Siemens FC121-ZA, FC122-ZA, FC123-ZA, FC124-ZA Technical Manual

Page 1
Fire Control Panel
FC121-ZA / FC122-ZA / FC123-ZA / FC124-ZA
Technical Manual
A6V10393190_h_en_-­2019-09-01
Smart Infrastructure
Page 2
Legal notice
Technical specifications and availability subject to change without notice. © 2014 Copyright by Siemens Switzerland Ltd.
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved.
Issued by: Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424
www.siemens.com/buildingtechnologies
Edition: 2019-09-01 Document ID: A6V10393190_h_en_--
2 Smart Infrastructure A6V10393190_h_en_--
Page 3
Table of contents
1 About this document.................................................................................. 7
2 Safety regulations .................................................................................... 10
3 System description .................................................................................. 13
3.1 System overview ................................................................................................... 13
3.2 Features ............................................................................................................... 13
3.3 Technical data....................................................................................................... 14
3.3.1 Electrical data ....................................................................................................... 14
3.3.2 Mechanical data .................................................................................................... 15
3.3.3 Environmental conditions ...................................................................................... 16
3.4 Standard and options EN 54.................................................................................. 17
4 Installation ................................................................................................ 18
4.1 Power supply – mains voltage connection ............................................................. 18
4.2 Instruction ............................................................................................................. 20
4.2.1 Connection overview ............................................................................................. 21
4.3 Zone modes .......................................................................................................... 22
4.3.1 Standard ............................................................................................................... 22
4.3.2 Mixed .................................................................................................................... 23
4.3.3 GB continuity ........................................................................................................ 24
4.3.4 Short = alarm ........................................................................................................ 25
4.4 Outputs ................................................................................................................. 26
4.4.1 Mainboard (OUT1 / OUT2) .................................................................................... 26
4.4.2 Output card (OUTA / OUTB).................................................................................. 26
4.4.3 Relay .................................................................................................................... 28
4.4.4 Dialer connection .................................................................................................. 29
4.5 Input ..................................................................................................................... 30
4.6 Accessories .......................................................................................................... 31
4.6.1 Key switch set ....................................................................................................... 31
4.6.2 Output card ........................................................................................................... 32
4.6.3 EVAC module (NL) ................................................................................................ 33
4.6.4 Zone indication field .............................................................................................. 34
4.7 Initial start-up ........................................................................................................ 35
4.7.1 Prepare the panel.................................................................................................. 35
4.7.2 Pre configuration ................................................................................................... 36
5 Function overview .................................................................................... 37
5.1 Operating functions ............................................................................................... 37
5.2 Access levels ........................................................................................................ 37
5.3 LED indication ....................................................................................................... 38
5.4 Buttons ................................................................................................................. 39
5.5 Display .................................................................................................................. 40
5.6 Password entry ..................................................................................................... 40
6 Operation .................................................................................................. 41
6.1 General fire alarm procedure ................................................................................. 41
6.1.1 Procedure without Alarm verification...................................................................... 42
6.1.2 Alarm Verification Concept (AVC) .......................................................................... 43
6.1.3 Procedure with Alarm Verification .......................................................................... 44
6.2 Fault procedure ..................................................................................................... 45
6.3 Access level 1 ....................................................................................................... 46
6.3.1 Actual events ........................................................................................................ 46
6.3.2 Login ..................................................................................................................... 47
6.3.3 Alarm counter........................................................................................................ 47
6.4 Access level 2 ....................................................................................................... 48
6.4.1 Manned / unmanned ............................................................................................. 48
6.4.2 Silence / resound .................................................................................................. 48
6.4.3 LED, display and buzzer test ................................................................................. 48
6.4.4 Display history log ................................................................................................. 49
6.4.5 Logout................................................................................................................... 49
6.4.6 Set date and time .................................................................................................. 50
Smart Infrastructure A6V10393190_h_en_--
3
Page 4
6.4.7 Enable / disable zone ............................................................................................ 51
6.4.8 Enable test mode .................................................................................................. 52
6.4.9 Enable / disable outputs ........................................................................................ 53
6.4.10 Panel information .................................................................................................. 54
6.4.11 Service information ............................................................................................... 54
7 Programming ............................................................................................ 55
7.1 Configure .............................................................................................................. 55
7.1.1 Zone ..................................................................................................................... 55
7.1.2 Output ................................................................................................................... 56
7.1.3 Input ..................................................................................................................... 57
7.1.4 Accessories .......................................................................................................... 58
7.2 Global ................................................................................................................... 59
7.2.1 Country settings .................................................................................................... 59
7.2.2 Language .............................................................................................................. 59
7.2.3 Change password ................................................................................................. 59
7.2.4 User interface........................................................................................................ 60
7.2.5 Zone options ......................................................................................................... 60
7.2.6 Output options....................................................................................................... 60
7.2.7 Mains power ......................................................................................................... 60
7.2.8 Set date and time .................................................................................................. 61
7.2.9 Summer / winter time ............................................................................................ 61
7.2.10 Manned / unmanned ............................................................................................. 61
7.2.11 Service information ............................................................................................... 61
7.2.12 Buzzer .................................................................................................................. 61
7.2.13 Calibrate line ......................................................................................................... 61
7.2.14 Delete history log .................................................................................................. 62
7.3 Logout................................................................................................................... 62
7.4 Reset alarm counter .............................................................................................. 63
7.5 Customer text........................................................................................................ 64
7.5.1 Button function ...................................................................................................... 64
7.5.2 Text entry .............................................................................................................. 65
8 Tool function ............................................................................................ 66
8.1 Set up communication ........................................................................................... 66
8.1.1 Tool installation ..................................................................................................... 66
8.1.2 Tool settings ......................................................................................................... 67
8.2 Transfer history log data to PC .............................................................................. 68
8.3 Save configuration file ........................................................................................... 69
8.4 Restore configuration file ....................................................................................... 70
8.5 Download firmware ............................................................................................... 71
9 Commissioning ........................................................................................ 73
10 Maintenance ............................................................................................. 74
10.1 Preparatory work ................................................................................................... 74
10.2 Function test ......................................................................................................... 74
10.3 Device Test ........................................................................................................... 75
10.4 Completion work ................................................................................................... 75
11 Battery capacity........................................................................................ 76
11.1 FC121-ZA calculation ............................................................................................ 76
11.2 FC122-ZA calculation ............................................................................................ 76
11.3 FC123-ZA calculation ............................................................................................ 78
11.4 FC124-ZA calculation ............................................................................................ 79
12 Trouble shooting ...................................................................................... 80
12.1 LED indication ....................................................................................................... 80
12.2 System.................................................................................................................. 81
12.3 Accessories .......................................................................................................... 81
12.4 Factory reset ......................................................................................................... 82
13 Components and spare parts .................................................................. 83
14 Disposal and environmental protection.................................................. 84
Appendix A: Site configuration, Factory Setting.............................................. 85
4 Smart Infrastructure A6V10393190_h_en_--
Page 5
Appendix B: Switch mains to AC 115 V ............................................................ 87
Appendix C: History log ..................................................................................... 88
Smart Infrastructure A6V10393190_h_en_--
5
Page 6
6 Smart Infrastructure A6V10393190_h_en_--
Page 7

1 About this document

Goal and purpose
The information provided in this manual is a summary of the key procedures and functions required to assemble, install, operate, commission and repair the system. It is intended to provide experienced and qualified personnel a guide on the required processes.
Scope
The technical manual applies to the Cerberus FIT fire control panel FC12x series.
Target groups
The information in this document is intended for the following target groups:
Target group Activity Qualification
Installation personnel
Commissioning personnel
Maintenance personnel
Assembles and installs the product components at the place of installation.
Carries out a performance check following installation.
Configures the product at the place of installation according to customer­specific requirements.
Checks the product operability and releases the product for use by the operator.
Searches for and corrects malfunctions. Carries out all maintenance work.
Checks that the products are in perfect working order.
Searches for and corrects malfunctions.
Document identification
Position Information
Title page
Footers
Last page
Product picture
Product type Product designation Document type
Pages Document ID Edition date
Document ID Edition date Manual Register
Has received specialist training in the area of building installation technology or electrical installations.
Has obtained suitable specialist training for the function and for the products.
Has attended the training courses for commissioning personnel.
Has obtained suitable specialist training for the function and for the products.
Smart Infrastructure A6V10393190_h_en_--
7
Page 8
Reference document and source language
l The source language of this document is English (en) l The reference version of this document is the international version in English. The
international version is not localized. The reference document has the following designation: ID_x_en_-­x = version, en = English, -- = international
Applicable documents
The list below is used as a reference for the fire control panel FC12x and as a supplement to this document.
Number Name
A6V10393192 A6V10393169 A6V10393171 A6V10371354
'List of compatibility for FC12x' Installation of FC121-ZA / FC122-ZA Installation of FC123-ZA / FC124-ZA Data sheet of FC12x
Abbreviations
Abbreviations Explication
AVC EOL MCP PSU
Alarm verification concept End of line Manual call point Power supply unit
8 Smart Infrastructure A6V10393190_h_en_--
Page 9
Modification history
Version
Edition date
Brief description
h 2019-09-01 - Chapter '8.1.1 Tool installation' g 2018-10-30 - Updated the company address f 2015-09-09 - Screenshot in appendix A replaced with
language dependent screenshot.
e 2015-07-07 - Chapter '4.3.4 Short = Alarm' updated
- Chapter '10.3 Device test': Information
about the detector test in collective mode added
d 2015-02-12 - Chapter '3.3.1 Electrical data'
- Chapter '7.2.10 Manned / unmanned'
c 2014-05-28 - Chapter '1 About this document':
Information about reference document and source language added
- Chapter '3.3.1 Electrical data': Values for Line resistance / capacitance changed
- Chapters '11.3 FC123-ZA calculation' and '11.4 FC124-ZA calculation': Value of threshold for requirement of external power supply changed from 1200 mA to 1000 mA
- Editorial changes made
b 2014-04-15 - On Page 11, Change color of
housing&cover ('grey, ~RAL 7035' to 'grey ~RAL-Design 000 50 00')
- On Page 12/50/55, Change device coincidence inhibit time (1015)
- On Page 18, Change mixed zone drawing (delete diode)
- Change 'Line resistance / capacitance'
- Add warning for ‘Short=alarm’ zone function
a 2014-02-19 First version
Smart Infrastructure A6V10393190_h_en_--
9
Page 10

