FC901 SYSTEM DESCRIPTION..................................................................................................................... 4
Power Supply ............................................................................................................................................... 4
Signaling Line Circuit (SLC) .......................................................................................................................... 5
Serial Interf ac e Cir c uit ................................................................................................................................... 5
Status Relays ............................................................................................................................................... 5
Programming Port ......................................................................................................................................... 5
Serial LCD Annunciators ............................................................................................................................... 6
FT Series LED Driver/Annunc iators ............................................................................................................... 6
Addressable Modules (Monitor and Control) .................................................................................................. 7
Manual Stati ons ............................................................................................................................................ 7
Sounder Base ............................................................................................................................................... 7
EVENT HISTORY ........................................................................................................................................... 9
GENERAL DESIGN FE ATURES .................................................................................................................. 10
Power Limiting ............................................................................................................................................ 10
Ground Fault Det ection ............................................................................................................................... 10
Security Features ........................................................................................................................................ 10
Primary Power Supply................................................................................................................................. 12
Secondary Power Supply ............................................................................................................................ 12
Auxiliary Power Outputs .............................................................................................................................. 12
Status Relays ............................................................................................................................................. 13
Serial Interf ac e Cir c uit ................................................................................................................................. 13
City Tie Circuits........................................................................................................................................... 13
Lamp Test .................................................................................................................................................. 18
History ........................................................................................................................................................ 18
Power Supply Mounting .............................................................................................................................. 27
Optional City Ti e Mounting .......................................................................................................................... 30
Main Board Assembly Installation................................................................................................................ 31
SYSTEM WIRING ......................................................................................................................................... 32
AC Connection............................................................................................................................................ 32
Power Supply and Battery Wiring ................................................................................................................ 36
Status Relays ............................................................................................................................................. 37
Auxiliary Power Outputs Wiring ................................................................................................................... 37
Serial Interf ac e Cir c uit ................................................................................................................................. 39
Serial Remote Device Wiring Overview ....................................................................................................... 40
SLC Addressable Devi c e Cir c uit ................................................................................................................. 41
GENERAL .................................................................................................................................................... 46
ii
Page 6
QUICK TEST ................................................................................................................................................ 47
APPENDIX-A: REFERENCE DATA ............................................................................................................. 49
Global ASA ................................................................................................................................................. 54
A. General .................................................................................................................................................. 55
B. System Events ....................................................................................................................................... 55
APPENDIX-H: OUTPUT FEATURES ........................................................................................................... 63
Output Activation- and Deactivation- Delays ................................................................................................ 63
APPENDIX-I: PAS / PRE-SIGNAL ............................................................................................................... 64
PAS ............................................................................................................................................................ 64
APPENDIX-L: GLOSSAR Y .......................................................................................................................... 73
iii
Page 7
Page 8
INTRODUCTION
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmabl e software. In ord er for the prod uct t o comply with th e requ i rements in the
Program Feature or Option
Possible Settings
Settings Permitted in UL 864
Supervision/Trouble Resound
Not enabled
Yes
DACT Phone Line Settings
Disable 1 phone line
Enable both phone line connections
CO Events
Alarm or Supervisory
Supervisory
CONTROL PANEL LIMITATIONS
This control panel may not show an alarm condition without compatible initiating dev ices
(smoke detectors, etc.) and notification devices (horn, strobes, etc.) connected to it. Electrical
ratings of the initiation and notification appliances must be compatible with the electrical ratings
of the control panel and must be properly interconnected. The wiring used for interconnection
must be large enough to carry the total current for all appliances without excessive voltage
drop.
The control panel must be connected to a dedicated primary electrical source that has a high
degree of reliability and adequate capacity for this control panel. The only means of
disconnecting this power source shall be available only to authorized personnel and clearly
marked "Fire Alarm Circuit Control".
The control panel must also have connected to a battery set (24V) that has enough capacity to
properly operate the system for 24 hours standby and 5 minutes alarm per UL864 9th edition
(section 63.2.3 and 63.2.5) . These batteries do lose capacity with age. Batteries must be
replaced when they fail to provide the control panel with the required standby and alarm power
or after 4 years, whichever happens first. These batteries must be checked for performance at
least two (2) times a year or more often if local requirements dictate.
Even though this control panel was made to last for the expected life of the fire alarm system,
any part could fail at any time. Therefore a regular test program should be followed and
documented to make sure that each part of the system i s tested as in Chapter 7 of NFPA 72 or
more often if dictated by local code requirements. Malfunctioning units must be replaced or
repaired immediately by factory author ized service personne l.
This control panel is designed to show an alarm condition when the initiating devices
connected to it detect sp ecific conditions. These conditions may or may not represent a lifethreatening condit io n. Also , evacu at ion of a building or area unnecessaril y may sub ject
individuals to an unn ecessary hazard. Therefore, it is most import ant that the bui lding owne r ,
manager, or represen t at ive promulgate, distribute, and/o r po st instructions describing st eps
to be taken when the fire alarm cont rol panel signals an alarm condition. These instructions
should be developed in cooperation and conformance with representat ives of the local
authorit y ha v in g jurisdiction.
As a precautionary measure, it is strongly sugg ested that one of these steps should be to
notify the local fire dep art ment of an abnormal condition even where th e DACT option (or
similar device) is included in the system.
Standard for Cont rol Units and Accessories for Fire Alarm S ystems, U L 864, certain progr am mi ng featur es or op t ions must be
limited to specific values or not used at all as indicated below.
0-30 hours
connection
1
1-24 hours
Page 9
PREFACE
Along with the use of this instruction manual, the appropriate following standards and the
manufacturer's instructions for initiating and notification devices should be used to install and
maintain a functioning fire alarm signaling system.
NFPA 72 National Fire Alarm Code
For other standards that may apply contact the authority having jurisdiction.
For NFPA publications, contact:
National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269
FCC PART 68 WARNING
1. This equipment compli es with Part 68 of the FCC rules and the requirements adopted by
the ACTA. On bottom of this equipment is a label that contains, among other i nformation, a
product identifier of [US:02XAL00BFCM901]. If requested, this number must be provided to
the telephone company.
2. If this equipment FC901 causes harm to the telephone network, the telephone company will
notify you in advance that temporary discontinuance of service may be required. But if
advance notice isn’t practical, the telephone company will notify the customer as soon as
possible. Also, you will be advised of your right to file a complaint with the FCC if you
believe it is necessary.
3. The telephone company may make changes in this facilities, equipment, operations or
procedures that could affect the operation of the equipment. If this happens the telephone
company will provide advance notice in order for you to make necessary modification to
maintain uninterrupted service.
4. If you experience trouble with this equipment, you disconnect it from the network until the
problem has been corrected or until you are sure that the equipment is not malfunctioning.
5. Please follow instructions for repairing if any (e.g. battery replacement section); otherwise
do not alternate or repair any parts of device except specified.
6. Connection to party line service is subject to state tariffs. Contact the state public utility
commission public service commi ssion or corporation commission for information.
7. If the telephone company requests information on what equipment is connected to their
lines, inform them of:
a) The telephone number that this unit is connected to,
b) The ringer equivalence number [0.0B]
c) The USOC jack required [RJ11C], and
d) The FCC Registration Number [US:02XAL00BFCM901]
Items (b) and (d) are indicated on the label. The ringer equivalence number (REN) is used
to determine how many devices can be connected to your telephone line. In most areas,
2
Page 10
the sum of the RENs of all devices on any one line should not exceed five (5.0). If too
many devices are attached, they may not ring properly.
Service Requirements
In the event of equipment malfunction, all repairs should be performed by our Company or an
authorized agent. It is the responsibility of users requiring service to report the need for service
to our Company or to one of our authorized agents. Service can be facilitated through our
office at:
SIEMENS INDUSTRY, INC. – BUILDING TECHNOLOGIES DIVISION – FIRE SAFETY
8 FERNWOOD RD., FLORHAM PARK, NJ 07932
+1-800-248-7976
3
Page 11
DESCRIPTIONS
FC901 SYSTEM DESCRIPTION
The FC901 is a compact but powerful standalone fire alarm control panel. It features advanced
addressable fire detection, keypad and offline programming, notification circuits, a 160 by 64
dots LCD display and event history retention capability. It’s typical configuration includes a
power supply, a signaling addressable device circuit, two notification appliance circuits (NAC),
Digital Alarm Communication Transmi tter (DACT), four system status relays and a USB
programming port.
All the components of the FC901 control panel are mounted in an 18.1" x 16.5" enclosure. The
FC901 has only one electronic main board which integrates most functional parts together (the
CPU board is mounted to main board before delivery), including DACT, System Display,
signaling line circuit, NAC, serial interface circ uits, system sta t us relays, programming port and
battery charging circuit. The main board is mounted on the supporting frame, and it provides
the connections for external field wiring. An optional city tie module can be mounted on the
backside of the main board. The power supply is located under the main board and supporting
frame.
The FC901 supports English and Spanish operation menu for user selection. When the tool
language changes from English to Spanish, it is recommended, but not necessary, to create a
new Spanish configuration and upload it to the panel.
The FC901 features one LCD screen which is used to indicate the spec ific indicati ons for
system events while LEDs indicate general panel status.
FC901 supports surface mounting and semi-flush mounti ng. Semi-flush mounting kits are
available for the enclosure.
System status information is provided by a 160 by 64 dots (7 by 26 characters), back lit LCD
and by discrete LED indicators for major control panel functions.
The LCD is used to display event data, including alarms and troubles conditions, zone or
device custom identification of messages, and a log of the system event history. A back light is
included in the display to assure visibility in low light. To conserve power, the back light is only
activated during a reported event or on operation of a display control button.
Individual LEDs on the panel are provided to indicate ALARM, SUPERVISORY, TROUBLE,
NAC SILENCED, AUDIBLE S ON, SYSTEM GROUND FAULT and SYSTEM POWER. Direct
push-button controls are provided for SILENCE, UNSILENCE, ACKNOWLEDGE, MENU, OK,
CANCEL, RESET and a four-way button for menu navigation.
Power Supply
A 26V (nominal) power supply provides all operating power to the control panel for both
standby and alarm conditions. Sufficient battery charging capability is available to charge 1218 AH sealed lead-acid batteries within code requirements for up to 24 hours of normal
standby operation plus 5 minutes of alarm operation. The battery will be automatically
disconnected at low battery voltage to prevent deep discharge and battery damage.
4
Page 12
Signaling Line Circuit (SLC)
The FC901 fire alarm control panel provides a signaling line circuit with the capacity of 50
addressable devices.
Notificati on A ppliance Circuits
The FC901 control panel has two independent notification appliance circuit (NACs). It can be
configured as two Class B (Style Y) NACs or one Class A (Style Z) NAC. Each circuit can be
selected to give continuous output or one of five sounding patte rns. There is also a system
coder capable of zone operation. All of the NACs are power limited and support
synchronization of listed devices using the Siemens sync protocol.
Serial Inter face Circuit (UFP)
The FC901 control panel has a Serial Interface Circuit (UFP) that will drive up to 8 dev ices, eg.
remote LCD annunciators, remote LED driver/tabular annunciator or remote printer module.
Status Relays
Four relays with dry contacts are provided. Three relays are dedicated to alarm, supervisory,
and trouble conditions on the panel. The remaining relay is programmable. The relay contacts
are Form C and are rated for 2A@30VDC resistive.
Programmi ng P ort
A USB standard type B plug is provided for temporary connection to a computer for panel
programming and firmware download when using the FXS901-U3 System Configurat ion Tool.
