ed circuit
1
cards
Output current per integrated
Max. 500 mA
circuit card
Addressable devices per
Max. 252
integrated circuit card
Connectable circuits per
2 style 6 or 4 style 4 (mixed variants are possible)
integrated circuit card
You will find detailed specif ications in the following
documents:
●A6V10315013 for Desigo
●A6V10333396 for Cerberus PRO
Connectable devicesSee 'List of compatibility'
Monitored for●Ground fault
●Short circuit
●Open circuit
●Circuit capacitance
Relay contactsPlug stripX1201
22 | 46
Design●Short-circuit-proof
●Voltage surge protection
●Open circuit
●Power limited
Design●Relay output
●Break or make contact
●Nonpower limited
●Alarm and trouble ac tive in degraded mode
operation
Switching voltageDC 30 V or AC 120/240 V ohmic
Switching current
5 A @ DC 30 V or AC 120 V
4 A @ AC 240 V
Page 23
Periphery board (250p) FCI2016
Technical data
1
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
Connection terminals
Inputs, out puts and det ector
circuits
●DesignPlug-in screw term inals
●Admissible cable cross-
Once 12...18 AWG or twice 16...18 AWG
section
Voice alarm supplyConnecting plugX304
Output+24 V
Output voltageDC 24 V nominal, filtered
Max. output current20 A
Design●Not power limited
●Short-circuit-proof
Building Technologies
23 |
Page 24
Periphery board (250p) FCI2016
Technical data
1
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry,
Inc.
2016-02-25
24 | 46
Page 25
Periphery board (500p) FCI2017
Description
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
2Periphery board (500p) FCI2017
2
2.1Description
The FCI2017 periphery board (500p) is used for fire control panels and voice alarm fire
control panels with max. 504 device addresses. The purpose of the periphery board is
to provide means for supervising and controlling various peripheral devices, such as
detectors and notification devices, and providing power f or the entire panel. There are
2 detector cores on the periphery board, each isolated from the rest of t he periphery
board, and each other. An auxiliary output circuit (1.5 A, 24 V) provides power t o
remote devices or internal modules. The integrated NAC circuit (NAC 1) provides up to
3 A of power for max. 1 class A circ uit or 3 A for each of max. 2 class B circuits. The
periphery board has expansion capabilities for leased line / cit y tie operation, a
releasing circuit wit h 2 zones, and an additional NAC circuit (NAC 2).
The periphery board has a battery charger and battery switchover circuit for AC fail or
brownout. The batter y charger is capable of charging up to 100 Ah batteries.
Building Technologies
25 |
Page 26
Periphery board (500p) FCI2017
Description
2
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry, Inc.
2016-02-25
Properties
●Two different power supplies can be connected:
–Power supply (170 W ) FP2011 only for fire control panels with a m aximum load
of 6.5 A
–Power supply (300 W) FP2012 for fire control panels and voice alarm fire
control panels with a max imum loading of 11.5 A
–Power supply (300 W ) FP2012 for voice alarm fire control panels in housings
(3HU) with a maximum loading of 22 A
●Battery charger capable of charging up to 100 Ah batteries at a maximum of 6 A.
●Power supply (300W) FP2012 must be used for batteries of more than 33 Ah.
●Power supply (170W) FP2011 must be used for batteries of 33 Ah or less.
●Ground fault s detected at <1 kΩ to ground.
●Ground fault detection for all circuits except the 2 detector c ircuits handled by PMI.
Each detector core has its own ground fault and supervision circuit.
●Two integrat ed FDnet/C-NET circuit cards, one for circuits 1 and 2 and one for
circuits 3 and 4, and EM C surge protection for eight style 4 or four style 6 circuits.
●Maximum of 252 device addresses can be controlled per integrated FDnet/C-NET
circuit card.
●Three relay outputs and one user programmable relay output for common alarm,
common trouble, common supervision, and user programmable.
●The auxiliary output is a regulated DC 24 V output with a max imum of 1.5 A.
●Degraded alarm and trouble m ode functions when either or both CPUs for the
periphery board or PMI are compromised.
