Siemens FT2040, FC2030, FC2020, FC2060, FC2040 Installation Manual

009197_h_--_--
Building Technologies
2016-04-20 Control Products and Systems
FS20
FT2040 / FC2020 / FC2030 FC2040 / FC2060
1 m
1
,
6..
.
1
,7m
Brandmeldeterminal Fire terminal Terminal d'exploitation incendie Terminal de incendio Terminale di com ando
Brandmeldezent rale Fire control panel Équipement de contrôle et signalisation Unidad de control de detección de incendios Centrale rivelazione incendio
3
4
2
121
1
3 4
1
1
2
1
2
344
2
11121
1
2 Building Technologies 009197_h_--_--
Fire Safety 2016-04- 20
FT2040 FC2020 FC2020 / FC2040
3442111
2
1
1
3 44
2
112
1
1
FC2030 FC2060
3
Building Technologies 009197_h_--_-­Fire Safety 2016-04- 20
en
Safety notes
Danger of damage to persons and
property
Please adhere to the following safety instructions:
l The installation is intended for stationary mounting
and dry rooms only.
l Work on electri cal installations must always be
performed by a qualified and authorized electrician
l All feed lines must be inserted from the top or
through the rear panel.
l The enclosed batteries may only be install ed in the
housing by an authorized service technician.
l If the station is mounted on a flammable wall, all
cut-out sections for the mounting holes must be sealed using the supplied aluminum patch tabs.
Mounting notes
l Any unevenness of the mounti ng surface
exceeding 5 mm must be equalized.
l Wall mounting is done with screws Ø 6 mm
(enclosed in the delivery).
l Rectangular cable entries must be provided with
edge protecti on stri ps.
l At maximum 8 cables can be i nserted per round
cable entry (20 mm wit h rubber grommet).
l Only one cable may be inserted through each
screwed cable gland (not included in the scope of delivery).
Hardware damage
The operating unit and components must always be assembled by an authorized service technician.
Mounting
1. Break out the desired cable entries (2), (3) or (4) on
the housing.
2. Mark the drillings (1) for the dowel holes by means
of the enclosed template.
3. Dril
l the holes and place the dowels (encl osed i n the
delivery).
4. Fix the housing wit h the screws (enclosed in the
delivery).
5. Stick the supplied aluminum patch tabs over all cut-
out sections for the mounting holes.
Danger of damag
e to persons and
property
Cables must always be inserted and connected by a qualified service technician.
6. Protect the electronic parts with the package cover
or other suitable means.
Reference docu ments
Documentati on relating to further work sequences, Document ID: 008851 Installation