DACT
The Digital Alarm Communication Transmitter (DACT) is integrated on the FC901 main board
and it will send control panel status information to a central or remote receiving station through
the Public Switched Telephone Network (PSTN).
OPTIONAL MODULES
City Tie Module (FCI2020-U1)
The city tie module provides local energy and polarity reversal connections. The polarity
reversal connections provide a trouble circuit and an alarm circuit with optional trouble output.
The city tie board mounts onto the main board.
Battery Sets
The FC901 control p anel is designed to use only rechargeable sealed lead-acid batteries for
back-up power. Maximum battery charging capacity for the FC901 is 18AH.
Remote Printer Module (FCA 2018-U1)
The Model FCA2018-U1 is a Universal Fire Protocol module that interfaces to a parallel
printer. It must be located where the re is access to the fire system serial interface circuit
network. Up to 2 FCA2018-U1 may be addressed by the communication circuit.
The Model FCA2018-U1 is required whenever a logging printer is needed. It translates the
serial interface circuit messages into a standard printer interface. When the PAL-1 is used with
the RPM (FCA2018-U1), the RPM supervises the printer for on/off line, power on, paper out,
paper jam, and wiring fault conditions, as required by Underwriters Laboratories for NFPA 72
proprietary systems.
5
Page 13
Note: For printer connection, wiring between the RPM and printer must be in conduit
within 6 feet and in the same room as the panel.
AUXILIARY MODULES
Serial LCD Annunciators
The FSD901 Serial L CD Annunciator consists of a backlit 160 by 64 dot (7 by 26 characters)
LCD display, acknowledge, silence, unsilence, and reset buttons, a four-way button for event
navigation, seven system status LED indicators and a security key switch. To prevent
unauthorized system operation, the control buttons are only enabled when the key switch is
activated. The display and controls of the FSD901 are the same as those on the front of the
control panel. The backlight activates only upon active button press or when events are
present in the system to conserve power.
FT Series LED D river/Annunci ators
The FT Series LED driver/annunciator includes three options. The FT2007-U1 is an LED
driver for use in graphic annunciators. The FT2008-U1/R1 is a 16-zone LED annunciator with
seven system status LED’s. The FT2008-U1/R1 also includes buttons for Acknowledge,
Signal Silence/Unsilence, Reset, and Lamp Test. Key switch lockout is provided for additional
security. The FT2009-U1/R1 includes an additional 16 zones for a total of 32 individual ly
programmable zones.
Up to 8 annunciators may be addressed by the communication circuit. Each annunciator
requires connection to the Serial Interface circuit on the mainboard, and 24VDC power.
6
Page 14
SLC ADDRESSABLE DEVICES
Smoke Detector
The control panel processor sends the sensitivity settings to the detectors and polls the
detectors for their status. The detector determines normal, trouble and alarm conditions and
communicates the conditions to the control panel.
Variable Thresholds - The detectors can be set to operate in various pre-programmed profiles,
depending on the environment where the detectors are used.
Operator Alerts - The control panel can indicate a trouble event automatically on the
occurrence of a number of conditions of the detector. The supported conditions include:
Channel Active
Unconfigured Device
Device Type Mismatch
Device Communication Trouble
Address Invalid
Address Unspecified
Multiple Device Response
Parameter Error
Device Type Unknown
Fatal Fault
General Trouble
Dirty
Replace
Heat Detectors
Addressable heat sensing detectors may be intermixed on the circuit for locations where heat
sensing may be the most effective detection method. The heat detectors may be programmed
for rate of rise operation or fixed temperature.
Addressabl e Modules (Moni tor and Control)
In addition to detectors, the circuit can communicate with addressable monitor and control
modules. Monitor modules allow remote contact closure initiating devices to generate event
conditions on the system. Control modules provide the system remote relay outputs or
notification appliance circuits
Manual Stati ons
Addressable manual stations may be intermixed on the circuit with proper response
programmed into the control panel.
Sounder Base
The ABHW-4B and ABHW-4S are the intelligent supervised audible based which provides 6
selectable tone patterns, 2 volume levels and 2 different power types for alarm.
The 6 tone patterns supported by the ABHW-4B and ABHW-4S are: Steady, Temporal 3,
Temporal 4, Temporal 4 low power, March time 120 and Canadian March time 30.
When the audible base ABHW-4B and ABHW-4S i s used with Global ASA/FD182UL detectors,
it can be programmed to 2 output channels, and up to 6 tone patterns can be selected using
7
Page 15
the system configuration tool. When users need to disable the audible base , they will need to
select the “disable audible base” option.
When the audible base ABHW-4B and ABHW-4S is used with H/8700 series detectors, it can
be programmed to 1 output channel, and only 2 tone patterns (steady, temporal 3) can be
selected using the system configuration tool. When users need to disable the audible base,
they will need to select the “disable outputs” option.
Note: When users need to dis ab le the ABHW-4B and ABHW-4S audible bases connected to
the entire loop consisting of H/8700 series and Global ASA/FD182 detectors, they will need to
select both the “dis ab le outputs” and “d isable audib le base” options.
There are two methods for powering the audible base during alarm. They are “Loop powered”
and “External powered” which can be configured by the system configuration tool. The ABHW4B can be powered by loop power and exter nal power, the ABHW-4S can only be powered by
external power.
For additional information please refer to installation manual of ABHW-4B (A6V10405587) and
ABHW-4S (A6V10405588).
Note: * When using external power source, the power supply unit must be UL Listed for fire
use only, Power Limited and rated 19-28 VDC.
* Audible signals are synchronized on zone basis.
Programming SLC Devices
SLC devices can be assigned the ir electronic address and be tested by using the DPU Device
Programmer/Loop Tester.
8
Page 16
EVENT HISTORY
The control panel includes a non-volatile memory recording 1000 system events. Identified
alarm, trouble, supervisory,status and other significant events will be recorded along with the
date and time of occurrence. The history event log can be viewed at the main system display
by operating menu controls from the panel. The history event log can also be transferred from
the panel to a computer using the FXS901-U3 system configuration tool.
Events recorded in the history are:
Alarm, trouble, supervisory and status conditions
Alarm silence/unsilence (Manual)
System reset
User level login/logout
Start and stop of quick test
Expiration of quick test Timer
Trouble/supervisory reminder
Acknowledgment
Trouble/supervisory restored to normal
9
Page 17
GENERAL DESIGN FEATURES
Environmental
The FC901 panels and subassemblies are suitable for use in a dry, indoor or protected
location.
Power Limiting
The AC power connection, battery wiring and four system status relays are not power limited.
All other circuits leaving the control panel meet the requirements for power limited circuits
when installed in accordance with the National Electrical Code and local requirements.
Ground Fault Detection
The control panel provides system ground fault detection. Main board ground fault event is
annunciated as a trouble condition on the system. In addition, the addressable circuit and
serial interface circuit have their own ground detection circuitry and indicator.
The notification appliance circuits are controlled by the system microprocessor in accordance
with the site specific system configuration.
The notification appliance circuits can operate audible and visual notification appliances. Each
NAC can provide any of five software-generated codes or continuous operation to audible
notification appliances. Also, each NAC supports synchronization of visual notification
appliances.
Sil ence Inhibit - The control panel may be programmed to inhibit silence for up to four minutes
from the first alarm.
All of the NACs are power limited.
Security Fea t ures
Multi-level password protection of programming functions prevents unauthorized configuration
changes.
Device type supervision: If the device type identifier reported by an addressable detector or
module does not agree with the configuration, the system reports a trouble condition.
Device address supervision: The system checks that all configured devices on the addressable
device circuit respond to an address poll. The system reports a trouble condition if the
following conditions are detected:
10
Page 18
Configured device is missing.
Unconfigured device is instal led.
Two devices are programmed with the same address.
Signaling line circuit experiences a wire-to-wire short.
Signaling line circuit experiences an earth ground condition.
REGULATORY STANDARDS
The FC901 control panel meets the requirements of industry and government regulatory
agencies as noted.
Underwrite r s Laboratories
The FC901 control panel is listed under UL Standard 864 for compliance to NFPA Standard 72
for fire service.
Federal Comm unications C om m ission
The DACT meets the Class A requirements of the Code of Federal Regulations (CFR 47), Part
15 for electromagnetic field emissions. The DACT also meets the requirements of the Code of
Federal Regulations (CFR 47), Part 68, for connection of equipment to the public switched
telephone network.
11
Page 19
GENERAL SP ECIFICATIONS
Operating specifications for the FC901 are as follows:
Environmental
Operating temperature - 32 - 120°F (0 - 49°C)
Relative humidity - Up to 93% @ 90°F (32°C)
To be installed in a indoor dry protected environment only
Primary Power Supply
Input: 120VAC, 60Hz or 240VAC, 50Hz
@ 2.0A Max.
Supervised
Output: 26VDC @ 6.5A Max.
Max current: 6.5A (2 hours Max.)
Filtered and Regulated
Non-resettable power output
Power limited
Alarm status: 0.75A
Normal stand by: 0.05A
Voltage: 19 to 28VDC
Ripple: 0.1VAC
Special Application
Resettable power output
Power limited
Alarm status: 0.75A
Normal stand by: 0.05A
Voltage: 19 to 28VDC
Ripple: 0.1VAC
Special Application
12
Page 20
Status Relays
Non-power limited
One programmable relay
Three non-programmable relays: Trouble, Supervisory, Alarm
Contact rating: 2A, 30VDC maximum
For m C contact
Notificati on A ppliance Circuits
Power limited
Supervised
Current Draw Maximum Line Resistance
2.5A 3.2Ω
2.0A 4.0Ω
1.5A 5.3Ω
1.0A 8.0Ω
0.5A 16.0Ω
Alarm voltage: 16 to 32VDC
Maximum ripple: 0.1VAC
Used for special application only
Two Style Y/Class B or one Style Z/Class A
Total Max. Current: 2.5A
Serial Inter face Circuit (UFP)
Power limited
Supervised
Maximum wire loop resistance: 50Ω total
Physical layer: RS485
SLC Addressable Devi ce C ircuits
32 VDC Max
Power limited
Supervised
Max. current: 0.07A(RMS)
Maximum wire loop resistance: 50Ω
Two Style 4 Class B or one Style 6 Class A circuit
Max. 50 addressable devices
City Tie Circuits
Supply Input:
Voltage: 26VDC
13
Page 21
Device Module
Manufacture
MX8000
Honeywell
18 – 28VDC for battery
Current: Max. 0.4A
Supervised
Output:
City Tie-Output 1
Normal output voltage: 19-28VDC (open circuit condition)
Supervisory current: 1mA
Maximum trip current: 400mA
Maximum coil plus wire resistance: 22.5Ω
Leased line-Output 1
Normal output voltage: 19-28VDC (open circuit condition)
Trouble output voltage: 0V
Alarm output voltage: -(19-28)VDC (open circuit condition)
Maxi mu m wi re resistance: 2-5KΩ
Maximum short circuit current: 25mA
Leased line-Output 2
Normal output voltage: 19-28VDC (open circuit condition)
Supervisory output voltage: -(19-28)VDC (open circuit condition)
Maxi mu m wi re resistance: 2-5KΩ
Maximum short circuit current: 25mA
DACT Circuits
Power limited
Supervised for short or open circuit conditions
Compliance to FCC part 68
Support RJ31X connection
Compatible Digital Alarm Communication Receiver (DACR) list,
CAUTION:
– To reduce the risk of fire, use only No. 26 AWG or larger telecommuni cation line cord.
