Siemens FC700A User Manual

FC700A Fire detection system
Planning
Fire & Security Products
Siemens Building Technologies
Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. © 2004 Copyright by Siemens Building Technologies AG
Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich machen oder außerhalb des Zweckes verwenden, zu dem es ihm übergeben worden ist.
We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
Nous nous réservons tous les droits sur ce document, ainsi que sur l'objet y figurant. La partie recevant ce document reconnaît ces droits et elle s'engage à ne pas le rendre accessible à des tiers, même partiellement, sans notre autorisation écrite préalable et à ne pas l'employer à des fins autres que celles pour lesquelles il lui a été remis.
1 About this document ..............................................................................6
2 Safety regulations...................................................................................8
2.1 Signal words and symbols ........................................................................8
2.1.1 Signal words and their meaning................................................................8
2.1.2 Symbols and their meaning ......................................................................8
2.1.3 Classification and meaning of additional symbols ....................................9
2.2 Safety-relevant working instructions .........................................................9
3 Main features.........................................................................................11
4 Technical data FC700A.........................................................................12
5 Logical and physical structure............................................................13
6 Bus systems..........................................................................................14
6.1 Bus overview...........................................................................................15
6.2 Modifying the impedance of the various C-Bus cables...........................15
6.2.1 Diagram...................................................................................................16
7 C-Bus stations.......................................................................................17
7.1 Station .....................................................................................................17
7.2 Types of stations.....................................................................................17
7.3 Hardware.................................................................................................17
7.4 Visualizer for Windows remote operation software (not available yet)...18
7.5 Logical AREAS........................................................................................19
8 Limitations of C-Bus participants .......................................................20
8.1 Main CPU limits.......................................................................................20
8.1.1 Maximum number of devices ..................................................................20
8.1.2 Limits in the logical structure...................................................................20
8.1.3 Maximum number of criteria in zones control 4 and 6............................20
8.1.4 Maximum number of ZONE time channel...............................................20
8.1.5 Maximum number of I-Bus-modules.......................................................21
8.1.6 Limits of 5V supply..................................................................................21
8.2 Control terminal limits (FC/FT)................................................................21
8.2.1 Limitation of visible texts on a FC700A...................................................21
8.2.2 Limitation of visible texts on a FT700A ...................................................21
8.3 Gateway limits (FG) ................................................................................22
9 Specify hardware required...................................................................23
10 Control unit FC700A .............................................................................24
10.1 Configuration...........................................................................................24
10.2 Block diagram .........................................................................................25
10.3 Modules...................................................................................................25
11 Auxiliary power supply.........................................................................26
11.1 Configuration...........................................................................................26
11.2 Block diagram .........................................................................................26
11.3 Modules...................................................................................................26
12 Control terminal B3Q700 (FC/FT) ........................................................27
12.1 Features .................................................................................................. 27
12.2 Options....................................................................................................27
12.2.1 Plexiglas door to B3Q700 (FC/FT)..........................................................27
12.2.2 Place of the E3I020 RS232 module (FT)................................................28
12.2.3 Place of the E3I040 LON interface (FT) .................................................28
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
3
12.3 Installation possibilities (FT)....................................................................29
12.4 Block diagram .........................................................................................29
12.5 Connection lines between control unit and external operating units ......30
12.6 Power supply (24V).................................................................................30
12.7 Modules...................................................................................................31
13 Range of cabinets H23 / H26 / H28 ......................................................32
13.1 Recessed mounting H23G230 and H28G200 ........................................33
13.2 Modules...................................................................................................33
14 19” accessories.....................................................................................34
14.1 Modules...................................................................................................34
15 Line modules .........................................................................................35
15.1 Overview .................................................................................................35
15.2 Modules...................................................................................................35
15.3 Detection line "addressable" SynoLOOP................................................36
15.4 Detection line "collective" SynoLINE600/-Ex ..........................................37
16 Connection factors, line resistances and capacitances...................38
16.1 Terminology and abbreviations...............................................................38
16.2 Collective detection line ..........................................................................38
16.3 Addressable detection line......................................................................38
16.4 Line resistance and capacitance.............................................................39
17 Control modules....................................................................................40
17.1 Application of control modules ................................................................40
17.1.1 Overview of the available modules with control outputs.........................40
17.2 Means of linking ......................................................................................40
17.3 Control outputs station type FC700A ......................................................41
17.4 Control outputs remote station type FT700A ..........................................41
17.5 Modules...................................................................................................41
17.6 CPU-overlapping controls .......................................................................42
17.7 Mimic Display panel outputs ...................................................................43
17.8 Modules...................................................................................................43
17.9 Relay outputs ..........................................................................................44
17.10 Modules...................................................................................................44
18 LON-Bus devices ..................................................................................45
18.1 Features ..................................................................................................45
18.2 LON-Bus as stub line ..............................................................................45
18.3 LON-Bus as free topology.......................................................................46
18.4 LON/Mimic Display p.c.b K3I050 ............................................................46
18.5 LON I/O card K3I110...............................................................................46
18.6 Indicator devices B3Q580 and B3Q590/595...........................................47
18.7 Modules...................................................................................................47
19 Gateway..................................................................................................48
19.1 Main features ..........................................................................................48
19.2 Application...............................................................................................48
19.3 Modules...................................................................................................49
20 Remote transmission............................................................................50
21 Printer interface.....................................................................................51
4
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
21.1 Features .................................................................................................. 51
21.2 Application variant FT .............................................................................51
21.3 Application variant FC.............................................................................51
21.4 Modules...................................................................................................51
22 Power supply.........................................................................................52
22.1 Concept...................................................................................................52
22.2 Special functions.....................................................................................52
22.3 Application...............................................................................................52
22.4 Power supply for the control unit.............................................................52
22.5 Auxiliary power supply ............................................................................52
22.6 Modules...................................................................................................53
22.7 Operation with power supply from control unit........................................53
22.8 Power supply for remote transmission equipment and accessories.......53
23 Emergency power supply ....................................................................54
23.1 Specifying battery capacity .....................................................................54
23.1.1 Battery rated capacity .............................................................................54
23.1.2 Ageing of battery.....................................................................................54
23.1.3 Calculation ..............................................................................................54
23.2 Capacity values for standard configurations...........................................54
23.3 Quiescent current table...........................................................................55
24 Alarm concept .......................................................................................56
24.1 Cerberus Alarm Concept (CAC) .............................................................56
24.2 Principle of the Cerberus alarm concept.................................................56
24.3 Determine the alarm organization...........................................................57
24.4 Organization of system operation ...........................................................57
25 Commissioning .....................................................................................58
26 Parameterization, Flash programming ...............................................59
26.1 Functions.................................................................................................59
26.2 Modules...................................................................................................59
27 FC700A modules in alphabetical order ..............................................60
28 Spare parts ............................................................................................62
29 Configuration sheets ............................................................................63
29.1 List of configuration sheets .....................................................................63
30 Control unit FC700A .............................................................................64
31 Auxiliary power supply.........................................................................65
32 Control terminal FT700A ......................................................................66
33 Display & operating terminals .............................................................67
34 Externally placed modules...................................................................68
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
5
About this document
1 About this document
Purpose
This document describes the project planning of the hardware modules of the con­trol unit FC700A. The consistent adherence to these instructions is a prerequisite for a safe application.
Scope
This document contains information of all FC700A components, including part numbers for ordering.
Target group
This product documentation and the work instructions are aimed at the following persons, who have a particular function and have the corresponding training and qualification.
Group of persons Activity Qualification
Project Manager The project manager is responsible for the local
project management. He co-ordinates the sched­ules of all groups of people working on a project as well as resources. He also continuously ob­tains the technical information required for project realization.
He has had the technical training appropriate to his function and the size of a project or the prod­uct line used in the project and has attended the training courses for project managers at the sup­plier’s works.
Reference documents
Information in Document
007831 Hardware description 007827 Installation housing H26... /H28... 007832 Visualizer Customizing / End user (not yet available) 007835 Operating instructions 007828 Installation / Hardware Commissioning 007833 Maintenance instructions 007894 Templates for inscription stripes 007895 Operating platform for Tools
Work and operational safety
Before personnel begin work on the system they must have read and understood the related operating instructions, in particular chapter 2 ”Safety regulations”.
Disregard of the safety regulations
Before they are delivered, products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or disregard of warnings of danger contained in the documentation. This applies in particular to:
Personal injuries or damage caused by improper use and incorrect use; Personal injuries or damage caused by disregarding safety instructions in the
documentation or on the product;
Personal injuries or damage caused by poor maintenance or a lack of mainte-
nance.
6
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
About this document
Conventions
(...) Additional information ..) Notes
’’......’’ / ’.....’ Definitions of designations
-> Details see page ...., chapter or document .....
Configuration sheets to fill out
Document identification
Place Signification
Title page System names
Last page
bottom left
bottom right
Product type Document purpose The document number consists of: Language, number, index Version date Manual Register
Modification index
Version Date Brief description
007836_a_en_-- 03. 2004 First edition
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
7
Safety regulations
2 Safety regulations
This chapter describes the danger levels and the relevant safety regulations appli­cable for the use of our products. Please read the work instructions as well as the chapter ”About this document” thoroughly before beginning any work.
2.1 Signal words and symbols
2.1.1 Signal words and their meaning
The danger level that is, the severity and probability of danger are indicated by the signal words listed below. Non-observance may lead to the consequences indi­cated:
DANGER
Imminent danger!
May cause serious bodily injury or danger to life!
WARNING
Dangerous situation!
May cause serious bodily injury or danger to life!
CAUTION
Possibly dangerous situation!
May cause light injuries!
NOTE
Possibly harmful situation!
May cause damage to the product or to objects in the immediate vicinity of the
product!
2.1.2 Symbols and their meaning
The symbols listed below indicate the nature and origin of the danger.
Signal word General danger
Signal word Electrical voltage
Example for a danger warning
DANGER External voltage
Disconnect the module from power supply.
8
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
2.1.3 Classification and meaning of additional symbols
Tips and information
Refers to extremely important or critical decisions to be taken into account before continuing the work.
2.2 Safety-relevant working instructions
Country-specific standards
The products are developed and produced in compliance with the relevant interna­tional and European safety standards. Should additional country-specific, local safety standards or regulations concerning project planning, assembly, installation, operation and disposal of the product apply in the place of operation, then these standards or regulations must also be taken into account in addition to the safety regulations mentioned in the product documentation.
Safety regulations
DANGER
Work on electrical installations
Any work on electrical installations may only be carried out by qualified electri­cians or instructed persons working under the guidance and supervision of a qualified electrician, in accordance with the electro technical regulations.
Electrical installations
Control units must be disconnected from the power supply during commissioning
or maintenance work.
Terminals with an external voltage supply must be provided with a sign ”DAN-
GER - External voltage”.
Mains leads to the control unit must be installed separately and provided with a
clearly marked fuse.