2 Safety regulations

Signal words
The signal word classifies the danger as defined in the following table:
Signal word Danger level DANGER DANGER identifies a dangerous situation, which will result
directly in death or serious injury if you do not avoid this
situation.
WARNING WARNING identifies a dangerous situation, which may result in
death or serious injury if you do not avoid this situation.
CAUTION CAUTION identifies a dangerous situation, which could result
in slight to moderately serious injury if you do not avoid this
situation.
NOTICE NOTICE identifies possible damage to property that may result
from non-observance.
Symbols
The symbols listed below indicate the nature and origin of the danger.
General danger
Electrical voltage
How risk of injury is presented
Information about the risk of injury is shown as follows:
WARNING
Nature and origin of the danger
Consequences if the danger occurs
Measures / prohibitions for danger avoidance
How possible damage to property is presented
Information about possible damage to property is shown as follows:
NOTICE
Nature and origin of the danger
Consequences if the danger occurs
Measures / prohibitions for danger avoidance
10 Smart Infrastructure A6V10393190_h_en_--
Page 11
Safety–relevant instructions
National standards, regulations and legislation
Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, assembly, installation, operation or disposal of the product apply at the place of operation, then these must also be taken into account together with the safety regulations in the product documentation.
Electrical installations
WARNING
Electrical voltage
Electric shock Work on electrical installations may only be carried out by qualified electricians or by instructed persons working under the guidance and supervision of a qualified electrician, in accordance with the electro technical regulations.
l Wherever possible disconnect products from the power supply when carrying out
commissioning, maintenance or repair work.
l Lock volt-free areas to prevent them from being switched back on again by mistake. l Label the connection terminals with external voltage using a 'DANGER External
voltage' sign.
l Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
l Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
l Produce earthing as stated in local safety regulations.
Assembly, installation, commissioning and maintenance
l The panel is designed for operation in a closed room, please note the
environmental conditions in this technical manual.
l Please check the country specific regulations and guidelines during installation and
programming of the fire control panel.
l Only operate the fire control panel with housing closed due to the danger of an
electric shock.
l If you require tools such as a ladder, these must be safe and must be intended for
the work in hand.
l When starting the fire control panel ensure that unstable conditions cannot arise. l Ensure that all points listed in the 'Testing the product operability' section below are
observed.
l You may only set controls to normal function when the product operability has been
completely tested and the system has been handed over to the customer.
Smart Infrastructure A6V10393190_h_en_--
11
Page 12
Testing the product operability
l Prevent the remote transmission from triggering erroneously. l If testing building installations or activating devices from third-party companies, you
must consult with the appointed people.
l The activation of fire control installations for test purposes must not cause injury to
anyone or damage to the building installations. The following instructions must be observed:
– Use the correct potential for activation; this is generally the potential of the
building installation.
l Inform people before testing the alarm control devices and allow for possible panic
responses.
l Inform people about any noise or mist which may be produced. l Before testing the remote transmission, notify the appropriate alarm and fault signal
receiving stations.
Modifications to the system layout and products
Modifications to the system and to individual products may result in faults, malfunctioning and safety risks. Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions.
Modules and spare parts
l Components and spare parts must comply with the technical specifications defined
by Siemens. Only use products specified or recommended by Siemens.
l Only use fuses with the specified fuse characteristics. l Wrong battery types and improper battery changing lead to a risk of explosion. Only
use the same battery type or an equivalent battery type recommended by Siemens (refer to Chapter 13).
l Batteries must be disposed of in an environmentally friendly manner. Observe all
national guidelines and regulations.
Disregarding safety regulations
Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation. This applies in particular to the following damage or injury:
l Personal injuries or damage to property caused by improper use and incorrect
application.
l Personal injuries or damage to property caused by disregarding safety instructions
in the documentation or on the product.
l Personal injury or damage to property caused by poor maintenance or lack of
maintenance.
Disclaimer
We have checked that the content of this document matches the hardware and software described. Despite this, we cannot rule out deviations and therefore assume no liability for them matching completely. The details in this document are checked regularly and any corrections needed included in subsequent editions.
We are grateful for any suggestions for improvement.
12 Smart Infrastructure A6V10393190_h_en_--
Page 13

3 System description

s

3.1 System overview

The conventional fire control system comprises all the components required for detection, evaluation and alarming in the event of fire.
The integrated operating unit processes signals from conventional and collective detectors. See list of compatibility A6V10393192.
The panel FC12x is self-contained with integral power supply and simple to operate, offering exceptional flexibility and comprehensive features.
Detector line series-110
Manual call point line
Mixed line
Intrinsically safe detectors

3.2 Features

System
l Stand-alone fire control panel l Switch mains to AC 115V (FC123-ZA / FC124-ZA only) l Monitored detector and sounder lines l Collective and conventional devices can be combined within the same zone l Display with 7 lines, max. 20 characters per line l Country specific settings l Multilingual variants l Up to 1000 events can be stored in history log with stamped date and time l Alarm counter for up to 9999 alarms l One man walk test
TM
Cerberus
FC120
okC
230 V output Sounder control
Fire output Dialer outputs
Optional hardware
l Output cards l Zone indication module (FC123-ZA / FC124-ZA only) l EVAC module l Key switch set
Periphery
l Compatible with 110-series / SynoLINE300 l Compatible with DS11 / SynoLINE600 l Mixed lines with detectors and MCPs
Programmable parameters
l Individual customer text for each zone l Automatic summer / winter time change l Alarm Verification Concept (AVC) l Cross zoning (Zone coincidence) l Detector coincidence for false alarm suppression
Smart Infrastructure A6V10393190_h_en_--
13
Page 14

3.3 Technical data

1
You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter:
· Document A6V10371354
FC121-ZA FC122-ZA FC123-ZA FC124-ZA
Zones
Number of zones 2 4 8 12 Number of detectors per zone Up to 32 Up to 32
Inputs
Number of inputs 2 3
Outputs
Number of monitored outputs
- Mainboard 2 2
- Output cards (Optional) 2
Number of relay outputs
- Mainboard 1 1
- Output cards (Optional) 2
Number of optional output cards 1
Alarm counter History log
9999 alarms 9999 alarms 1000 events 1000 events

3.3.1 Electrical data

FC121-ZA FC122-ZA FC123-ZA FC124-ZA
Zone
Operating voltage
- Standard zone
- GB continuity zone
Line resistance / capacitance Collective & Conventional
device
- GB continuity
- Mixed zone
Used Conventional device
- Standard
- Short=alarm
Collective & Conventional device
- Standard
- Short=alarm zone
DC 16.5…19 V DC 21…28.6 V
50 Ω / 1 μF50 Ω / 1 μF
100 Ω / 1 μF
100 Ω / 1 μF
80 Ω / 1 μF
80 Ω / 1 μF
1,2,4,6
1,2,4,6
1,2,4,5
1,4
1,2,3,4,5,6
1,3,4
4 6
4 2
DC 16.5…19 V
DC 21…28.6 V
50 Ω / 1 μF50 Ω / 1 μF
100 Ω / 1 μF
1,2,4,6
1,2,4,6
1,2,4,5
100 Ω / 1 μF
80 Ω / 1 μF
80 Ω / 1 μF
1,2,3,4,5,6
1,3,4
6 3
1,4
Detector 110-series;2 Detector FDOOT241-X, OOH740, FDF221-9, FDF241-9, FDL241-9;
3
Detectors series DS11, Synova Series 600C;4Synova Series 300C;5Conventional MCP;6Collective MCP
Alarm trigger Z-Diode 5.6 V or resistor 410…820 Ω Z-Diode 5.6 V or resistor 410…820 Ω
14 Smart Infrastructure A6V10393190_h_en_--
Page 15
FC121-ZA FC122-ZA FC123-ZA FC124-ZA
EOL element
- Standard zone
- Short=alarm
- Mixed zone
- GB continuity zone
18V TVS 18V TVS
18V TVS
10 μF capacitor
18V TVS 18V TVS
18V TVS
10 μF capacitor
Monitored output mainboard
Voltage / Current (max.) 24 V / 0.5 A 24 V / 1.0 A EOL element Diode (1N4007) Diode (1N4007)
Relay output mainboard 1.0 A @ DC 30 V AUX. power output (max.) DC 24 V / 200 mA
1.0 A @ DC 30 V
DC 24 V / 500 mA
Power supply
Mains voltage AC 196…253 V AC 196…253 V
or
AC 97…127 V
Mains fuse F1 AC 250 V @ 1.6 AT
AC 250 V @ 2.5 AT
AC 115 V @ 2.5 AT Power consumption 25 W 70 W Max. nominal output current with
battery charging, I
max a
Max. nominal output current without battery charging, I
Min. output current I
max b
min
max. 0.3 A max. 0.9 A
max. 0.9 A max. 2.5 A
0.1 A 0.1 A System supply voltage DC 21…28.6 V DC 21…28.6 V Mains failure delay 0…30 min. / default 5 min. 0…30 min. / default 5 min. Battery low discharge cut off DC 20.5 V…DC 21 V DC 20.5 V…DC 21 V Temperature compensation Yes Yes
Battery
Operation time Up to 72 h Up to 72 h Battery size 2 x 12 V, 4.5 Ah / 7 Ah, lead acid
2 x 12 V, 7 Ah / 12 Ah / 17 Ah, lead
acid Voltage DC 21…28.6 V DC 21…28.6 V Load resistance R
imax
max. 2.5 Ω max. 1.0 Ω

3.3.2 Mechanical data

FC121-ZA FC122-ZA FC123-ZA FC124-ZA
Terminals 0.2...2.5 mm Dimensions (W x H x D) 360 x 310 x 85 mm 430 x 399 x 124 mm Weight 2.0 kg without batteries 4.5 kg without batteries Color
- Housing, Cover
grey, ~RAL-Design 000 50 00
2
Smart Infrastructure A6V10393190_h_en_--
15
Page 16

3.3.3 Environmental conditions

FC121-ZA FC122-ZA
Operating temperature
-5…+40 °C Storage temperature -20…+60 °C Humidity (no condensation
95 % rel.
permitted) Protection category IP30
FC123-ZA FC124-ZA
-5…+40 °C
-20…+60 °C
95 % rel.
IP30
16 Smart Infrastructure A6V10393190_h_en_--
Page 17

3.4 Standard and options EN 54

EN 54-2 Definitions
The fire control panel is designed to comply with the requirements of EN 54 part 2 / 4.
The EN 54-2 options are fulfilled if the following configurations are used.
Installation Configuration / Operation Chapter
7.8
7.9.1
7.9.2
7.10.1
7.11.1
7.11.2
7.12.1
7.12.2
Output to fire alarm device EN 54-1 / C
Output to fire alarm routing equipment EN 54-1 / E
Alarm confirmation input from fire alarm routing equipment
Outputs to fire protection equipment EN 54-1 / G
Delays to outputs V1 / V2 timer for alarm organization
Switch on /off delays to outputs, V1 / V2 timer for alarm organization
Dependencies on more than one alarm signal. Type A dependency from the same detector, or another in the same zone
Dependencies on more than one alarm signal Type B dependency cross zoning
Monitored output e.g. OUT 1
Monitored output e.g. OUT 2
Input
Monitored output e.g. OUT 4
Sounder control
7.1.2
6.4.2
7.2.6
Alarm dialer 7.1.2
7.2.4
Dialer device confirmation signal; LED fire brigade activated via input
7.1.3
7.2.4
Fire output 7.1.2
Alarm Verification Concept; Manned / unmanned
6.1.3
7.2.10
Button 'Manned/unmanned' 6.4.1
7.2.10
Detector coincidence inhibit time 15 - 60 sec.
7.1.1
7.2.5 Reset of the first alarm after 90 sec.
Zone coincidence
7.1.1 (= cross zoning)
7.13
Alarm counter (option with requirement)
8.8
Output to fault warning routing equipment
8.9
Output to fault warning routing equipment according EN 54-1 / J
10
Test condition (option with requirements)
EN 54-13 Definitions
5.3.4.2
Open and short circuit on a transmission path
Alarm counter 6.3.3
7.4
Relay output
Fault dialer 7.1.2
e.g. OUT 3 Monitored output
Fault dialer 7.1.2
e.g. OUT 4
Test zone 6.4.8
The EN 54-13 standard is achieved, if the following system functions are fulfilled:
Installation Chapter
Zone mode 'standard' 7.1.1 Outputs card supervised
Card 1, OUT A / B: 4 / 5
4.4.2
7.1.2
Card 2, OUT A / B: 8 / 9 Card 3, OUT A / B: 12 / 13
Fault dialer
4.4.4
Card 1, OUT A: 4 Card 2, OUT A: 8 Card 3, OUT A: 12
Smart Infrastructure A6V10393190_h_en_--
17
Page 18

4 Installation

241
3

4.1 Power supply – mains voltage connection

WARNING
Electrical voltage
Electric shock
l Before connecting the mains cable, make sure that the cable is current-free. l Ensure that the mains is secured against inadvertently being switched on.
3
1
2
4
FC121-ZA / FC122-ZA FC123-ZA / FC124-ZA
Explanation
1. Mains supply
2. Boundary of mains zone
3. Safety zone (no high-voltage power permitted)
4. Signal and control lines
l The cables must be inserted from above. Use only the provided cable openings. l The mains lead must be placed along the left side of the housing (observe
boundary of mains zone).
l Signal and control lines must only be fed into the housing on the right from
above or from the rear.
l Batteries must be installed so that they cannot leak. l Open cable entries must be closed completely.
18 Smart Infrastructure A6V10393190_h_en_--
Page 19
To avoid the risk of a connected wire become loose and can come in contact with the
5 mm
5 mm
966
9
6
mains terminal, a single wire must not be so long that it can come into contact with the mains terminal or tie at least two such wires together so that the free end of a single wire cannot reach the mains terminal!
10
7
8
5
FC123-ZA / FC124-ZA
fixing mains wire
7
Strip the insulation from the wire
FC121-ZA / FC122-ZA secure wires
6
7
10
FC123-ZA / FC124-ZA secure wires
Explanation
5. Fixing cables and removing the outside isolation.
6. Lay the mains cable along the left side and signal and control lines to the right side of the housing.
7. Fix the mains wire with cable ties.
8. Insulate the mains, signal and control lines wires as needed and connect it to the terminals according to the pin assignment specified in chapter 4. Use mains cable with cross section of 3*1.5 mm2up to 3*2.5 mm2.
9. Fix the signal and control lines with cable ties.
10. Shield connection terminal.
19
Smart Infrastructure A6V10393190_h_en_--
Page 20