●Integrat ed NAC circuits, specified for DC 24 V, configured for either one class A
(style Z) or two class B (style Y) circuits, with a maximum of 3 A for one class A or
max. 3 A for each of the two class B circuits. NACs have integrated
synchronization protocol for audible or visual notification appliances.
–All NAC circuits are supervised and protected for overcurrent and direct short-
circuited output .
●Two slots for optional extensions, one of which is for NAC module (1A/2B) or
releasing module (XCI2001):
–NAC module (1A/2B) FCI2001 for one additional class A circuit or two class B
circuits (sam e data as integrated NAC circuits) (P/N S54400-A54-A1). The
module connects to X901.
–Releasing module (XCI2001) (P/N S54400-A69-A1) The module connects to
X901.
–Leased line or city t ie module FCI2020 (P/N 54400-A57-A1). The module
connects to X902.
●Additional periph eral data bus connection (X202) for LED or DACT modules.
●Main CPU and detector core CPUs capable of being updated in the f ield through
the PMI.
26 | 46
Page 27
Periphery board (500p) FCI2017
Installation
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
2.2Installation
2
3
The chapter describes how to install periphery board (500p) F CI2017 in fire control
panels and voice alarm fire c ontrol panels.
2
1
Figure 7: Installi ng the periphery boar d (500p)
1Threaded standoffs on back box
212x fixing screw
3Periphery board (500p)
w The back box is installed.
w The openings for passing through cables have been broken out.
w The power cable is fed through and is disconnected from the power supply.
w The batteries are not installed or connected.
1. Install the periphery board (500p) (3) on the threaded sleeves (1) of the back box
with the 12 fixing screws (2).
2. Wire the periphery board (500p) according to the pin assignments in the following
chapters.
3. Set the jumpers.
4. Re-install any modules that you m ay have had to remove.
Building Technologies
27 |
Page 28
Per
iphery board (500p) FCI2017
Views
2
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry, Inc.
2016-02-25
X801
X901
F301
X303
X304
X301
X202
X1101
X1802
X1402
X1702
X201
X601
X305
1
1111111
111
1
1
X603
X602
X605
X606
X604
X302
F302
2.3Vi ews
X1401X1801
H1701
H1301
X1302
S100
X403
X902
X204
11
1
1
1
3
1
16
7
12
X1001
1
3
Figure 8: Printed circuit board view for FCI2017
ElementDes.Function
FusesF30130 A fuse for battery
F302Fuse 20 A for voice alarm DC 24 V output
LEDsH1301Status indicator for detector core A (circuits 1 and 2)
H1701Status indicator for detector core B (circuits 3 and 4)
Reset buttons S100
Reset button for m icroprocessor for periphery board circuit ry (not including detector
circuits)
X602DEGRADED MODE ENABLE/DISABLE for NAC 1 class A or NAC 1-1 class B
X603DEGRADED MODE ENABLE/DISABLE for NAC 1-2 class B
X604NAC 1 class A/B selection
X605NAC 1 class A/B selection
X606NAC 1 class A/B selection
X305Power supply 2 ON/OFF
ConnectorX201PMI & mainboard bus
X202Peripheral data bus output
X204Future expansion
X301Connector for power supply 1 (PS1)
X302Connector plug for power supply 2 (PS2) in housing (3HU)
X303Battery connection
2
X304
DC 24 V connection t o Card Cage VCA2002 for feed to the voice alarm modules and
associated peripherals
X601NAC1 output
X801Bell follower input
X901NAC 2 expansion or releasing module
X902Leased line / city tie module
X1001Auxiliary DC 24 V output
X1101Common alarm relay positions 1…3
The periphery board has jum pers that are used to configure the system functions. The
jumper settings are described in the following sections.
2.4.1Wiring power supply input and battery
Power supply 1 connection (170 W or 300 W)
Connection X301 must be used for a single power supply.
Jumper X305 must be plugged onto position 1-2.
X301
+
BROO
PSSI2
1
GND
+26V
3
4
Connection for power supply 2 (only 300 W)
Only one power supply (300 W ) may be connected to X302.
A 2nd power supply (300 W) is only allowed in an housing (3HU).
Jumper X305 must be plugged onto position 2-3.