Earthing must be carried out in compliance with local safety regulations. When work is carried out in explosion-hazardous areas, the appropriate safety
precautions must be taken.
Assembly, installation, commissioning and inspection work
If any tools or accessories such as ladders are required, safe and suitable de-
vices must be used.
Prevention of spurious tripping of the remote transmission must be assured. Always inform the fire brigade before testing the remote transmission. The activation of fire control installations for test purposes must not cause dam-
age to the system or parts thereof.
Fire control installations must only be activated after the test has been com-
pleted and the system has been handed over to the customer.
Third party systems or devices must only be activated in the presence of the re-
sponsible person.
When work on management stations and system terminals are performed, the
safety regulations of the connected sub-systems must be observed. This espe­cially applies when switching-off system components.
In the case of extinguishing systems, always use the ”General installation in-
structions” as a guideline. This guideline is available on request.
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
9
Safety regulations
Testing the product operability
Evacuate and cordon off extinguishing sector. Inform people about the possibility of occurring fog and noise. Inform people before testing of alarm devices; take the possibility of panic reac-
tions into account.
Inform the alarm and fault receiving stations connected to the system before
running the tests.
Modifications to the system design and the product
Modifications to a system or to individual products may cause faults or malfunctioning. Please request written approval from us, and the relevant authorities concerning in­tended system modifications and system extensions.
Modules and spare parts
Locally procured modules and spare parts must comply with the technical speci-
fications laid down by the manufacturer. This compliance is always ensured for original spare parts supplied by us.
Only use fuses with the specific fuse characteristics. Wrong battery types and improper battery exchange may introduce the danger
of explosion. Only use the specified battery type or an equivalent battery type recommended by the manufacturer.
Batteries require environmentally safe disposal. They must be handed in at the
local collecting points.
Please take into account that the extinguishing agent cylinders are pressurized
and must be exchanged in compliance with the local safety regulations.
10
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
3 Main features
Fire detection system for modular configuration Up to 1000 detectors per FC700A possible For the processing of addressable and conventional detectors Logical and physical structure totally separated Control console as main CPU Interfaces for VdS peripheral equipment, printer, host systems Different types of input and output modules Special Mimic Display terminal activating module Multidetector logic Up to 16 free selectable type of stations per C-Bus Comfortable operation with soft keys and large LC display Up to 64 independent logical AREAS (Organization levels) Single-AREA or multi-AREA operation Event memory with sub-menu / search functions Integrated real time clock with auxiliary battery Automatic summer/winter time switchover Integrated emergency operation function Flexible detector parameters setting via maintenance PC
Connectible detector systems
Synova™ 300/600, Special detectors
SynoLOOP
Stations
Control terminal / Main-CPU ‘FC700A’
B3Q700
Main features
Control terminal ‘FT700A’
B3Q700
CPU
SynoLINE300
SynoLINE600 / SynoLINE600-Ex
Special detectors
E
-
A
1
0
1
1
O
D
e
p
y
S
N
T
E
®
M
s
E
u
I
r
e
S
b
r
e
C
x
E
E
x
i
b
I
I
C
T
4
P
T
B
N
r .
WINDOWS based
Configuration software
FG700A
Gateway
SWE700A
11
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Technical data FC700A
4 Technical data FC700A
Operating voltage 115 / 230VAC ±15% 50... 60Hz Power consumption 40... 220VA (per converter B2F020) Battery operation in the event of mains failure
- Standard operating period
- Optional Environmental conditions Temperature during operation Storage Humidity
IP protection category (EN 60529 / IEC 529)
- Control unit
- Remote control terminal
Dimensions
- Control unit cabinet
- Separate control terminal in cabinet H26G220 H28G200 Colors
- Control unit cabinet
- Operating unit front terminal B3Q700
- Control terminal cabinet H26G220 H28G200 H28T110/120
12...24h Up to 72h (see chapter 23)
0°C... +40°C
-20°C... +60°C Max. 95%, no condensation Complies with class 3K5 according to IEC 721–3–3
IP50
IP52 H26G220 cabinet IP40 H28G200 cabinet
W = 520mm, H = 602mm, D = 100mm / 155mm
W = 366mm, H = 219mm, D = 76mm W = 520mm, H = 300mm, D = 70mm
RAL 7035 light grey
Dark grey like Pantone 431C, Pantone 429C grey
Pantone 421 grey RAL 7035 light grey 1E110 dark grey
12
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
5 Logical and physical structure
r
r
g
In the FC700A fire detection system, the logical structure is completely separated from the physical structure. This enables the greatest possible flexibility. Display and control terminal are based on the geographical and organizational aspects and are independent of the actual hardware installation of the detector network.
Geographical features (-> building structure)
Logical and physical structure
Main building (Area)
Logical structure
The logical structure is a configuration of the geographical features of a system. It can be modified easily to the building structure, room utilization etc.
Within the same control unit the logical struc­ture is independent of the wiring of the detec­tor network.
Linking
The lowest levels of both structures are linked to each other. It is determined which physical devices (e.g. detectors) are in which logical or geographical location.
Physical structure
The physical structure is a configuration of the hardware. It results from the hardware instal­lation. The number of used levels is depend­ing on the type of hardware.
Area
Section
Zone
Element
Level 2
Level 1
Device
Level 2
Level 1
Function unit
Station
st
floor (Section)
1
Ware house
Line 1
Control terminal ‘FT’
2nd floor
1st floor
ground floo
logical structure
Ground floor
Reception
Line 2
Room
Line 3
C-Bus
physical structure
Room 101
building
Room
102
103
Linkin
Line 4
Line modules E3M111
I-Bus
Main
1st floor
Room 102
Room 103
Room 104 (Zone)
Room
104
SynoLOOP
Control unit ‘FC’
Room 104
Canteen
2nd floor
1st floo
EDP room
13
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Bus systems
6 Bus systems
In the FC700A fire detection system there are 5 communication levels:
I-Bus
Internal data bus between individual modules in the control unit (line modules,
control modules etc.)
C-Bus
Local data bus between control unit(s), control terminal(s) and Gateway(s)
SynoLOOP and SynoLINE600
Local detector bus; connects the detectors to the control unit
LON-Bus
Local data bus for floor repeater panels, mimic display converter and LON I/O
card
Data Bus
Local data bus for parallel indicator panel, synoptic panel or relay
Control terminal
FT700A
CPU
B3Q700
I-Bus
Databus
C-Bus
SynoLOOP
E3I040
E3M111
LON-Bus
I-Bus
Line modules
E3M080
SynoLINE600
Gateway
FG700A
E3H020
E3I040
LON-Bus
RS232
Building
management
system
ISO1745 Protocol
Control unit FC700A
B3Q580/ B3Q590/
B3Q595
K3I110
In-/Outputs
K3I050
Databus
B3R051
or
K3R072/
K3G060
14
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Bus systems
6.1 Bus overview
Features C-Bus I-Bus SynoLOOP SynoLINE600 LON-Bus Data Bus
Field of applica­tion
Speed of trans­mission Length of line
Number of users connected or addresses Number of wires 2
Type of cable
Loop line T-branch
Short-circuit proof Yes
Network structure Scanning
Principle
Local system bus Inside control unit
57kBaud 1000kBaud 2 messages/sec
Max. 1000m
(G51 ∅ 0,8: 1400m)
… 16
C-Bus devices
(+3 wires for emer-
gency operation)
Twisted 1) Flat cable
– – – –
Each user con­nected with line
separator
Master/master Master/slave Master/slave Master/slave Master/slave Master/slave
Event-controlled,
presence monitoring
Serial Bus
- Cerberus protocol
- Collision detection
- Manchester coding
For addressable
detectors
Max. 3m (only
inside cabinet)
… 16
I-Bus modules
26 2 2 2
Cyclic,
Event controlled
C-Bus
- Cerberus protocol
- SPI/Motorola
Max. 150Ω/300nF
See chapter 16
… 128
D-Bus devices
Twisted
(Un-twisted per-
missible)
Yes Each user con­nected with line
separator
Cyclic
- typ. all 64s
- Interrupt on alarm
Sensor/actor-Bus
- Cerberus proto­col 'K31'
- Serial 8bit
- Start-up: daisy­chain
For collective
detectors
(Direct current
signal)
Max.
150/250/4µF
See chapter 16
1 address
(Max. 25 detec-
tors)
Twisted
(Un-twisted
permissible)
– – –
No No Yes
Conventional
- Current gain principle
- Voltage levels
Local data bus
for floor indicator
panels
78kBaud SPI-Bus 2KHz
Max. 500m as
free topology
Max. 1000m as
stub line
… 32
LON-Bus de-
vices
Twisted Twisted
(See chapter 18)
Event-controlled,
presence moni-
toring
(All 60s)
Network
- Echelon Chip (LON protocol)
- Cerberus specific telegram
1 Calibrated according to cable impedance: 50 (MICC) / 110 (G51, ø
0.8mm, not shielded)
Local data bus
parallel ind.
panel, synoptic
panel or relay
Max. 1000m
… 24
Max. 8 addresses
6
(+3 wires supply)
Cyclic
- typ. all 250ms
Serial bus
- Cerberus proto­col
6.2 Modifying the impedance of the various C-Bus cables
C-Bus standard cables have a characteristic impedance of 110. The driver and end-of-line resistors are soldered to solder lugs and can be adapted accordingly with other characteristic impedances (see diagram chapter 6.2.1).
1. Explanation A cable must be terminated with resistors. The resistance value must correspond to the impedance of the cable. Each C-Bus user has four end-of-line resistors (Ri). In addition two driver resistors (Rd) are integrated on the p.c.b. In order that the resistors can be exchanged easily they are all soldered to solder lugs.
C-Bus p.c.b. Ri Rd
B3Q700 R31 ... R34 R49, R50 E3H020 R173, R174, R177, R178 R180, R183
The driver resistors specify the current on the C-Bus. In order that the signal on the C-Bus always has the same amplitude (1.35Vpp), the following correlation is valid:
Rd = Ri x 3,65 (45 < Ri < 200)
15
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Bus systems
6.2.1 Diagram
Ri [Ohm]
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
0
20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440
Standard
Lifeline
Radox
MICC
460 480 500 520 540 560 580 600 620 640 660 680 700 720 740
Rd [Ohm]
2. Procedure
Request characteristic impedance of the cable from manufacturer (45 ... 200Ω) Select the value of the Ri the same as the value of the cable characteristic im-
pedance and insert the four end-of-line resistors on the p.c.b.
Insert two driver resistors Rd = Ri x 3.65 on the p.c.b. Each C-Bus user must be adapted
If only the inductance and the capacitance are known for a cable, the impedance can be calculated with the aid of the following formula:
Zc: Cable impedance [Ω] Lc: Cable inductance [µH] Cc: Cable capacitance [µF]
Zc =
Lc Cc
3. Mixing of different types of cable In a C-Bus loop (or stub line) only one type of cable may be used.
4. Operation as a stub line If the C-Bus is operated as a stub line, two end-of-line resistors (values as for Ri) must be inserted externally at both ends of the line (default 110Ω). In the choice of other cables the above rules apply (the Ri are in this case the external end-of-line resistors).
