Siemens FC7xx, FT724 Operation Manual

FC7xx / FT724
Building Technologies
Fire control panel / fire terminal
Operation Manual
IP6
A6V10211076_i_en_--
2015-12-15 Control Products and Systems
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-
15
Legal notice
Technical specifications and availability subject to change without notice.
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved.
Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724-2424 www.siemens.com/buildingtechnologies
Edition: 2015-12-15 Document ID: A6V10211076_i_en_--
© Siemens Switzerland Ltd, 2008
2 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-
15
Table of contents
1 About this document ............................................................................. 9
1.1 Applicable documents ................................................................................10
1.2 Technical terms and abbreviations .............................................................10
1.3 Revision history .........................................................................................11
1.4 How displays are represented in the document ..........................................13
1.5 Download center ........................................................................................13
2 Safety ............................................................................................... 14
2.1 Safety instructions .....................................................................................14
2.2 Safety regulations for the method of operation ...........................................16
2.3 Standards and directives complied with......................................................18
2.4 Release Notes ...........................................................................................18
2.5 Cyber security disclaimer ...........................................................................18
3 Setup of the Person Machine Interface .................................................. 19
3.1 PMI............................................................................................................19
3.1.1 EVAC NL ....................................................................................21
3.1.2 Key switch (optional) ...................................................................22
3.1.3 Standard keys .............................................................................22
3.1.4 Other alarms ...............................................................................23
3.2 Person Machine Interface with FBP [AU]....................................................23
3.3 Display ......................................................................................................26
3.3.1 Normal view ................................................................................26
3.3.2 Extended view ............................................................................27
3.3.3 Fire brigade view.........................................................................27
3.3.4 Display with window and list ........................................................27
3.3.5 Display with window and input field .............................................28
3.3.6 Display with window and command response ..............................28
3.4 Soft keys ...................................................................................................29
3.5 Navigation buttons .....................................................................................30
3.6 Keypad ......................................................................................................30
3.6.1 Menu button ................................................................................31
3.6.2 Button 'ok' ...................................................................................31
3.6.3 Button 'C' ....................................................................................31
3.7 LEDs .........................................................................................................31
3.8 Menu structure...........................................................................................32
3.9 Cerberus Remote ......................................................................................33
3.10 Cerberus Mobile ........................................................................................34
4 Operation functions............................................................................. 35
4.1 Selection and opening / execution ..............................................................35
4.2 Scrolling ....................................................................................................35
4.3 Indication of the position and length of the list ............................................36
4.4 Shortcut .....................................................................................................36
4.5 Favorites ...................................................................................................36
3 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
4.6 Entry of numbers and letters ...................................................................... 37
4.7 Cerberus Remote operation modes ........................................................... 38
4.8 Cerberus Mobile operation modes ............................................................. 39
5 Operation ...........................................................................................40
5.1 ALARM Procedure ..................................................................................... 40
5.2 ALARM procedure PMI with FBP [AU] ....................................................... 42
5.3 Procedure in case of Fault ......................................................................... 44
5.4 Switching off / Switching on ....................................................................... 45
5.4.1 Switching a detector zone off / on................................................ 45
5.4.2 Switching a detector off / on ........................................................ 48
5.4.3 Temporary switching-off .............................................................. 51
5.4.4 Switching off / on the remote transmission Fire ........................... 53
5.4.5 Switching off alarm activation ...................................................... 57
5.4.6 Switching off sabotage evaluation [DE] ....................................... 57
5.5 Log in / Change access level ..................................................................... 58
5.6 Logging out from an access level ............................................................... 58
5.7 Switching between 'Manned' / 'Unmanned' operation modes ...................... 59
5.8 Changing visibility ...................................................................................... 60
5.8.1 Deactivating standby ................................................................... 60
5.8.2 Activating / deactivating expanded visibility ................................. 61
5.9 Main menu / Open menu item .................................................................... 62
5.10 Execute commands – Basics ..................................................................... 62
5.10.1 Execute commands – General .................................................... 63
5.10.2 Execute commands – object-oriented .......................................... 64
5.10.3 Executing commands – function-oriented .................................... 66
5.10.4 Hide command confirmation message ......................................... 67
5.11 Selecting elements or events ..................................................................... 68
5.11.1 Select events .............................................................................. 68
5.11.2 Selection in the topology ............................................................. 69
5.11.3 Searching for elements ............................................................... 71
5.12 Testing ...................................................................................................... 74
5.12.1 Testing detectors ........................................................................ 74
5.12.2 Carrying out an installation test ................................................... 75
5.12.3 Carrying out the walk test ............................................................ 75
5.12.4 Control test ................................................................................. 76
5.12.5 Testing indicators ........................................................................ 77
5.13 Activation / Deactivation / Reset ................................................................. 78
5.13.1 Activating an alarm indicator (AI) ................................................. 78
5.13.2 Deactivating / Activating alarm devices ....................................... 81
5.13.3 Activating / resetting zone ........................................................... 82
5.13.4 Activating / deactivating fire control ............................................. 85
5.13.5 Activating evac controls .............................................................. 87
5.14 Show information ....................................................................................... 89
5.14.1 Polling alarm counters / remote transmissions ............................. 89
5.14.2 Polling the IP address of the 'Station' .......................................... 90
5.15 Polling reports ........................................................................................... 91
4 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-
15
5.16 Entering the configuration ..........................................................................92
5.17 Auto-configure station ................................................................................93