Only to a loop start telephone circuit and not to a ground start telephone circuit.
To verify the integrity of the call forwarding feature every 24 hours.
14
Page 22
CONTROL PANEL OPERATION
OPERATION INSTRUCTIONS
Standby Condition
In normal standby oper ation, the green AC POWER ON LED should be illuminated and no
other indicator operating. The display will show the system label and the current time.
Alarm Condi tions
ALARM
When the system detects an alarm condition, the alarm LED activates (ON – flashing) and the
local panel buzzer activates in a specific pattern to indicate an alarm condition. Programmed
system outputs, including audible and visual notification appliances, relays activate, and the
LCD display indicates the zone or point initiating the alarm.
Upon receipt of an alarm, building occupants should proceed in accordance with the
established emergency response plan. System responders should assure that all personnel
are accounted for, and notify the Fire Department.
Operating the ACKNOWLEDGE button will silence the local panel buzzer and change the LED
alarm indicator from flashing to steady. The LCD display will indicate that the active events
have been acknowledged.
To silence the audible and/or visual notification appliances (where permitted by the codes and
control panel programming), press ALARM SILENCE. The notification appliances will be deactivated, and the alarm silence LED will be off.
POSITIVE Alarm Sequence (PAS)
Activation of an initiating device in an input group programmed for PAS activates the Alarm
LED, LCD display, and the local panel buzzer. System and user-programmed outputs do not
activate imm ediately.
Operation of the ACKNOWLEDGE button within 15 seconds of the activation of the initiating
devices will delay activation of system and user-programmed outputs between 60 and 180
seconds(selected during system configuration) for the purpose of investigating the alarm. If the
ACKNOWLEDGE button is not operated within 15 seconds, the system and user-programmed
outputs activate at the expiration of the 15 second delay.
If the initiating device and the panel are reset before the programmed delay expires, the alarm
sequence is aborted.
During the investigation period, an alarm condition on a detector programmed for direct alarm
response (such as the key switch on a manual station) will override the programmed delay and
activate the additional user-programmed outputs immediately. User can configure Manned
status of FACP to enable/disable PAS feature. FACP will not perform PAS feature in
Unmanned status. After logged in as L2/L3 user, user can select Unmanned item in operate
menu to enter Unmanned status and bypass all on-going PAS alarms.
15
Page 23
PRE-SIGNAL AL ARMS
Activation of an initiating device in an input group programmed for PRE-SIGNAL, activates the
Alarm LED, LCD display, and the local panel buzzer. System and user-programmed outputs
activate imm ediately except NAC.
The delay of activation of user-programmed outputs can be programmed from 60 to 180
seconds. If the system is not reset during this period, the NAC outputs will activate.
During the delay period, an alarm condition on a detector programmed for direct alarm
response (such as the key switch on a manual station) will override the programmed delay and
activate the user-programmed NACs immediately.
Do not reset the system until the alarm condition has been cleared. Th e LCD displ ay will
indicate the area in which the alarm w as detect ed. The detector or module associated with the
device initiating the alarm will display a light indicating activation (if applicable).
When the alarm condition has been corrected, return the system to standby operation by
pressing the RESET button.
Trouble Conditions
When the system detects a trouble condition, the trouble LED will be flashing, the LCD
displays trouble events and the local panel buzzer activates in specific pattern that
distinguishes the event from an alarm event. Refer to the applicable section of the system
manual to determine the probable cause of the trouble and the action to be taken.
Operating the ACKNOWLEDGE button will silence the local panel buzzer and change the LED
trouble indicator from flashing to steady. The LCD display will indicate that the active events
have been acknowledged.
If the panel is configured for Supervisory/Trouble Resound Reminder, and the trouble condition
is not corrected the local panel buzzer will re-activate when the reminder timer has relapsed to
remind users of the trouble condition.
If the FC901 is configured as “Trouble self restoring”, the system shall return to the “system
normal” status if the trouble condition is restored, unless there are additional events on the
system. If the FC901 is not configured as “Trouble self restoring”, the system reverts to
standby condition only after the RESET button is pressed.
Supervisor y Conditions
When the system detects a supervisory condition, the supervisory LED will be flashing, the
LCD display supervisory events, and the local panel buzzer activates in a specific pattern that
distinguishes it from an alarm event.
Operating the ACKNOWLEDGE button will silence the local panel buzzer and change the LED
supervisory indicator from flashing to steady. The LCD display will indicate that the active
events have been acknowledged.
If the panel is configured for Supervisory/Trouble Resound Reminder, and the supervisory
condition is not corrected, the local panel buzzer will re-activate when the reminder timer has
relapsed to remind users of the supervisory condition.
16
Page 24
If the FC901 is configured as “Supervisory self restoring”, the system shall return to the
“System Normal” status if the supervisory condition is restored unless there are additional
events on the system. If the FC901 is not configured as “Supervisory self restoring”, the
system reverts to standby condition only after the RESET button is pressed.
17
Page 25
ADDITIONAL OPERATING PROCEDURES
In addition to the basic fire alarm instructions above, several features are included to facilitate
maintenance and increase the versatility of the system. The following are pr ocedures used to
initiate these functions.
Lamp Test
When selected, Lamp Test activates LCD, the buzzer and turns on all the LEDs on the user
interface, then back to its previous state.
To initiate a Lamp Test, pr oceed as follows:
Press "MENU".
On the MENU display, select "Oper".
Select “Lamp Test “to run.
Note that lamp test operates the indicators only on the units being operated and no record is
reported to system history.
The lamp test lasts 10 seconds.From 0 to 4 seconds LCD test; From 4 to 7 seconds LEDs
test; From 7 to 10 seconds buzzers test.Operator doesn't need to turn it off manually. Lamp
test will automatically quit when it completes.
History
The last 1000 system events are time-tagged and recorded for review in the user level event
history. This history and all user-level functions are available to users with the door key.
Operation of history:
New events overwrite old when filled.
For more information see the Event History section.
Access to history:
To recall past events, proceed as follows:
• Press “MENU” button.
• On the “MENU” display, select “View”.
• Select “History”.
Operate up button adjacent to the LCD for previous event display.
Operate down button adjacent to the LCD for next event display.
18
Page 26
FC901 OPERATING INSTRUCTIONS
Authorized Personnel Only
steady
Fuse Replacement and Batt er y Maintenance
Alarm Operation
In case of alarm, the Alarm LED flashes, LCD displays alarm conditions and the panel buzzer sounds in a
distinct alarm pattern. Local audible and v isual signals and remote alarm signal s operat e.
When an alarm occurs, proc eed ac c or ding to the established emergency plan. Assure that all personnel are
accounted for, and notif y the Fi r e Depar tment to advise of the alarm and/or v erify that an automatic signal has
been receiv ed at the Fir e Departm ent.
To acknowledge the alarm:
To acknowledge the al arm, pr ess the Acknowledge button. The loc al buz z er will be sil enc ed and the
Alarm LED will change fr om on-flashing to on-steady.
To silence the alarm:
To silence the notification appliances after evacuation, where permitt ed, pr ess the Alarm S ilenc e
The silenceable notificat i on appli ances will be silenced. The Silenced LED
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm fro m bei ng sil enced for a
predetermin ed time.
To reset panel after alarm:
When the alarm conditi on is corr ec ted, return the panel to normal standby oper ation by pressing the
Reset button.
Trouble is indicated by:
TroubleLED flashes, LCD displ ay s tr ouble conditions. Panel buz z er sounds in trouble pattern.
To acknowledge the trouble:
Press the Acknowledge button. The Trouble LED turns on-steady and the buzzer turns off. When the
trouble conditi on has been cleared, you need to reset the panel t o r estor e to a normal standby condition
if panel is not confi gur ed as “T r ouble self restoring”. When panel i s confi gur ed as “T r ouble self
restoring”, it will restore automatic ally to norm al standby c ondition after clearing of t r ouble condition.
Warning: devices in trouble condition may no t report a fire alarm.
Viewing Events on the System:
Events are displayed ac c or ding to the following rules:
1: Events priority :
Unacknowledged Al arm > Unacknowledged Supervi sory > Unack nowledged Trouble > Acknowledged
Alarm > Acknowledged Superv isory > Acknowledged Trouble > Status > Test
2: Within event s of the same priority, all events are displayed in the order of occurrence with the latest
displayed the first.
3: Status events are displayed according to the event sett ing. If it is configured as “No display”, it will not
be listed in Event List.
Trouble Ope ration
Event Scr olling
will change f r om off t o on-
button.
Battery fuse(F304): 15A blade type (Littelf use: 0257015.PXPV or Bussmann: ATC-15)
City tie fuse(F1-F4): 1.25A cartridge type (Littelfuse: 02151.25P or Schur ter: SPT 0001.2505)
This product requir es two 12V batteries in series, for a combined voltage of 24V. Replace bat teries every 3 to 5
years.
Recommended battery manufacturers:
Power Sonic: PS-12120, PS-12140, PS-12180 Yuasa: NP-12-12
Battery capacity: min. 12Ah / max. 18Ah
For service, contact: _______________________Telephone Number: ______________________________
Frame these instructions and mount them near the control panel for operator reference.
Charge current: max. 0.45A
19
Page 27
signal has been received at the Fire Department.
Authorized Personnel Only
Normal Standby Conditi on
FSD901 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the Alarm LED flashes, LCD displays alarm condition and the buzzer sounds. Local
audible and visual signals and remote alarm signals operat e.
When an alarm occurs, proc eed ac c or ding to the established emergency plan. Assure that all personnel
are accounted for, and not ify the Fire Department to advise of the alarm and/or verify that an automatic
To acknowledge the alarm:
To acknowledge the alarm, enable the control buttons by operating the keyswitch, and press the
Acknowledge button.
flashing to on-steady.
To silence the alarm:
To silence the notification appliances after evacuation, where permitt ed, pr ess the Alarm S ilenc e
button. The silenceable notification applianc es wil l be sil enc ed, and LED indications will change
from flashing t o continuous. The Alarm Silenced LED will be lit .
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alar m silen ce inhi bit (if set) pre ve nts the alarm from being silenced for a predetermined time.
To reset panel after al arm:
When the alarm conditi on is corr ec ted, return the panel to normal standby oper ation by pressing
the Reset button.
The local buzzer will be silenc ed and the Alarm LED will change from on-
Enable the control but tons by operating the keyswitch, and press the Acknowledge button. The
Trouble LED turns on-steady. When the trouble condition has been cleared, you may need t o
reset the panel to restore t o a normal standby condition.
Warning: Devices in trouble condition may not report a fire alarm.
Viewing Events on the System:
Events are displayed in the system by event priority (Unacknowledge d A larm > Unacknowledged
Supervisory > Unacknowledged Trouble > Acknowledged Alarm > Acknowledged Supervi sory >
Acknowledged Troubl e > S tatus > Test) followed by event occurrence (lat est to oldest event) in a
circular list.
According to settings, some events can be suppressed (not display) on annunciator.
The green AC Power On LED will be lit and no other indicators on.
For service, contact: ___________________________________________
Frame these instr uc ti ons an d mount th em n ear the annunc iator for o p erator refer ence.
20
Page 28
CONTROL PANEL INSTALLATION
Description
Part No.
Qty
FC901 enclosure black
A5Q00039701
1
Installation instruction
A5Q00039693
1
T45 key
N/A 2 #8-32 grounding cabl e nut
N/A
2
Description
Part No.