For further information, see document 007831
16
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
7 C-Bus stations
r
The C-Bus network contains max. 16 stations (user connected)
Within the limits stated below (FC, FT, FG) are any stations in any arrangement
possible
Max. 64 AREAS
Control terminal
C-Bus Network
- max. 16 Stations
- 3 different types of stations
- loop line max. 1400m with G51 ø 0.8mm
FT700A
(max.15)
Building mangement system
ISO1745 Protocol
FG700A
(max.15)
Gateway
C-Bus
C-Bus stations
Control terminal
Main-CPU
FC700A
(max.16)
7.1 Station
Function unit within C-Bus network Several stations are be located in geographically dispersed cabinets
7.2 Types of stations
Differentiated by function and represented by a certain module Certain modules can be used for different types of stations
Types of stations available:
FC700A Combination of main CPU and operating unit FT700A Control terminal FG700A Gateway (e.g. conversion of C-Bus Protocol -> ISO1745)
7.3 Hardware
Type of station Module
FC700A B3Q700 FT700A B3Q700 FG700A E3H020
I-Bus
Line
modules
’Main CPU’
Control modules
Detecto
Function
Function
’Operation’
Function
’Gateway’
17
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
C-Bus stations
7.4 Visualizer for Windows remote operation software (not avail­able yet)
Operating platform requirements in detail see document 007895 For details see document ……. (not available yet)
max. length of line
C-BUS
FC/FT
FC/FT
E3I020
E3I020
E3I020
B3D021
E3I020
dependent on type of modem
Modem
Tel.
Modem
(RS232) ....15m
Standard PC with keyboard, software
’Visualizer for Windows’,
Tel .
Modem
e.g. Service Notebook, software ’Visualizer for Windows’, SWE700A for Windows
Dedicated line
temporary public telephone line
temporary public telephone line
Modem
Tel .
Modem
Tel .
Modem
Visualizer
Remote Operation
(temporary)
18
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
7.5 Logical AREAS
A
FC FC FC FC
C-Bus stations
1 2
AREA
34
5 6
78
FC FC
Within one main CPU (FC) max. 4 AREAS can be configured CPUs cannot link up with AREAS of other CPUs CPU overlapping controls are possible Control terminals (FT) can be freely allocated to AREAS as required Visibilities on gateways (FG) shall be set per station only, not per AREA!
.. ..
All AREAS control terminal
.. ..
61 62
63 64
REA
FGFG
19
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Limitations of C-Bus participants
8 Limitations of C-Bus participants
This chapter describes the quantitative limits of the FC700A station. The selection of the station type depends on the requirements. The following vari­ants are available:
Station type Modules
FC700A B3Q700 CIY00760 4x512Kx8Bit – – FT700A B3Q700 CTY00760 4x512Kx8Bit –
FG700A E3H020
Flash ROM
(2x1024Kx8Bit)
'Program file'
8.1 Main CPU limits
8.1.1 Maximum number of devices
1000 devices (with AMPK=1) per FC700A.
SRAM
Soldered
EPROM set RAM set
CKQ007.60
(2x512Kx8Bit)
2 x Z3S070
(2x512Kx8Bit)
(Assembly ex works)
8.1.2 Limits in the logical structure
The limits in the logical structure are given by the node-type, by the highest possi­ble CSX number and the maximum amount of display-digits. These limits are given by the system and are independent of the memory capacity.
Table 'Limits of the logical structure'
Maximum rating
AREAS per STATION
... 4 …255 …255 …99
Maximum rating
SECTIONS per AREA
Maximum rating
ZONES per SECTION
8.1.3 Maximum number of criteria in zones control 4 and 6
The maximum number of control zones with 16 criteria is limited by 200.
To optimize the performance of your system minimize the number of CPU-overlapping controls as
much as possible. A maximum of 40 CPU-overlapping controls (zone control 6) are admissible per C-Bus.
8.1.4 Maximum number of ZONE time channel
Max. 16 ZONES time channel are permitted per station.
Maximum rating
ELEMENTS per ZONE
International 5: …255
20
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
8.1.5 Maximum number of I-Bus-modules
Table 'Maximum number of I-Bus-modules'
Station type FC700A
I-Bus modules ... 16 1) ... 8 2) 3)
1) Limited by software
2) Value based on experience (depends on cabinet size and/or 5V current consumption)
3) Battery charging unit E3C011 counts as one I-Bus module
8.1.6 Limits of 5V supply
All I-Bus modules are supplied with 24V and 5V. The available current for the 5V, supplied from main CPU is limited:
'Main CPU' Available current
B3Q700 / E3C011 250mA
Table '5V-Current consumption of I-Bus modules'
I-Bus module
E3M080 55mA E3G060 10mA E3M111 25mA E3G070 10mA
E3L020 10mA E3C011 12mA E3L030 35mA E3I020* 100mA E3G050 8mA E3I040 70mA
* Not an I-Bus module, but supplied via the 'Main CPU'
Current consumption
from 'Main CPU'
Limitations of C-Bus participants
I-Bus module
Current consumption
from 'Main CPU'
8.2 Control terminal limits (FC/FT)
8.2.1 Limitation of visible texts on a FC700A
The number of texts of other stations (i.e. AREAS) that can be displayed on one control terminal is limited by 14'000 texts. To evaluate how many control panels FC700A can be displayed to one FC700A, the following calculation must be used:
Twice the number of visible sections (worst case 1000)
+ The number of visible ZONES (worst case 1000) + The number of visible ELEMENTS with element text (worst case 1000) = Number of texts per FC/FT (worst case 4000)
Example (worst case) 14'000 : 4000 (e.g.) = 3 fully configured FC can be displayed to one FC
8.2.2 Limitation of visible texts on a FT700A
The number of texts of other stations (FC700A) that can be displayed on one con­trol terminal is limited by 14'000 texts. To evaluate how many control panels FC700A can be displayed to one FT700A, the following calculation must be used:
Twice the number of visible sections (worst case 1000)
+ The number of visible ZONES (worst case 1000) + The number of visible ELEMENTS with element text (worst case 1000) = Number of texts per FC/FT (worst case 4000)
Example (worst case) 30'000 : 4000 (e.g.) = 7 fully configured FC can be displayed to one FT
21
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Limitations of C-Bus participants
8.3 Gateway limits (FG)
Via one gateway a maximum of 8 C-Bus stations (FC700A) can be addressed. If more than 8 C-Bus stations (FC700A) are present, they must be split up on two gateways. Also for special applications, more than two gateways can be configured. Visibilities of C-Bus stations (FC700A) on gateways must be set station wise, not area wise!
22
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
9 Specify hardware required
In order to be able to specify the hardware required, system key data must be specified according the following procedure:
1. Specify number and type of detection lines
Dependent on:
Detector series Number of detectors, input and output modules Building structure
2. Specify number and type of fire control installations
Dependent on:
The fire protection installations to be activated Location of the contacts (centralized or decentralized) Individual types of contact (250VAC/10A or 30VDC/1A)
3. Specify number of operating units
Dependent on:
Operating concept Parallel indicator panels, fire department control panels
4. Specify Accessories required
Dependent on:
Printer interface and printer Remote transmission equipment Gateway, etc.
5. Specify emergency power supply battery capacity
Dependent on:
Total quiescent current Required emergency current operating period (according to country) Type of remote transmission
6. Provide configuration sheet/sheets (see chapter 29)
Dependent on:
Select sheets corresponding to the configuration Complete everything
Specify hardware required
23
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Control unit FC700A
V
X1X
10 Control unit FC700A
10.1 Configuration
Pre-assembled compact control unit E3G070 and E3M111 are pre-wired on terminal block 'X1' Place for additional terminal block 'X2', modules, relay and batteries Batteries as required either 2x 12V/15Ah or 2x12V/27Ah Control terminal built into front terminal (also serves as main CPU) Installation of parallel indicator panel B3R051 possible Door right hinged, can be locked with 2 Allen screws
520
602
147
155 incl. projecting door hinges
Module chassis view 'Modules'
EMC Precaution:
Slot rows with E3C011 module is not be allowed with E3I040 module
46
E3H020 and E3L030 requires 2 module spaces
E3H020 + 2 x Z1K030 E3L030 + 2 x Z1K or Z3I
E3....
Z1K or Z3I
E3....
Z1K or Z3I
View A
27
37
47
57
E3I020
E3M111
E3....
E3....
Z1K or Z3I
28
E3C011
Z1K030
38
E3G070
Z3I1050
48
E3....
Z1K or Z3I
5856
E3....
Z3I470
Z3I1050
Z1K or Z3I
Z1K or Z3I
21
B2F020
AC/DC converter
31
(Akku 12V)
AX1201
or
AX1210
51
(Akku 12V)
AX1201
or
AX1210
Converter 115/230VAC
-> 29.6VDC/6A
Cabinet front view
23
Mains
terminals
Z3B171
1
Z3B171
10
Battery charging module
Module chassis view ‘Terminals’
FC700A-1
AB
Control module ‘universal’
Line module ‘SynoLOOP’
Terminal block ‘X1’ with 2x20 terminals in two levels
pre-mounted and pre-wired recommended space
allocation
Z3I1060
2
Z3I1060
iew B
Control terminal
Cover plate
Z1K030
connection direct
Z3I1050
connection via terminal block ‘X2’
24
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
10.2 Block diagram
B3Q700 ‘FT’
(additional operating facilities)
Control unit FC700A
RT = Remote transmission
Batteries AX12..
1........7
Z3B171
I-Bus
E3L030
FSK
FBF HM
VdS peripheral
equipment
E3M111
1..........4 1.............8
SynoLOOP
E3M080
SynoLINE600
E3G...
E3L...