4.2 Instruction

ADB
Follow the instructions and consider the power calculation.
WARNING
Voltage
Electric shock Assembly and installation work may only be undertaken by qualified staff and when the system is de-energized.
NOTICE
Electrostatics
Damage to electronics Suitable protective measures must be taken when working with electronics modules.
Steps:
1) Remove the cover.
2) Define the mounting location.
3) Mark position of mounting holes (A).
4) Cut out the cable entries (B) and cover all open entries with cable glands (C) (not included).
5) Optional: Mount accessories (D). See chapter 4.6.
6) Install chassis on the wall / screws ( min. 5 mm) and plastic dowels are not included.
7) Switch off the mains supply and connect the power cable.
8) Connect signal and control lines of installed field device (zones, outputs and inputs).
9) Initial start-up, see chapter 4.7.
L
N
N
C
FC121-ZA / FC122-ZA FC123-ZA / FC124-ZA
20 Smart Infrastructure A6V10393190_h_en_--
Page 21

4.2.1 Connection overview

4
-
7
1
2
-
1
5
8
-
1
1
COM
EOL
EOL
EOL
*
Monitored
Relay
Class change sig.
Relay
Fire output (C)
Fire output (D)
Supervised
Sounder
control (A)
Sounder
control (B)
R
External PSU fault
The graphic below shows the default configuration of the panel.
Available zones, outputs and inputs are considered in the chapter 3.3.
EOL
+
EOL
+
+
+
EOL
+
+
+
+
EOL
6
b
1 1
a
5
6
1
b
1
a
5
AUX 24V ZONE1 ZONE2 ZONE n INPUT OUT1 OUT2
+
+
Standard zone
Example FC124-ZA
+
+ n
OUT3
NO
Aux 24 V / 0.5 A
eset
Sounder control
Alarm Dialer
Fault dialer (#)
(#) 'Fault dialer' contact is open as long as the panel is in fault condition.
Provided EOL elements:
Picture EOL element Function
Transzorb diode (18 V TVS)
EOL element for all zones except GB continuity
Capacitor 10 μF EOL element for GB continuity
Diode 1N4007
Smart Infrastructure A6V10393190_h_en_--
EOL element for monitored and supervised outputs
2019-09-01
21
Page 22

4.3 Zone modes

+++
+
+
AUX 24V
. . . . . .
1
a
1
b
1
a
1
b
EOL
1
a
1
b
EOL
+
+
EOL

4.3.1 Standard

The Standard line supports collective and conventional devices within the same zone.
Technical:
- Each line must be terminated with EOL element Transzorb diode (18 V TVS).
- Max. 32 devices on each line
Programming:
- Configure g Zone g Zone 1 – n g Mode g Standard
6 5
6 5
6 5
ZONE1
+
+
+
ZONE n
Zone mode 'Standard' complies with EN 54-2 and EN 54-13.
22 Smart Infrastructure A6V10393190_h_en_--
Page 23

4.3.2 Mixed

.
The mixed line allows a mixture of detectors and manual call points within the same zone. Moreover it can distinguish between direct and delayed alarming.
Technical:
- Siemens detectors 110-series or detectors with an alarm resistor are required for
delayed alarming (AVC, V1 / V2).
- MCPs require a Z-diode for direct alarming (AVC).
- Max. 32 devices on each line.
- Each line must be terminated with EOL element Transzorb diode (18 V TVS).
Programming:
- Configure g Zone g Zone 1 – n g Mode g Mixed MCP & det.
- Configure g Zone g Zone 1 – n g AVC g Via AVC timer MCP direct
Zone mode 'Mixed' does NOT comply with EN 54-13. Behavior of MCP in zone coincidence with function 'direct alarming' is not supported
23
Smart Infrastructure A6V10393190_h_en_--
Page 24

4.3.3 GB continuity

EOL
The GB continuity line allows a mixture of MCPs and detectors within the same zone. In addition this mode supports a reliable operation, even though one or more detectors are removed from its base. The CIE detect the removed detector and report a zone fault.
Technical:
- Special detector bases equipped with a diode (1N5819):
DB110D part number S54372-F6-A1 or DB110RD part number S54372-F8-A1
- MCPs require a Z-diode for direct alarming (AVC).
- Siemens detectors 110-series or detectors with an alarm resistor are required for
delayed alarming (AVC, V1 / V2).
- Each line must be terminated with EOL element Capacitor 10 µF.
- Limitation: Max. 18 detectors per line is allowed due to voltage drop on the detector
base.
- MCPs have no limitation and can be installed to reach the maximum of 32 devices.
Programming:
- Configure g Zone g Zone 1 – n g Mode g GB continuity
- Configure g Zone g Zone 1 – n g AVC g Via AVC timer MCP direct
6
1
b
1
5
ZONE1
a
+
+
+
NOTICE
See details of the specification in chapter 3.3.1.
Zone mode ‘GB continuity’ does NOT comply with EN 54-13. Behavior of MCP in zone coincidence with function 'direct alarming' is not supported.
24 Smart Infrastructure A6V10393190_h_en_--
Page 25

4.3.4 Short = alarm

Even if a zone
is switched off, a short
is evaluated as an alarm.
ZONE1
. . . . . .
EOL
This line supports a mixture of detectors and MCPs within the same zone. In addition, this line supports devices with a closed contact for alarm. Only automatic fire detectors can be switched off. Manual call points with the alarm criterion 'Short = Alarm' are always switched on and cannot be switched off.
Technical:
- Short in the line is detected as an alarm and not as a fault.
- Max.32 devices on each line.
- Each line must be terminated with EOL element Transzorb diode (18 V TVS).
- Does not fulfill EN 54-2.
Programming:
- Configure g Zone g Zone 1-n g Mode g Short = alarm
6
b
1
a
1
5
+
+
+
+
+
ZONE n
Zone mode 'Short = alarm' does NOT comply with EN 54-2 and EN 54-13.
Special detectors FDOOT241-9, OOH740, FDF221-9, FDF241-9, FDL241-9 NOT compatible with the zone mode 'Short = alarm'.
Smart Infrastructure A6V10393190_h_en_--
25
Page 26

4.4 Outputs

OUTA
OUTB
OUTC
OUTD
EOL
EOL
COM
COM
Outputs are used to transmit system status information. As a result three different types are available: Monitored, Supervised and Relay.
+
OUT1
Monitored
+
+
OUT2
COM NO
OUT3
Relay
Monitored or Supervised
Mainboard

4.4.1 Mainboard (OUT1 / OUT2)

Functionality 'Monitored line':
The panel monitors the line in terms of open and short circuits from the panel to the EOL element.
Application:
Sounder controls, fire outputs and dialer
Technical:
- Max. current
FC121-ZA and FC122-ZA à 24 V / 0.5 A FC123-ZA and FC124-ZA à 24 V / 1 A
- Each line must be terminated with EOL element (Diode 1N4007)
- Supervised functionality: Not available
+
+
NONC
NONC
Relay
Output card
Programming:
- Configure g Output g Output 1 – n g Mode g Sounder control

4.4.2 Output card (OUTA / OUTB)

The output can be either programmed as 'Monitored' or 'Supervised'.
Functionality 'Monitored line':
The panel monitors the line in terms of open and short circuits from the panel to the EOL element.
Application:
Sounder controls, fire outputs and dialer
Technical:
- Max. current 24 V / 1 A
- Each line must be terminated with EOL element (Diode 1N4007)
Programming:
- Configure g Output g Output 4 – n g Mode g Sounder control
26 Smart Infrastructure A6V10393190_h_en_--
Page 27
Functionality 'Supervised line':
max
min
min
min
min
OUT A
The panel monitors the line in terms of open and short circuits from the panel to the EOL element. In addition to the line monitoring, the panel will recognize a change of line resistance. Due to aging or other circumstances (creeping effect), the transition resistance on contacts may increase, which in turn leads to voltage drop.
In order to detect the creeping effect (supervision), the line must be calibrated during the commissioning process. A line fault is indicated if the resistance is higher than 35 .
Checking the line resistance depending on the required current
It is calculated that the supply of the connected devices is met. The picture shows the dependence of the line resistance (R Line) in relation to the device voltage (U
) and the available output current (I
min
) and the minimum required current of
max
the connected devices (I Load).
R Line
Load
EOL
Procedure for determining the maximum available device current (I Load):
1) Determine the line resistance R Line.
Programming: see chapter 7.2.1 (Calibration) Configure à Output à Output 4 – n à Calibrate line
2) Detecting the voltage U
according to the device datasheet.
min
3) Verification: Are all parameters satisfied for the correct operations?
Table 1 can be used for this check, here are maximum values shown. Details are individual to calculate.
Table 1
R Line
U
I
= 9 V U
= 14.5 V U
= 16.8 V U
= 18 V
1 A 0 ~ 7 Ω 0 ~ 3.5 Ω 0 ~ 2 Ω 0 ~ 1 Ω
0.5 A 0 ~ 14.5 Ω 0 ~ 7.5 Ω 0 ~ 4.5 Ω 0 ~ 3 Ω
0.3 A 0 ~ 25 Ω 0 ~ 13 Ω 0 ~ 8 Ω 0 ~ 5.5 Ω
0.1 A 0 ~ 35 Ω 0 ~ 35 Ω 0 ~ 26 Ω 0 ~ 18.5 Ω
0.05 A 0 ~ 35 Ω 0 ~ 35 Ω 0 ~ 35 Ω 0 ~ 35 Ω
Counteractive measures: Reduction of I Load or of R Line.
Functionality 'Supervised line for fault dialer and relay':
The line is supervised, from the terminal including the activated relay in the fault dialer, in terms of open and short circuit. In addition to the line supervising, the panel will recognize a change of line resistance. Due to aging or other circumstances (creeping effect), the transition resistance on contacts may increase, which in turn leads to voltage drop.
27
Smart Infrastructure A6V10393190_h_en_--
Page 28
In order to detect the creeping effect (supervision), the line must be calibrated during the
commissioning process. A line fault is indicated if the resistance is higher than calibrated.
The range of the line resistance including the relay is between 200-1000 .
Application:
With EOL diode: Sounder controls, fire outputs and alarm dialer. With monitored relay for fault dialer: Only OUT A is specified to supervise the device
relay, see details in chapter 4.4.4.
Technical:
- Max. current 24 V / 1 A
- Line resistance max. 35
- Each line must be terminated with EOL element (Diode 1N4007)
Programming:
- Configure g Output g Output 4 – n g Mode g e.g. Sounder control
- Configure g Output g Output 4 – n g Supervision EN 54-13
- Configure g Output g Output 4 – n g Calibrate line

4.4.3 Relay

Relay outputs are used for controls without line monitoring.
Application:
LED indication on a remote terminal
Technical:
- Max. current 30 V / 1 A
Programming:
- Configure g Output g Output 6 – n g Mode g Fire output
28 Smart Infrastructure A6V10393190_h_en_--
Page 29

4.4.4 Dialer connection

O U T
3
C O M
N O
+
+
_
X .
2
4
+
+
_
O U T
A
+
_
C O M
N O
+
200 1000
Ω ~ Ω
FC12x
Dialer
FC12x
Dialer
The FC12x fire control panel provides 'monitored' and 'supervised' dialer connections:
Application 1
- 'Alarm dialer' output (OUT2) monitors the line to the dialer.
- 'Fault dialer' output (OUT3) has no line monitoring to the dialer.
(Does not fulfill chapter 8.9 in EN 54-2)
Programming:
- Configure g Outputs g Output 2 g Alarm dialer g
Activation condition 'General Alarm'
- Configure g Outputs g Output 3 g Fault dialer g Activation condition 'Any fault'
Application 2
- 'Alarm dialer' output (OUTB) supervises the line to the dialer.
- 'Fault dialer' output (OUTA) supervises the line and the build in relay of the dialer.
The relay takes over EOL element functionality, if the resistance is between 200­1000 Ω.
Programming:
- Configure g Outputs g Output 5 g Alarm dialer g
Supervision EN 54-13 / Calibrate line / Activation condition 'General Alarm'
- Configure g Outputs g Output 4 g Fault dialer g
Supervision EN 54-13 / Calibrate line / Activation condition 'Any fault'
_
X.24
+
INPUT 1*
_
+
AU
INPUT 1*
_
_
+
(1)
OU
OUT2
_
+
Application 1 Application 2
(1) Dialer device confirmation signal
As an option, the panel can receive the dialer activation if desired.
The output 'fault dialer' is closed (Inverse function) in quiescent mode. In case of fault, the output opens.
_
T B
+
29
Smart Infrastructure A6V10393190_h_en_--
Page 30