5.18 Auto-configure line .....................................................................................94
5.19 Enabling / Disabling Cerberus Remote .......................................................96
5.20 Connecting Cerberus Remote ....................................................................98
5.21 Setting up Cerberus Remote link with integrated IP ....................................99
5.22 Operating Cerberus Remote ......................................................................99
5.23 Specifying the operation mode for Cerberus Mobile .................................100
5.24 Enabling a smartphone ............................................................................100
5.25 Removing a smartphone ..........................................................................101
5.26 Polling / Deleting the event memory .........................................................102
5.27 Settings / Administration ..........................................................................103
5.27.1 Change language......................................................................103
5.27.2 PIN administration .....................................................................104
5.27.3 Setting the buzzer sound level ..................................................105
5.27.4 Adjusting the display brightness ................................................106
5.27.5 Setting time and date ................................................................106
5.28 Entering/Changing customer text .............................................................107
5.29 Insert printing paper .................................................................................107
5.30 Switching off the printer ...........................................................................110
5.31 Show version ...........................................................................................110
6 System functions .............................................................................. 111
6.1 Note on the configuration of the local fire detection installation .................111
6.2 Operating condition ..................................................................................112
6.3 Operation modes .....................................................................................112
6.3.1 Normal operation ......................................................................112
6.3.2 Isolation ....................................................................................113
6.3.3 Renovation ...............................................................................113
6.4 Normal operation .....................................................................................113
6.5 Test .........................................................................................................114
6.5.1 Detector test .............................................................................114
6.5.2 Installation test ..........................................................................114
6.5.3 Walk test ...................................................................................115
6.5.4 Control test ...............................................................................115
6.5.5 Test variants .............................................................................115
6.6 Isolation ...................................................................................................116
6.7 Renovation ..............................................................................................116
6.8 Access level and access rights ................................................................116
6.8.1 PIN input dialog ........................................................................118
6.8.2 Logout timeout ..........................................................................118
6.9 Visibility ...................................................................................................118
6.9.1 Standby visibility .......................................................................119
6.9.2 Expanded visibility ....................................................................119
7 Commands with required access levels ............................................... 120
7.1 'Switching on/off' command group ............................................................120
7.2 Command zone 'Test' ..............................................................................121
5 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
7.3 'Activating/deactivating' command group .................................................. 123
7.4 Command group 'Information' .................................................................. 124
7.5 'Configuration' command group ................................................................ 124
7.6 'Maintenance' command group ................................................................ 125
7.7 'Report' command group .......................................................................... 126
7.8 Other commands ..................................................................................... 126
8 List of elements ................................................................................ 127
9 System description ............................................................................ 129
9.1 Overview ................................................................................................. 129
9.2 Topology ................................................................................................. 131
9.2.1 Hardware tree ........................................................................... 131
9.2.2 Detection tree ........................................................................... 132
9.2.3 Control tree ............................................................................... 136
9.2.4 Operating tree ........................................................................... 138
9.2.5 Network tree ............................................................................. 140
9.2.6 Assigning with the hardware tree............................................... 141
9.2.7 Functional allocation ................................................................. 142
9.3 Acquisition ............................................................................................... 143
9.4 Evaluation ............................................................................................... 144
9.5 Control .................................................................................................... 148
9.5.1 Fire control................................................................................ 149
9.5.2 Evacuation control .................................................................... 150
9.5.3 Extinguishing control with sprinkler ............................................ 152
9.5.4 Extinguishing control with extinguishing control unit XC10 ......... 153
9.5.5 Damper control ......................................................................... 154
9.6 Alarm verification concept (AVC) ............................................................. 158
9.6.1 Attendance check ..................................................................... 159
9.6.2 Investigation time ...................................................................... 159
9.6.3 Example of a verification process .............................................. 159
9.6.4 Fire alarming ............................................................................. 161
9.7 Intervention concept (IC) .......................................................................... 163
9.7.1 Attendance check ..................................................................... 165
9.7.2 Intervention monitoring.............................................................. 165
9.7.3 Example of an intervention process ........................................... 165
9.7.4 Intervention alarming ................................................................ 167
9.8 Events ..................................................................................................... 168
9.8.1 Event categories ....................................................................... 168
9.8.2 Event status identification.......................................................... 169
9.8.3 Event memory .......................................................................... 169
9.8.4 Message overview .................................................................... 170
9.9 List representation and list types .............................................................. 171
9.9.1 Event lists ................................................................................. 171
9.9.2 Element lists ............................................................................. 172
9.9.3 Selection lists ............................................................................ 172
9.10 Version display for station / configuration data ......................................... 173
6 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-
15
10 Faults / Troubleshooting .................................................................... 174
11 System maintenance ........................................................................ 175
11.1 Maintenance recommendation .................................................................175
11.2 Opening the control panel [DE] ................................................................175
Glossary ................................................................................................... 176
Index ...................................................................................................... 179
7 | 184
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
8 | 184
A
bout this document
Applicable documents
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15