Basic equipment Option
E3I040
LON-Bus
LON synoptic converter
LON I/O card
Floor repeater terminal
B3Q580/
FC700A
K3I050
K3I110
B3Q59x
24V
E3I020
RS232
1
Printer
C-Bus
2
B3Q700
‘FC’
24V
Mains
1..2
E3C011
24V
E3G070
24V
RT
250VDC / 10A
Fire control
installation
B2F020
5V
B3R051
10.3 Modules
Component Order-No. Description Notes Control unit
FC700A-1 A5Q00004734 Control unit pre-assembled Including B3Q700, H23B010, B2F020, E3C011,
Control terminal, Parallel indicator panel
B3Q700 A5Q00004719 Control terminal B3R051 490513 Parallel indicator panel
LON-Bus devices
E3I040 499310 LON interface K3I050 496766 LON/Mimic Display converter K3I110 528854 LON I/O card B3Q580 496177 Floor repeater panel B3Q590 496180 Floor repeater panel with control functions B3Q595 534110 Floor repeater panel with control functions
Line modules
E3M111 511531 Line module SynoLOOP E3M080 460268 Line module SynoLINE600/-Ex
Control modules
E3G050 460255 Control module 'Contacts' E3G060 542539 Control module 'monitored' E3G070 546661 Control module 'universal' E3L020 546645 Control module 'Driver' Z3B171 484383 Relay module
Interfaces
E3H020 460475 Gateway module Details see chapter 19 E3I020 460239 RS232 module Details see chapter 12 and 21 E3L030 475994 Control module VdS
Power supply AX1201 225487 Battery 12V/27Ah AX1210 475570 Battery 12V/15Ah
Accessories Z3I1060 A5Q00004722 Terminal block, 2x20 terminals in two levels For additional modules Z3I1050 A5Q00004717 Connection cable 19 conductors For connection via terminal 'X2' Z1K030 484231 Terminal block with p.c.b. Chassis To direct connection Z3I380 475567 Cable set I-Bus long To connect modules at the bottom with modules
Z3I470, E3G070, Z3I380, 2x Z3I1050, 1x Z3I1060 pre-wired
Details see chapter 12
Details see chapter 18
Details see chapter 15
Details see chapter 17
at the top
25
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Auxiliary power supply
11 Auxiliary power supply
11.1 Configuration
Module chassis view 'Modules'
27
28
37
38
E3C011
Z3I470
47
46
56
57
View A
48
58
31
B2F020
51
Cabinet front view
AX1201
or
AX1210
AX1201
or
AX1210
23
Mains
terminals
H38G310
A
absolutely essential
B2F020
Converter 115/230VAC
-> 29.6VDC/6A
Z3I470
Cable set, terminal strip with card holder
AX1201 / AX1210
Batteries
E3C011
Battery charging module
11.2 Block diagram
* TF = Temperature sensor for battery temperature monitoring
Mains
B2F020
Extension
TF*
H38G310
Batteries
AX12..
FC700A
TF*
Basic emergency power supply
Batteries
AX12..
Mains
B2F020
E3C011
Battery charging unit
Cascading
E3C011
Monitoring via HW monitoring path
Details see document 007831, chapter 'Cascading principle'
To activate the supervision path of the E3C011, the device "Fu supply ext. supply supervision" must be created in the tool SWE700A.
11.3 Modules
Component Order-No. Description Notes
H38G310 484930 Housing set Door without cut-out B2F020 470588 Converter 115/230VAC -> 29,6VDC 6A E3C011 505479 Battery charging unit Z3I470 484341 Cable set with card holder AX1201 225487 Battery 12V / 27Ah Capacity based battery make 'ALARMCOM' (FIAMM) AX1210 475570 Battery 12V / 15Ah
26
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
12 Control terminal B3Q700 (FC/FT)
12.1 Features
Double-sized (240x128 dots), backlit LC-Display for most intuitive and user-
friendly operation
Context- and system state adjusted operation functions via soft keys Functionally grouped, ergonomically operating and indicating elements Detailed event information like event type and location, intervention instruction
texts, system operating conditions etc.
Integrated emergency operation function Insertable inscription strips in various languages Access to system functions via four different operating levels depending on user
profile
Configurable for single or multi AREA operation Access authorisation via password or key switch Options
Lockable Plexiglas door H26T030 RS232 module E3I020 LON interface E3I040 for LON devices (floor control terminals etc.) Parallel indicator panel B3R051
Control terminal B3Q700 (FC/FT)
12.2 Options
12.2.1 Plexiglas door to B3Q700 (FC/FT)
Z3S200
for the locking of doors and/or
access authorization for operation
H26T030
Plexiglas door
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
27
Control terminal B3Q700 (FC/FT)
12.2.2 Place of the E3I020 RS232 module (FT)
B3Q700
Use flat cable F20A020
12.2.3 Place of the E3I040 LON interface (FT)
RS232 module E3I020 is mounted at the rear of the control terminal ‘FT’ by means of accessories Z1B020
-> Details see document 007827
Supplied with Z1B020:
Plug-in terminal 12 cont. Installation material
Protective cover
H28T110
B3Q700
H28G200
LON interface E3I040 connected at the I-Bus of a remote control terminal 'FT', only mounted in the housing H28G200
-> Details see document 007827
Supplied with Z1B070:
- Mounting bracket with card holder and terminal block numbering in red
- I-Bus flat and supply cable
28
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
12.3 Installation possibilities (FT)
B3R051
B3Q700
H23G230
19“ cabinet
H26G220
Dimensions B = 520 H = 300 T = 70
Dimensions
Built into H23/H26 cabinets Built into H28 cabinet
H23 cabinet B = 125 H = 219 T = 76
Dimensions H26 cabinet B = 366 H = 219 T = 76
Built into 19“ cabinet
G2A130
H28T110
By choice B3R051 H23B020 H23B020+E3I040
Control terminal B3Q700 (FC/FT)
H28G200
B3Q700
H28T120
B3Q700
G2A140
By choice B3R051 H23B020
12.4 Block diagram
FC, FT, FG
FC/FT
E3I020
RS232
1
Printer
C-Bus
2
B2F020
I-Bus
F12A100
B3R051
Can be installed separately, however at max. 1000m Max. 24 units, however max. 8 addresses Free allocation of the LEDs (programming according to application) Line and equipment not monitored
4xB3R051
Mains
E3C011
Batteries AX12..
B3R051B3R051 B3R051B3R051
F12A100 F12A100/470
LON-Bus
E3I040
24V Supply line
Databus
max.
1000m
separately connected
parallel indicator
Activation of Mimic Display, see chapter 'Mimic Display panel outputs'
Parallel branching permissible
Basic equipment Option
29
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Control terminal B3Q700 (FC/FT)
12.5 Connection lines between control unit and external operating units
Control terminal FT700A
Options
B3R051 (Parallel indicator panel) E3I040 (LON module) Printer
Loop C-Bus
Control unit FC700A
2…11 leads
max. 1000m per loop with 0,6mm G51 (incl. return line) max. 1400m per loop with 0,8mm G51 (incl. return line)
When planning a system the following condition must be complied with:
At least one operating unit must comply with standard EN54, i.e. it must be equipped with emergency operation and emergency power supply.
Control terminal FT700A
EN54 requirements:
Communication as loop line -> design C-Bus as a loop line Operating units also with emergency operation -> 3 additional wires Second de-coupled 24V supply -> 3 additional wires or autonomous power
supply The number of wires in the connection cable depends on the application and the distances between the stations:
Application C-Bus 24V supply
24V supply from control unit
EN54 complied with
24V supply from control unit without emergency operation and emergency power supply
(2 wires)
(2 wires)
(3 wires)
(3 wires)
Emergency power
supply
(3 wires)
Note:
Emergency operation circuit required including between CPUs or for a sepa-
rately connected Gateway
Emergency operation circuit and emergency supply are not designed as a loop
line
Emergency supply via separate cable or C-Bus feedback
Emergency opera-
tion circuit
(3 wires)
5
Number of wires
11
12.6 Power supply (24V)
Operating unit B3Q700 is designed for the voltage range 18...45VDC The maximum current at 24V is 400mA Max. Length of line (approximate):
For cables ø 0.8mm -> 180m
For cable cross-section 1mm
The current consumption for the options (parallel indicator panel, LON-module)
must be taken into account separately
30
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
2
-> 360m
Control terminal B3Q700 (FC/FT)
12.7 Modules
Component Order-No. Description Notes
B3Q700 A5Q00004719 Control terminal FT700A Operating unit CTY00760 (OSS) Flash program file For control terminal CIY00760 (OSS) Flash program file For control unit FCA725 A5Q00004833 Inscription set 'Spanish' FCA775 A5Q00004834 Inscription set 'Italian' FCA785 A5Q00004835 Inscription set 'polish' H26T030 570530 Plexiglas door Incl. mounting accessories Z3S200 570349 Key switch module (KABA) For operating access B3R051 490513 Parallel indicator panel '2x24 LEDs' E3I020 460239 RS232 module For the connection of a printer -> see chapter 21 Z1B020 475907 Mounting accessories for E3I020 Essential when mounting E3I020 on the rear terminal of
F20A020 476317 Flat cable micro 20 conductors 0.165m Link between E3I020 -> B3Q700, if E3I020 on the rear of
E3I040 499310 LON interface Converter between I-Bus and LON-Bus Z1B070 A5Q00001720 Mounting accessory for E3I040 Essential when mounting E3I040 in housing H28G200 Z3I481 491185 Cable set for control terminal FT700A in
Cabinets H23/H26/H28 for details referring cabinets -> see chapter 13
H28G200
B3Q700 (FT)
B3Q700 (FT)
Comprising -> Terminal block with made-to measure cable, cleat and cable clips
-> Details see document 007827
31
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Range of cabinets H23 / H26 / H28
13 Range of cabinets H23 / H26 / H28
H23G230
Dimensions 125x219x76mm Material Plastic Colour Pantone 421 grey Protection category IP40
H26G220
Dimensions 366x219x76mm Material Plastic Colour Pantone 421 grey Protection category IP40
H28G200
Housing with lock (DOM) Dimensions 520x300x70mm Material Steel sheet Colour housing RAL7035 light grey Protection category IP30
H28G200
Front can not be pivoted
Front can not be pivoted
Details of the cabinets -> see document 007827
H28T110
H28T120
H28T110
Door with cut-out for control terminal and parallel indicator panel B3R051 or cover plate H23B020 Colour door RAL7035 dark grey Protection category IP30
H28T120
Door with cut-out for 4 parallel indicator panel B3R051 Colour door RAL7035 dark grey Protection category IP30
Doors are hinged at left!