X302
+
BROO
1
PSSI2
GND
+26V
3
4
Battery connection
X303
-
BAT-12
BAT+
+
30 | 46
Page 31
Periphery board (500p) FCI2017
Configuration input power and battery
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
2.4.2X301 Power supply terminal block 1
Terminal X301 must always have a power supply connected.
To power down the system, f irst disconnect the batteries and then the line supply .
Make sure AC is disconnected. Wire power supply (300 W or 170 W) connection to
X301. Check whether jum per X305 is in position 1-2 before a single power supply is
connected.
Do not connect AC or batteries until all jumpers and modules are configured and
connected in the system. Once everything is installed and connect ed, first AC, then the
batteries must be connected.
PinDesignationDescription
2
1BROO
(White) AC low signal. Signals when the supply system
connection drops below AC 102 V.
2PSSI
(Green) Power supply status indication. Used by the
periphery board to know t he health of the power supply.
3GND(Black) Return ( ground)
4+24 V(Red) DC +24 V system supply
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
Building Technologies
31 |
Page 32
Periphery board (500p) FCI2017
Confi
guration input power and battery
2
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry, Inc.
2016-02-25
Terminal block X302 may only be used for an additional PS300 when the system
Terminal X301 must always have a power supply connected. When a single power
1
2
3
1
2
3
2.4.3X302 Power supply 2 terminal block
requirements exceed 300 W. The housing (3HU) is the only housing that is capable of
having two PS300 supplies connected at the same time. No power supply (170 W)
may be connected to term inal block X302.
supply is used, it must be c onnected to terminal X301.
Check whether jumper X305 is in position 2-3 before PS300 #1 is connect ed to X301
or #2 to X302. Make s ure line voltage is not present on the system, and that the
breaker in the panel is off. Both power supplies need to be connected before line
voltage is switched on at t he panel. X301 and X302 should never be
connected/disconnect with line voltage present. Batteries may only be connected after
the system is brought up on line voltage power.
PinDesignationDescript ion
1BROO
(White) AC low signal. Signals when the supply system
connection drops below AC 102 V.
2PSSI
(Green) Power supply status indication. Used by the
periphery board to know t he health of the power supply.
3GND(Black) Return ( ground)
4+24 V(Red) DC +24 V system supply
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
2.4.4X305 jumper – Power supply 2 on/off
This jumper is used to configure the periphery board for one or two power supplies.
The factory setting m ay only be changed when a second power supply (300 W) in an
housing (3HU) is supported.
X305Jumper positionFunctionMeaning
1 - 2
2 - 3
Deactivated
PS 2 300 W
Activated
PS 2 300 W
Default sett ing; for power supply (170 W) and a single power
supply (300 W).
For a second power supply (300 W) in an housing (3HU).
The power supply is activated and is monitored by the system.
2.4.5X304 Voice supply +24 V
The X304 connector on the periphery board provides the power for all Voice option
modules inside the VCA2002 Card Cage and for the connected peripherals. The cable
that connects X304 on the Periphery Board to X101 on the Card Cage is inc luded in
the VCA2002's scope of supply.
32 | 46
Page 33
Periphery board (500p) FCI2017
NAC circuits
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
2.4.6X303 Battery terminal
The battery connection is only made once the whole system has been conf igured
The hardware required to connect the batteries to the periphery board is in the battery
The NAC circuit can be configured such that, when
degraded mode is active, the
A cable harness is required to connect batteries to the periphery board. The battery
connector end that goes on the periphery board at X303 can only connect one way
because it is keyed.
through jumpers and modules , and after AC has been applied.
PinDesignationDescription
1BAT (+)DC 24 V feed for battery (RED WIRE)
2BAT (-)Return (Ground) feed for battery (BLUE WIRE)
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
kit.
2
2.5NAC circuits
The periphery board has an NAC circuit that can be configured for 1 class A (style Z)
or 2 class B (style Y) circuits. Configuration is done via 3 jumpers (X 604, X605 and
X606).
NAC circuit is activ ated by an alarm in the case of a CPU error on the periphery
board.
For the status of degraded mode during an active alarm, NAC activation is set by the
jumpers X602 and X603.