1 About this document

Goal and purpose
This document describes the operation of fire control panels and fire terminals in the fire detection system FS720. The reader shall understand the structure of a fire detection installation, the PMI setup and the functions in the overall system. This understanding makes an adequate behaviour possible in the event of fire or fault.
Scope
The document applies to the fire control panels and the fire terminal of type Fx72x, introduction package IP6.
Target groups
The information in this document is intended for the following target groups:
Target group Activity Qualification
1
Operating personnel
Commissioning personnel
Maintenance personnel Carries out all maintenance work.
Carries out procedures to correctly operate the product.
Configure the product at the place of installation according to customer-specific requirements.
Check the product operability and release the product for use by the operator.
Searches for and corrects malfunctions.
Checks that the products are in perfect working order.
Searches for and corrects malfunctions.
Source language and reference document
The source/original language of this document is German (de).
The reference version of this document is the international version in English.
The international version is not localized.
No particular basic training is needed.
Has been instructed by the commissioning personnel.
Has obtained suitable specialist training for the function and for the products.
Has attended the training courses for commissioning personnel.
Has obtained suitable specialist training for the function and for the products.
Building Technologies
Document identification
The document ID is structured as follows:
ID code Examples
ID_ModificationIndex_Language_COUNTRY
-- = multilingual or international
A6V10215123_a_de_DE A6V10215123_a_en_-­A6V10315123_a_--_--
Date format
The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD).
9 |
About this document
Applicable documents
1
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
The 'i' symbol identifies supplementary information and tips for an easier way of
Conventions for text marking
Markups Special markups are shown in this document as follows:
Requirement for a behavior instruction
1.
2.
Version, option, or detailed information for a behavior instruction
Intermediate result of a behavior instruction
End result of a behavior instruction
[➙ X] Reference to a page number
'Text' Quotation, reproduced identically
<Key> Identification of keys
>
Text Identification of a glossary entry
Supplementary information and tips
working.
Behavior instruction with at least two operation sequences
Numbered lists and behavior instructions with an operation sequence
Relation sign and for identification between steps in a sequence, e.g., 'Menu bar' > 'Help' > 'Help topics'

1.1 Applicable documents

Document ID Title
008399 XC10 Extinguishing Control Panel, Technical Manual
A6V10210416 FS720 Fire Detection System, Commissioning / Maintenance / Troubleshooting
A6V10210424 FS720 Fire Detection System, Configuration
A6V10217440 FS720 Fire Detection System, Inscription Strips
A6V10479789 FS720 Fire Detection System, Inscription Strips [AU]
A6V10418718 FXS7224 Cerberus Mobile, Commissioning

1.2 Technical terms and abbreviations

You will find details of technical terms and abbreviations in the 'Glossary' chapter.
10 | 184
About this document
Revision history
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15

1.3 Revision history

The first edition of a language version or a country variant may, for example, be
The reference document's version applies to all languages into which the reference document is translated.
version 'd' instead of 'a' if the reference document is already this version.
The table below shows this document's revision history:
Version Edition date Brief description
i 2015-12-15 Edition for IP6
New: Polling the IP address of the 'Station' Person Machine Interface with FBP [AU] ALARM procedure PMI with FBP [AU] Glossary entries in the text marked with '' Damper control Cyber security disclaimer Revised: Chapter 'Deactivating / activating alarm devices' adapted for PMI with FBP [AU],
referenced documents updated. Information added in chapter 'Cerberus-Remote operation modes' for configuration of the permanent operation mode. Information added to chapter 'Change language' on the preferred language and on retaining the language after restarting. Safety and warning notices updated in chapter 'Switching off/on' and subchapters. Information added to chapter 'PIN administration' on PIN configuration in Engineering Tool. Information added to chapters 'Carrying out an installation test' and 'Installation test' on manual call point zones and flashing behavior of the internal alarm indicator. Information added to chapters 'Testing detectors' and 'Detector test' on the validity of the detector test for all detector zone types. 'Information' and 'Maintenance' command groups updated. # symbol added in chapter Event status identification [ 169]
1
h 2014-02-10 Chapters 'Commands with required access levels' and 'LEDs' updated
Building Technologies
11 |
About this document
Revision history
1
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
Version Edition date Brief description
g 2013-11-14 Edition for IP5
Change to date format according to ISO 8601 New: PIN administration Cerberus Mobile Cerberus Mobile operation modes Specifying the operation mode for Cerberus Mobile Enabling a smartphone Removing a smartphone Polling the isolation time Expiry reminder for temporary switching-off Polling reports 'Report' command group Revised: 'Temporary switching-off' for levels 'Zone' and 'Detector', 'Override for different
settings' in 'Temporary switching-off', information on 'Temporary switching-off' in 'Switching a detector zone off / on' and 'Switching a detector off / on', menu structure, information on license keys, operating Cerberus-Remote with a PC keyboard, country-specific pre-configuration for 'Counter control', 'Commands with required access levels'
f 10.2012 Correction to 'Temporary switching-off' of a 'Zone'
e 08.2012 IP4 edition
Revised: Polling the alarm counter, command group 'Information' Commands revised, Test chapter revised, 'Walk test' new, note concerning buzzer
volume according to EN 54-2 Para. 12.10.2
d 07.2010 Edition MP3.0 XS:
Revision history redefined and standardized, GAP new, router station new, CAP removed, commands revised, glossary revised, new chapter: "Change language"
c 03.2009 Commands revised
b 10.2008 Tamper alarm, new
a 07.2008 First edition
12 | 184
About this document
How displays are represented in the document
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15