32
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Range of cabinets H23 / H26 / H28
13.1 Recessed mounting H23G230 and H28G200
H23U220
H23G230
H23G230
H23Z230
H23U230
H23Z230
UPR28
H28Z010
H28G200
Details of the cabinets -> see document 007827
13.2 Modules
Component Order-No. Description Notes
H23G230 475091 Plastic cabinet For additional indicators and operating units H26G220 462800 Plastic cabinet For remote control terminal B3Q700 (FT) H28G200 409944 Cabinet (without door) For various applications H28T110 474982 Cabinet door for B3Q700 (FT) / B3R051 H28T120 474995 Cabinet door for 4 B3R051 Parallel indicator
H23B020 476278 Cover plate For H28T110/120 H28Z010 410593 UP frame set For recessed mounting of cabinet H28G200 H23U220 379126 Recess box to B3R051 For recessed mounting of cabinet H23G230 H23U230 532879 Recess box to B3Q580/590/595 For recessed mounting of cabinet H23G230 H23Z230 532882 Cover frame to B3Q580/590/595/B3R051 For recessed mounting of cabinet H23G230 UPR28 430434 Recess box For 1 H28G200 cabinet (poss. required)
panel
33
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
19” accessories
14 19” accessories
Application of 3rd party cabinets
G2A130
G2A140
19”
Z2G030
6HU
14.1 Modules
Component Order-No. Description Notes
Z2G030 378198 Hinge 19"/6HE Consisting of hinge and spacer profile G2A130 475088 Adapter plate 19"/6HE For control terminal B3Q700 (FT) G2A140 484228 Adapter plate 19"/6HE For parallel indicator panel B3R051
34
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
15 Line modules
15.1 Overview
E3M111 for addressable detectors SynoLOOP E3M080 for collective detectors SynoLINE600/-Ex
FC700A
E3M111
Line modules
I-Bus
E3M080
24V
max. 500mA
24V
max. 500mA
1 2......... 8
Detector system SynoLOOP SynoLINE600/-Ex Number of lines 4 8 Number of addresses 4 x 128 8 Loop line Stub line Short-circuit separator In each device - Special features Separate supply output 24V for
input/output modules
✔ ✔
Line short circuit can be evaluated
as a fault or as an alarm
-
Z3I1050 or
E3M111
Z1K030
E3M080
15.2 Modules
Component Order-No. Description Notes
E3M111 511531 Line module SynoLOOP Addressable E3M080 460268 Line module SynoLINE600/-Ex Collective Z3I1050 A5Q00004717 Connection cable 19 conductors For connection via terminal block 'X2' Z1K030 484231 Terminal block with p.c.b. Chassis For direct connection
35
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Line modules
15.3 Detection line "addressable" SynoLOOP
Number of addresses per line max. 128 with APMK1 All detectors, manual call points and input/output modules with integrated line
separator
Connectable types of detectors and connection see document 007831
4 Loop lines
E3M111
24VDC
AI340
1
2
3
4
24VDC
DBZ1197A
DC1192
SB3
DM1103
DO1101-Ex
DT1101-Ex
DF1101-Ex
SynoLINE600-Ex
collective
max. 25
DM1133/MT320A
CB320A
OH320C
HI32xC
OP320C
SynoLINE300
conventional
max. 32
OP620A
24VDC
HI32xA
DC1192
SynoLINE600
collective
max. 25
24VDC
OP620C
HI62xC
OH320A
DC1192
24VDC
OP320A
DC1192
DLR11 . .
AI300
DLO1191
DF1191/92
ABI322A
EB322A
AB322A
BFST
Some detectors have different loading factors, to evaluate how many special de-
tectors can be connected to one addressable line see chapter 16.3
Control output for 1 external response indicator in each detector base
fixed allocation (output active as soon as the internal LED is flashing)
Room 101
Room 102
ZONE 7
ZONE 5
Room 103
Room 104
36
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
15.4 Detection line "collective" SynoLINE600/-Ex
All detectors on a line have the same collective address (ZONE) Number of detectors per line max. 25 with KMK1 Line termination depending on application by means of Transzorb or EOL22 (Ex) Connectable types of detectors and connection see document 007831
8 Stub lines
1
DBZ1197A
DLO1191
DM1103
DF1191/92
HI62xC
OP620C
Line modules
Line termination: Transzorb 20V/EOL22 Line resistance: max.150
E3M080
2
3
DLR11 . .
SynoLINE600
SynoLINE600-Ex
DM1103
DO1101A-Ex
DT1101xA-Ex
DF1101-Ex
Line termination EOL22 (Ex)
24VDC
DC1192
SB3
8
OP620C
HI62xC
Some detectors have different loading factors, to evaluate how many special de-
tectors can be connected to one collective line see chapter 16.2.
37
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Connection factors, line resistances and capacitances
16 Connection factors, line resistances and capacitan-
ces
16.1 Terminology and abbreviations
KLK Collective line factor (SynoLINE600) KMK Load factor for collective / conventional elements (SynoLINE600/300) APLK addressable line factor (SynoLOOP) APMK Load factor for addressable elements (SynoLOOP)
16.2 Collective detection line
The modules E3M080 / DC1192 have the collective line factor KLK 25 Line resistance max. 250Ω, 150Ω depending on evaluation required (line type 1,
11)
Line capacitance max. 4µF
The entire line from the control unit to the last detector as well as all response
indicator lines must be included when working out capacitance.
Details see document 007831
The total amount of detectors connected to one collective line should not ex­ceed a loading factor of 25
Element Short designation Load factor KMK
Smoke detector OP620C/OP320C 1 Heat detector HI620C/622C/HI320C/322C 1 Multisensor smoke detector OH320C 1 Smoke detector DO1101-Ex 1,6 Heat detector DT1101-Ex 1 Infrared flame detector DF1101-Ex 6 Infrared flame detector DF1191/92 6 Linear smoke detector DLO1191 25 Manual call point DM1101, DM1103 1 In-/output module DC1192 1
16.3 Addressable detection line
The line module E3M111 has the addressable line factor APLK 128 Line resistance see chapter 16.4 Line capacitance see chapter 16.4
For a description of the E3M111 line module, see document 007831 'Hardware de­scription'.
The total amount of detectors connected to one addressable line should not exceed a loading factor of 128
Element Short designation Load factor APMK
Smoke detector OP620A, OP320A 1 Heat detector HI620A/622A, HI320A/322A 1 Multisensor smoke detector OH620A, OH320A 1 Infrared flame detector DF1191/92 5 Manual call point MT320A, DM1133 1 Input module EB322A 1 Output module AB322A 2 In-/output module ABI322A 2 In-/output module DC1192, CB320A 3
Do not install lines longer than 2000m
38
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Connection factors, line resistances and capacitances
16.4 Line resistance and capacitance
The max. line resistance of the entire detector loop respectively from the detec-
tor furthest away to each of the two control unit connections must not exceed 150 .
The entire line from the control unit to the equipment connected and back again
to the control unit as well as response indicator lines must be included when working out capacitance.
max. C
E3M111
24VDC
max. R
EB322A
DC1192
CB320A
DC1192
24VDC
DC1192
24VDC
Max. Resistance 150 (max. R) Max. Capacitance 300nF (max. C) -> max. 600nF with max. 50 line resistance
24VDC
DC1192
ABI322A
AB322A
39
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Control modules
A
17 Control modules
17.1 Application of control modules
Activation of fire control installations (shutting-down ventilation, closing fire
dampers etc.)
Activation and monitoring of alarm device Activation and monitoring of remote transmission equipment Activation of Mimic Display panels
17.1.1 Overview of the available modules with control outputs
Modules Monitored con-
trol lines
For alarm devices
E3G070 2 7 1) 2) E3L020 16 1) E3G050 8 E3G060 6 5) K3R072 48 3) K3G060 24 NO contact 4) K3I110 16 NO contact 5)6)
1 Can also be used as control inputs (e.g. 'acknowledgement') 2 These inputs/outputs also serve for the activation of the remote transmission
equipment
3 For activation of Mimic Display panel, connected to the operating terminal
B3Q700 or K3I050 (no I-Bus module) -> Details see chapter 17.7 4 Applicable only with K3R072 -> Details see chapter 17.9 5 Programmable 6 LON-Bus module -> Details see chapter 18.5
Driver outputs
Programmable
Contact outputs
(Volt free)
Programmable
Remote transmis-
sion interface
To remote transmis-
sion equipment
17.2 Means of linking
Any statuses of entry nodes can be linked to control ZONES Normally, only 1 control ELEMENT is contained in 1 control ZONE (= control
output)
A user text is allocated to each control ZONE
Acquisition level Control level
addressable collective
Visible statuses:
- active
- switched off
- executed ('Acknowledgem.')
- fault
AREA SECTION ZONE
Digital input
‘active’
Operating level
Operatable functions:
- switch on/off
- activate/de
-activate
Statuses:
- alarm
- info
- switched off
- on detector TEST
- fault
- etc.
Control ZONE
E3G050 K3I110
E3L020 E3G070
E3G060
cknowledgement circuit
not
monitored
monitored
40
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
17.3 Control outputs station type FC700A
)
A
30VDC/1A
CPU
Basic equipment
B3Q700
E3G070
24V
1...............7
Z3B171
250VAC/10A
Fire control installations
Driver
dditional control modules according to application
I-Bus
E3L020
Driver Driver
1..........16
Z3B171
250VAC/10A
E3G050
1..........8 1..........6
30VDC/1A
E3I040
Converter I-Bus/LON
LON-Bus
K3I110
1......16
Control modules
E3G060
max. 24V/2A
(max. 4A/E3G060
Z3I1050
Up to 2 Z3I1050 (with additional terminal block) can be used other-
E3I040
E3L020
wise Z1K030 must be used.
K3I110
17.4 Control outputs remote station type FT700A
I-Bus
B3Q700
E3I040
converter
I-Bus/LON
LON-Bus
Z1K030
Z3I1050
E3G070
E3G060
E3G050
E3I040
K3I110
1......16
30VDC/1A
Z1B070
K3I110
Details mounting E3I040 see document 007827
17.5 Modules
Component Order-No. Description Notes
E3G070 546661 Control module 'Universal' Included in FC700A-1 package E3L020 546645 Control module 'Driver' 16 control inputs or outputs E3G050 460255 Control module 'Contacts' 8 control output contacts E3G060 542539 Control module 'Monitored' 6 monitored control lines for alarm equipment K3I110 528812 LON-I/O card 16 programmable in-/outputs Z3B171 484383 Relay module 1x 250VAC/10A To switch from external voltage E3I040 499310 LON module Converter between I-Bus and LON-Bus Z1B070 A5Q00001720 Mounting accessory for E3I040 Essential for mounting E3I040 in housing H28G200 Z3I1050 A5Q00004717 Connection cable 19 conductors 1 of each per E3L020/E3G050/60 Z1K030 484231 Terminal block with p.c.b. Chassis For direct connection
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
41
Control modules
17.6 CPU-overlapping controls
CPU
1
all-AREA
FC
single-AREA
FTFT
C-Bus
FC FC FC
CPU CPU CPU
2 3 n
Gateway
FG
A1
A2 A3 A4
= AREA
A5 A6 A7 A8 A9 A10 A11 A12 A.. A.. A.. A..
initiating data point
control ZONE/ELEMENT
control device
Limitation: see chapter 8
must be within the CPU
same
42
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
17.7 Mimic Display panel outputs
Control modules
B3Q700 (FT)
B3Q700 (FC/FT)
24V
F12A100
or
F12A470
Parallel branching permissible
24V
Z3I530
(Adapter)
max.1000m
(not monitored)
K3R072
Data bus
1
48
Details see document 007831
K3R072:
Short circuit-protected outputs Output for local buzzer and LED operation Inputs for button 'buzzer switch-off' und 'lamp test' Only suitable for the activation of LEDs Outputs can only be allocated the statuses from one logical node Max. 24 devices however max. 8 addresses
LED flat cable
cable length 1m, 24 red LEDs
LED flat cable
1
K3R072
48
F50F410
F50F410
LED flat cable
cable length 1m, 24 red LEDs
LED flat cable
Mimic Display panel
F50F410
F50F410
Mimic Display panel
Synoptic display panel housing
K3R072
K3R072
Z3I520
Short-circuit proof in-/outputs only for housing application
inside
LED 1....24
wires 49+50 for 'LED operation'
LED 25....48
wires 49+50 unused
Key 'Switch-off buzzer' Key 'Lamp test' Buzzer
max. permissible length
B3Q700
of the data bus 1000m
These in-/outputs can be in parallel with other K3R072 if located in same cabinet
17.8 Modules
Component Order-No. Description Notes
K3R072 528605 Mimic Display activation Z3I520 484969 Cable set for K3R072 Comprises 12 cables (2-wire with connector, length=0.5m) F50F410 529141 LED flat cable for K3R072 50-wire, 24 red LEDs, cable length 1m Z3I530 484972 Adapter To adapt flat cable to terminals F12A100 495275 Flat cable Micro 12-pin, 0.4m From B3Q700 (FT) to K3R072/B3R051 F12A470 495288 Flat cable Micro 12-pin, 1.5m From B3Q700 (FT) to K3R072/B3R051
43
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Control modules
17.9 Relay outputs
24V
F12A100
B3Q700 (FT)
or
F12A470
1
48
K3R072
max. 24 units,
however max.