The outputs are power limit ed and are supervised for short-circuit and open cir cuit.
They are protected against direct short-circ uit of the output terminals.
The synchronization protocol is built into the panel, so no module is needed.
The NAC is configured in the Engineering tool set. This includes the output pattern and
class A/B selection. Please note that the periphery board also has three jumpers (X 604,
X605 and X606) that must m atch the settings in the Engineering tool set. If they do not
match, a trouble will post on the system.
The end-of-line resistor is 2.4 kΩ, 1/2 W.
These circuits are for NAC circuits NFPA 72 Local only. For NFPA 72 Municipal Tie or
NFPA 72 Leased Line, use the leased line/city tie module FCI2020. The module
connects to X902.
You will find information on the installation in the followi ng documents:
●A6V10315015 for Desigo
●A6V10333409 for Cerberus PRO
You will find information on the configuration in the following documents:
●A6V10315023 for Desigo
●A6V10333423 for Cerberus PRO
Building Technologies
33 |
Page 34
Periphery board (500p) FCI2017
NAC circuits
2
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry, Inc.
2016-02-25
To ensure proper functioning, the
jumpers must be set correctly for class A/B
+
+
-
-
+
-*EOL
2.5.1Wiring the NAC circuits
The following wiring diagrams show how to connect notification devices to the circuit,
either as class A (style Z) or class B (style Y) circuit. For class A, no end-of-line resistor
is needed. It is built int o t he circuit.
selection.
In the diagrams below, polarity is shown in activated condition.
Notification appliance c ircuit supervised and power limited.
X601
+
NAC1-1
NAC1-1
NAC1-2
NAC1-2
Figure 9: X601: Class A (style Z) supervised output connection
4
-
3
+
2
-
1
X601
+
NAC1-1
NAC1-1
NAC1-2
NAC1-2
Figure 10: X601: Class B (style Y) supervised output connection
4
-
3
+
2
-
1
+
-
EOL
* EOL resistance must be connec ted during non-use.
EOL resistance: 2.4 kΩ, 0.5 W
2.5.2X601 te rminal block – NAC 1 class A / NAC 1-1 class B / NAC
1-2 class B
PinDesignationDescription
4NAC1-1 (+)Positive feed for notification appliances for NAC 1 class A or NAC 1-1 class B
3NAC1-1 (-)Return feed for notification appliances f or NAC 1 class A or NAC 1-1 class B
2NAC1-2 (+)Positive feed for notification appliances for NAC 1 class A or NAC 1-2 class B
1NAC1-2 (-)Return feed for notification appliances f or NAC 1 class A or NAC 1-2 class B
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
34 | 46
Page 35
Periphery board (500p) FCI2017
NAC circuits
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
2.5.3X602 jumper – ENABLE/DISABLE DEGRADED MODE for
1
2
3
123
123
NAC 1 class A or NAC 1-1 class B
Errors of the power P C are displayed on the PMI & mainboard when degraded mode is
activated.
X602Jumper positionFunctionMeaning
3 - 2Enable degradeEnable degraded mode for NAC 1 class A or NAC 1-1 class B.
Circuit will activate the notification appliances if degraded
mode is activated and an alarm is present.
1 - 2Disable degradeDisable degraded mode for NAC 1 class A or NAC 1-1 class B.
Circuit will not activate the notification appliances if degraded
mode is activated and an alarm is present.
2.5.4X603 jumper – ENABLE/DISABLE DEGRADED MODE for
NAC 1-2 class B
Errors of the power P C are displayed on the PMI & mainboard when degraded mode is
activated.
2
X603Jumper positionFunctionMeaning
3 - 2Enable degrade
Enable degraded mode for NAC 1-2 c lass B. Circuit will not
activate the notification appliances if degraded mode is
activated and an alarm is present.
1 - 2Disable degrade
Disable degraded mode for NAC 1-2 class B. Circuit will not
activate the notification appliances if degraded mode is
activated and an alarm is present.