Qty
FC901 enclosure
A5Q00039702
1
Installation instruction
A5Q00039693
1
T45 key
N/A 2 #8-32 grounding cabl e nut
N/A
2
Description
Part No.
Qty
FC901 main board
A5Q00039689
1
FC901 main board support
frame
A5Q00039705
1
FC901 English film
A5Q00039715
1
FC901 English strip
A5Q00042803
1
FC901 rubber key
A5Q00042362
1
FC901 battery bracket left
(optional)
A5Q00039703
1
FC901 battery br acket ri ght
(optional)
A5Q00039704
1
FC901 battery cable
A5Q00039710
1
FC901 battery cable to main
board
A5Q00039711
1
FC901 earth cabl e
A5Q00042829
1
Terminal block 2 pi n
A5Q00011337
8
Terminal block 3 pi n
X7403000
4
Terminal block 4 pi n
A5Q00016176
2
FC901 cable ties
A5Q00036742
6
PARTS SUPPLIED – FC901
FC901 Enclosure Assembly FH901-U3(Black)/FH902-U3(Red)
FC901 Main Board Assembly FCM901-U3
Power Supply Assembly FP2011-U1
FC901 City Tie Module Assembly (optional) FCI2020-U1
FC901 Configuration Kit (optional) FXS901-U3
1. FC901 Encl osure Package
FC901 black enclosu re
FC901 red enclosure
2. FC901 Main Board Package
21
Page 29
FC901 main board installation
instruction
A5Q00039713
1
FC901 operation and
programming instruction
N/A in BSCE
1
FC901 wiring diagram
A5Q00039694
1
#8-32 x 3/8” screws
A5Q00043106
8
#4-40 x 1/4” screws
A5Q00043105
19
Grounding cable
A5Q00044075
1
Description
Part No.
Qty
FC901 Configuration
programming disk
A5Q00039718
1
FC901 Commissioning cable
(FCA3600-A1)
A5Q00039712
1
3. FC901 Configuration Kit Package
22
Page 30
CAUTIONS
1. Remove the printed circuit boards for any procedure that may cause dust, metal shavings,
grease (or such matter that may affect the operation of the boards) to get in contact with
the units.
2. Disconnect all sources of power prior to installing or removing modules, connecting or
disconnecting wiring.
CONTROL PANEL LOCATION
The control panel should be located near an exit at ground level, where the normal ambient
temperature is maintained within the control panel specification (See General Specifications).
The unit should be in an area that is free of dust, vibration, moisture and condensation. Any
auxiliary battery box or other accessory not connected through a protective device or a circuit
designed for remote connection must be within 15 ft (14AWG). and in the same room,
connected through electrical conduit.
INSTALLATION
The enclosures must be fastened securely to a clean, dry, shock-free, and vibration-free
surface in a protected environment. Consider the following when mounting the box.
Mounting height for visual and manual access to the Display Board
Weight and size of backbox
Local mounting codes
When mounting the backbox, position the backbox clear of obstructions so that the door can
open freely and so that indicators and controls are easily accessible.
The fire alarm control panel must be mounted in a properly accessible location as required by
applicable codes.
Installation is to be done only by qualified personnel who have thoroughly read and understood
these instructions.
Enclosure Mounting
Install the backbox:
Select a clean, dry, shock and vibration free surface in a protected env ironm ent.
Position the backbox clear of obstructions so that the front door opens freely and the controls
and indicators are easily accessible.
Mark the locations of the two upper mounting bolts of the backbox on the wall.
23
Page 31
2. Hinge axis can
be removed
1. Remove t he hinge
axis lock pin
There are two key-shaped cu touts on the top of the backbox. Make sure the end with the two
key-shaped cutouts is on top when installing the backbox.
The front door can be removed from the enclosure for more convenient installation.
Drill the two holes located in the previous step and screw in the top bolts, leaving a small gap
between the wall and each top bolt.
The screw type and length must be able to support the control panel, options and battery set.
Place the backbox over the two top bolts and allow it to slide down over the bolts.
Mark, drill, and install the two bottom bolts in the backbox.
Tighten all four bolts securely against the back wall of the backbox.
If a semi-flush mount installation is desired, use the Semi-flush Trim for the FC901. The
backbox can be mounted up to 3 1/2 inches into the wall. Place the semi-flush trim around the
backbox and affix to the wall with four #10 x 3/4 inch wood screws (provided with trim).
You may need a different screw type, depending on the wall mater ial.
You may need a different screw t ype, depending on the wall material.
24
Page 32
FC901 Enclosure Mounting Pictures
25
Page 33
16”
1 2
5/6
4”
31
23/
64”
1 1/32”
1 61/64”
6-2 3/8”
1
7/
16”
1 7/16”
1
31
/
3
2
”
2
5/
1
6
”
1 3/16”
1 31/32”
2 5/16”
2
5/16”
FC901 Installation Size
Remove Knock-Outs
Prepare the enclosure for electrical wiring by breaking out the appropriate conduit entr y points.
Segregation is required between power limited and non-power limited conductors. In order to
maintain the minimum separation, follow the wire routing illustrated on page 31. Separation of
at least 1/4 inch is required between the non-power limited and power limited conductors.
Power limited and non-power limited wiring must be run in separate conduit.
Attach conduit (if required) and run wires as required. Label each field cable for future
reference.
Basic system wiring and detector location must be in accordance with NFPA 72 or other
instructions from the appropriate local authority having jurisdiction. Unit connections and
limitations are as indicated on the wiring diagrams included in System Wiring part of this
manual.
Wire reference data ar e included in Appendix A.
26
Page 34
Power Supply Mounting
Secure the power supply to the back of enclosure us ing the four provided #8-32 x 3/8 screws.
AC Input terminals must be located at the right side of the enclosure.
27
Page 35
Enclosure back box
Enclosure outer door
Ground Wire I nstallation
Install one end of the grounding cable on the enclosure back box.
Install the other end of the grounding cable on the enclosure outer door.
28
Page 36
Battery Installation
Use the battery calculation chart to determine the battery size. Place the batteries in the space
provided in the bottom of the backbox. Secure the battery bracket (if required) to the back of
enclosure using the eight provided #8-32 x 3/8 screws.
Recommended battery size : Length:5. 94 inch, Width: 3.86 inch, Height:3.7 inch.
A separate enclosure must be used if a battery set larger than 12 AH in the FC901 is required.
The CAB-BATT or any enclosure UL Listed for Fire Protective Signaling Use may be used.
29
Page 37
2 #4 screws
Spacer
T2
T1
T3
City tie
module
Detail A
T1
T2
T3
Detail A City tie cabling
X2 Output 2
Connect to T2
X3 Output 1
Connect to T3
From left to right:
TP1295,TP1294,TP1293,TP1292
Detail T1
From 1 to 4
TP1295,TP1294,TP1293,TP1292
1
2
3
4
Optional City Tie Mounting
Secure the city tie to the main board using the two provided #4-32 x 3/8 screws.
Connect the city tie cable between city module and mai n board.
30
Page 38
Main Board Assembly Installation
4 #8 screws
Secure the nut on the stud
Plug the earth cable on the
connector on the main boar d
Secure the main board assembly to the enclosure using the four provided #8-32 x 3/8 screws
Earth Cable Installation
Connect the earth cable to the backbox and connector at the upper left corner of the main
board.
31
Page 39
SY STEM WIRING
Before connecting the field wiring, check the wiring for opens, shorts, grounds and stray
voltages.
WARNING
Damage may result if a high voltage insulation tester is used on wiring while connected to the
control pa ne l.
Terminate the field wiring to the main board in accordance with the diagrams in System Wiring
Section.
All wiring must be in accord ance with lo cal co des and the National Electrical Code.
AC Connection
Wire the AC supply to power supply on the back of enclosure. The supply should originate
from a dedicated 15A (minimum) branch circuit. It should be provided with a breaker or other
means of isolation that must be colored red.
Observe the wiring order — the top terminal is ground and must be wired back to the electrical
panel ground (earth) bonding point or another good ground acceptable to the authority having
jurisdiction and the electrical inspector. The neutral wire must be taken back to the electrical
panel neutral distribution bar.
Battery Connection
WARNING
Improper battery connections or shorting battery terminals may damage the system
and/or batteries and may cause personal injuries.
The control panel uses a 24V battery set. Connect the two 12V batteries in series with
provided wire. Route the battery leads to the battery connector at bottom of the main board.
The battery leads are not power-limited. DO NOT CONNECT BATTERIES YET.
WIRING
Basic system wiring and detector locations must be in accordance with NFPA 72 or other
instructions from the appropriate local authority having jurisdiction.
Devices that may be satisfactorily used with the control panel are shown in the compatible
device listing in Appendix B.
Wire reference data ar e included in Appendix A.
32
Page 40
Control Panel Wiring O verview
In compliance with NEC Article 760 and UL 864, all power limited fire protective signaling
conductors must be separated a minimum of 1/4 inch from all of the following wiring located
within a control panel:
Elec tric light
Power
Class 1 or non-power limited fire protective signaling conductors
To meet these requirements, the following guidelines must be observed when installing
modules and wiring to this control panel.
When installing power limited field wiring, the installer must comply with NEC article 760, which
states:
The fire alarm power-limited circuits are installed using Types FPL, FPLR, FPLP or
permitted substitute cable, provided these power-limited cable conductors extending
beyond the jacket are separated by a minimum of 0.25 in. ( 6.35 mm) or by a nonconductive
sleeve or nonconductive barrier from all other conductors.
If energy limited cable or equivalent is not used within the FC901 enclosure, then the following
guidelines do not apply. In that case, be sure to follow standard wiring practices.
Wiring Entering Enclos ure
Non-Power Limited Wiring - Wiring entering the enclosure from the right side of the backbox is
considered non-power limited wiring. Wiring must be in the shortest route and must not overlap
any other wiring.
Power Limited Wiring - Wiring entering the enclosure from the left side of the backbox is
considered power limited. Wiring must be in the shortest route and must not overlap any other
wiring.
Install Wiring
The primary mains input must have a separate or dedicated circuit breaker. Wire in
accordance with local codes and NEC 760.
Remove the knockouts in the backbox for the entry of field wiring. (Refer to Enclosure
Mounting Pictures on page 26 and Wiring Separation Diagram on next page for the location of
knockouts.)
Pull all field wiring into the backbox. Do not dress the wiring until the location of all the
equipment is known.
Install the wiring from the external power source to the approximate location of the power
supply.
33
Page 41
AC input
NAC-2
NAC-1
P2
Dialer
Relay-1
Relay-2
7 Optional field wire knock-outs
Power limited
N
on
po
we
r
l
i
mi
te
d
Relay-3
Relay-4
Wiring Separation
All high voltage and non-power limited wiring must be kept separate from power limited wiring.
A separation of at least 1/4 inch must be maintained with high voltage and non-power limited
wiring running in separate conduit openings from power limited wiring.
34
Page 42
Internal Structure
Enclosure
Power supply
Batteries
Battery bracket
left
Battery bracket
right
Main board assembly
35
Page 43
Brownout
GND
+26
GND
L
N
G
Connec t to Main board
wit h provided power cable
Earth GND
Neutral
(Grounding conduc tor)
AC
Power input
for PCBA
USB port
Battery c onnec tor
Conn ect to pow e r
Battery Connections
Keep All Non-Power Lim ited Wiring Separate from Po wer Limited Wiring
Non-Pow er Li mit ed
For local program mi ng
Power Supply and Battery Wiring
Route all high voltage and non-power limited wiring together and away from power limited
wiring. Use the batter y calculation chart to determine battery size.