1.4 How displays are represented in the document

You will also find information about search variants and links to mobile
With very few exceptions, the fire control panels and fire terminals are displayed in this document in tables.
Deviations between the original and the table are indicated by means of examples in the figures below:
Figure 1: Display w ith window and bar
1
Main menu Exit with <C>
Message summary Functions Favorites Topology
Function
On/Off
Table representation: Display without window
Selecting element category
Zone Section Area Sounder Physical channel
Table representation: 'Select element category' window without bar
(1) (2) (3) (4)
Element search Event memory Login/logout Settings/administration
Function
All
(1) (2) (3) (4) (5)
Access level 3
LED
test
The table representation has the following key deviations from the original:
Font and representation (not inverted)
Windows are indicated separately without display background
No bars to indicate the position and list length
No frame around selection
(5) (6) (7) (8)

1.5 Download center

You can download various types of documents, such as data sheets, installation instructions, and license texts via the following Internet address:
http://siemens.com/bt/download
κ Enter the document ID in the 'Find by keyword' input box.
applications (apps) for various systems on the home page.
Building Technologies
13 |
Safety
Safety inst
ructions
2
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15

2 Safety

2.1 Safety instructions

The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements:
Symbol for danger
Signal word
Nature and origin of the danger
Consequences if the danger occurs
Measures or prohibitions for danger avoidance
Symbol for danger
This is the symbol for danger. It warns of risks of injury. Follow all measures identified by this symbol to avoid injury or death.
Additional danger symbols These symbols indicate general dangers, the type of danger or possible
consequences, measures and prohibitions, examples of which are shown in the following table:
General danger Explosive atmosphere
Voltage/electric shock Laser light
Battery Heat
Signal word
The signal word classifies the danger as defined in the following table:
Signal word Danger level
DANGER
WARNING
CAUTION
NOTICE
DANGER identifies a dangerous situation, which will result directly in death or serious injury if you do not avoid this situation.
WARNING identifies a dangerous situation, which may result in death or serious injury if you do not avoid this situation.
CAUTION identifies a dangerous situation, which could result in slight to moderately serious injury if you do not avoid this situation.
NOTICE
observance.
identifies possible damage to property that may result from non-
14 | 184
Safety
Safety instructions
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15
How risk of injury is presented
Nature and origin of the danger
Measures / pr
ohibitions for danger avoidance
Nature and origin of the danger
Information about the risk of injury is shown as follows:
WARNING
Consequences if the danger occurs
How possible damage to property is presented
Information about possible damage to property is shown as follows:
NOTICE
Consequences if the danger occurs
Measures / prohibitions for danger avoidance
2
Building Technologies
15 |
Safety
Safety regulations for the method of operation
2
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
Electrical voltage
regulations.
Noncompliance with the following safety regulations
Compliance w
ith the following regulations is required.