2.5.5X604, X605, X606 Jumper – NAC 1 class A/B
Class A/B setting of the onboard NAC circuit
X604
X605
X606
Jumper positionFunctionMeaning
3 - 2Class AConfigures periphery board NAC 1 for class A wiring
1 - 2Class B
Configures periphery board NAC 1-1 and NAC 1-2 for class B
wiring
The class A/B configuration of the jumpers on the periphery board must be transferred
in the Engineering tool set. An error is generated if the configurations do not match.
Building Technologies
35 |
Page 36
Periphery board (500p) FCI2017
Bell follower input
2
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry, Inc.
2016-02-25
123
2.5.6X403 jumper – DEGRADE ALARM SILENCEABLE
Degraded mode behavior of the NAC ci rcuit during an alarm
X403Jumper positionFunctionMeaning
3 - 2NONSILENCEABLE
1 - 2SILENCEABLE
2.6Bell follower input
The periphery board has an input designed to connect to an external f ire alarm control
unit's NAC circuit so that the periphery board's NAC circuits can follow t he activation of
the NAC circuits from an external source.
2.6.1Wiring
NAC is active.
*1) Fire detect ion device or bell extender.
When degrade mode is active in the system, and an alarm is
present, this setting prevents the user from turning off the
notification appliances .
When degrade mode is active in the system, and an alarm is
present, this setting allows the user to turn off the notification
appliances. The notification devices remain switched off in the
event of a further alarm.
X801
-
BF1
+
BF
2
+
*1
36 | 46
2.6.2X801 Bell follower terminal block
PinDesignationDescription
1BF (-)
2BF (+)
Admissible cable cros s-section: 1 x 12-18 AWG or 2 x 16-18 AWG
Input from external fire control panel and voice alarm fire
control panel.
The return feed of the external fire control panel's NAC
circuit connect s here.
Input from external fire control panel and voice alarm fire
control panel.
The active positive output signal of the external fire
control panel's NAC cir cuit connects here.
Page 37
Periphery board (500p) F
CI2017
Auxiliary DC 24 V output
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
2.7Auxiliary DC 24 V output
Auxiliary output DC 24 V with a maximum output current of 1.5 A. The output can be
used for devices such as door holders, DACT, or RDT. The circuit is power limit ed and
is protected against a direct shorted output. The out put is power limited and supervised
for overcurrent. To configure the output to shut down during AC loss to conserve the
battery, you must configure the system with the Engineering tool set.
If the output is configured to turn off on battery, then the output is used for
supplementary purposes only.
2.7.1Wiring
X1001
+
AUX
AUX
AUX
AUX
1
-
2
+
3
-
4
2
2.7.2X1001 Au xiliary output termi nal block
PinDesignationDescription
1AUX (+)Positive feed for Aux circuit (DC +24 V)
2AUX (-)Return feed Aux circuit
3AUX (+)Positive feed for Aux circuit (DC +24 V)
4AUX (-)Return feed Aux circuit
Admissible cable cros s-section: 1 x 12-18 AWG or 2 x 16-18 AWG
2.8Relays
Common alarm relay
The alarm relay changes state whenever a fire alarm is detected. In degrade mode, the
alarm relay will still activate in case of a fire, without processor control.
Common trouble relay
The trouble relay c hanges state whenever a system trouble is detected. In degrade
mode, the trouble relay will still activate without processor control.
Common supervisory relay
The supervisory relay changes state whenever a supervisory trouble is detected. In
degrade mode, the supervisory relay will not function.
Building Technologies
Programmable user relay
The user programmable relay changes state depending on the configurat ion set in the
Engineering tool set.
In degrade mode, the user relay will not activate.
37 |
Page 38
Periphery board (500p) FCI2017
Detector circuits, circuit driver 1 (circuits 1 and 2) and circuit driver 2 (circuits 3 and 4)
2
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry, Inc.
2016-02-25
C
2.8.1Wiring
Supervisory
C NCNO
1
7
C NCNO C NCNO
NC NO
TroubleAlarm
6
12
2.8.2X1101 Relay terminal block
PinDesignationDescription
1CCommon contact common alarm relay
2NCNormally closed contact common alarm relay
3NONormally open cont act common alarm relay
4CCommon contact common trouble relay
5NCNormally closed contact common trouble relay
6NONormally open cont act common trouble relay
7CCommon contact common supervisory relay
8NCNormally closed contact common supervisory relay
User
9NONormally open cont act common supervisory relay
10CCommon contact programmable relay
11NCNorm ally closed contact programmable relay
12NONormally open contact programmable relay
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
NO/NC (normally open / normally closed) relates to the fire detection system's normal
status.