4.5 Input

INPUT
The programmable input function allows control of the panel by a third-party system.
Programming:
- Configure g Input g Input 1-n g Mode g e. g. Class change signal
+
AUX 24V
Third-party system
1 2 3
30 Smart Infrastructure A6V10393190_h_en_--
Page 31

4.6 Accessories

X40
X10
X30
X20
X50
X10
X40
X30
X20
Connect the accessories as shown.
FC121-ZA / FC122-ZA
Terminals Accessories
X50 not used X40
FTO1201-H1 EVAC Module (NL 2&4 Z) FTO1203-H1 EVAC Module (NL 8&12 Z)
FTO1202-Z1 Zone ind. field 12x2LED
X30 FCA1203-Z1 Output card 2M 2R X20 FCA1206-Z1 Key switch set (Nordic SE) X10 FDUZ221 MCL-USB adapter
FDUZ227 MCL-USB adapter (radio)

4.6.1 Key switch set

The key switch set is available for the following panels.
FC121-ZA FC122-ZA FC123-ZA FC124-ZA
FCA1206-Z1
FC123-ZA / FC124-ZA
þ þ þ þ
FCA1206-Z1
Example FC124-ZA
Function:
The key switch enables 'access level 2' (see chapter 6.4) without password.
Programming:
- No programming is required.
31
Smart Infrastructure A6V10393190_h_en_--
Page 32

4.6.2 Output card

2
EOL
EOL
Earth con
n
ection
(only used for FCA1203
-
Z1)
The output card is available for the following panels.
Output card Mounting slot FC121-ZA FC122-ZA FC123-ZA FC124-ZA FCA1203-Z1
Example FC124-ZA
þ þ þ þ
þ þ
þ
FCA1203-Z1
1
3
FC121-ZA / FC122-ZA
Function:
Each output card provides four outputs and one power input 24 V for external powering of the outputs A and B. Check power calculation in chapter 11 whether you have to power those outputs internally or externally.
Internal:
By default, output A and B are supplied by the internal PSU.
External:
Connect the wires from an external PSU to the terminal '24V In'. The output card switches automatically from internal to external supply.
Programming:
- Output cards are automatically enabled if plugged in before initial start-up.
Output:
The output numbers include a reference to the respective output cards:
Mounting slot
Outputs for programming
A B C D
4 5 6 7 8 9 10 11
32 Smart Infrastructure A6V10393190_h_en_--
12 13 14 15
Page 33

4.6.3 EVAC module (NL)

FTO1203-H1
The EVAC module is available for the following panels.
EVAC Module (NL) FC121-ZA FC122-ZA FC123-ZA FC124-ZA FTO1201-H1 FTO1203-H1
FC121-ZA / FC122-ZA
Function:
The EVAC module NL provides the Dutch special function. All sounder controls are changed to EVAC sounder NL.
Mounting module before initial start-up:
- If the module is connected before the initial start-up, the NL presetting and language
is pre-selected automatically.
- The functionality and EVAC sounder NL are available if the pre-selected setting is used.
þ þ
þ þ
FTO1201-H1
FC123-ZA / FC124-ZA
Mounting module after initial start-up:
- Enable the EVAC module in the programming.
- Change all programmed sounder outputs to EVAC sounder NL.
Programming: Configure g Accessory g EVAC module Configure g Output g Output n g Mode g EVAC Sounder NL
Operating:
All programmed outputs to 'EVAC Sounder NL' are activated by pressing the start button twice.
1
3 4
2
No. Description Status Function
1 LED: EVAC zone active ON Evacuation is activated. 2 LED: EVAC fault Flashing Fault on the EVAC sounder lines(s) has occurred. 3 Button: START Press twice to start the evacuation. 4 Button: STOP Press twice to stop the evacuation.
33
Smart Infrastructure A6V10393190_h_en_--
2019-09-01
Page 34

4.6.4 Zone indication field

The zone ind. field FTO1202-Z1 as shown in the graphic below.
FC121-ZA FC122-ZA FC123-ZA FC124-ZA
FTO1202-Z1
þ þ
Example FC124-ZA
Function:
The zone ind. field shows the actual status of each zone.
- LEDs are fixed assigned and cannot be changed.
Programming:
FTO1202-Z1
- No programming is needed.
1
2
3
No. Description Status Function
1 Zone alarm
(Red)
2 Zone fault
(Yellow)
ON The zone is in alarm state.
Flashing The zone is in first alarm state.
ON The zone is disabled.
Flashing Zone is in fault.
3 Inscribable fields Inscription of zone number and customer text.
34 Smart Infrastructure A6V10393190_h_en_--
2019-09-01
Page 35

4.7 Initial start-up

The initial start-up is required with every new installation.

4.7.1 Prepare the panel

Make sure that the installation instructions, steps 1-8 are fulfilled (chapter 4.2) and all accessories are connected (chapter 4.6).
1) Switch on the mains supply.
N
2) Connect the battery.
L
Red (+)
Black (-)
Smart Infrastructure A6V10393190_h_en_--
35
Page 36

4.7.2 Pre configuration

ok
ok
p
q
After the panel is powered up, the following display is shown.
Country settings Presetting t Factory setting u
Language t English u
Country settings Presetting t Factory setting u
Language t English u
Country settings Presetting < UK >
Panel
Language < English >
will restart!
p
t
t
u
q
p
u
t
Change country setting by the navigation key <u>.
Move to the second line with <q> and
u
select the appropriate Language with <u>.
q
Confirm the entry by the <ok> button. The panel will restart with the country specific presetting.
Set date & time
01.01.2000 00:00
Set date & time
22.12.2012 08:08
p
t
u
p
Change the first value ‘day’ with <p> / <q>
t
u
and move to the next with <u> and so on.
q
q
Confirm the entry by the <ok> button. The system is now ready for individual programming (see chapter 7).
Relevant to NL with EVAC module only: If the EVAC module is mounted, the country setting is automatically selected by the system.
36 Smart Infrastructure A6V10393190_h_en_--
Page 37

5 Function overview

5.1 Operating functions

The operating functions are related to the following topics.
Alarm Disable / Enable System test
- Acknowledge
- Reset
- Silence sounder
- Manned / unmanned
- Cancel alarm delay

5.2 Access levels

The FC12x provides four different access levels.
Access
level
1 No need End user to view pending events. 2 5555
3 6666 Commissioning personnel:
Password Function
or key switch
- Zone
- Sounder control
- Fire output
- Alarm dialer
- Fault dialer
Instructed and authorized end user:
- Switch on / off zones and outputs.
- Automatic logout after 2 minutes of no operation.
- Password is not necessary if a key switch is used.
- System programming.
- Automatic logout after 10 minutes of no operation.
- The basic function of panel will not continue.
- Mode walk test with sounder activation for 1 second
- LED test
4 6666
and front cover open
6669 - Reset alarm counter.
Smart Infrastructure A6V10393190_h_en_--
Commissioning personnel:
- Save and restore site configuration.
- Upload history log.
- Update firmware.
37
Page 38

5.3 LED indication

put
The following LED indications are available:
1
2
3 4
5 6
q
7
No. Description Colour Status Function
1 Alarm Red ON The fire control panel is in 'Alarm' condition. 2 Acknowledge Yellow Slow Indicates where action is expected. 3 More alarm Red Slow More than two zones have triggered a fire alarm.
4 Reset Yellow Slow Indicates the action in case of an alarm or fault. 5 Fire brigade Red ON Depending on the programming mode.
6 System on Green ON The system is in operation. 7 General fault Yellow ON Indicates any fault in the system. 8 System fault Yellow ON Indicates CPU failure. 9 Sounder fault Yellow ON Sounder lines are disabled.
10 Alarm dialer fault Yellow ON Alarm dialer output is disabled.
8
9 10
Option 1: Call the fire brigade, panel is in alarm mode. Option 2: Call the fire brigade, output Alarm dialer is active. Option 3: Fire brigade is called.
Slow Sounder line is in fault state.
Slow Alarm dialer output is in fault state.
11 12
13 14 15
11 Test condition Yellow ON At least one zone is in test state. 12 Isolation Yellow ON At least one zone or output is disabled. 13 Manned / Unmanned Yellow ON Manned operation (AVC).
OFF Unmanned operation (AVC).
Fast 2 Hz Reaction time V1 is running (AVC).
Slow 1 Hz Investigation time V2 is running (AVC).
14 Resound Red ON Sounder lines are activated. 15 Silence Yellow ON Sounder lines are silenced.
38 Smart Infrastructure A6V10393190_h_en_--
Page 39

5.4 Buttons

▲►▼
The following buttons are available:
11
10
9 8 7
6
5
1 432
No. Description Function
1 MORE ALARM Move to the next 'fire alarm'.
2 RESET Reset the fire control panel to quiescent condition.
· Starts the investigation time V2 (AVC).
3 ACKNOWLEDGE
· Silence the buzzer until a new alarm event occurs.
· Silence the sounder until a new event occurs (if programmed).
4 SILENCE BUZZER Silence the buzzer until a new event (alarm, alert or fault) occurs. 5 SILENCE
RESOUND
· Silence the sounder control(s) in the event of alarm.
· Manually re-activate the sounder control(s) during alarming.
· If programmed, activation of all sounder control(s)
(activation mode only in quiescent condition).
MANNED /
6
UNMANNED
· Switch between manned / unmanned.
· Cancel the alarm delay V1 / V2 when V1 / V2 is running.
7 LAMP TEST Activate all LEDs, the buzzer and the display on the PMI. 8 CANCEL Move one step back without saving the change. 9 OK Confirm the selected value.
10 MENU Enter the main menu.
· Select the menu or change the time: <p> and <q>.
11 NAVIGATION
· Change the selection: <t> and <u>.
· Change to the next level or select value in the checkbox: <u>.
Smart Infrastructure A6V10393190_h_en_--
39
Page 40

5.5 Display

ok
????
The display is divided into 4 sections.
1
Menu 2:00 Actual events u
Enable / disable u
2
History log u Set date & time u Login u Logout u
1: Title
This line displays the main menu.
2: Window
This window displays the sub menus and its parameters.
3: AVC timer or access level
- Countdown of the AVC timer V1 and V2
- Indication of the access level
4: Scrollbar
Scrollbar is provided if more information is visible in a second window.

5.6 Password entry

3
4
How to get access to the fire control panel.
Login 1
1 2 3 4 5 6 7 8 9 0
Access levels according to chapter 5.2.
l Select the 1st number of the password by
the navigation button and confirm with <ok>.
p
ut
q
l Repeat until the last '?' is replaced. l If the password is correct, the respective
access level is granted.
40 Smart Infrastructure A6V10393190_h_en_--
Page 41

6 Operation

6.1 General fire alarm procedure

In case of a fire alarm, the following indication is shown on the panel:
· The fire alarm is indicated by the LEDs (1).
· The first and last alarm zone are displayed (8).
· Further fire alarms are indicated by the flashing LED (2). In order to move to the
next alarm event, press the button (4).
· The internal panel buzzer indicates a fire condition acoustically. As an option, the buzzer can be silenced by pressing the button (7). A new alarm event will reactivate the buzzer again.
· Output alarm dialer is activated when LED (3) is ON. (Call the fire brigade.)
· Programmed system outputs, including connected audible and visual
notification appliances, get activated.
· The flashing acknowledge LED (5) indicates the possible action to acknowledge by pressing the button (6).
Smart Infrastructure A6V10393190_h_en_--
41
Page 42

6.1.1 Procedure without Alarm verification

The Alarm dialer is activated in the event of a fire alarm.
Fire alarm 1 Zone 1 1/1
Meeting room 1
MAJOR INCIDENT: A real fire emergency
Fire alarm 1 Zone 1 1/1
Meeting room 1
MINOR INCIDENT: No fire alarm
Press the <ACKNOWLEDGE> button. If the alarm event is acknowledged, the panel
turns off the panel buzzer.
è Access level 2 password is required.
Optional: Silence the sounder lines by pressing <RESOUND / SILENCE> button.
Check if the fire brigade called.
Normal Operation
Siemens FC12X
22.12.2012 08:08
1
Reset the system to quiescent mode by pressing <RESET> button.
è Access level 2 password is required. Inform the fire brigade about the actual situation.
Notice
The fire alarm reoccurs if any device remains in fire condition.
42 Smart Infrastructure A6V10393190_h_en_--
Page 43