2.2 Safety regulations for the method of operation

National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation, operation or disposal of the product apply at the place of operation, then these must also be taken into account together with the safety regulations in the product documentation.
Electrical installations
WARNING
Electric shock
Work on electrical installations may only be carried out by qualified electricians or by instructed persons working under the guidance and supervision of a qualified electrician, in accordance with the electrotechnical
Wherever possible disconnect products from the power supply when carrying out commissioning, maintenance or repair work on them.
Lock volt-free areas to prevent them being switched back on again by mistake.
Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
Route mains connections to products separately and fuse them with their own, clearly marked fuse.
Fit an easily accessible disconnecting device in accordance with IEC 60950-1 outside the installation.
Produce earthing as stated in local safety regulations.
CAUTION
Risk of injury to persons and damage to property
Specialist electrical engineering knowledge is required for installation.
Only an expert is permitted to carry out installation work.
Incorrect installation can take safety devices out of operation unbeknown to a layperson.
16 | 184
Safety
Safety regulations for the method of operation
2
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15
Mounting, installation, commissioning and maintenance
If you require tools such as a ladder, these must be safe and must be intended for the work in hand.
When starting the fire control panel ensure that unstable conditions cannot arise.
Ensure that all points listed in the 'Testing the product operability' section below are observed.
You may only set controls to normal function when the product operability has been completely tested and the system has been handed over to the customer.
Testing the product operability
Prevent the remote transmission from triggering erroneously.
If testing building installations or activating devices from third-party companies,
you must collaborate with the people appointed.
The activation of fire control installations for test purposes must not cause injury to anyone or damage to the building installations. The following instructions must be observed:
Use the correct potential for activation; this is generally the potential of the
building installation. – Only check controls up to the interface (relay with blocking option). – Make sure that only the controls to be tested are activated.
Inform people before testing the alarm devices and allow for possible panic responses.
Inform people about any noise or mist which may be produced.
Before testing the remote transmission, inform the corresponding alarm and
fault signal receiving stations.
Modifications to the system design and the products
Modifications to the system and to individual products may lead to faults, malfunctioning and safety risks. Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions.
Modules and spare parts
Components and spare parts must comply with the technical specifications defined by Siemens. Only use products specified or recommended by Siemens.
Only use fuses with the specified fuse characteristics.
Wrong battery types and improper battery changing lead to a risk of explosion.
Only use the same battery type or an equivalent battery type recommended by Siemens.
Batteries must be disposed of in an environmentally friendly manner. Observe national guidelines and regulations.
Disregard of the safety regulations
Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation. This applies in particular to the following damage:
Personal injuries or damage to property caused by improper use and incorrect application
Personal injuries or damage to property caused by disregarding safety instructions in the documentation or on the product
Personal injury or damage to property caused by poor maintenance or lack of maintenance
Building Technologies
17 |
Safety
Standards and directives complied with
2
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
Limited or non
-
existent fire detection
detection installation.
Incorrect planning and/or configuration
detection installation.

2.3 Standards and directives complied with

A list of the standards and directives complied with is available from your Siemens contact.

2.4 Release Notes

Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.
WARNING
Personal injury and damage to property in the event of a fire.
Read the 'Release Notes' before you plan and/or configure a fire detection installation.
Read the 'Release Notes' before you carry out a firmware update to a fire
NOTICE
Important standards and specifications are not satisfied. Fire detection installation is not accepted for commissioning. Additional expense resulting from necessary new planning and/or configuration.
Read the 'Release Notes' before you plan and/or configure a fire detection installation.
Read the 'Release Notes' before you carry out a firmware update to a fire

2.5 Cyber security disclaimer

Products, solutions and services from Siemens include security functions to ensure the secure operation of building automation and control, fire safety, security management, and physical security systems. The security functions on these products, solutions and services are important components of a comprehensive security concept. Drafting, implementing and managing a comprehensive and up­to-date security concept, customized to individual needs, is nevertheless necessary, and may result in additional plant- or site-specific preventive measures to ensure secure operation of your site regarding building automation and control, fire safety, security management, and physical security. These measures may include, for example, separating networks, physically protecting system components, user training, multi-level defensive measures, etc. For additional information on security as part of building technology and our product, solution and service offerings, please contact your Siemens sales representative or project department. We strongly recommend to always comply with our security advisories on the latest security threats, patches and other related measures.
18 | 184
http://www.siemens.com/cert/en/cert-security-advisories.htm
Setup of the Person Machine Interface
PMI
4
A6V10211076_i_en_
--
Fire Safety
2015-12-15

3 Setup of the Person Machine Interface

3.1 PMI

All stations (fire control panel or fire terminal) have an integrated operating unit. The operating unit includes the Person Machine Interface, through which the fire detection installation can be operated. All important information from the fire detection installation is indicated spontaneously on the PMI or can be polled there.
3
1 Alarm indicator Light up red in the event of an alarm
2 Display Event indication, e.g. type, place, status of event
Menu, element and command indication
Instructions may be displayed in the event of an alarm
3 Navigation buttons
4
Keypad with Menu key, ok key and Cancel key
5 Area for fitting options Printer
For navigation in the display for e.g. menu and command selection and scrolling in lists.
Keypad for PIN entry (password), shortcut (menus), address entry (element ID), parameter entry, entry of customer text
The menu button opens the main menu
The <ok> button can be used to run a selected command or open a
menu item. In windows with an entry field, the <ok> button moves the cursor to the next entry.
With the <C> cancel button, any operation sequence can be canceled, and any open list or window can be closed.
EVAC [NL]
LEDs
Building Technologies
19 | 18
Setup of the Person Machine Interface
PMI
3
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
Inscription strips may be inserted to label the PMI.
6 Key switch (optional) An access level can be enabled with the key switch.
The accessible access level is configurable.
The key switch has two positions: On (horizontal position), Off
(vertical position)
7 <Alarm device> button
Deactivates the alarm devices in the event of alarm (password required)
8 System fault LED (yellow) Lights up yellow when a fault is present
9 Operation LED (green) Lights up green during operation
A <More alarms> button Pressing <More alarms> opens the 'ALARMS' event list.
If the 'ALARMS' event list is already open, <More alarms> assumes the function of the button <>, changing to the next alarm event upon activation.
S Softkeys 1–3
Softkeys are buttons by means of which functions may be carried out that are displayed in the three fields of the softkey line on the display.
These three black fields contain the names of the functions in white font.
The functions of the softkeys may change depending on the situation and the contents of the display.
Always the most important functions are assigned to the softkeys 1 and 2.
X
<Silence buzzer>, <Acknowledge>, <Reset>, <Alarm delay off>, <Premises manned> standard buttons
<Silence buzzer> switches the buzzer off.
<Acknowledge> acknowledges all events that can be acknowledged.
Confirms presence ( AVC, IC). Switches off the buzzer and internal sounders.
<Reset> resets all events that can be reset (password required).
<Alarm delay off> switches off the alarm delay for all events. In the
event of an alarm, the remote transmission or global alarming is activated immediately.
<Premises manned> switches between 'Manned' and 'Unmanned' operation modes (password required). Opens the event list in the case of a "mixed" condition ( visibility on several areas with different 'Manned' and 'Unmanned' settings).
k1 Configurable keys with LEDs
These two keys may, for example, be configured with the following functions: 'VdS counter' or 'Switch off detector zone' display.
k2 Configurable LEDs Freely configurable for the indication of events or conditions
You will find a template for this in document A6V10217440. See chapter 'Applicable documents'.
20 | 184
Setup of the Person Machine Interface
PMI
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15