AC connection is done on power supply.
operation
Supervised
Non-Pow er Li mit ed
For FC901
24V Battery Set (12 to 18AH)
36
suppl y with power
cable provided by
factory for main board
power input.
Page 44
Wiring terminals located on top of main board
T_
NC
T_
CO
T_
NO
Status relays
Trouble event relay
A
_NC
A_
CO
A
_NO
U
_NC
U_
CO
U_NO
S
_NC
S_
CO
S_NO
Alarm event relay
User defined relay
Supervisory event relay
X1_P
X1_N
X2_P
Auxiliary power outputs
X2_N
Resettable
Non-resettable
EARTH
S_BN
S_BP
EARTH
S_AN
S_AP
X2_P
X2_N
X1_P
X1_N
EARTH
SE_B
SE_A
GND1
EARTH
PR_B
PR_A
GND1
CT_P
CT_N
LL_SP
LL_SN
N_BP
N_BN
N_AP
N_AN
DACT
PORT1
DACT
PORT2
S_NO
S_CO
S_NC
U_NO
U_CO
U_NC
A_NO
A_CO
A_NC
T_NC
T_CO
T_NO
Power limitedNon power limited
P2 device
circuit
Auxiliary power
output
Series Interface
Circuit
City tie and
lease line
NAC
DACT
Status Relays
Relay contacts
Status Relays
Four relays with dry contacts are provided at the upper right corner of the main board. One
relay is programmable and the trouble relay, supervisory relay and alarm relay are nonprogrammable. The relay contacts are Form C and are rated for 2A@30VDC resistive.
Auxiliary Power Outputs W iring
The main board provides resettable and non-resettable auxiliary power connections. The
resettable terminal interrupts the power for 5 seconds after a reset condition.
Auxiliary Power Outputs
0.75A max. @24VDC nominal
Supervised, Power Limited
(Shown in normal standby
condition)
2A@30VDC max. resistive
Supervised
NC – Normal closed
NO – Normal open
CO – Common
37
Page 45
24K 0.5W
resistor*
…..
N_AN
N_AP
N_BN
NAC
N_BP
Same as above
…..
N_AN
N_AP
N_BN
NAC
N_BP
NAC Wiring
Two individual NACs are provided and the polarity shown is when the NAC is activated.
Power Limited
Supervised
Current Draw Maximum Line Resistance
2.5A 3.2Ω
2.0A 4.0Ω
1.5A 5.3Ω
1.0A 8.0Ω
0.5A 16.0Ω
Alarm voltage: 16 to 32VDC
Maximum ripple: 0.1VAC
Used for special application only
Two Style Y/Class B or one Style Z/Class A
Total maximum curr ent: 2.5A
Refer to Cerberus Pro_NACs_A6V10333532_c_en to determine synchronized notification
appliances allowed per NAC
Style Y, Class B
Supervised
Power Limited
See Appendix B for compatible devices
EOL available in the package as part of accessory
Style Z, Class A
Supervised
Power Limited
See Appendix B for compatible devices
No EOL devices
38
Page 46
GND1
PR_A
PR_B
Serial interface circuit (UFP)
EARTH
Primary part
(X5)
GND1
SE_A
SE_B
EARTH
Secondary part
(X6)
Serial Inter face Circuit (UFP)
The serial interface circuit can address up to 8 devices, which include annunciators and printer
modules. Up to 2 printers can be addressed. Devices on the circuit may be connected up to
4000 feet from the control panel.
Serial Interface Circuit (UFP)
(PR_A, PR_B) RS-485 levels
Wire Type-Twisted Pair For Data
EARTH – shielding earth connection
Wire Resistance-50 ohms/line (4000’ max)
Supervised, Power Limited.
Remote Device Power – The on-board auxiliary power can provide power for ONLY one
annunciator. If more power is required for the connected dev ices, external power must be
provided. Each address on the circuit must be fully powered from either auxiliary power of
control panel or external power.
: If the annunicator is connected to a Separated Power Supply, the separate power
supply needs to be UL Listed for Fire Safety Use and Power Limited.
39
Page 47
SE
_A
/B
PR_
A/B
Control Panel
In
Out
Annunciator
In
Out
RPM
In
Out
Annunciator
In
Out
Annunciator
InOut
RPM
In
Out
Annunciator
SE_A/B
PR_A/B
Control Panel
InOut
Annunciator
InOut
RPM
InOut
Annunciator
Serial Remote Device Wir ing Overview
When connecting devices on the Serial Interface Circuit (UFP), the data wires must be daisy
chained and with no T-taps to preserve the integrity of the data. The following diagrams show
the proper wiring.
Class B Style 4
Class A Style 6
40
Page 48
SLC Addressable Device Circuit
S_AN
S_AP
S_BN
P2 addressable device
S_BP
Addressable device
EARTH
EARTH
These devices are polled by the control panel every few seconds and input or output functions
communicated to determine device status or function. The control panel monitors all device
addresses for alarm and trouble conditions.
Addressable Device Circuit
Style 4 (Class B) or Style 6 (Class A) Operation
Max. 50 devices can be connected to the circuit.
Wire Resistance-50 ohms ma x
(See Appendix A, Line Resistance Graph)
Supervised, Power Limited
See Appendix B for Compatible Devices
41
Page 49
- S_AN
+ S_
AP
- S_BN
+ S_BP
ISOLATOR
MODULE
SEE NOTE
SEE
NOTE
SEE
NOTE
ISOLATOR
MODULE
SEE NOTE
SEE
NOTE
SEE
NOTE
ISOLATOR
MODULE
SEE NOTE
SEE
NOTE
SEE NOTE
TO OPTIONAL
BRANCH(
ES) OF
LOOP CIRCUIT
-
+
SUPERVISED
POWER LIMITED
SUPERVISED
POWER LIMITED
PORT-B SUPPORTS
THE SAME WIRING
AS PORT-A
-
+
PORT-APORT-B
SLC Addressable Devi ce W iring Diagrams
Refer to the instruction sheets packed with each device.
Detectors and modules may be wired together according to several NFPA defined wiring
styles. The wiring style that is appropriate for your installation should be determined from the
relevant building codes and the local Authority Having Jurisdiction.
Style 4 wiring permits branching of circuit connections. The control equipment supervises
modules because they are active and must respond periodically to the control panel’s poll.
NOTE: Siemens SLC D e vices: D etec t ors , Mon itor Modu l es, or C on trol Mod ul es u p to a ma xi mum of 50 devices (include both PORT-A an d
PORT-B). A Maximum of 20 devices recommended per Isolator Module. A Maximum of 15 Isolator Modules per addressable device circuit.
NOTE : If more th an on e HC P int elligent control p oin t module is ins talled on an addressable d evice circu it, S t yl e 4 wiring cann ot b e us ed.
NOTE: Siemens SLC D e vices: D etec t ors , Mon itor Modu l es, or C on trol Mod ul es u p to a ma xi mum of 50 devices. A Maximum of 20 device s
recomm en d ed b etween Is olator Modu l es. A M axi m u m of 15 Is olator M odu l es p er address abl e device circu it .
NOTE: If more than one HCP is used on a SLC device loop, the loop must be wired Class A or the riser conductors must be installed in
accordance with the Survivability From Attack By Fire requirements in the National Fire Alarm Code, NFPA 72. If wired Class A, at least one
HLIM loop isolator mus t be inst all ed between e ac h HCP and betw ee n the panel and t h e fir s t and l ast HCP. See the HLIM installation
instruct ions for th e ma xi mu m nu m ber of isol ator s all ow ed p er loop an d other wiri ng ins tructi ons .
43
Page 51
CT_P
CT_N
LL_SP
City tie
LL_SN
+
-
Master Box
CT_
P
CT_
N
LL_SP
Leased line
LL_SN
+
-
+
-
leased line
alarm/
trouble
detection circuit
leased line
supervisory
detection circuit
Panel
RJ31X
RJ31X
Telephone line #1
Telephone line #2
Optional output to tel
Optional output to tel
Optional City Tie/Leased Line
FC901 provides one city tie or two leased lines to connect with local energy and polarity
reversal.
City tie and Leased line
Supervised, Power Limited
DACT Wiring
FC901 will provide two connections to Public Switched Telephone Network (PSTN).
44
Page 52
PROGRAMMING THE CONTR OL PANEL
KEYPAD P ROGR AMM I N G
Customized programming of the control panel may be accomplished through the keypad
included in the control panel.
PC PROGRAMMING
Programming the panel may also be done by a temporary connection to the programming port
with a computer. This is the recommended method to program the panel.
The Siemens FXS901-U3 software is available to allow programming the control panel by
connection to a Personal Computer (PC) with an USB port. This allows ease of operation by
preparing the program in advance and downloading to the control panel in a simple, rapid
operation.
PROGRAMMING SECURITY
The following levels of security protect the system fro m unauthorized use:
Level 1 (User) – Locked Door
Level 2 (Maintenance) – Locked Door and 4-digit Maintenance Password
Level 3 (Technician) – Locked Door and 4-digit Technical Password
The User Level is also accessible from FSD.
45
Page 53
MAINTENANCE
GENERAL
The FC901 provides maintenance functions to allow for the setting and controlli ng of various
features in the system.
The maintenance functions are protected by a four digit password. To access the maintenance
features press the “MENU” button and select Login item in the View menu, enter the four digit
code when prompted and then press “OK”.
FC901 Maintenance is separated into two levels. The user can enter a different password to
enter different levels.
Level 2: Protected by level 2 password, Level 2 provides control functions.
Level 3: Protected by level 3 password, Level 3 provides control functions and parameter
change functions.
The following functions are accessible to L2 and L3 user by selecting items in the Operate
menu.
Disable/Enable Devices
Disable/Enable NACs
Disable/Enable City Tie
Disable/Enable DACT
Disable/Enable Status Relays
Disable/Enable Detector Applications
Disable/Enable PAS
Starting and Configuring Quick Test
Set the Time
Set the Date
The functions listed below are provided specifically to L3 users.
Edit Device Labels
Edit System Labels
Program a Device
Change the Maintenance Password
Disabling any input and output devices, applications will annunciate a trouble
condition.
46
Page 54
QUICK TEST
The Quick Test mode makes it fast and easy to test a system by eliminating the need to
disconnect panel from remote connections to the Fire Department or other monitoring stations.
In this way, operator can test all devices locally without annunciating any condition to remote
connections.
To configure the Quick Test parameter s, enter L2 user level and navigate to the Quick Test
item in the Operate menu. Configure the following parameters prior to starting Quick Test:
• Quick Test Time – FC901 will automatically quit Quick Test mode after the configured
time
• Disable Output – Doesn’t activate any output on events in Quick Test Mode
• Annunciator Off – Doesn’t send any events to annunciators in Quick Test Mode.
• History Off – Doesn’t record any even ts in History Recor d in Quick Test Mode
• NAC Off – Doesn’t activate NAC’s in Quick Test Mode
To initiate the Quick Test mode, navigate through the menu using the following steps:
1) Login at L2 or L3
2) Press the Menu button
3) Press right arrow to OPER
4) Press down arrow to Quicktest
5) Press OK
6) Modify Quicktest parameters as needed-(time, NAC on/off, etc…)
7) After setting all Quicktest parameters, and while still in the Quicktest screen, Press the
Menu button
8) Press the OK button to initialize Quicktest
NOTE:The countdown timer will be indicated in the upper right corner of the main board
display.