8 addresses
Flat cable supplied with K3G060
1
24 outputs
max. 30V/1A
24
1
24 outputs
max. 30V/1A
K3G060 K3G060
24
B3Q700 (FC/FT)
Parallel branching permissible
24V
Data bus
Z3I530
(Adapter)
max.1000m
(not monitored)
K3G060:
2 K3G060 can be connected to each K3R072 24 volt-free relay-make contact Contacts not monitored Contacts can be individually connected via jumper to externally supplied V+ or
V- potential
1
48
K3R072
max. 24 units, however max.
8 addresses
1)
Flat cable supplied with K3G060
K3G060K3G060
External potential
(switchable via jumper X1......X24)
1
24
1
24
+/-
24 outputs
max. 30V/1A
24 outputs
max. 30V/1A
1)
+/-
Housing supplied by customer
1)
24 Relay outputs
K3R072
K3G060
24 Relay outputs
K3G060
17.10 Modules
Component Order-No. Description Notes
K3G060 528786 Relay card incl. flat cable Option to K3R072 Z3I530 484972 Adapter To adapt flat cable to terminals
44
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
18 LON-Bus devices
18.1 Features
Activation via local communication Bus 'LON' 4 different types of device available
B3Q580 = Text display terminal B3Q590/595 = Text control terminal K3I050 = LON/Mimic Display converter K3I110 = LON I/O card
Connection via I-Bus/LON module E3I040 (converter between I-Bus and LON-
Bus)
The function 'LON-Bus' is possible once per station type 'FC' and 'FT' Max. 32 devices per LON-Bus (device type can be mixed as required) Monitored two-wire-Bus without loop line function All devices require a separate feed line from E3I040 Wiring of the LON-Bus
As 'stub line' up to 1000m (without T-branches) As 'free topology' up to 500m (length of line to all devices added) with 'MICC'
as 'stub line'.... 700m / as 'free topology'... 300m
With special cable (Belden 85102 or 8471) and as 'stub line' up to 2700m Only possible via twisted line (10 turns per meter)
CPU-overlapping functions possible B3Q59x: bottom three LEDs are pluggable. Allows application with different LED
colour
LON-Bus devices
18.2 LON-Bus as stub line
B3Q700
E3I040
LON-Bus
Z1K030
E3I040
Z3I1050
Z1B070
Details K3R072 see page 43 Details B3R051 see page 29
I-Bus
K3I110
E3I040
max. length of LON-Bus 1000m
24VDC
K3I050
24VDC
Data bus
B3Q580
(not monitored)
K3R072
B3R051
FC/FT
B3Q590/
595
or
K3R072
or
B3R051
45
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
LON-Bus devices
18.3 LON-Bus as free topology
I-Bus
B3Q700
E3I040
max. length of LON-Bus 500m
LON-Bus
K3I110
24VDC
K3I050
24VDC
18.4 LON/Mimic Display p.c.b K3I050
Allows connection of Mimic Display p.c.b. K3R072 or parallel indicator panels
B3R051 (max.24 units, however max. 8 addresses)
Various local inputs/outputs
Dimensions: 106 x 200 x 14mm
K3I050
Data bus
B3Q580
B3Q580
(not monitored)
K3R072
or
B3R051
FC/FT
B3Q590/
595
K3R072
or
B3R051
to K3R072/B3R051
H23G230
Input key 'buzzer switch-off'
The functions of the
Input key 'lamp test'
in-/outputs refer on the K3R072 resp. B3R051
Output local buzzer
Output LED 'operation'
18.5 LON I/O card K3I110
Input/output card
16 programmable monitored control inputs 16 programmable control outputs
Dimensions: 122 x 220 x 14mm
K3I110
Lon-Bus 24V
50cm
Z3I530
Z3I520
H23G230
K3I050
Z3B230
K3I110
46
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
18.6 Indicator devices B3Q580 and B3Q590/595
Both devices have identical dimensions Recessed mounting see page 33
LON-Bus devices
H23G230
B3Q580
H23G230
B3Q590 B3Q595
(Nordic lock) (KABA lock)
Function B3Q580 Text display terminal B3Q590/595 Text control terminal
LCD 2x40 characters backlight yellow Alarm event indicator All ZONES from 1...4 selectable SECTIONS All ZONES per station (not selectable) Fault event indicator Selectable (yes/no via SWE700A) Selectable (yes/no via SWE700A) Selectable operating mode 14 (selectable via SWE700A) 14 (selectable via SWE700A) Buzzer, can be silenced 3 programmable LEDs Function key ’Onward switching’ (also serves to silence buzzer + lamp test) (also serves to silence buzzer + lamp test) Function key ’Acknowledge’ / ’Reset’ Key switch for operating access
For installation in housing H23G230 Slide–in inscription strips Operating voltage 9...45VDC 9...45VDC Current consumption at 24V Quiescent: 20mA / max: 180mA Quiescent: 18mA / max: 185mA
✔ ✔
✔ ✔
✔ ✔
B3Q590 = Nordic
B3Q595 = KABA
18.7 Modules
Component Order-No. Description Notes
E3I040 499310 LON module Converter between I-Bus and LON-Bus Z3I1050 A5Q00004717 Connection cable 19 conductors For connection via terminal block 'X2' Z1K030 484231 Terminal block with p.c.b. chassis For direct connection K3I050 496766 LON/Mimic Display converter Interface between LON-Bus and Data Bus for
K3I110 528854 LON I/O card 16 programmable control in-/outputs B3Q580 496177 Floor repeater panel B3Q590 496180 Floor repeater panel with control functions with
B3Q595 534110 Floor repeater panel with control functions with
H23G230 475091 Plastic housing Z3I520 484969 Cable set to K3R072 Comprises 12 cables (2-wire with connector,
Z3I530 484972 Adapter To adapt flat cable to terminals Z3B230 559001 Support plate-set For K3I050 in H23G230 Z1B070 A5Q00001720 Mounting accessory for E3I040 For mounting in housing H28G200
K3R072 or B3R051
Nordic lock
KABA lock
length=0.5m)
47
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Gateway
19 Gateway
19.1 Main features
Connection C-Bus network <-> Building management system via V28 interface
(RS232) ISO1745 Protocol
Per C-Bus network are several gateway possible, see chapter 8 Install preferably in the fire detection system control unit cabinet
FT FT
C-BUS
19.2 Application
FC
Module chassis view modules
27
37
E3M111
46
47
Line-
modules
28
E3C011
38
E3G070
48
FC
I-BUS
Line- Control-
Detector
Fire detection control unit
C-Bus
I-BUS
Control-
modules
Detector
E3C011
E3M111
47
57
E3G070
module
24VDC
Z1K030
FG700A
E3H020
RS232
X2
ISO1745 Protocol
ISO1745 Protocol
56
58
E3H020 + 2xZ1K030
E3H020
48
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
19.3 Modules
Component Order-No. Description Notes
E3H020 460475 Gateway module Requires 2 module spaces CKQ007.60 A5Q00005137 EPROM set Software for ISO1745 Protocol for E3H020 Z1K030 484231 Terminal block with p.c.b. Holder For direct connection
Note:
The E3H020 is factory side equipped with 4 RAMs (4x 512Kx8Bit) details see document 007831
Gateway
49
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Remote transmission
20 Remote transmission
Most fire detection systems are linked to a remote transmission system. Therefore in case of alarm (alarm stage 2) the fire detection system must initiate the remote
transmission device (RT-device).
Remote transmission device
Located in cabinet of control unit Required space depends on the type of remote transmission device Powered by 24VDC of the fire control unit Single channel (alarm + fault) or multi channel (several alarm channels) Disabling/enabling via B3Q700 (FC/FT)
Interfacing
Via output contacts and special control in-/outputs of the E3G070
Interfacing via E3G070
I-Bus
B3Q700 (CPU)
E3G070
alarm fault
K2
RT-device
24V
FC700A
50
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
21 Printer interface
r
21.1 Features
Provided with station types FC, FT Designed for commercially available printer with ISO-Latin1 or EPSON character
set
Always allocated to all existing AREAS for the station used The printer can be individually switched on/off via operating terminal The event memory can be printed only if the printer is connected to a station FC
or FT
21.2 Application variant FT
B3Q700
I-Bus
FT
B3Q700
Printer interface
E3I020
ST2
to printe
ST1
RS232
E3I020
ST2
C-Bus
ST2
F20A020
max.1000m
21.3 Application variant FC
B3Q700
C-Bus
ST2
F20A140
I-Bus
ST1
RS232
max.1000m
E3I020
X2
FC
to printer
F20A020
Z1K030
E3I020
in cabinet H26/H28
B3Q700
Housing control unit
Z1B020
F20A140
21.4 Modules
Component Order-No. Description Notes
E3I020 460239 RS232 module Level adaptation HCMOS -> RS232 Z1B020 475907 Mounting accessories To mount E3I020 at the rear of B3Q700 (FT) F20A020 476317 Flat cable 'Micro' 20 conductors, 0.165m Z1K030 484231 Terminal block with p.c.b. Holder To mount E3I020 on the module space Pos.27 F20A140 496863 Flat cable 'Micro' 20 conductors, 0.650m
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
51
Power supply
22 Power supply
22.1 Concept
The power supply for the FC700A fire detection system consists of:
Converter (mains voltage -> system voltage 29,6V) Battery charging unit (by means of E3C011) Batteries (lead) (capacity as required)
22.2 Special functions
Automatic battery load test Battery charging characteristic can be programmed according to make
22.3 Application
Determine required battery capacity individually -> see chapter 23 Max. 27Ah per battery charging unit (> 27Ah = auxiliary power supply) Parallel operation of several battery charging units possible Battery lead without EMI-protection (battery cannot be mounted separately)
22.4 Power supply for the control unit
Battery charging module E3C011 required
Mains
FC
B3Q700
B2F020
40...220VA
29,6V
E3C011
22.5 Auxiliary power supply
* TF = Temperature sensor for battery temperature monitoring
Mains
AX12..