6.1.2 Alarm Verification Concept (AVC)

Unmanned
State
'ALERT
unmanned:
unmanned:
The graphic below illustrates the difference between the AVC and the DIRECT alarm procedure. The AVC concept takes the interaction of personnel into consideration.
AVC DIRECT
Manned
· Buzzer activated
· Sounder output activated if programmed
· Reaction time 'V1” has started
No
Yes
Fire?
Manned/
V1 time out
State 'ALARM'
· Buzzer (re-)activated
· Sounder output (re-)activated
Manned operation
Manned operation enables the responsible personnel to examine the fire alarm before initiating the intervention force. This may avoid hassles in case of false alarms.
Reaction time (V1)
In case of a fire incident, the responsible personnel must confirm the alert at the fire control panel by pressing the acknowledge button (ACK). Investigation time V2 starts if activated. If nobody confirms the alert state, the V1 timer expires and the panel automatically goes to 'ALARM' state.
In the event of a major incident (emergency), the nearest ‘Manual call point’ or <Manned/Unmanned> button must be pressed to turn the fire control panel into 'ALARM' state. (1function depends on programming)
Ack:
No
Yes à V2 start
No
Fire?
Reset: Manned/
V2 time out
Yes
· Fire output activated
· Alarm dialer activated (Intervention)
1
Investigation time (V2)
During the investigation time V2 the operating personnel may examine the location of fire:
In the event of a major incident (emergency), the nearest ‘Manual call point’
2
or <Manned/Unmanned> button must be pressed to turn the fire control panel into 'ALARM' state. (2function depends on programming)
The panel goes to 'ALARM' state if the investigation is not confirmed within time V2. The operator may reset the panel in the case of a minor incident or false alarm.
Smart Infrastructure A6V10393190_h_en_--
2019-09-01
43
Page 44

6.1.3 Procedure with Alarm Verification

In the event of a fire alarm, the reaction timer V1 gets started.
Fire alarm 2:00 Zone 1 1/1
Meeting room 1
Fire alarm 3:00 Zone 1 1/1
Meeting room 1
Action is requested
During the investigation time, examine the location of the fire and decide whether it is a MAJOR INCIDENT or MINOR INCIDENT.
MAJOR INCIDENT: A real fire emergency
V1
V2
Press the <ACKNOWLEDGE> button to confirm the attendance. If the alarm event is acknowledged, the buzzer turns off.
è Access level 2 password is required.
The investigation timer V2 is started.
Optional: Silence the sounder by pressing <RESOUND / SILENCE> button.
Fire alarm 2:00 Zone 1 1/1
Meeting room 1
MINOR INCIDENT: No fire alarm
Normal Operation
Siemens FC12X
22.12.2012 08:08
Notice
The fire alarm reoccurs if any device remains in fire condition.
Cancel the investigation time by pressing the <MANNED / UNMANNED> button.
è Access level 2 password is required.
Reset the system to normal operation by pressing <RESET> button.
è Access level 2 password is required.
44 Smart Infrastructure A6V10393190_h_en_--
Page 45

6.2 Fault procedure

A list of possible '
Faults
' can be found in
chapter
12
.
In the event of a fault, the panel displays the fault. As an option, programmed outputs can be activated (e.g. fault dialer).
Fault 1 Battery 1/2
Zone 1 2/2
Action is requested.
Solve the cause of the fault.
Press the <SILENCE BUZZER> button. Buzzer is turned off.
Normal Operation
Siemens FC12X
22.12.2012 08:08
Acknowledge and reset the system to normal operation by pressing the <ACKNOWLEDGE> and <RESET> button.
è Access level 2 password is required.
Notice
The fault reoccurs if acknowledged but not resolved.
Smart Infrastructure A6V10393190_h_en_--
45
Page 46

6.3 Access level 1

C
ok
p
ok
tpq
t
Operation is available without password.

6.3.1 Actual events

The actual events will display all pending events.
Menu 1 Actual events u Login u Alarm counter 0001
Actual events 1 Fire alarm u 0 Fault u 2 Isolation u 0 Test u 0 Information u 0
Push button <MENU>.
u
Select ‘Actual events’ with navigation button and confirm with <ok>.
t
u
The left picture shows the 5 entry points. Select one event type and confirm with <ok>.
q
Fault 1 Battery 1/2
Output 1 2/2
p
t
u
q
The details are visible with the number of events indicated for the category. e.g. two events exist in this category.
Go back to the main menu with <C>.
46 Smart Infrastructure A6V10393190_h_en_--
Page 47

6.3.2 Login

C
ok
**
??
ok
t
The panel is protected against unauthorized user operation. Therefore enter the password or turn the key switch (optional).
Menu 1 Actual events u Login u Alarm counter 0001
Push button <MENU>.
p
t
u
q
Select ‘Login’ and confirm with <ok>.
Login 1(#)
1 2 3 4 5 6 7 8 9 0

6.3.3 Alarm counter

The alarm counter counts all fire alarms.
Menu 1 Actual events u Login u Alarm counter 0001
l Select the digit using the navigation button
p
ut
q
and confirm it with <ok>.
l The ‘?’ is replaced by ‘*’ with every entered
digit.
l Press <C> to cancel the input.
(#) shows the actual access level.
t
Push button <MENU>.
The number of counted alarms is shown.
Exit with <C>.
47
Smart Infrastructure A6V10393190_h_en_--
Page 48

6.4 Access level 2

Operation is available with password or key switch.

6.4.1 Manned / unmanned

In case of attendance switch the fire control panel to manned operation.
Information 2 Manned operation 1/1
Manned mode activated

6.4.2 Silence / resound

Sounders are activated in the event of a fire alarm.
Press the <MANNNED / UNMANNED> button to toggle.
Manned mode – LED ON Unmanned mode – LED OFF
Press the <SILENCE / RESOUND> button to silence the sounders. It is possible to reactivate the sounders in the event of a fire alarm at any time.
Every new alarm event will reactivate the sounders again, if programmed.
Optional: The sounders can be activated at any time 'Toggle function' (no alarm event is required) if programmed.

6.4.3 LED, display and buzzer test

Test the panel indication.
Press the button <LAMP TEST> and all LEDs, the display and the internal buzzer are activated for a
period of 5 seconds.
48 Smart Infrastructure A6V10393190_h_en_--
Page 49

6.4.4 Display history log

ok
tpq
C
p
ok
p
Logout
u
t
All events such as alarm(s), fault(s), isolation(s), input(s) and output(s) activation are stored in a history log.
Menu 2 Actual events u Enable / disable u History log u Set date & time u Login u
History log 2 Fault 1/2 Set date & time
10.08.2012 12:18
Push button <MENU>.
t
u
q
Select ‘History log’ and confirm with <ok>.
All events are visible.
t
u
q
Fast scrolling is possible by holding <p> / <q> navigation button.

6.4.5 Logout

Manual logout to access level 1. Panel automatically logs out if no action is taken within 2 minutes.
Menu 2 Actual events u Enable / disable u History log u Set date & time u Login u Logout u
Successful
Go back to the main menu with <C>.
t
u
1
Push button <MENU>.
Select ‘Logout’ and confirm with <ok>.
The panel is logged out successfully to previous access level.
49
Smart Infrastructure A6V10393190_h_en_--
Page 50

6.4.6 Set date and time

ok
qut
ok
t
p
q
Push button <MENU>.
Menu 2 Actual events u Enable / disable u History log u Set date & time u Login u Logout u
Set date & time
01.01.2000 00:00
Set date & time
22.12.2012 08:08
p
t
t
u
q
p
u
Select ‘Set date & time’ and confirm with <ok>.
Change the first value with <p> / <q> and move to the next with <u> and so on.
Confirm with <ok>.
50 Smart Infrastructure A6V10393190_h_en_--
Page 51

6.4.7 Enable / disable zone

C
Zone
6tOn
u
ok
p
Zone
6tOn
u
ok
p
ok
Each zone can be isolated individually.
Menu 2 Actual eventsu Enable / disable u History log u Set date & time u Login u Logout u
Enable / disable 2 Zone u
Sounder t On u outputs Fault t On u dialer
Enable / disable 2 Zone 1 t On u Zone 2 t Off u Zone 3 t Off u Zone 4 t On u Zone 5 t On u
t
p
t
t
t
u
q
u
q
p
u
t
q
q
Push button <MENU>.
Select ‘Enable / disable’ and confirm with <ok>.
Select ‘Zone’ and confirm with <ok>.
Select a zone and change its property with <u>.
u
Change zone properties for other zones as needed.
Isolation 2
Successful
Zone 6 t On u
Enable / disable 2 Zone 1 t On u Zone 2 t Off u
ok save and exit
Zone 3 t Off u
C exit without
Zone 4 t On u
saving
Zone 5 t On u
Confirm all changes with <ok>.
Exit menu without change by pressing the button <C> for the first time and then a second time while the information is displayed.
51
Smart Infrastructure A6V10393190_h_en_--
Page 52

6.4.8 Enable test mode

Enable the test mode for each zone
.
C
Zone
6tOn
u
ok
Zone
6tOn
u
p
q
q
Zone
6tOn
u
ok
ok
t
Menu 2 Actual eventsu Enable / disable u History log u Set date & time u Login u Logout u
Enable / disable 2 Zone u
Sounder t On u outputs Fault t On u dialer
Push button <MENU>.
p
t
u
q
Select ‘Enable / disable’ and confirm with <ok>.
Select ‘Zone’ and confirm with <ok>.
Enable / disable 2 Zone 1 t Test u Zone 2 t On u Zone 3 t On u Zone 4 t On u Zone 5 t On u
Enable / disable 2
Successful
Zone 1 t On u Zone 2 t Off u Zone 3 t Off u Zone 4 t On u Zone 5 t On u
Enable / disable 2 Zone 1 t On u Zone 2 t Off u
ok save and exit
Zone 3 t Off u
C exit without
Zone 4 t On u
saving
Zone 5 t On u
p
u
t
t
Select a zone and change its property with <u>.
u
Change zone properties for other zones as needed.
Confirm all changes with <ok>.
Exit menu without change by pressing the button <C> for the first time and then a second time while the information is displayed.
52 Smart Infrastructure A6V10393190_h_en_--
Page 53

6.4.9 Enable / disable outputs

C
ok
p
Output
6tOn
u
ok
ok
Disable outputs generally and / or individually.
Menu 2 Actual eventsu Enable / disable u History log u Set date & time u Login u Logout u
Enable / disable 2 Zone u
Sounder t On u outputs Fault t On u dialer
Enable / disable 2 Output 1 t Off u Output 2 t On u Output 3 t On u Output 4 t On u Output 5 t On u
t
p
t
t
u
q
p
u
Push button <MENU>.
Select ‘Enable / disable’ and confirm with <ok>.
Select the respective Output (e.g. ‘Fire outputs‘) and confirm with <ok>.
q
p
u
t
q
t
q
Select an output and change its property with <u>.
u
Change output properties for other outputs as needed.
Fire output 2 Output 1 t On u
Successful
Fire output 2 Output 1 t On u
ok save and exit C exit without
saving
Confirm all changes with <ok>.
Exit menu without change by pressing the button <C> for the first time and then a second time while the information is displayed.
53
Smart Infrastructure A6V10393190_h_en_--
Page 54

6.4.10 Panel information

C
ok
t
C
Output card
3
u
ok
p
t
Information about the software is displayed.
Menu 2 Panel informationu
Alarm counter 0001 Service information u
Panel information 2 Type: FC124-ZA App: 01.00.19 Boot: 01.00.04 Output card 1u Output card 2 u
Push button <MENU>.
t
u
q
Select ‘Panel information’ and confirm with <ok>.
Exit with <C>.

6.4.11 Service information

The service information is shown in quiescent mode (e.g. contact address of the service provider and panel information).
Menu 2 Panel informationu
Alarm counter 1 Service information u
Service information 2
xxxxxx FC12X xxxxxxu
Push button <MENU>.
p
t
u
q
Select ‘Panel information’ and confirm with <ok>.
Exit with <C>.
54 Smart Infrastructure A6V10393190_h_en_--
Page 55
Configure

7 Programming

For programming, access level 3 is required.
All outputs are automatically isolated during programming mode. All disabled outputs are automatically enabled if access level 2 is reached.