Test conditions will be annunciated on the panel to indicate that pane l is in Quick Test
Mode. Initiation of any addressable device will not activate associated NACs if “NAC
OFF” is enabled in Quick Test mode.
By selecting the Extend (Quick Test) item in the Operate menu, L2 user can extend the quick
test time. L2 user can quit the quick test mode by selecting the Cancel (Quick Test) item in the
Operate menu.
HZM in Qui ck Test
Testing conventional detectors in Quick Test requires a few more steps than testing
addressable devices. Since the HZM only guarantees that one detector will stay in active at a
time, its detector loop must be reset after each detector is activated. This can be accomplished
in the following ways:
• By shorting the device loop for at least six seconds.
• By interrupting power to the device loop or the active device for at least six seconds.
Either of these methods will cause the active detector to reset.
The previous detector must be clear of smoke after resetting the loop or it will
generat e an ot h er alarm.
47
Page 55
This page is left intentionall y blank.
48
Page 56
APPENDIX-A: REFERENCE DATA
AWG
Ohms per Thousand Feet*
18
8.08
16
5.08
14
3.19
12
2.01
This appendix provides reference for the following topics:
Wire selection guides
Battery size calculations
WIRE SELECTION GUIDES
Resist ance of Solid Copper W ire
*NEC Chapter 9, Table 8.
Addressabl e D evice Circui t W ire Selecti on Guide
Each addressable device circuit must meet the following requirements:
Total loop resistance - 50 o h m max imum w it h 5 0 devices
Total loop capacitance - 0.5uF max line to line per km and 1.0uF max line to shield per km
The terminal blocks of Siemens SLC devices are rated for a maximum of 14AWG wire.
49
Page 57
System Current Draw Com ponents
Standby(A)
Alarm(A)
Main board
0.1590
0.1864
NAC
0
C1
SLC
C2
C3
Auxiliary power
C4
C5
City tie module
0.0017
0.0158
SLC Current Draw Component s
Standby(A)
Alarm(A)
HFP-11 / 8713
0.00140
0.00140
HFPO-11 / 8710
0.00140
0.00140
HFPT-11 / 8712
0.00140
0.00140
OOHC941
0.00075
0.00075
OOH941
0.00068
0.00068
OH921
0.00030
0.00030
OP921
0.00030
0.00030
HI921
0.00028
0.00028
FDCIO42
0.00120
0.00120
HMS / 8700 -S/D/M
0.00140
0.00140
HTRI-S / 8702
0.00140
0.00140
HTRI-D / 8703
0.00140
0.00140
HTRI-R / 8704
0.00140
0.00140
HZM / 8705
0.00140
0.00140
HCP /8706
0.00140
0.00140
ILED / 8726
0.00140
0.00140
FDOOTC441
0.00075
0.00075
FDOOT441
0.00068
0.00068
FDOT421
0.00030
0.00030
FDO421
0.00030
0.00030
FDT421
0.00028
0.00028
ABHW-4B
0.00030
0.00030
ABHW-4S
0.00030
0.00030
BATTERY SIZE CALCULATIONS
System C urrent D r aw B r eak down
SLC Current Draw Break down
Total Standby Current = 0.1590 + C2 + C4 + 0.0017(if used)
Total Alarm Current = 0.1864 + C1 + C3 + C5 + 0.0158(if used)
Where
C1 = NAC1 current + NAC2 current, should be less or equal to 2.5A.
C2 = ∑quantity of each type of detector x standby current/each
C3 = ∑quantity of each type of detector x alarm current/each
C4 = External device current draw through Aux1 and Aux2 in standby stage, either one of
Aux1 and Aux2 should be less than or equal to 0.75A.
C5 = External device current draw through Aux1 and Aux2 in alarm stage, either one of Aux1
and Aux2 should be less than or equal to 0.75A.
50
Page 58
Battery Size
Total Standby
Hours of Standby
(4, 24 or 90)
AH for
A
X Hours
=
Total Alarm
(from above)
5 Minutes of Alarm
per NFPA 72 Standard
AH for Alarm
A
X Hours
=
A.H. for
A.H. for
Calculated
De-rating
A.H.
Capacity
+ =
X 1.1
=
Current
(from above)
Required per NFPA 72
Standard
Standby
Current
Operation
Standby
Alarm
A.H.
Factor
Required
Battery
Notes:
An additional multiplier is included to compensate for the higher discharge rate in alarm.
Battery capacity decreases with age.
51
Page 59
Siemens
Cat. No.
Description
HMS-S
Manual Stati on, Single Action
HMS-D
Manual Stati on, Double Action
HMS-M
Metal Manual Station, Single Action
HMS-2S
single action manual pull station with 2-stage key switch
Siemens
Cat. No.
Description
HTRI-M
Transmit-Receiv e Interface – Mini-Module
HTRI-S
Transmit-Receiv e Interface – Single Monitor Circuit
HTRI-D
Transmit-Receiv e Interface – Dual Monitor Circuit
HTRI-R
Transmit-Receiv e Interface – Dual Monitor Circuit with Programmable Relay
HCP
Intelligent Control Point
HLIM
Line Isolator Module
FDCIO422
Input / Output Interface module
Siemens
Cat. No.
Description
DB-11
Detector Base
DB-11E
Detector Base
ADBH-11
Audible Base
ABHW-4B/ABHW4S
Audible Base
DB-HR
Relay Base
DB2-HR
Relay Base
FDBZ492
Addressable air duct housing
FDBZ492-HR
Addressable air duct housing with relay
Siemens
Cat. No.
Description
ILED-HC
Intelligent Rem ote Lamp, Ceiling mount
ILED-HW
Intelligent Rem ote Lamp, Wall mount
RL-HC
Remote Lamp, Ceili ng m ount
RL-HW
Remote Lamp, Wall mount
AD2-XHR
Air Duct Housing with Relay
AD2-P
Air Duct Housing
FDBZ492-RTL
Remote test switch
FDBZ-WT
Weather Tight enclosure
APPENDIX-B: COMPATIBLE DEVICES
DEVICES FOR ADDRESSABLE DEVICE CIRCUITS
Siemens SLC Manual Pull St ations
Siemens SLC Modules
Siemens SLC B ases
Siemens SLC A ccessories
52
Page 60
Siemens
Cat. No.
Description
8700-S
Manual Stati on, Single Action
8700-D
Manual Stati on, Double Action
8700M
Metal Manual Station, Single Action
Siemens
Cat. No.
Description
8710
Photo Detector
8712
Thermal Detect or, Fixed or Fixed/Rate of Rise
8713
Photo/Therm al Detector
Siemens
Cat. No.
Description
8702
Single input interface module
8703
Dual input interface module
8704
Single input interface module with relay
8701
Mini single input i nterface module
8706
Intelligent c ontrol point
8705
Conventional zone module
8709
Line isolat or
Siemens
Cat. No.
Description
8853
Detector Base
8715
Detector Audible Base
8716
Relay Base
Siemens
Cat. No.
Description
8726C
Intelligent Rem ote Lamp, Ceiling mount
8726W
Intelligent Rem ote Lamp, Wall mount
8727C
Remote Lamp, Ceili ng m ount
8727W
Remote Lamp, Wall mount
8741
Air Duct Housing with Relay
8743
Air Duct Housing
Point detectors
Description
OP921
Smoke detector
OH921
Smoke heat detector
HI921
Heat detector
8700 SLC Manu al Pull Stati ons
8700 SLC Detectors
8700 SLC Modules
8700 SLC Bases
8700 SLC Acces sories
Notes:
1. Siemens SLC d evices, det ectors and m odu l es, up t o a maxi m u m of 50 add resses m ay b e us ed.
2. For specific wiring and installation information, read the instructions provided with each device.
3. If more than one HCP is used on a SLC device loop, the loop must be wired Class A or the riser conductors must be installed in
accordance with the Survivability From Attack By Fire requirements in the National Fire Alarm Code, NFPA 72. I f wir ed Class A, at least
one HLIM loop isolator must be installed between each HCP and between the panel and the first and last HCP. See the HLIM installation
instruct ions for th e ma xi mu m nu m ber of isol ator s all ow ed p er loop an d other wiri ng ins tructions.
FD182UL
53
Page 61
Point detectors
Description
OOH941
Dual optical/t hermal multisensor detector
#
OOHC941
Dual optical/t hermal
Siemens
Cat. No.
Description
FT2007-U1
LED drive board
FT2008-U1
LED annunciator-16 Zone, black
FT2008-R1
LED annunciator-16 Zone, red
FT2009-U1
LED annunciator-32 Zone, black
FT2009-R1
LED annunciator-32 Zone, red
FSD901-U2
Floor repeater display, Desigo, black
FSD901-R2
Floor repeater display, Desigo, red
FSD901-U3
Floor repeater display, Cerberus, black
FSD901-R3
Floor repeater display, Cerberus, red
FCA2018-U1
Remote Peripher al M odule
Global AS A
Note: # FC901 support OOHC941 CO function. CO channel can be configured as automatic alarm event and
supervisory event in the detection tree of FC901. But it does not comply with UL 2017 standard when CO
channel was configur ed to automatic alarm event. It does com ply with UL 864.
UFP devices
54
Page 62
APPENDIX-C: TROUBLESHOOTING
ENTRY
INDICATES
Disabled
The device has been disabled
Ground
The device is in ground fault
Open
The device is in open trouble
Short
The device is in short tr ouble
Overload
The SLC line is overloaded
GeneralTrouble
The device reports general trouble
Unconfig
The system finds a SLC device that is not in the config file
TypeMismatch
The SLC device type is not consistent with the config file
CommunicationTrouble
The communication between the device and the panel is abnormal
Multiple Device Response
More than one SLC device has the sam e address
TypeUnknown
The device type is unknown to the panel
Dirty
The SLC device is dirty
Replace
The SLC device needs to be replaced
ParameterError
The SLC device has inv alid parameter setting
AddressInvalid
The address of SLC device is invalid
AddressUnspecified
The SLC device has no address
ACFail
The AC power of the system is in troubl e
MessageLost
The DACT lost some messages because of limited memory space
FatalFault
The SLC device repor ted fatal fault trouble
VoltageLow
The battery voltage is too low
VoltageHigh
The battery voltage is too high
OverCurrent
The NAC is in over current state
CircuitTrouble
The battery charge cir c uit is in trouble
BatteryAbsent
The battery is missing
ENTRY
INDICATES/NOTES
Reset
Panel reset
Silence
Silence all silenceable outputs
Unsilence
Unsilence all sil enc ed outputs
Test
Start quick test
QuitTest
Exit quick test
Acknowledge
Panel events acknowledged
Unacknowledge
Resound of the trouble/supervisory
LogIn
User level login
LogOut
User level logout
DEFINITIONS FOR EVENT HIS TORY ENTRIES
A. General
B. Sys t e m Events
55
Page 63
A - Smoke detector goes into alarm. (LED on device turns to red)
AB - Retard Period, FACP senses detector in alarm and delays alarm si gnal for 50s. In this
BC - Confirmation Period, Detector is operational for alarm at point B. If detector is still in alarm
CD – Restart next alarm verification period if new alarm occurs.
APPENDIX-D: ALARM VERIFICATION
period, no alarm event reports on FACP.
at point B, FACP will report alarm. If detector is not in alarm, system returns to standby. If the
detector re-alarms at any time during the confirmation period the FACP will alarm. The period
length is 60s.