B2F020
C-Bus
FT
Basic emergency power supply
Batteries
TF*
TF*
I-Bus
Batteries
AX12..
Mains
Extension
B2F020
TF*
Batteries
AX12..
Battery charging
24V
unit
E3C011
E3C011
FC
52
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Monitoring via HW monitoring path
Power supply
22.6 Modules
Component Order-No. Description Notes
B2F020 470588 Converter 115/230VAC -> 29,6VDC 6A (... 220VAC) E3C011 505479 Battery charging unit Z3I470 484341 Cable set with card holder AX1201 225487 Battery 12V / 27Ah Capacity based battery make 'ALARMCOM'
(FIAMM)
AX1210 475570 Battery 12V / 15Ah
22.7 Operation with power supply from control unit
FT
+ / - /Earth
Output 1
B3Q700
24V / 2A
Output 2
FC
I-Bus
Note: A 2nd supply output is only necessary for operating units, which must com-
ply with EN54 (at least 1 operating unit per system)
22.8 Power supply for remote transmission equipment and acces­sories
FC
B3Q700
I-Bus
E3G070
24V / 0.63A
24V / 0,63A
Remote transmission
or other equipment
53
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Emergency power supply
23 Emergency power supply
23.1 Specifying battery capacity
23.1.1 Battery rated capacity
The battery rated capacity is based on the discharge over a period of 20 hours Faster discharge causes a loss of capacity:
Discharge over 12-hour period: 9% loss (K = 1.1)
23.1.2 Ageing of battery
With increasing age, the battery suffers a loss of capacity
Allow a safety factor for ageing
(Total quiescent current y 1.25 or battery capacity y 0.8) > 24h in conformity with DIN VDE 0833, part 2, no safety factor is necessary
23.1.3 Calculation
Battery capacity must be calculated individually! Formula: Ah = A x h x 1.25 (poss. x K)
Ah = Battery capacity in Ah A = the sum of the quiescent current for all modules h = Required operating period in hours
1.25 = Safety factor for ageing K = Capacity loss if discharge is over considerably less than 20 hours
23.2 Capacity values for standard configurations
Configuration Quiescent current
128 detectors addressable 7outputs 235mA 3,8Ah 7,0Ah 16,9Ah 16 collective lines 7 outputs 315mA 5,1Ah 9,4Ah 22,6Ah
Notes:
Equipped with 1 control terminal B3Q700 Discharge over a 12-hour period, 9% loss of capacity taken into account Factor 1.25 for ageing taken into account at 12h and 24h (72h without safety
factor)
Without remote transmission equipment Only quiescent current taken into account
Battery capacity requirement for
12h 24h 72h
54
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Emergency power supply
23.3 Quiescent current table
Quiescent current when on battery operation (24V) As basis for individual calculation of emergency power supply The current for the 5V supply is included in these values
Module Quiescent current at 24VDC (typical) Additional current with alarm condition
B2F020 0 0 B3Q700 100mA LCD backlight ’inactive’ (active = + 200mA) + 230mA B3Q580 20mA + 160mA B3Q590/595 18mA + 167mA B3R051 40mA all LEDs inactive + 2mA per activated LED E3C011 20mA 0 E3G050 10mA all relays inactive + 11mA per activated relay E3G060 25mA all control lines terminated + 23mA per activated control line, without external load E3G070 25mA control line ’Horn’ terminated + 34mA without external load (horns etc.) E3H020 100mA 0 E3I020 25mA 0 E3L020 22mA + ..mA depends from the activated device E3L030 18mA + 40mA without external load (FBF, HM, FSK) E3M080 85mA 37mA + 6mA per terminated line + 10mA per line in alarm E3M111 210mA (=50mA + 0,31mA per D–Bus device) 1)
(without external 24V load) K3G060 6mA + 3mA per relay K3R072 40mA + 2mA per activated LED
Z3B171 0 + 27mA per activated relay E3I040 15mA without external 24V load 0 K3I050 15mA + 0mA or 4mA per activated LED K3I110 24mA max. 184mA all relay activated incl. service LED + 10mA per activated relay
1 Only valid for device with APMK = 1 (multiply value for devices > 1)
0
0 per activated relay
+ 0,5mA per input with closed contact
55
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Alarm concept
p
V
V
24 Alarm concept
The alarm concept must be worked out individually for each system The important thing is to pass on the alarm message quickly to the appropriate
group of recipients
The requirements vary between
'Discreet alerting' of the reconnaissance squad, e.g. via staff paging system 'Alarm / evacuation' for people familiar with the location 'Alarm / evacuation' for people unfamiliar with the location 'Area evacuation', e.g. building storey
24.1 Cerberus Alarm Concept (CAC)
The Cerberus alarm concept prevents the unnecessary turnout of the fire de-
partment for minor incidents
The CAC is based on an alarm organization involving the presence or absence
of personnel:
Presence of operating personnel or "Day" Absence of operating personnel or "Night"
The response of the operating personnel is monitored by two independent time
circuits (V1 and V2) monitored
The CAC is an integrated part of the FC700A control unit. The required parame-
ters can be entered via the user functions
24.2 Principle of the Cerberus alarm concept
During the "Day" operating mode, if an alarm is activated its source is located
and the decision is taken "Emergency" or "Minor incident"
During "Night" operating mode, all signals immediately generate a "Remote
alarm"
The activation of a manual call point always immediately generates a "Remote
alarm"
Alarm event
Local alarm
manned or unmanned
F
unmanned
manned
V1
running
1 = 0
<Acknowledge>
'Emergency'
<Alarm delay OFF>
F
ressed
- or -
pressed
Operating mode
'Minor incident'
V2
<Reset>
pressed
running
General alarm
Remote alarm
2 = 0
Normal operation
56
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
24.3 Determine the alarm organization
The FC700A fire detection system has up to 64 programmable organization lev-
els (AREAS)
A number of "Alarm variants" are possible (can be selected per ZONE) The time countdown memories "V1" and "V2" must be specified individually The time countdown memory "V2" can be defined per ZONE (if required) Various special local functions are provided The alarm organization is programmed individually (via maintenance PC)
24.4 Organization of system operation
The place of operation of the fire detection system must be determined from an
organizational point of view
If required a second operating facility must be provided If operating units are particularly exposed, they must be fitted with a lockable
Plexiglas door (H26T030 + Z3S200)
The type of event and the location are displayed on the operating unit in plain
text
The locations (rooms etc.) are individually defined by means of the "User text"
(via maintenance PC)
If required, an additional event-related instruction, a so-called counter-
measures text, can be allocated
The fire detection system may only be operated by instructed personnel (operat-
ing access is therefore protected by password or key switch)
Details of control terminal FT700A see chapter 12
Alarm concept
57
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Commissioning
25 Commissioning
The FC700A fire detection system is designed for rational systems engineering. Connection work at the control unit can be due by non-specialist personnel (e.g. outside electricians). However, co-ordinated supervision is still essential. Specially trained personnel with a maintenance PC are required for commissioning (service engineer).
Details see document 007828
58
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Parameterization, Flash programming
26 Parameterization, Flash programming
Parameters are set for the FC700A fire detection system via the maintenance
PC by means of the software tool set 'SWE700A'.
Online-Help text
Flash programming is only relevant if B3Q700 is used as replacement for FC700A
New software is programmed by means of the 'Flash Tool' software. For the
modules B3Q700 the application software is now loaded into the Flash ROM via the maintenance PC by means of the 'Flash Tool' software.
Details see Online-Help in SWE700A
26.1 Functions
B3Q700 (FT700A)
Control terminal
ST2
C-Bus
ST2
B3Q700 (FC700A)
Control unit
- for flash programming new application software
- download all system data
Modem box
RS232
B3D021
FC
I-Bus
E3M...