2.9Detector circuits, circuit driver 1 (circuits 1 and 2) and
circuit driver 2 (circuits 3 and 4)
The periphery board (500p) has two independent integrated circuit cards. Each
integrated card is a driver that has 2 circuits that can handle a maximum of 252
devices. Circuit driver 1 supports circuits 1 and 2 and circuit driver 2 supports circuits 3
and 4.
Each circuit driver can be configured for two style 6 circuits or four style 4 circuits:
The detector circuits are isolated from the periphery board's main circuit. Each circuit
card has a microprocessor which supervises ground fault, short -circuit, open circuit,
and line capacity.
38 | 46
Page 39
Periphery board (500p) FCI2017
Detector circuits, circuit driver 1 (circuits 1 and 2) and cir
cuit driver 2 (circuits 3 and 4)
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
2.9.1Wiring
X1402
No EOL requi red
X1402
No EOL required
132
4
Initiating
device
2
No EOL required
X1401
Figure 11: Style 6 wiring
3
2+
1
24
X1802X1801
2-1 + 1-
Both circuits are supervised and power limited.
No EOL required
Initiating
device
X1401
X1802X1801
2+
2-1+ 1-
Figure 12: Style 4 wiring
Both circuits are supervised and power limited.
3
2+
1
24
2-1+ 1-
1324
2+
2-1+ 1-
Building Technologies
39 |
Page 40
Periphery board (500p) FCI2017
Detector circuits, circuit driver 1 (circuits 1 and 2) and circuit driver 2 (circuits 3 and 4)
2
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry, Inc.
2016-02-25
2.9.2X1401 and X1801 terminal block – detector circuits 1 and 3
X1401: Circuit driv er 1, circuit 1
X1801: Circuit driv er 2, circuit 3
PinDesignationDescript ion
12-Return feed for circuit 1-2 or circuit 3-2
22+Positive output for circuit 1-2 or circuit 3-2
31-Return feed for circuit 1-1 or circuit 3-1
41+Positive output for circuit 1-1 or circuit 3-1
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
2.9.3X1402 and X1802 terminal block – detector circuits 2 and 4
X1401: Circuit driv er 1, circuit 2
X1801: Circuit driv er 2, circuit 4
PinDesignationDescript ion
12-Return feed for circuit 2-2 or circuit 4-2
22+Positive output for circuit 2-2 or circuit 4-2
31-Return feed for circuit 2-1 or circuit 4-1
41+Positive output for circuit 2-1 or circuit 4-1
Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG
40 | 46
Page 41
Periphery board (500p) FCI2017
Indicators
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
2.10Indicators
Standard LED indicators
LEDColorConditionMeaning
H1301YellowOFFDefault
2
ON
1 flash every 2 secondsFailsafe active (no communication to PMI)
2 fast flashes (every 2 seconds)Failsafe active + local alarm
1 fast flash (every 1 second)Failsafe act ive + signaling (local alarm)
Flash (every 1 second) and 2 fast flashes
(every 2 seconds)
H1701YellowOFFDefault
ON
1 flash every 2 secondsFailsafe active (no communication to PMI)
2 fast flashes (every 2 seconds)Failsafe active + local alarm
1 fast flash (every 1 second)Failsafe act ive + signaling (local alarm)
Flash (every 1 second) and 2 fast flashes
(every 2 seconds)
Startup problems FDnet/C-NET core A
(clock)
Failsafe active + local alarm + signaling
Startup problems FDnet/C-NET core B
(clock)
Failsafe active + local alarm + signaling
2.11Reset Buttons
2.11.1S100 RESET periphery board
ButtonFunctionPositionMeaning
S100
Building Technologies
Reset main microproc essor on
periphery board
Not pressedNormal
Pressed
Resets only the main
microprocessor on the periphery
board.