56
Page 64
APPENDIX-E: APPLICATION SPECIFIC
ASD APPLICATIONS of H-seri es and 8700-series detector
ASD Application
ASD Description
Disable
No Applications (St andar d P hoto/thermal Detect or )
Office (Retail)
Reasonably cl ean, climate controlled atm osphere
Airborne dust, equipment, fork truck and light to medium dock
area exhaust fumes
Relativ ely clean area, temperature changes, cellular phones,
smoking
Very controlled environment, clean, temper ature closely
air ve locity
Airborne dust and tem per ature changes, living quarters, cooking
fumes, smoking
Healthcare
Higher level ri sk, relatively clean, electr onic equipment
Parking Garage
Airborne dust, c ar and di esel fumes, temperature swings
Normal to somewhat dirty env ir onm ent, heat from running
equipment
Sensitive materi als or equipment storage, clean dust-free
environment, earliest warning desired
Dirty, dusty, humid, wide temperature swings, high air velocity
DETECTION
Application Specific Detection (ASD) allows the system designer to program a detector’s
sensitivity, pre-alarm threshold, and other alarm-related parameters using English descriptions
of the detector's environment (application). This eliminates the need for detailed knowledge of
smoke detector terminology and operation. The designer can set all of the critical detector
parameters by simply selecting an application description that closely fits the one where the
detector is to be installed.
For example, to use ASD to select the optimal parameters for a detector in a hotel lobby,
select the LOBBY application in the FXS901-U3 tool for that device. The system will
automatically transmit the factory determined sensitivity, pre-alarm threshold, and detection
algorithm (R-algorithm) to the corresponding device. This eliminates the guesswork of
selecting these parameters for different environments.
Warehouse (Light Manufacturing)
Lobby
Computer Room
Dormitory
Equipment Storage ( Transformer) Room
Precious Storage ( S ensi tive Environment)
Hostile Envir onm ent
regulated, high c ost cl ean m ac hiner y oper ating, no smoking, high
57
Page 65
APPENDIX-F: TESTING/MAINTENANCE
If the system is connected to the fire department, etc., or actuates an internal system, disarm
the appropriate outputs before servicing to prevent actuation. Notify the fire department and
personnel at your facility that a System test is being performed so that any alarm sounding can
be ignored during the test. Notify the fire department before resetting the system.
Inspection, Testing, and Maintenance of the fire alarm system should be performed in
accordance with NFPA 72, The National Fire Alarm Code and all applicable local codes.
BATTERY MAINTENANCE
Perform the following tests at the recommended interval. Replace the battery set every four
years or if any of the test criteria are not met.
Initiation / Reacceptance
1. Charger Test—With the batteries fully charged and connected to the char ger, measure the
voltage across the battery set. It must read 27.3V ± 0.3V.
2. Discharge Test—With full system alarm load, the voltage on a fully charged batter y must
not fall below 20.4V after 30 minutes.
3. Load Voltage Test—With full system alarm load, the voltage on a fully charged battery must
not fall below 24.6V after one minute.
Testing Interval
1. Semiannually—Perform the Load Voltage Test.
2. Annually—Perform the Charger Test and Discharge Test.
58
Page 66
APPENDIX-G: LCD, CONTROLS AND
This indicat es that t he m ain power i s i n trouble
status and system i s working on battery.
This indicat es that t her e ar e alarm events, and
all alarm events have been acknowledged.
The Silenced LE D can onl y be steady on when
activated.
This indicat es that t her e ar e trouble events,
This indicat es that t her e is no tr ouble event in
system.
This indicat es that t her e ar e trouble events in
acknowledged.
This indicat es that t her e ar e supervisory
acknowledged.
INDICATORS
The FC901 has a buzzer, 7 LEDs, 4 navigational push buttons, 4 dedicated push buttons,
alphanumeric keypad, 3 menu control buttons (menu, cancel, ok) and a communication port
connector.
Communication Port Connector
The communication port is connected to the USB portof the computer that has the FXS901-U3
programming tool. This is used to upload and/or download panel configuration if this method of
programming is used.
The computer must be disconnected from the panel if not in use.
LEDS, Buzzer and Dedicated Pus h Buttons
The LEDs operate as follows:
This indicat es that t he system's power works
Power Green
Steady ON
OFF
normally. Both the main power and battery are
in normal status.
This indicat es that t he system is not powered
on yet. This LED can be OFF only when the
system is shut down.
Alarm Red
Silenced Yellow
Trouble Yellow
Flashing
Steady ON
OFF
Flashing
Steady ON
OFF
Steady ON
OFF
Flashing
This indicat es that t her e is no al arm event in
system.
This indicat es that t her e ar e alarm events in
system, but some of them hav e not been
acknowledged.
the following conditions are all met:
1. There are activ ated silenceable devices,
and all of them have been silenced.
2. There is no non-silenceable NAC
The Silenced LED will be OFF when above
conditions cannot be met.
and all of them have been acknowledged.
system, but some of them hav e not been
Supervisory Yellow Steady ON
events, and all of them hav e been
59
Page 67
This indicat es that t her e is no superv isory
event in system.
This indicat es that t her e ar e Ground Fault
events in syst em.
This indicat es that t her e is no Ground Fault
event in system.
This indicat es that t her e ar e gr ound fault
been acknowledged.
The Audibles On LED can only be steady on
and some of them are not silenc ed.
The Audibles On LED will be OFF when above
conditions are not met.
OFF
This indicat es that t her e ar e supervisory events
Flashing
Steady ON
in system, but some of them hav e not been
acknowledged.
Ground Fault Yellow
Audibles On Red
OFF
Flashing
Steady ON
OFF
events in system, but some of them have not
when any of the following c onditions are met:
1. There are activated NACs and some of
them are not silenced.
2. There are sil enc eable dev ic es activated
The buzzer operates as follows:
Normally OFF – indicates that the system is in normal condition or all events in the system
have been acknowledged.
ON (200 pulse per minute) – indicates that at least ONE unacknowledged alarm is present in
the system.
ON (85 pulse per minute) – indicates that at least ONE unacknowledged non-alarm (trouble,
supervisory) event is present in the system.
60
Page 68
The buttons operates as follows:
Numeric buttons for P MI oper ation. They are used to enter the password to
Alarm Silence Press
Acknowledge Press Acknowledges all unack nowledged events in system .
Reset Press
Unsilence Press
Menu Press Menu button for PMI operation.
OK Press OK button for PMI operation.
C Press Cancel button for PMI operat ion.
0-9 Press
* Press * button for PMI operati on.
Silences all silenceable devices in system. T his will c ause all activated
silenceable dev ic es to bec om e sil enc ed.
Clears all obsolete ev ents and resets all devices, except those disabl ed ones
and hold-through-reset devices in system.
Unsilences all sil enc ed dev ic es i n system. This will cause all silenced dev ices to
become activ ated.
access the maint enanc e and technician modes of the panel. It allows the user t o
program the panel usi ng these keypads without using the FXS901-U3
programming t ool.
# Press # button for PMI operation.
Four-way button Press A four-way button for menu navigation.
61
Page 69
Trouble 02/13 L2 12:12
V Open IN
Line 1
10-30-2010 12:00:00
V AutoAlarm IN
Zone 1
10-30-2010 12:00:01
LCD Dis play
The LCD operates as follows:
Line 1 – Index and Category of current selected event, User level, current time
Line 2 – Acknowledged status, Event Type
Line 3 – Customer text of the device associated with the event
Line 4 – Time when the event happened
Line 5~7 – Another event followed
The LCD can display two events at a time. User can cycle through a circular list once the first
event or last event message is reached.
Events are displayed according to the following rules:
1: Events priority:
Unacknowledged Alarm > Unacknowledged Supervisory > Unacknowledged Trouble >
Acknowledged Alarm > Acknowledged Supervisory > Acknowledged Trouble > Status > Test
2: Within events of the same priority, all events are displayed in the order of occurrence the
latest displayed the first.
3: Status events are displayed according to the event setting. If it is configured as “No display”,
it will not be listed in Event List.
When Supervisory is configured as Non-SelfRestoring, a Supervisory OUT Event will be
displayed in the event list when supervisory condition disappears. Th is also applies to Trou ble
and Status.
62
Page 70
APPENDIX-H: OUTPUT FEATURES
OFF
ON
Output State
Activation
Delay
Deactivation
Delay
On Activate
Command
On
Deactivate
Command
Output Activ at ion- and Deactivation- Delays
Each output device has a selection for Activation delay and Deactivation delay when it is
installed in the configuration. The Activation delay refers to the delay in which the output will
activate after the reception of its activation command. If the Activation delay is set to 0 (default
setting), the output immediately activates. The Deactivation delay refers to the delay in which
the output will deactivate after the reception of its deactivation command. If the Deactivation
delay is set to 0 (default setting), the output immediately deactivates.
Output device during activation delay will not respond to deactivate command. This means an
output device with activation delay will definitely be activated after receiving activate command.
Output device during deactivation delay will respond to activate command immediately and the
deactivation delay will be cancelled.
Assuming an output channel on SLC is configured to be interlocked by supervisory condition of
FACP with Activation Delay of 10s and Deactivation Delay of 10s. When FACP enters
supervisory condition at 00”00’, the output channel will be activated at 00”10’. Then if the
supervisory condition goes at 00”30’, the output channel will be deactivated at 00”40’.
This function only apply to IO module on SLC
63
Page 71
Remote
devices ON
Remote
devices OFF
Remote
devices ON
Remote
devices OFF
Remote
devices ON
Remote
devices OFF
1st Alarm
Initiated
PAS
Delay
time
15s
Alarm
Acknowledge
2nd Alarm
Initiated
Panel
Reset
Investigation time
Figure A
PAS Normal
Sequence
Figure B
When Ack
before PAS
delay time
Figure C
When 2nd
Alarm is
Initiated
APPENDIX-I: P AS / PRE-SIGNAL
PAS (Positive Alarm Sequence) and Pre-Signal features allow the user to delay the activation
of the audibles, strobes and other output devices when an initial alarm is detected. Output can
be interlocked by zones. When an initial alarm is detected, all outputs except remote devices
(off-premises devices like general relays and city tie) associated with PAS Zone (Zone
configured with PAS feature) will be activated immediately. When PAS delay timer elapses,
other remote devices will also be activated. The delay timers are configurable.
PAS
When an alarm causing device associated with a zone with PAS feature is initiated, the alarm
condition is reported on the panel. The activation of its related remote outputs (e.g. output
relays) are delayed for 15 seconds (PAS delay time) waiting for a manual acknowledgement
response.
If no response is received within 15 seconds, the panel proceeds to activate the associated
remote outputs. See Figure A.
If the alarm event is acknowledged during the PAS delay time, the programmable PAS
investigation time (60-180 seconds) is added to the PAS delay time before remote outputs are
activated. See Figure B.
However, if a 2nd alarm is initiated anytime during the PAS delay time or PAS investigation
time, the remote output devices are immediately activated. See Figure C.
Pressing the Reset button at anytime during the PAS sequence will initiate a reset condition
and restore the panel to stand-by state.
64
Page 72
Pre-Signal
1st Alarm
Initiated
2nd Alarm
Initiated
Panel
Reset
Pre-Signal Delay time
Figure A
Figure B
When 2nd
Alarm is
Initiated
Audible ON
Audible OFF
Audible ON
Audible OFF
Pre-Signal
Normal
Sequence
When an alarm causing device in a Pre-Signal input group is initiated, the alarm condition is
reported at the panel. Its associated NACs are not activated until the programmed
investigation delay has relapsed or 2nd Alarm is initiated anytime during the Pre-Signal delay
time (see figure below).