3.1.1 EVAC NL

Uitgeschakeld
Ontruimingsalarm
cbd
e
7
Selecteer
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
3
a
1
2
Totaal Alarm
Zoemer
uit
3
4
Bedrijf
Storing
Zone 1
Zone 2
Zone 3
Zone 4
5
IN/UIT
6
g
f
i
Start
Stop 2x
Zone 10
Figure 2: PMI evacuation alarm
Button LED
1 Totaal alarm a Totaal alarm (red)
2 Zoemer uit b Bedrijf (green)
3 Start c Uitgeschakeld (yellow)
4 Stop d Storing (yellow)
5 IN/UIT e
EVAC zone
(yellow)
selection
6 LED TEST f Fault/Isolation (yellow)
7 Selecteer g Alarm (red)
i Information about using the keys
Building Technologies
21 |
Setup of the Person Machine Interface
PMI
3
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
3.1.1.1 Functions on the EVAC PMI
Button Function
1 Totaal alarm Pressing the button selects all EVAC zones
2 Zoemer uit Silences the buzzer of the EVAC PMI
3 Start Activates selected EVAC zones
4 Stop Deactivates selected EVAC zones
5 IN/UIT Switches selected EVAC zones on or off
6 LED TEST Activates the LED test on the EVAC PMI
7 Selecteer
LED Function
a Totaal alarm Indicates that 'Overall Alarm' has been activated
b Bedrijf Active as long as power supply is available
c Uitgeschakeld Active when at minimum one EVAC zone is switched off
d Storing Active when at least one fault is present in an EVAC zone
Active (flashing) when the connection to the fire control panel is faulty
e
EVAC zone selection
f Fault/Isolation Active when an EVAC zone has been switched off or a fault is present
g Alarm Active when all EVAC zones are activated
Active when the zone has been selected
Selects an EVAC zone for the issuing of additional commands (Start, Stop, ON/OFF)

3.1.2 Key switch (optional)

You can use the key switch to release an access level. The accessible access level is configurable.
The key switch has 2 positions:
On (horizontal position)
Off (vertical position)

3.1.3 Standard keys

22 | 184
See also
1 Logout timeout [ 118]
With the standard buttons, functions can be performed at the push of a button.
<Silence buzzer>
Switches the 'Station' buzzer off.
<Acknowledge>
Acknowledges all events that can be acknowledged.
Confirms presence (↑ 'AVC', 'IC')
Switches the buzzer off
Setup of the Person Machine Interface
Person Machine Interface with FBP [AU]
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15
<Reset>
The two buttons a and b in the figure above are configurable standard buttons.
Fire brigade operation
Full operation
Resets all events that can be reset (password required).
<Alarm delay off>
Switches off the alarm delay for all events.
In the event of an alarm, the remote transmission or ↑ global alarming is
activated immediately.
<Premises manned>
Switches between 'Manned operation' and 'Unmanned operation' operation modes (password required).
Opens the event list in case of a "mixed" condition ( visibility on several 'Areas' with different 'Manned operation' and 'Unmanned operation' settings).
<Alarm device>
Deactivates the alarm devices in the event of alarm (password required).
Configurable buttons
3
You can, for example, configure these two buttons with the following functions:
'Poll RT counter'
'Non-MCP zones OFF'

3.1.4 Other alarms

Pressing the 'More alarms' button opens the 'ALARMS' event list. If the 'ALARMS' event list is already open, <More alarms> assumes the function of
the button <>, changing to the next alarm event upon activation.