7.1 Configure

Zone
Zone 1..n
Mode

7.1.1 Zone

Configure parameter for each zone.
Select a zone for programming.
Standard
Mixed MCP & det.
GB continuity
Short = alarm
Automatic detectors and manual call points can be mixed within the same zone. Device could be either conventional or collective.
InputOutputZone
AVC option '1', '2'
AVC option '1', '2', '3'
Accessory
card(s)
If detectors are removed, the zone will work properly.
Any short is detected as 'Fire Alarm'.
AVC
*Device
coincidence
Zone
coincidence
Customer
text
Smart Infrastructure A6V10393190_h_en_--
Direct Via V1 / V2
Via AVC timer MCP direct
If selected, the 'Alarm' state is achieved, if the second device activation in the same zone occurs within 90 seconds. The first device activation is inhibited from the zone and automatically reset after a defined time, (default value: 15 second, see chapter 7.2.5).
If selected, the 'Alarm' state is achieved, if the second corresponding zone is in 'Alarm' as well. The zone pairs (1&2, 3&4, 5&6, etc) are predefined in the system,
e.g. if zone 6 is selected, zone 5 is automatically linked as well and vice versa.
Name the zone, see chapter 7.5.
*Do NOT use this function in combination with FDOOT241-9 (ES<13). For detailed information refer to document A6V10393192.
No delay, immediate alarm.
'1' '2' Delayed alarm. V1: reaction time, 3 min.
- Delayed alarm for automatic
'3'
detectors.
- No delay for MCPs.
V2: investigation time, 5 min. (Change value, see
chapter 7.2.10).
55
Page 56

7.1.2 Output

upervision
1..n
Output
Output
Mode
S
EN 54-13
Configure the output parameters.
Select an output for programming.
Sounder control Sounder control is used to activate sounder lines.
(EVAC module replaces 'sounder control' with 'EVAC sounder NL'.)
Alarm dialer
Alarm dialer is used to transmit the fire alarm to the intervention force, e.g. fire brigade.
Fault dialer
Fault dialer is used to transmit the fault signal to the intervention force, e.g. service provider.
Fire output
Fire outputs are used to activate / deactivate controls,
e.g. door holders, lifts, air-condition, etc.
EVAC Sounder NL
EVAC sounders are used to activate sounder lines. This option is available if the EVAC module is implemented.
Enables supervision, creeping open and short for the outputs: 4, 5, 8, 9, 12 and 13.
Calibrate
line
Activation condition*
The line calibration is needed to achieve supervision. As a result of the calibration the line resistance is indicated and can be proved using your own calculation.
This option is only availible on output cards and if supervision is set.
General Alarm Output is activated if the alarm condition is fulfilled:
Zone 'Direct' is activated, V1 / V2 is expired, cross zoning 2nd zone is activated.
Active by zone alarm Output is activated if the selected zone(s) is in alarm. General Alert
Output is activated if cross zoning 1st zone is in alarm or V1 / V2 time is running.
Active by zone alert Output is activated if the selected zone(s) is in alarm by cross zoning
1st zone or V1 / V2 time is running.
Alert by ext. input
Output is activated if one input is activated and programmed as 'activate alert mode'.
Any isolation Output is activated if any isolation is set. Any fault Output is activated if any fault condition occurs.
Manned mode
Output is activated if manned mode is activated.
activated Alarm dialer fault Output is activated if the alarm dialer fault via input is in fault condition.
Dialer device
Output is activated if the programmed input is activated.
confirmation signal V1 / V2 is running
(SE function)
Output flash during V1; Output on during V2.
* Options available depending on the selected mode.
Pulse
time
56 Smart Infrastructure A6V10393190_h_en_--
This option is available in Alarm and Alert state.
Default on 0.5 sec. off 0.5 sec. Details see chapter 7.2.6.
Page 57

7.1.3 Input

between manned / unmanned if the signal change on the input.
Input
Input 1..n
Mode
Configure the input parameters.
Select an input for programming.
Class change signal Dependency reset
Activate all sounder controls as long as the input is closed.
Reset function is suppressed if the Alarm dialer is activated or if ACK
is not pressed before. Level 2 access Disable dialer outputs Manned / unmanned
Toggle manned /
Enables the access level 2 as long as the input is closed.
Disable fault and Alarm dialer as long as the input is closed.
Switch to manned as long as the input is closed.
Toggle unmanned
External PSU fault
Activate fault condition from the external PSU fault as long as the
input is closed. Alarm dialer fault
Activate general fault and LED 'Alarm dialer fault' until reset.
Application remote transmission device is in fault state. Dialer device
confirmation signal
Generate an event of 'Fire brigade is called' and is used to activate outputs and the LED 'Fire brigade is called' as long as the input is closed.
*Customer
text
Activate alert mode
This mode (alert) supports that the output(s) is activated as long as
the input is closed.
Menu: ConfiguregOutputsgActivation conditiongAlert by ext. input ACK SE ACK function
Reset
Acknowledge all events if the input is activated.
Acknowledge function is suppressed if the Alarm dialer is activated. Reset function is always available independently of the access level.
If the mode 'Class change signal' is selected, you can edit the customer text. See chapter 7.5.
It is not allowed to configure two or more inputs as 'Class change signal'.
Smart Infrastructure A6V10393190_h_en_--
57
Page 58

7.1.4 Accessories

1
card
The accessories (output cards / EVAC module) are automatically recognized by the system if connected before the initial start-up. An EVAC-Module NL, added after initial start-up, must be enabled manually.
Accessory card(s)
Output
Option
output card
1..n
EVAC
module
Configure accessories
When an output card is removed, the quantity must be modified accordingly.
External power input is used
Change the power concept from internal to external, if required.
External power is automatically enabled if provided. Therefore check the calculation in chapter 11, max. external device power for FC121-ZA/FC122-ZA g 0.5 A and FC123-ZA/FC124-ZA g1.2 A.
Enable the EVAC module (must be connected first).
Before installing an output card, power should be switched off. If the quantity of configured output cards does not match the quantity of installed output cards, all outputs will report fault. After pressing <RESET> only outputs with fault are displayed.
The key switch set and the LED indication field do not need any configuration.
58 Smart Infrastructure A6V10393190_h_en_--
Page 59
Global

7.2 Global

The Global menu includes system wide parameters.
Country settings
Country settings
Manned/
unmanned
Service
information
Language
Summer/
winter time
Buzzer
Change
password
Set date &
time
Calibrate
line
User
interface
Mains
power

7.2.1 Country settings

Factory setting Factory default setting provides all possible programming. n Selection of the country specific setting.

7.2.2 Language

Zone
options
Output
options
Language
Change
password
English All display texts are in English. n Selection of the language.

7.2.3 Change password

Change password for access level 2.
Smart Infrastructure A6V10393190_h_en_--
59
Page 60

7.2.4 User interface

selectable
User
interface
Zone
options
Lamp test available at access level 2
Silence key with EVAC function
Silence on ACK ACK available at
access level 1 LED fire brigade
activated by alarm dialer output
LED fire brigade activated via input
Display view Standard: Fulfills EN 54-2
If selected, the lamp test function is only available at access level 2.
Otherwise it is available at access levels 1 and 2.
If selected, all sounder control lines can be activated by pressing
the button <Silence / resound> if access level 2 is achieved. If selected, all sounder lines can be silenced by <ACK>. If selected, the button function <ACK> is available in access level 1
in addition to the access level 2.
If selected, the LED is activated when the output 'Alarm dialer' is
active. Otherwise, the LED is activated by general alarm.
If selected, the LED is activated if the dialer device confirmation signal is given.
UK only FC122: 4 zones without customer text are displayed.

7.2.5 Zone options

Device coincidence inhibit time
The fire condition is achieved with the second detector activation in the same zone only. The inhibit time, between the first and the second activation can be set to from 15 to 60 seconds. The higher the value, the more reliable the application.
Output
options
Mains
power

7.2.6 Output options

Pulse time Fire alarm: Select the time for switch on / off for the respective
outputs. Value range : On 0 - 3 sec. Off 0 - 5 sec. Alert: Select the time for switch on / off for the programmed outputs.
Value range: On 0 - 3 sec. Off 0 - 5 sec.
Resound on new alarm
If selected, the sounder line will resound with a new alarm.

7.2.7 Mains power

Fault delay time Delay time for Mains power fault. Time delay up to 30 min.
in 5 min. steps.
60 Smart Infrastructure A6V10393190_h_en_--
Page 61

7.2.8 Set date and time

& time
Set date
Summer/
winter time
Manned/
unmanned
Set date and time.

7.2.9 Summer / winter time

Automatic switching If selected, the panel will switch automatically to the summer /
winter time each year.

7.2.10 Manned / unmanned

V1 time Select the reaction time V1, value from 30 sec. - 4 min. V2 time Select the investigation time V2, value from 1 min. - 10 min.
Allowed time with regards to EN 54-2 is V1+V2 = 10 min.
Automatic switch to unmanned
Switching time
Enable the daily switching time.
Set the switching time to unmanned.
Service
information
Buzzer
Calibrate
line

7.2.11 Service information

The service information is shown in quiescent mode. Insert text as per chapter 7.5, e.g. FC12x 'address and telephone number'.

7.2.12 Buzzer

On: Enable the panel’s internal buzzer. à Comply with EN 54-2 Off: Disable the panel’s internal buzzer. à Not comply with EN 54-2

7.2.13 Calibrate line

Calibration for all programmed supervision outputs at once. Line calibration is needed to achieve supervision. As a result of the calibration, the line
resistance is indicated and can be provided using your own calculation.
61
Smart Infrastructure A6V10393190_h_en_--
Page 62

7.2.14 Delete history log

If no action has been taken within 1
0
minutes, the panel will automatically lea
ve the
ok
p
ok
p
Logout
u
Access level 3 is required to delete the history log.
Menu 3 Actual events u Enable / disable u History log u Set date & time u Login u
History log 3 Fault 1/2 Set date & time
10.08.2012 12:18
History log 3 Fault 1/2
ok Delete all
Set date & time
the history Log C exit
10.08.2012 12:18:18
t
t
u
q
u
q
Select the ‘History log’.
Enable the deletion by pressing <u>.
Confirm the deletion by the button <ok>. This action is available as long as the information is displayed.
History log 3 Fault 1/2
In progress
Set date & time
10.08.2012 12:18:18

7.3 Logout

Exit the actual access level to the previous access level; Access level 3 g Access level 2; Access level 2 g Access level 1
access level 3 to access level 2.
History log gets deleted.
62 Smart Infrastructure A6V10393190_h_en_--
Page 63

7.4 Reset alarm counter

ok
q
????
ok
t
Reset the alarm counter by pressing <u> and enter password '6669'.
Menu 3 Alarm counter 0001
Display main menu with <MENU>.
p
Alarm counter 3
1 2 3 4 5 6 7 8 9 0
t
u
q
p
ut
Select the ‘Alarm counter’ and press <u>.
Enter the password (6669).
Alarm counter is reset if the password is correct.
63
Smart Infrastructure A6V10393190_h_en_--
Page 64
Cokok
C

7.5 Customer text

B
C
p
q
q
Input customer text for:
l Zones, see chapter 7.1.1. l Input function 'class change signal', see chapter 7.1.3. l Service information, see chapter 6.4.11.
The window is structured into the following sectors:
A
40 3
B
q w e r t y u I o p < a s d f g h j k l , >
3
C
h z x c v b n m
Sector A Remaining space, out of 40 on two lines B Text area C Selection area of letters, numbers, characters and toggle function
Legend:
h
Toggle between capital and lower letters Delete the character to the left of the cursor position Insert space Change entry to the second customer text line Switch to numeric Switch to letter Toggle between country specified character
f / g
Page up / down

7.5.1 Button function

The button function depends on the curser position. Select the curser position by navigation key.
29 3
Abcdef12345 q w e r t y u I o p <
a s d f g h j k l , > h z x c v b n m
29 3
Abcdef1s345 q w e r t y u I o p <
a s d f g h j k l , > h z x c v b n m
Curser position, area
p
ut
The <ok> button confirms the text entry and exits the menu.
The <C> button deletes the letter to the left of the flashing curser.
Curser position, area
The <ok> button confirms the selected letter.
ut
The <C> button enables the exit and without save.
64 Smart Infrastructure A6V10393190_h_en_--
Page 65

7.5.2 Text entry

Letter
Country specified character
ok
ok
ok
q
36 3
Abcd q w e r t y u I o p <
a s d f g h j k l , >
h z x c v b n m
p
ut
Select the letter by the navigation button and confirm with <ok>. Repeat until the desired text is displayed in the text area. Toggle between capital and lower case letters ‘h ’.
29 3
Abcdef12345 1 2 3 4 5 6 7 8 9 0 ,
@ # % & ( ) - \ .
! ; : ‘ “ ? /
25 3
Abcdef12345 à á â ã
à á â ã ä å æ ç è é ê ë ì í î ï ð ñ ò ó ô õ ö ÷ ø ú û üý þ ÿ
p
ut
Change to numeric entry by selecting this symbol ‘ ‘ and confirm with <ok>. Select the desired number by the navigation key
Numeric
q
and confirm with <ok>. Toggle between Numeric’s ‘f’ / ‘g’ Toggle back to letters ‘
p
Change to special character by selecting symbols ‘ ‘ or ‘ ‘ and confirm with <ok>.
ut
q
Select the desired character and confirm with <ok>.
Toggle betweencountry specified charactersf’ /
g
Toggle back to letters ‘
Smart Infrastructure A6V10393190_h_en_--
65
Page 66

8 Tool function

FDUZ22x
The tool provides the following functions:
· Transfer history log data to the PC.
· Save panel configuration to the PC.
· Restore configuration to the panel.
· Firmware update.