Load new application software (Flash) if necessary Prepare/supplement structure of the system Define user functions (system-specific) Specify/correct user text Detector localization Data transfer of user functions to control unit
Maintenance PC with
'SWE700A' + 'FlashTool' software
26.2 Modules
Component Order-No. Description Notes
B3D021 505259 Modem box for SWE700A (DUAL RS232 ITF) Complete with flat cable 20 conductors,
L=0.2m
- 505330 Flat cable L=0,2m As spare part M3C700 A5Q00004798 USB Dongle Key for SWE700A
59
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
FC700A modules in alphabetical order
27 FC700A modules in alphabetical order
Component Order-No. Description Notes
AX1201 225487 Battery 12V / 27Ah Capacity based battery make 'ALARMCOM' (FIAMM) AX1210 475570 Battery 12V / 15Ah B2F020 470588 Converter 115/230VAC -> 29,6VDC 6A
B3D021 505259 Modem box for SWE700A (DUAL RS232 ITF) Complete with flat cable 20 conductors, L=0.2m B3Q580 496177 Floor repeater panel B3Q590 496180 Floor repeater panel with control functions With Nordic lock B3Q595 534110 Floor repeater panel with control functions With KABA lock B3Q700 A5Q00004719 Control terminal FT700A Operating unit B3R051 490513 Parallel indicator panel '2x24 LEDs' CIY00760 (OSS) Flash program file For control unit CKQ007.60 A5Q00005137 EPROM set Software for ISO1745 Protocol for E3H020 CTY00760 (OSS) Flash program file For control terminal E3C011 505479 Battery charging unit E3G050 460255 Control module 'Contacts' 8 control output contacts E3G060 542539 Control module 'monitored' 6 monitored control lines for alarm equipment E3G070 546661 Control module 'universal' Included in FC700A-1 package E3H020 460475 Gateway module Requires 2 module spaces E3I020 460239 RS232 module For the connection of a printer E3I040 499310 LON module Converter between I-Bus and LON-Bus E3L020 546645 Control module 'Driver' 16 control inputs or outputs E3L030 475994 Control module VdS E3M080 460268 Line module SynoLINE600/-Ex For collective detectors E3M111 511531 Line module SynoLOOP For addressable detectors F12A100 495275 Flat cable Micro 12-pin, 0.4m From B3Q700 (FT) to K3R072/B3R051 F12A470 495288 Flat cable Micro 12-pin, 1.5m From B3Q700 (FT) to K3R072/B3R051 F20A020 476317 Flat cable micro 20 conductors 0.165m Link between E3I020 -> B3Q700, if E3I020 on the
F20A140 496863 Flat cable 'Micro' 20 conductors, 0.650m F50F410 529141 LED flat cable for K3R072 50-wire, 24 red LEDs, cable length 1m FC700A-1 A5Q00004734 Control unit pre-assembled Including B3Q700, H23B010, B2F020, E3C011,
FCA725 A5Q00004833 Inscription set 'Spanish' FCA775 A5Q00004834 Inscription set 'Italian' FCA785 A5Q00004835 Inscription set 'polish' G2A130 475088 Adapter plate 19"/6HE For control terminal B3Q700 (FT) G2A140 484228 Adapter plate 19"/6HE For parallel indicator panel B3R051 H23B010 476210 Cover plate for FC700A As spare part H23B020 476278 Cover plate For H28T110 H23G230 475091 Plastic cabinet For additional indicators and operating units H23U220 379126 Recess box to B3R051 For recessed mounting of cabinet H23G230 H23U230 532879 Recess box to B3Q580/590/595 For recessed mounting of cabinet H23G230 H23Z230 532882 Cover frame to B3Q580/590/595/B3R051 For recessed mounting of cabinet H23G230 H26G220 462800 Plastic cabinet For remote control terminal B3Q700 (FT) H26T030 570530 Plexiglas door Incl. mounting accessories H28G200 409944 Cabinet (without door) For various applications H28T110 474982 Cabinet door for B3Q700 / B3R051 H28T120 474995 Cabinet door for 4 B3R051 parallel indicator
H28Z010 410593 UP frame set For recessed mounting of cabinet H28G200 H38G310 484930 Housing set Door without cut-out K3G060 528786 Relay card incl. flat cable Option to K3R072 K3I050 496766 LON/Mimic Display converter Interface between LON-Bus and Data Bus for K3R072
K3I110 528854 LON I/O card 16 programmable control in-/outputs K3R072 528605 Mimic Display activation Comprises 12 cables (2-wire with connector,
M3C700 A5Q00004798 USB Dongle Key for SWE700A UPR28 430434 Recess box For 1 H28G200 cabinet (poss. required) Z1B020 475907 Mounting accessories for E3I020 Essential when mounting E3I020 on the rear terminal
Z1B070 A5Q00001720 Mounting accessory for E3I040 Essential when mounting E3I040 in housing H28G200 Z1K030 484231 Terminal block with p.c.b. holder Z2G030 378198 Hinge 19"/6HE Consisting of hinge and spacer profile Z3B171 484383 Relay module 1x 250VAC/10A To switch from external voltage Z3B230 559001 Support plate-set For K3I050 in H23G230 Z3I1050 A5Q00004717 Connection cable 19 conductors With terminal block and p.c.b. Holder Z3I1060 A5Q00004722 Terminal block, 2x20 terminals in two levels For additional modules Z3I380 475567 Cable set I-Bus long To connect modules at the bottom with modules at the
60
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
(...220VAC)
rear of B3Q700 (FT)
Z3I470, E3G070, Z3I380, 2x Z3I1050, 1x Z3I1060 pre-wired
panel
or B3R051
length=0.5m)
of B3Q700 (FT)
FC700A modules in alphabetical order
Component Order-No. Description Notes
Z3I470 484341 Cable set with card holder Z3I481 491185 Cable set for control terminal FT700A in
H28G200
Z3I520 484969 Cable set for K3R072 Comprises 12 cables (2-wire with connector,
Z3I530 484972 Adapter To adapt flat cable to terminals Z3S200 570349 Key switch module (KABA) For operating access
top
Comprising -> Terminal block with made-to measure cable, cleat and cable clips
length=0.5m)
61
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Spare parts
28 Spare parts
Component Order-No. Description Notes
- 505739 Buzzer 12-36V 3500Hz 85DB for B3Q700
- 463686 Card holder for Z1K030/Z3I1050
- 462790 Cover frame (plastic) for B3Q700
- 463809 Cover frame (plastic) for B3R051/B3Q580/590/595
- 564669 Duplicate key DOM at locking 2C 2500 for H28G200 EOL22 516222 End of line element
- 505330 Flat cable L=0,2m for B3D021
- 471451 Flat cable I-Bus + supply cable 'short' for I-Bus modules
- 467478 Flat cable micro 20 conductors, 0.17m for E3I020
- 145635 Fuse 0.25A slow blow for E3G070
- 145606 Fuse 0.4A slow blow for B3R051, K3R072, K3G060
- 145648 Fuse 0.5A slow blow for E3G050
- 450388 Fuse 0.5A slow blow, with high breaking capacity for B3Q700, E3L020
- 145680 Fuse 0.63A slow blow for E3G070
- 467177 Fuse 0.8A slow blow, with high breaking capacity for B3Q700, E3H020
- 450391 Fuse 1.0A slow blow, with high breaking capacity for E3M111
- 424246 Fuse 1.25A quick acting for E3L020
- 450414 Fuse 2.0A slow blow, with high breaking capacity for E3H020, E3L030, E3G060/70
- 338879 Fuse 5A slow blow for E3G070
- 145729 Fuse 6.3A slow blow for E3G060
- 433363 Fuse 6.3A slow blow, with high breaking capacity for E3C011 KABA100 163837 Key 'KABA 8' (#100) for B3Q595
- 484396 Key 'Nordic' for B3Q590
- 459729 Lithium battery 3V, to solder for B3Q700
- 475774
- 475237 Terminal block, pluggable, 12 cont., orange for E3I020
- 495440 Terminal block, pluggable, 3 cont., orange for E3H020
- 483669 Terminal block, pluggable, 4 cont., grey for B3Q700 (C-Bus)
- 463977 Terminal block, pluggable, 4 cont., orange for all I-Bus modules (K1)
- 483672 Terminal block, pluggable, 4 cont., black for B3Q700 (power supply monitoring)
- 463951 Terminal block, pluggable, 5 cont., orange for B3Q700 (emergency operation)
- 463964 Terminal block, pluggable, 6 cont., orange for B3Q700, B3R051, K3R072, E3G070
- 460051 Transzorb diode bidirectional 20V, 5%, 600W/ms for E3M080
- 319351 Zero-Ohm resistor for various modules (jumper)
- 505330 Flat cable L=0,2m for B3D021
PTC, 2kΩ, 0.5%, with cable
for E3C011
62
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
29 Configuration sheets
The following pages can be copied or used as a basis for individual local require­ments. The configuration for specific systems is entered on these pages (location of units, number and type of modules, etc.).
29.1 List of configuration sheets
FC700A
Configuration with control terminal B3Q700 as main CPU (control unit)
Details see page 64
Auxiliary power supply
Details see page 65
FT700A
Configuration for control terminal B3Q700
Details see page 66
Configuration sheets
B3Q580/590/595, B3R051
Configuration display & operating terminals
Details see page 67
K3I110, K3I050, K3R072, K3G060 etc.
Externally placed modules
Details see page 68
63
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Control unit FC700A
V
V
30 Control unit FC700A
Type of detection line SynoLOOP SynoLINE600/-Ex
Number of detector addresses Number of lines
Fire control installations for 30V for 250V
Number of control outputs
23
max. 10x Z3B171
28
E3C011
38
E3G070
Z1K030
48
58
Z3I470
Z1K030
Mains
terminals
AB
iew B
Terminalblock
X1
40 Terminals
X2
EMC Precaution:
Slot rows with E3C011 module must not be fit with either E3I040 module
21
B2F020
AC/DC converter
31
AX1201
or
AX1210
or
..............
51
AX1201
or
AX1210
or
..............
iew A
27
37
E3M 111
47
46
57
56
FC700A-1
Control unit FC700A including:
E3C011, E3G070, E3M111, 40 Terminals, B2F020 pre-wired
Control unit FC700A-1 A5Q00004734
Inscription sets FCA… A5Q0000….
Modules E3M111 511531 E3M080 460268 E3L020 546645 E3G050 460255 E3G060 542539 E3I020 460239 E3I040 499310 E3H020 * 546658 E3L030 * 475994
* requires 2 module spaces
Cable, terminals, relay Z1K030 484231 Z3I1050 A5Q00004717 Z3I1060 A5Q00004722 Z3I380 475567 Z3B171 484383
Batteries AX1201 225487 AX1210 475570
EPROM to E3H020 CKQ007.60 A5Q00005137
Details see chapter 10
64
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
31 Auxiliary power supply
A
31
51
H38G310
AX1201
or
AX1210
or
..............
AX1201
or
AX1210
or
..............
View A
27
23
Mains
terminals
28
Auxiliary power supply
Housing H38G310 484930
Power supply B2F020 470588 E3C011 505479
Cable set Z3I470 484341
Batteries AX1201 225487 AX1210 475570
37
38
E3C011
Z3I470
B2F020
AC/DC converter
47
46
56
48
57
58
Details see chapter 11
65
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Control terminal FT700A
32 Control terminal FT700A
No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 FT700A
Control terminal 'FT' B3Q700 A5Q00004719
Inscription sets FCA… A5Q0000….
Accessories H26T030 570530 Z3S200 570349
RS232 interface & accessories E3I020 460239 Z1B020 475907 F20A020 476317
LON interface & accessories E3I040 499310 Z1B070 A5Q0001720
Cabinet H26 H26G220 462800
Cabinet H28 H28G200 409944 H28T110 474982 H28Z010 410593 UPR28 430434
Additional equipment B3R051 490513
Cover plate H23B020 476278
Cable set Z3I481 491185
H26T030
H28T110
H28T120
B3Q700
Z3S200
H26G220
Z1B020
FCA...
Z1B070
UPR28
H28Z010
H28G200
B3R051
H23B020
Details see chapter 12
66
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
33 Display & operating terminals
H23Z230
H23Z230
H23U230
H23G230
H23U220
B3Q590
B3Q595
B3Q580
H23G230
H23G230
K3I110
Display & operating terminals
Floor panels B3Q580 496177 B3Q590 496180 B3Q595 534110
Cabinet H23G230 475091
Accessories for recess mounting H23Z230 532882 H23U230 532879 H23U220 379126
LON/Mimic display converter K3I050 496766
LON I/O card K3I110 528812
Support plate Z3B230 559001
Additional equipment B3R051 490513
B3R051
H23G230
H23G230
K3I050
Z3B230
Details see chapter 18
67
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Externally placed modules
34 Externally placed modules
K3R072
K3I050
Z3I530
Z3I520
Z3I530
Z3I520
F50F410
K3G060
F12A...
K3I110
Mimic & accessories K3R072 528605 Z3I520 484969 Z3I530 484972
Relay card K3G060 528786
Flat cable, LED flat cable F12A100 495275 F12A470 495288 F50F410 529141
LON/Mimic display converter K3I050 496766
LON I/O card K3I110 528812
Details see chapter 17.7 / 17.9 / 18
68
Siemens Building Technologies 007836_a_en_--.doc Fire & Security Products 03.2004
Siemens Building Technologies AG Alte Landstr. 411 CH-8708 Männedorf Tel. +41 1 - 922 6111 Fax +41 1 - 922 6450
www.sibt.com
Document no. Edition 03.2004 Section 2
007836_a_en_-- Manual FC700
Loading...