FC724
Cerberus™ PRO
Fire control panel
FS720 series, IP6
κ Compact, pre-assembled, microprocessor-controlled fire control panel with
integrated operating unit for up to 504 addresses
κ Fire control panel can be used as a standalone version or can be networked
κ Up to 64 stations – control panels and terminals – can be linked to form a
network
κ Integrated degraded mode function
κ Redundant network node, degraded mode operation according to EN 54
κ Fast Ethernet interface for a heterogeneous network
κ Integrated user-friendly operating unit
κ Can be extended by adding printer, key switches, LED indicators
κ Slots for RS232 and RS485 serial interfaces
κ Emergency power supply for emergency operating time of up to 72 hours
κ Detection and automatic reading in (auto-configuration) of all C-NET devices,
ready for operation immediately
κ Processes signals from Cerberus PRO FD720 detector series
κ Floor repeater displays, floor repeater operating units, and alarm devices on C-
NET detector line
κ Flexible configuration of complex applications and controls
κ Configuration data can be uploaded/downloaded via remote access
κ Firmware for all processor-controlled control pan el components can be
updated

2
Building Technologies
Fir e Safety
A6V10207176_h_en_--
2016-05-23
System overview
FC10 or X C10
Fire detection or
Extinguishing
control unit
collective
4 (8) loops
4 outputs
24VDC ext.
possible
FDCL221
FDM22x
FDM221
FDS221/
FDS229
DBS720
OH720
HI722
HI720
OP720
4 inputs
FDCIO221
1 input
24VDC ext.
2 in-/outputs
optionally
Detection line collective Siemens,
Synova SynoLINE300 or
SynoLINE600
TM
FDCIO223
alarm signal
Transmission of a
fault signal
Operating Tool
FC724
FT724
Mimic display
FT2001- A1
DBS721 / DBS729
FT2010/FT2011
Floor repeater terminal /
Floor repeater display
Explosion-
hazard area
FDA241
FDM233-Ex
OOH740-A9-Ex
FDCI723

3
Building Technologies
Fir e Safety
A6V10207176_h_en_--
2016-05-23
Networking of several fire control panels
Up to 32 control panels and terminals can be linked to form a cluster (CWEB/SAFEDLINK network). If the cluster is connected to a danger management
system via BACnet, up to 16 control panels and terminals can be networked.
DL3750+
Matrix printer
RS232
FC722
FT724/FC72x
Cluster

4
Building Technologies
Fir e Safety
A6V10207176_h_en_--
2016-05-23
An optical Ethernet network (C-WEB/LAN) allows up to 14 clusters with up to 16
stations to be operated on one network. A maximum of 64 stations is supported in total.