8.1 Set up communication

Connect the FDUZ22x MCL USB adapter with the FC12x control panel.

8.1.1 Tool installation

Install the communication tool 'Hyper Terminal'. This tool is a Windows freeware and can be downloaded via internet. General information of the tool:
https://docs.microsoft.com/en-us/previous-versions/windows/it-pro/windows-server­2003/cc737746(v=ws.10)
Download link:
https://drive.google.com/file/d/0BxSEu8_tErjCVDl0UUc0OXhBbE0/view
66 Smart Infrastructure A6V10393190_h_en_--
Page 67

8.1.2 Tool settings

manager
1. Start the Hyper Terminal and enter an appropriate name.
3. Select the following properties.
2. Select communication port.
Make sure your PC is connected to the FDUZ22x box and the driver is installed.
Check the communication port on the device
67
Smart Infrastructure A6V10393190_h_en_--
Page 68

8.2 Transfer history log data to PC

Transfer the history log data from the FC12x control panel to the PC as a *.csv file. Edit this file in excel and print out as needed.
1. Select the following option on the panel. 2. Enable the Hyper Terminal to receive data.
Upload / download 3 History log data
Panel -->PC u Transfer data Panel -->PC u Transfer data PC --> Panel u
3. Select the folder to receive the file and select protocol ‘Xmodem’.
5. The progress is indicated.
4. Insert the filename 'Historylog.xls' and confirm the download with <OK>.
Historylog.xls
68 Smart Infrastructure A6V10393190_h_en_--
Page 69

8.3 Save configuration file

1. Select the following option on the panel. 2. Enable the hyper terminal to receive data.
Upload / download 3 History log data
Panel -->PC u Transfer data Panel -->PC u Transfer data PC --> Panel u
3. Select the folder to store the file and select the protocol ‘Xmodem’.
5. The progress is indicated.
4. Insert the filename 'Setting.txt ' and confirm the download with <OK>.
Smart Infrastructure A6V10393190_h_en_--
69
Page 70

8.4 Restore configuration file

1. Select the following option on the panel.. 2. Enable the hyper terminal to 'Send file'.
Upload / download 3 History log data
Panel -->PC u Transfer data Panel -->PC u Transfer data PC --> Panel u
CC
3. Select the file to be sent out and select the protocol.
4. The progress is indicated.
70 Smart Infrastructure A6V10393190_h_en_--
Page 71

8.5 Download firmware

The FC12x is delivered with operable firmware. In general, there is no need to update the firmware. In case of any emergency, you update the panel on site.
Save the configuration prior to updating, see chapter 8.2. A firmware update deletes all configurations.
1. Click <PROPERTY>. 2. Select the folder 'Settings' and click 'ASCII Setup'.
3. Select the check boxes accordingly. 4. Confirm the data transfer on the panel.
Upload / download 3 Download
Firmware u
Press <ok> to continue.
Upload / download 3
Confirm PC connection is built up
Download
ok: Yes
Firmware u
C: No
Press <ok> to continue.
Smart Infrastructure A6V10393190_h_en_--
71
Page 72
5. PC will display as below. Press '2'.
6. 'CC…' shows the connection is established and ready for transfer.
7. Click menu ‘Transfer’ and select ‘Send File’ to open send file dialog.
Please select Firmware and transfer
CCCCCC
9. The progress is indicated.
8. Select the file to be sent out and select the protocol.
If downloading is successful, panel will start application. The window ‘Xmodem file send for test’ disappears automatically after download is complete.
If downloading has failed, panel will show error
code: 0001: no firmware or firmware fault 0002: communication fault 0009: hardware fault
72 Smart Infrastructure A6V10393190_h_en_--
Page 73

9 Commissioning

Planning
l Assign the field devices to the floor plan as per local regulations. l Document the panel parameters (see Appendix A). l Calculate battery standby time (see chapter 11).
Field installation
l Install detection lines (detectors and manual call points) and terminate with EOL
element.
l Install control (sounder) lines and terminate with EOL element.
Warning
Pay attention to external voltage (AC 230 V)!
Panel installation
l Fire control panel must be mounted. l Connect all detection lines or terminate with EOL element. l Connect all control lines or terminate with EOL element. l Connect alarm and fault dialer. l Inscription stripes must be inserted for zone ind. field (optional). l Switch off the main supply fuse AC 230 V. l Connect the power cable and check the earth connection. l Switch on the main supply fuse AC 230 V. l Place and connect battery. l Fill in and place the provided label at the top, right-hand side of the housing.
Programming
l Initial start-up of the panel. l Program the system and resolve the faults.
Function test
l Initiate lamp test and check all LED, internal buzzer. l Test each device (Detector, MCP, etc.) individually and check the correctness of
the system behavior in terms of outputs (e.g. Sounder, Fire output, etc.).
l Test fire and fault transmission. l Make sure that the panel is in normal operation, the buzzer and all system parts are
enabled.
The system can now be handed over to the customer.
Smart Infrastructure A6V10393190_h_en_--
73
Page 74

10 Maintenance

It is assumed that the site was commissioned in accordance with the existing directives, i.e. all functions have been tested and the site data has been saved or logged to the table 'site configuration'.

10.1 Preparatory work

Inform the system owner of the scope and expected duration of work. Disable the following system components as needed:
l Alarm transmission (log out on the receiving centre) l Fire controls and sounder lines l Extinguishing stations

10.2 Function test

We recommend the following schedule. However, local regulations have priority.
Function Activity
Zones Activate all automatic detectors and all manual call points. X
Activate a detector or manual call point per zone and verify zone assignment and if usage is in accordance with regulations.
Check all detectors and manual call points for soiling and verify if usage is in accordance with regulations.
Activate a fault, short circuit and open line, for each zone and verify zone
assignment and if usage is in accordance with regulations. Inputs Activate each input and verify if usage is in accordance with regulations. X Outputs Check sounder controls and all acoustic alarm devices. X
Activate fire outputs and check if usage is in accordance with regulations. X
Activate alarm and fault dialer and check the transmission. X Alarm
organization
Mode Manned
Activate a detector and manual call point and check the timer V1 and V2 and
the transmission of the alarm dialer.
Mode Unmanned
Activate a detector and check the transmission of the alarm dialer.
Interval in years
1 2 5
X
X
X
X
X
Panel Check date and time. X
Check the display and LEDs. X
Check earth connections. X
Activate mains and battery fault condition and verify if usage is in accordance
with regulations.
74 Smart Infrastructure A6V10393190_h_en_--
X
Page 75

10.3 Device Test

Smoke detector
1. Enable test mode for the zone.
2. Place detector tester RE6 or RE8ST on detector head.
3. Wait until LED is on – Sounder sounds 1 sec.
4. Remove testing unit -
Automatic reset of test alarm after 15 sec.
5. Set zone to normal mode operation.
Heat detector
1. Enable test mode for the zone.
2. Place detector tester RE6T or RE7T on detector head
and turn on heater.
3. Wait until LED is on – Sounder sounds 1 sec.
4. Remove testing unit -
Automatic reset of test alarm after 15 sec.
5. Set zone to normal mode operation.
Manual call point
1. Enable test mode for the zone.
2. Depending on type of call point, insert test key or
open cover to activate.
3. Wait until LED is on - Sounder sounds 1 sec.
4. Remove test key or close door -
Automatic reset of test alarm after 15 sec.
5. Set zone to normal mode operation.
Detector test for multiple protocol detectors FDOOT241-A9 and FDOOT241-9 in collective mode
In collective mode, the FDOOT241-A9 and FDOOT241-9 multiple protocol detectors can only be activated via the command '2.4 ALARM' using the FDUD292 detector exchanger and tester and the FDUD293 intelligent detector tester.

10.4 Completion work

1. Activate a test alarm through the system operator with remote transmission.
2. Disable all 'OFF' status.
3. Have system owner confirm the revision.
Smart Infrastructure A6V10393190_h_en_--
2019-09-01
75
Page 76

11 Battery capacity

If the total current of the outputs (Sounders, etc.) is higher than
500mA
, then an external
-
The battery capacity depends on panel type and standby time. The standby time is regulated by local code of praxis or the EN regulation. The required battery size can be identified using the following calculation. Moreover, the calculation indicates whether an external power supply is needed.

11.1 FC121-ZA calculation

Type Description
Standby
[mA]
FC121-ZA 2 zone panel 38 107
Out 1 (e.g. Sounders) Out 2 (e.g. Sounders)
Aux. output Accessory cards FCA1203-Z1
(1st) FTO1203-H1 EVAC Module 0.5 2.2
Standby current [A] Alarm current [A]
Output card 2M 2R 12 25
Out A&B (e.g. Sounders)
power supply is required. In order to reduce the total current:
Alarm
[mA]
Panel (internally) Sounders, etc…
Standby
[mA]
Alarm
[mA]
- Power the output A&B from the external power supply (possible per card).
Move the Auxiliary output to the external power supply.
Standby
[mA]
Alarm
[mA]
Choose the appropriate battery size depending on the calculated capacity.
[(Standby time × Standby current) + (Alarm time × sum alarm current)] × Aging factor = Capacity (max.12 Ah) _ _ h × 0._ _ _ A + 0.5 h × _._ _ _ A × 1.25 =
Standby time [h]: 24, 30 or 72 Alarm time [h]: 0.5 hour Aging factor: 1.25 Standby current [A]: Total current in standby mode Alarm current [A]: Total current in alarm mode Capacity [Ah]: 4.5 Ah; 7 Ah
11.2 FC122-ZA calculation
Type Description Standby Alarm Panel (internally) Sounders, etc…
76 Smart Infrastructure A6V10393190_h_en_--
Page 77
[mA] [mA]
If the total current of the outputs (Sounders, etc.) is higher than
500mA
, then an external
-
Standby
[mA]
Alarm
[mA]
FC122-ZA 4 zone panel 54 123
Out 1 (e.g. Sounders)
Out 2 (e.g. Sounders)
Aux. output Accessory cards
Standby
[mA]
Alarm
[mA]
FCA1203-Z1 (1st)
Output card 2M 2R 12 25
Out A&B (e.g. Sounders) FTO1203-H1 EVAC Module 0.5 2.2
Standby current [A] Alarm current [A]
power supply is required. In order to reduce the total current:
- Power the output A&B from the external power supply (possible per card).
Move the Auxiliary output to the external power supply.
Choose the appropriate battery size depending on the calculated capacity.
[(Standby time × Standby current) + (Alarm time × sum alarm current)] × Aging factor = Capacity (max.12 Ah) _ _ h × 0._ _ _ A + 0.5 h × _._ _ _ A × 1.25 =
Standby time [h]: 24, 30 or 72 Alarm time [h]: 0.5 hour Aging factor: 1.25 Standby current [A]: Total current in standby mode Alarm current [A]: Total current in alarm mode Capacity [Ah]: 4.5 Ah; 7 Ah
Smart Infrastructure A6V10393190_h_en_--
77
Page 78