41 |
Page 42
Periphery board (500p) FCI2017
Technical data
2
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry, Inc.
2016-02-25
2.12Technical data
Supply inputPlug stripX301/302
Operating voltageDC 24 V nominal, filtered
Operating current (standby)120 mA
Max. operating cur rent.136 mA
Input current (active)
●PS170W (only fire detection
Design
●1 x PS300W 11.5 A
●2 x PS300W 20 A
Not power limited
BatteryPlug stripX303
Voltage
DC 20.4 V…DC 26.4 V
(DC 24 V nominal)
Curent11.5 A
NAC circuitPlug stripX601
VoltageDC 24 V
Special Application for strobe loads
Regulated for non-pulsing loads
Standby operating cur rentMax. 10 mA
Active operating current
Max. 1x class A circuit or 2x class B
circuits
Max. 3 A for 1x class A circuit
Max. 3 A per class B circuit
2x 3 A = 6 A for 2x class B circuits
Maximum circuit res istance1.4 Ω @ 3.0 A
systems) 6.5 A at
Supervised for●Open circuit
●Short circuit
●Ground fault
Design●Short-circuit protection
●Voltage surge protection
●Power limited
AUX outputPlug st ripX1001
VoltageDC 24 V nominal "Special Application"
For use with: FN2006/FN2007, HZM,
HCP, FCA2018, FT2014/FT2015,
FTI2001
CurentMax. 1.5 A
Design●Short-circuit protection
●Voltage surge protection
●Power limited
42 | 46
Page 43
Periphery board (500p) FCI2017
Technical data
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
Bell follower inputPlug stripX1001
VoltageDC 24 V filtered or full wave
CurentMax. 4 mA
DesignVoltage surge protection
X1802 circuit card 2, circuit 4
Output voltageDC 24 V, filtered
Number of integrat ed circuit cards2
Output current per integrated circuit card Max. 500 mA
Connectable devicesSee List of compatibility
Monitored for●Ground fault
●Short circuit
●Open circuit
●Circuit capacitance
Design●Short-circuit-proof
●Voltage surge protection
●Open circuit
●Power limited
Relay contactsPlug stripX1201
Building Technologies
Design●Relay output
●Break or make contact
●Nonpower limited
●Alarm and trouble ac tive in degraded
mode operation
Switching voltageDC 30 V or AC 120/240 V ohmic
Switching current
5 A @ DC 30 V or AC 120 V
4 A @ AC 240 V
43 |
Page 44
Periphery board (500p) FCI2017
Technical data
2
Building Technologies
A6V10315038_f_e n_
--
Siemens Industry, Inc.
2016-02-25
Connection terminalsI nputs, outputs and detector circuit s:
●DesignPlug-in screw term inals
●Admissible cable cross-sectionOnce 12...18 AWG or twice 16...18 AWG
Voice alarm supplyConnecting plugX304
Output+24 V
Output voltageDC 24 V nominal, filtered
Max. output current20 A
Design●Not power limited
●Short-circuit-proof
44 | 46
Page 45
FCC Statement
46
A6V10315038_f_en_
--
Siemens Industry, Inc.
2016-02-25
3FCC Statement
Installation and usage of equipment is not in accordance with instructions manual
●
Read the following information.
WARNING
Radiation of radio frequenc y energy
Interference to radio communications
●Install and use equipm ent in accordance with instructions manual.
This equipment generates, uses, and can radiate radio frequency energy and if not
installed and used in accordanc e with the instructions manual, may cause interference
to radio communicat ions.
It has been tested and found t o comply with the limits for a Class A computing device
pursuant to Part 15 of FCC Rules, which are designed to provide reasonable protection
against such interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely t o cause interference in which
case the user at his own expense will be required to take whatever measures may be
required to correct the interference.
3
Building Technologies
45 |
Page 46
Issued by
Siemens Industry, Inc.
Building Technologies Division
8 Fernwood Road
Florham Park, NJ 07932
+1 973-593-2600
www.sbt.siemens.com/FIS
Document ID: A6V10315038_f_en_--SAP order no.: A5Q00050751FS20/FS920
Edition: 20 16-02-25
Technical specifications and availability subject to change without notice.