Pressing the reset button at anytime during the Pre-Signal sequence will initiate a reset
condition and restore the panel to stand-by state.
65
Page 73
APPENDIX-J:
The DACT (Digital Alarm Communicator Transmitter) is an optional module for the FC901
control panel that allows transmission of event information to a remote receiver at a monitoring
station using a dial-up modem connection. These events are transmitted in one of the following
formats:
A few aspects of the operation of the DACT are clarified below.
Lines / Accounts
The DACT supports two independent lines and can report to two separate accounts. “Lines”
should not be confused with “accounts”. “Lines” are the actual telephone cords that plug into
the DACT module, which are in turn connected to the PSTN (Public Service Telephone
Network). If line 1 is not functioning (no dial tone, etc.), the DACT will try line 2 instead.
“Accounts” are the phone numbers that the DACT dials. Once the DACT has found a “live” line
to dial out on, it transmits the event(s) on that line, starting with the first account that is
configured to send that event. If the first account does not respond after the programmed
number of attempts (busy, account not responding, etc.), the DACT will automatically attempt
to send the event to the second account, providing the event is set to report for that account.
DAC T INFORMATION OVERVIEW
The DACT may be configured for connection to lines that ar e set up for Rotary and/or Tone
dialing. See the FC901 Programming Manual, P/N 315-049 4033, for deta i ls.
Must / Can / Must Not
Each event type (Alarm, Alarm Restoral, etc.) can be configured as “Must”, “Can” or “Must Not”
report independently for each account. If configured as “Must Not” repor t, the DACT will not
report the event to that account. If configured as “Can” report, the DACT will only attempt to
report the event to the account if it has not reported it on the other account. If configured as
“Must” report, the DACT will attempt to report the event to the account even if it has already
reported it to the other account. In summary:
Must Report The event will be reported to this account even if it has repor ted it to the other
account.
Can Report The event will only report to this account if it has not been successfully
reported to the other account.
Must Not Report The event will never report to this account.
66
Page 74
To configure an event to be reported to Account 1 and Account 2, set it to Must report on both.
Scenario 1 – Must/
Must
Alarm Event is set to Must Report on Account 1 and
2
.
Step 1:
Panel goes into alarm.
Step 2:
Panel tries to send event
to Account 1, but is
unsuccessful.
N
Account 1
Account
2
Step 3:
Panel keeps trying to send event to Account 1 until the programmed Number
Of Attempts has been reached.
Step 4
:
Panel switches to Account
2 and attempts to transmit,
but is unsuccessful too.
N
Account 1
Account 2
Step 5:
Panel keeps trying to send event to Account 2
until the programmed Number
Of Attempts has been reached.
Done.
If the event needs to be reported to either Account 1 or Account 2, set it to Can report on both.
If it has to be reported to Account 1, but only needs to be reported on Account 2 if Account 1 is
temporarily out-of-order, set the event to Must Report on Account 1 and Can Report on
Account 2.
Following are examples for illustration purposes.
Note: If both accounts failed to send an event within configured Number of Attempts, the event
will be discarded and a message lost condition will be declared on panel. This means the
panel will not try infinitely to send an event and each account can try at most (programmed
Number of Attempts) times. This applies to all Scenarios of DACT transmission.
67
Page 75
Scenario 2 – Must/Can
Alarm Event is set to Must Report on Account 1 and Can
Report on Account 2. Panel fails on Account 1 the first
time.
Step 1:
Panel goes into alarm.
Step 2:
Panel tries to send event
to Account 1, but is
unsuccessful.
N
Account 1
Account 2
Step 3:
Panel keeps trying to send event to Account 1 until the programmed Number
Of Attempts has been reached.
Step 4:
Panel switches to Account
2 and attempts to transmit,
but is unsuccessful too.
N
Account 1
Account 2
Step 5:
Panel keeps trying to send event to Account 2 until the programmed Number
Of Attempts has been reached.
Done.
68
Page 76
Done.
Scenario 3
–
Must/Can
Alarm Event is set to Must Report on Account 1 and Can
Report on Account
2
. Panel succeeds on Account 1 the
first time
.
Step
1
:
Panel goes into alarm.
Step 2:
Panel tries to send event
to Account 1 successful.
YAccount 1
Account 2
Step 3:
Panel does NOT attempt to send event to Account 2, since Account
2 is set for
Can Report and the event was transmitted to Account 1 successfully.
69
Page 77
Scenario 4 – Can/Can
Alarm Event is set to Can Report on Account 1 and
Account 2. Panel succeeds on Account 2 before Account
1.
Step 1:
Panel goes into alarm.
Step 2:
Panel tries to send event
to Account 1, but is
unsuccessful.
NAccount 1
Account 2
Step 3:
Panel keeps trying to send event to Account 1 until the programmed Number
Of Attempts has been reached.
Step 4:
Panel switches to Account
2 and successfully
transmits the event.
Y
Account 1
Account 2
Done.
Note: The same sequence of events would happen if Account 2 was set to
Must Report.
70
Page 78
DACT Compatible Alarm Communicators
Manufacturer
Model
Communication
Installation
Tellular
TG7GFS04
GSM
56044102
Bosch
C900V2
IP
F01U087780-01
DSC
TL300CF
IP
29007636/29007842
DSC
3G370-CF
GSM
29008179
The FC901-U3/-R3 DACT is also compatible with Alarm communicators that utilized different
communication technologies (IP and GSM technologies) to connect to compati ble Receivers
using compatible protocol listed within this documentation.
COMPATIBLE ALARM COMMUNICATORS
Number
Technology
Part Number
NOTE:
DACT is configured with the alarm communicator for other transmission
technologies, off-premise signaling for UL. DACT is used for off-premise signal
transmission for ULC.
When using these alarm communicators, the DACT shall be configured for
Contact ID.
Refer to the Alarm Communicator Installation Instruction for compatible
receivers.
Wiring between the DACT and the alarm communicator shall be within 20 feet,
and in conduit.
The C900V2 shall be installed in accordance with its installat ion instructions.
71
Page 79
APPENDIX-K:DRIFT COMPENSATION
The H-Series/8700 optical detector cannot implement drift compensation on its own. Drift
compensation is the panel’s respons ibi lity.
While t he system is running, the detector sends its chamber real-time values to the panel
periodically and does not do compensation by itself.
For the first hour after a panel startup, the panel will check the detector chamber values every
10 minutes. After that, the panel will check the chamber reading every 24 hours. If the panel
detects the detector is a little dirty than before, it would send a compensation value to detector.
If a panel has detected that a detector has reached the upper limit of compensation, the panel
reports a “dirty” trouble. Otherwise the pan e l will continuously compensate the detector until it
reaches the upper limit.
72
Page 80
APPENDIX-L: GLOSSARY
AC Power Fail. Refers to a condition in which AC power loss is detected by the system.
Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm
for fire from a manual station, a waterflow alarm, or an automatic smoke detector.
Alarm Silence Inhibit. An option that prevents an operator from silencing the notification
appliances for a preset period of time.
Alarm System. A combination of compati ble initiating devices, control panels, and notification
appliances designed and installed to pr oduce an alarm signal in the event of a fire.
Alarm Verification. A preset option that causes the control panel to verify alarms originated by
smoke detectors before indicating an alarm.
Annunciator. A remotely located, electrically powered display, separate from the control
panel, containing LEDs or lamps to indicate the states of the fire alarm system.
Audible Signal. An audible signal is a sound made by one or more audible notification
appliances, such as bells or horns, in response to the operation of an initiating device.
Auto-Silence. The capability of a control to automatically silence the notification appliances
after a preset period of time.
Class A Circuit. An initiating device or notification appliance circuit within which all
components remain fully functional, even though a single open or ground exists in the circuit.
Class B Circuit. An initiating device or notification appliance circuit within which some or all
components may be disabled with a single open exists in the circuit.
Detector - FirePrint™. An intelligent fire detector that blends photoelectric, thermal and neural
network technologies for superior protection without false alarms.
Detector - Smoke, Photoelec tr ic Type. A detector employing the photoelectric principle of
reflection or obstruction of light by smoke.
Detector - Thermal Type. An addressable thermal sensor that is programmable as either a
fixed temperature (135° F) or as a rate of rise detector.
Enable / Disable. Refers to the state of individual circu its (inputs and outputs) or logic
functions regardless of the presence of its corresponding modules.
End Of Line (EOL). A device used to terminate a supervised circuit.
Ground Fault. A trouble condition in which a low resistance has been detected between the
system wiring and conduit ground.
Hold-Thru Reset Condition. Refers to a condition where the hold-thru reset output will remain
in its current state before and after the reset until the OFF time delay has elapsed. Initiation of
73
Page 81
fan restart usage has higher priority than the OFF time delay and will therefore immediately
deactivate the hold-thru reset outputs.
Initiating Device. A manually or automatically operated device such as a manual pull station,
smoke detector, heat detector, waterflow switch or tamper switch.
Initiating Device Circuit (IDC). A circuit to which initiating devices are connected.
Labeled. Equipment or materials to which have been attached a label, symbol, or other
identifying mark of an organization acceptable to the authority having jurisdiction and
concerned with product evaluation, that maintains periodic inspection of the production of such
labeled equipment or materials. And by whose labeling the manufacturer indicates compliance
with appropriate standards or performance in a specified manner.
Listed. Equipment or materials included in a list published by an organization acceptable to
the authority having jurisdiction and concerned with product evaluation, that maintains periodic
inspection of production of listed equipment or materials. And whose listing states either that
the equipment or material meets appropriate standards or has been tested and found suitable
for use in a specified manner.
NEC. National Electrical Code also published as NFPA standard 70.
Notification Appliance. An electrically operated appliance used to indicate the system status
such as a bell, horn, strobe light or speaker.
Notification Appliance Circuit (NAC). A circuit to which notification appliances are
connected.
Power Supply. That portion of the fire alarm control panel, which provides the power needed
to operate all control panel modules, as well as that, needed to operate all electrically powered
initiating devices and all notification appliances.
Programming Tool. Refers to an external proprietary softwar e package that allows the user to
program the panel (FXS901-U3 for the FC901 panel).
Quick Test. A term pertaining to the test mode of the system, that automatically resets after a
service technician tests initiating devices.
Reset Condition. Condition in which the panel is forced to return to its normal state, usually
performed by pressing the “SYSTEM RESET” button after all known events / conditions are
cleared.
Supervisory. A signal indicating the operation of a supervisory device.
Supervisory Device. A device that monitors the condition of a sprinkler system such as a
gate-valve switch, water-level switch, low pressure switch, low temperature switch or fire pump
monitor.
Trouble Signal. An audible signal indicating trouble of any nature, such as a circuit break or
ground, occurring in the device or wiring associated with a fire alarm signal.
74
Page 82
Waterflow Switch. An assembly approved for service and so constructed and installed that
any flow of water from a sprinkler system equal to or greater than that from a single automatic
sprinkler head will result in activation of this switch and subsequent indication of an alarm
condition.
Zone. A designated area of a building. Commonly, zone, is interchanged with initiating device
circuit.
Serial interface circuit. Circuit connect to annunciator, RPM (FCA2018-U1).
Signaling line circuit. Circuit connect to field devices.