3.2 Person Machine Interface with FBP [AU]

The operating unit [AU] includes the PMI [AU] with the 'Fire brigade panel' (FBP), through which the fire detection installation can be operated. All important information from the fire detection installation is indicated spontaneously on the PMI or can be polled there.
Fire brigade operation is enabled with the key switch. The fire brigade has access level 2,1. The <Silence buzzer>, <Silence Alarm>, <Reset>, <Disable>, and <SEVERAL ALARMS> buttons can be operated by the fire brigade .
Full operation of all buttons from access level 2,2 can only be enabled with the PIN.
Building Technologies
23 |
Setup of the Person Machine Interfac
e
Person Machine Interface with FBP [AU]
3
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
CONTROL FUNCTION
ACTIVATED/CONFIRM.
ALARM ROUTING
6127
345
8
2
FIRE BRIGADE PANEL
001 AAA
001 ABC ABC
ZZZ ZZZ ZZZ
SEVERAL ALARMS
11
YYYY
910
SILENCE BUZZER
SILENCE A LARM
RESET
DISABLE
ACKNOWLEDGE
PREMISES MANNED
c
~
b
e
a
d
123
i
l
h
g
s
r
q
p
n
k
j
m
456
v
y
u
x
t
w
789
0#
*
C
f
o
z
ok
15
14
FC72x-xx
1
FIRE
FIRE PROTECTION ACTIVATED
SMOKE CONTROL ACTIVATED
WARNING SYSTEM ACTIVATED
ALARM ROUTING ACTIVATED
SYSTEM
POWER FAULT
13
1 Alarm indicator Light up red in the event of an alarm
2 Display Event indication, e.g. type, place, status of event
Menu, element and command indication
Instructions may be displayed in the event of an alarm
WARNING SYSTEM
SILENCED
FAULT
ISOLATION
DETEC TOR TEST
CONTROL FUNCTION ACTIVATED FAULT/OFF
WARNING SYSTEM ACTIVATED FAULT/OFF
FIRE P ROTECTI ON ACTIVATED FAULT/OFF
SMOKE CONTROL ACTIVATED FAULT/OFF
ACTIVATED FAULT/OFF
3 Navigation buttons
For navigation in the display for, e.g., menu and command selection and scrolling in lists
Access level 2,2 required
4
Keypad with Menu key, ok key and Cancel key
Keypad for PIN entry (password), shortcut (menus), address entry (element ID), parameter entry, entry of customer text
The menu button opens the main menu
The <ok> button can be used to run a selected command or open a
menu item. In windows with an entry field, the <ok> button moves the cursor to the next entry.
With the <C> cancel button, any operation sequence can be canceled, and any open list or window can be closed.
PIN entry required
5 Operating unit (AU) Pre-configured LEDs
LEDs which can be configured according to specific customer requirements
6 Key switch Enabling fire brigade operation with access level 2,1
7
<Silence buzzer>, <Silence Alarm>, <Reset>, and <Disable> standard buttons
Access level 2,1 required; fire brigade operation with key switch:
<Silence buzzer> switches the buzzer off
<Silence Alarm> deactivates alarm devices
<Reset> resets all events that can be reset
<Disable> stops the alarm in all 'Zones' which have issued an alarm
24 | 184
Setup of the Person Machine Interface
Person Machine Interface with FBP [AU]
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15
8
You can use inscription strips to inscribe the PMI. You will find a template for this
<Acknowledge> and <Premises manned> standard buttons
3
<Acknowledge> acknowledges all events that can be acknowledged. Confirms presence (AVC, IC).
<Premises manned> switches between 'Manned' and 'Unmanned' operation modes (PIN entry required). Opens the event list in the case of a "mixed" condition (visibility on several areas with different 'Manned' and 'Unmanned' settings).
9 Softkeys 1–3
Softkeys are buttons by means of which functions may be carried out that are displayed in the three fields of the softkey line on the display.
These three black fields contain the names of the functions in white font.
The functions of the softkeys may change depending on the situation and the contents of the display.
Always the most important functions are assigned to the softkeys 1 and 2.
Access level 2,2 required.
10
Configurable buttons with LEDs (can be configured
Functions can be configured according to specific customer requirements
independently)
11 <SEVERAL ALARMS> button Pressing <More alarms> opens the 'ALARMS' event list.
If the 'ALARMS' event list is already open, <More alarms> assumes the function of the button <>, changing to the next alarm event upon activation.
Access level 2,1 required; fire brigade operation with key switch
12 Configurable LEDs Freely configurable for the indication of events or conditions
13 System fault LED (yellow) Lights up yellow when a fault is present
14 Operation LED (green) Lights up green during operation
15
<Fire Protection Activated>,
Light up red when activated
<Smoke Control Activated>, <Warning System Activated>, and <Alarm Routing Activated> standard LEDs
Building Technologies
in document A6V10479789.
Different access levels for Australia as of MP6
The following access levels apply to FS720 fire detection systems for the Australian market as of MP6:
Access levels as of MP6 Access levels <MP6
1 1
2 2.1
3.1 2.2
3.2 3
The access levels that apply as of MP6 work in exactly the same way as the access levels for versions <MP6.
As stipulated by AS 4428.3, the operating elements within the 'Fire brigade panel' are disabled in the event of a fire alarm if the operator has access level 2. The introduction of access level 3.1 as of MP6 enables operating personnel who are present during a fire to operate the 'Fire brigade panel' accordingly.
25 |
Setup of the Person Machine Interface
Display
3
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15
Events occurring in the fire detection installatio
n are indicated on the display. A
ABCDEFGHI
1
2
3

3.3 Display

The display of the station has two displaying variants:
Display without window – Normal view – Expanded visibility – 'Fire Brig. view'
Display with window for following representations – Lists – Input fields – Command responses

3.3.1 Normal view

The display of a 'Station' in 'Standard view' has three sections.
001 AAA
001 ABC ABC
YYYY 1
ZZZ
ABCDEFGHI
Figure 3: Display in normal view
ZZZ
ABCDEFGHI
ZZZ
Position Designation Function
1 Header Status indication and system time
Information and titles for the working area
Instructions for the operator
Information for the operator
2 Working area Indication of lists
Selection of list items
Indication of windows
3 Softkey bar
Display of the three functions that can be directly executed with the softkey buttons
Identification of messages
special identification informs on the status of an event.
You will find details on the identification in the chapter 'Event status identification'.
26 | 184
See also
1 Event status identification [ 169]
Setup of the Person Machine Interface
Display
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15

3.3.2 Extended view

The display of events, elements, etc., comprises two lines in 'Standard view'. The extended view shows a 4-line depiction of the selection. Additional information
such as e.g. additional customer texts can be displayed this way. In the extended view there is a frame around four lines.
Figure 4: Display with extended view
With the <Switch to Extended view> and <Switch to Standard view> softkeys, you can switch from 'Standard view' to 'Extended view' and vice versa.
Alternatively, the navigation buttons <> and <> can be used to switch over.
3

3.3.3 Fire brigade view

For 'ALARM' events, the 'Fire Brigade message view' can be configured in the Engineering tool.
An 'ALARM' event is displayed in double font size in the 'Fire Brigade message view'.
Display with 'Fire Brig. view'

3.3.4 Display with window and list

The display with window and list is for the selection of a list item, which corresponds to a submenu.
The figure below shows the display with an exemplary list:
Building Technologies
Figure 5: Example of the display with window and list
27 |
Setup of the Person Machine In
terface
Display
3
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15

3.3.5 Display with window and input field

The display with window and input field has one or several input fields for entering e.g. the PIN, an address or customer text.
The figure below shows the display with an exemplary window with input field:
Figure 6: Example of the display with window and input field

3.3.6 Display with window and command response

The display with window and command response is open after a command has been entered. The operator therefore receives a confirmation for the command entered.
Figure 7: Example of the display w ith window and command response
28 | 184
Setup of the Person Machine Interface
Soft keys
184
A6V10211076_i_en_
--
Fire Safety
2015-12-15

3.4 Soft keys

When the user navigates through the topology, the softkey allocation does not
The figure below shows the part of the PMI including the softkeys.
Button for softkey function
Softkeys are buttons which you can use to carry out functions and which are displayed in the three fields of the softkey line on the display. These three black fields contain the names of the functions in white font.
The functions of the softkeys change dynamically depending on the situation and the contents of the display.
Always the most important functions are assigned to the softkeys 1 and 2.
3
change depending on the context; the assignment remains fixed. If a softkey function cannot be executed at a point in the topology, the inscription in the field is hidden.
The table below lists an exemplary softkey assignment.
Softkey / Option Function
'Show intervention text'1 Shows the intervention text of the selected event.
'Jump back'
Displays the list the selected event has been taken from. Back from the view Intervention text or Details.
'Execute command' Opens the 'Select command' window.
'More options' Opens the 'Select option' window.
'Show details'
2
Shows details of the selected event or element.
'Lower level' Changes to the next lower hierarchy level.
'Upper level' Changes to the next higher hierarchy level.
'Jump to begin' / 'Jump to
Within a list, jumps to the top or end of the list
end'
'Show topology '
3
Jumps to the selected element in the topology.
'Show active detectors' Shows a list of all active detectors, corresponding to an event list.
1
Softkey / Option is only displayed when intervention text is available at this point
2
Softkey / Option only available in 'Access level 3'
3
Softkey / Option only available as of 'Access level 2.1'
See also
1 Normal view [ 26]
Building Technologies
29 |
Setup of the Person Machine Interface
Navigation buttons
3
Building Technologies
A6V10211076_i_en_
--
Fire Safety
2015-12-15

3.5 Navigation buttons

The following figure shows the navigation buttons in the PMI:
Figure 8: Navigation buttons
The navigation buttons work in the same way as the arrow keys on a PC keyboard.
The next entry in a list can be highlighted with the buttons <▲> and <▼>.
It is possible to change to a higher or lower hierarchy level with the buttons <◄> and <>.
In a command list, the highlighted command can be executed with the button <►>.
When characters are entered, the character to the left of the cursor position is
deleted by pressing the button <>.

3.6 Keypad

The following figure shows the keyboard and <MENU>, <ok> and <C> (Cancel) buttons:
2
1
1 Keypad 3 <ok>
2 <MENU> 4 <C> (Cancel button)
The key panel serves for numeric and alphanumeric entries.
34
30 | 184
Loading...
+ 154 hidden pages