11.3 FC123-ZA calculation

If the total current of the outputs (Sounders, etc.) is higher than
1000mA
, then an
-
Type Description
Standby
[mA]
FC123-ZA 8 zone panel 86 155
Out 1 (e.g. Sounders)
Out 2 (e.g. Sounders)
Aux. output Accessory cards FCA1203-Z1
(1st) FCA1203-Z1
(2nd) FTO1202-Z1 Zone indicator field 12*2 1 2.5
FTO1203-H1 EVAC Module 0.5 2.2
Standby current [A] Alarm current [A]
Output card 2M 2R 12 25
Out A&B (e.g. Sounders)
Output card 2M 2R
Out A&B (e.g. Sounders)
12 25
Alarm
[mA]
Panel (internally) Standby
[mA]
Alarm
[mA]
Sounders, etc…
Standby
[mA]
Alarm
[mA]
external power supply is required. In order to reduce the total current:
- Power the output A&B from the external power supply (possible per card).
Move the Auxiliary output to the external power supply.
Choose the appropriate battery size depending on the calculated capacity.
[(Standby time × Standby current) + (Alarm time × sum alarm current)] × Aging factor = Capacity (max. 17 Ah) _ _ h × 0._ _ _ A + 0.5 h × _._ _ _ A × 1.25 =
Standby time [h]: 24, 30 or 72 Alarm time [h]: 0.5 hour Aging factor: 1.25 Standby current [A]: Total current in standby mode Alarm current [A]: Total current in alarm mode Capacity [Ah]: 7 Ah; 12 Ah; 17 Ah
78 Smart Infrastructure A6V10393190_h_en_--
Page 79

11.4 FC124-ZA calculation

If the total current of the outputs (Sounders, etc.) is higher than
1000mA
, then an
-
Type Description
Standby
[mA]
FC124-ZA 12 zone panel 118 187
Out 1 (e.g. Sounders)
Out 2 (e.g. Sounders)
Aux. output Accessory cards FCA1203-Z1
(1st) FCA1203-Z1
(2nd) FCA1203-Z1
(3rd) FTO1202-Z1 Zone indicator field 12*2 1 2.5
FTO1203-H1 EVAC Module 0.5 2.2
Standby current [A]
Output card 2M 2R 12 25
Out A&B (e.g. Sounders)
Output card 2M 2R
Out A&B (e.g. Sounders)
Output card 2M 2R
Out A&B (e.g. Sounders)
12 25
12 25
Alarm
[mA]
Panel (internally) Standby
[mA]
Alarm
[mA]
Sounders, etc…
Standby
[mA]
Alarm
[mA]
Alarm current [A]
external power supply is required. In order to reduce the total current:
- Power the output A&B from the external power supply (possible per card).
Move the Auxiliary output to the external power supply.
Choose the appropriate battery size depending on the calculated capacity.
[(Standby time × Standby current) + (Alarm time × sum alarm current)] × Aging factor = Capacity (max. 17 Ah) _ _ h × 0._ _ _ A + 0.5 h × _._ _ _ A × 1.25 =
Standby time [h]: 24, 30 or 72 Alarm time [h]: 0.5 hour Aging factor: 1.25 Standby current [A]: Total current in standby mode Alarm current [A]: Total current in alarm mode Capacity [Ah]: 7 Ah; 12 Ah; 17 Ah
Smart Infrastructure A6V10393190_h_en_--
79
Page 80

12 Trouble shooting

12.1 LED indication

1
Fault description
General fault 1 ON Any system fault is indicated:
2
3 4
LED Status
Cause / Action
- Zone line fault
- Sounder line fault (LED 3)
- Alarm dialer line fault (LED 4)
- Fault dialer if monitored
- Fire output
- Mains and battery fault
See display for detailed information and check common issues:
- Short / break in the line
- Missing EOL element
- Earth fault
- Input condition e.g. dialer, external PSU
- AUX 24V output
- Output - 24VDC too low
- EVAC module
- Set date & time
System fault Additional indication:
- General fault LED ON
- Buzzer ON (interval tone)
- Display show earth fault
System fault Additional indication:
- General fault LED ON
- Buzzer ON (interval tone)
- Display frozen
- Button functions are ignored
80 Smart Infrastructure A6V10393190_h_en_--
2 ON
2 ON CPU has failed (system not working).
Earth fault indication in combination with the programming of the GB continuity zone.
Switch the power off and restart, if fault continues replace mainboard.
Page 81
Fault description
P
lease contact your service provider
if you cannot eliminate troubles.
LED Status
Cause / Action
Sounder fault 3 Fast
Alarm dialer fault 4 Fast

12.2 System

Fault description Cause / Action
Set date & time fault. Power down, requires date & time, chapter 6.4.6. Buzzer does not work. Check the setting, chapter 7.2.12.
Any fault on sounder lines is indicated.
See display for detailed information and check common issues:
- Short / break
- Missing EOL element
- If output is supervised à calibrate line
Fault of alarm dialer line
See display for detailed information and check common issues:
- Short / break
- Missing EOL element
- If output is supervised à calibrate line

12.3 Accessories

Fault description Cause / Action
DC 24 V is too low. Check voltage input '24V In' on the output card(s) 2M2R. All four outputs from one
output card 2M2R indicate a fault.
The EVAC module indicates a fault.
Key switch set No indication is given, change the device. LED indication field No indication is given, change the device.
Locate the faulty output card according to chapter 4.6.2.
- Ribbon cable connected properly, chapter 4.6.2.
- Output card programmed, chapter 7.1.4.
Check the following:
- Ribbon cable connected properly, chapter 4.6.3.
- EVAC module enabled, chapter 7.1.4.
Smart Infrastructure A6V10393190_h_en_--
81
Page 82

12.4 Factory reset

A factory reset will delete all configurations. Save configuration, see chapter 8.3.
Step 1: Disconnect mains and battery. Step 2: Press and hold the buttons
<Silence Buzzer> + <ACK> + <ok> + <C> at the same time. Step 3: Connect mains and battery. Step 4: Release the buttons if the display is shown as below:
Country settings Presetting t Factory u
Language t English u
Step 5: Select the language independent of the country presetting. e.g. English.
setting
82 Smart Infrastructure A6V10393190_h_en_--
Page 83

13 Components and spare parts

Components
Type Part no. Designation
FC121-ZA S54400-C131-A1 Fire panel conv. (2Z) FC122-ZA S54400-C130-A1 Fire panel conv. (4Z) FC123-ZA S54400-C129-A1 Fire panel conv. (8Z) FC124-ZA S54400-C128-A1 Fire panel conv. (12Z)
Accessory
Type Part no. Designation
FCA1203-Z1 FTO1202-Z1 FTO1201-H1 S54400-B120-A1 EVAC Module (NL 2&4 Z) FTO1203-H1 FCA1209-Z1 FCA1206-Z1
Additional power supply
Type Part no. Designation
FP120-Z1
Battery
Type Part no. Designation
AX1213 FA2003-A1 FA2004-A1
S54400-B142-A1 S54400-B119-A1 Zone ind. field 12x2LED
S54400-B118-A1 EVAC Module (NL 8&12 Z) S54400-B124-A1 Output module (230V) S54400-S125-A1 Key switch set (Nordic SE)
S54400-S122-A1 Power supply kit A 70W
4392990001 A5Q00019353 A5Q00019354 Battery 12V, 12Ah, VDS
Output card 2M 2R
Accumulator 12V 4.0Ah Battery 12V, 7Ah, VDS
FA2005-A1
Spare part
Type Part no. Designation
FP2015-A1
Smart Infrastructure A6V10393190_h_en_--
A5Q00019677 Battery 12V, 17Ah, VDS
S54400-B121-A1
Power supply (70W)
83
Page 84

14 Disposal and environmental protection

This equipment is manufactured using materials and procedures which
comply with current environmental protection standards as best as possible. More specifically, the following measures have been undertaken:
l Use of reusable materials l Use of halogen-free plastics l Electronic parts and synthetic materials can be separated
Larger plastic parts are labelled according to ISO 11469 and ISO 1043. The plastics can be separated and recycled on this basis.
Electronic parts and batteries must not be disposed of with domestic
waste.
l Take electronic parts and batteries to local collection points or
recycling centre.
l Contact local authorities for more information. l Observe national requirements for disposing of electronic parts
and batteries.
84 Smart Infrastructure A6V10393190_h_en_--
Page 85

Appendix A: Site configuration, Factory Setting

Customer: ____________________________________________________________
Sounder control
Fault dialer
Active by zone alarm
General Alert
Alert by ext. input
Manned / unmanned
Toggle manned / unmanned
Alarm dialer fault
ACK
Date of Installation: ____________________
Mixed MCP & det.
Direct
Level 2 access
Manned mode activated
Dialer device confirmation signal
V1 / V2 is running
Control panel:* FC121-ZA (2 zones) /* FC122-ZA (4 zones) /* FC123-ZA (8 zones) /* FC124-ZA (12 zones) Menu On side programming
Zone 1 2 3 4 5 6 7 8 9 10 11 12
Mode
AVC
Device coincidence Zone coincidence (zone pairs; 1&2, 3&4, etc.)
Output 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Mode
EN 54-13 supervision Activation condition
Standard
GB continuity Short = alarm
Via V1 / V2 Via AVC timer MCP direct
Alarm dialer
Fire output No EVAC Sounder NL
General Alarm
Active by zone alert
Description Default
Yes No No No No Yes No No No
Out 1 Out 2 Out 3
No
Out 1,2
Input
Accessory
Any isolation Any fault
Alarm dialer fault
Pulse time
Mode
Output card No
EVAC module No Zone indication field No Key switch set No
Class change signal Dependency reset
Disable dialer outputs
External PSU fault
Dialer device confirmation signal Activate alert mode
SE ACK function Reset
Card 1 Card 2 Card 3
Out 3
Input 1
Input 3
Input 2
No No
1 2 3
Y / N
Ext. powered
Smart Infrastructure A6V10393190_h_en_--
85
Page 86
Global
Mains power
5 Min.
Y / N
0.5
UK only FC122
Fault delay time
V1 time
activated by alarm dialer output
activated by input
0.5
T2 (Off)
T1 (On)
Automatic switch to unmanned
Lamp test available at access level 2
Silence on ACK
Language
Presetting
Password (Level 2) User interface
Display view
Zone options 10 Sec. Output options
Summer / winter time Yes Manned / unmanned
Description Customer text
Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7
Silence key with EVAC function
ACK available at access level 1 LED fire brigade
LED fire brigade
Standard
Device coincidence inhibit time Fire alarm pulse time Alert pulse time Resound on new alarm
Automatic switching
V2 time
Switching time
Factory setting English 5555
Yes No No No
Yes
No Yes No
0.5 0.5
Yes
3 Min. 5 Min. No 18:00
Description Customer text
Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Input class change Service information
86 Smart Infrastructure A6V10393190_h_en_--
Page 87

Appendix B: Switch mains to AC 115 V

M a
i
n
N o t
U s
e
d
B a
t
t
e
r
y
N
L
!
N o t
U s
e
d
230 V
115 V
X
Selected voltage
230 V
115 V
X
X
Only available for the fire control panel FC123-ZA and FC124-ZA.
Step 1: Remove power supply FP2015-A1 and open it.
Step 2: Move the jumper on the PCB board from X12 to X11.
Jumper X12 for AC 230 V
Jumper X11 for AC 115 V
Step 3: Mark AC 115 V with 'x' and AC 230 V with '-----' on the label as indicated below.
s
Power supply (70 W)
Typ FP2015-A1
:
P.Nr.
:
S54400-B121-A1
ES
:
Control Code
:
Rated voltage 115/230 V Frequency: 50~60 Hz I in 1/0.5 A
:
Output 70 W
XXYZ WWW
DO NOT OPEN COVER
Siemens Switzerland Ltd Country of Origin: China
X2 X1
Akku
Usys
- + - +
:
:
Selected voltage
EN54-4 VdS: G
213083
0786-CPR-21302
87
Smart Infrastructure A6V10393190_h_en_--
Page 88

Appendix C: History log

Message Meaning
Fire alarm Zone # Zone # has triggered an alarm.
Fault Zone # Zone # is in fault state.
Isolation Zone # Zone # was disabled.
Fault Output # Output # is in fault state.
Fault AUX 24V output Auxiliary 24 V output is in fault state.
Isolation Output # Fire output # was disabled.
Active Output # Output # is activated when V1 / V2 is running.
Isolation Fault dialer 'Fault dialer' outputs were disabled.
Isolation Alarm dialer 'Alarm dialer' outputs were disabled.
Isolation Sounder outputs
Isolation EVAC sounder NL 'EVAC sounder NL' outputs were disabled.
Fault Mains power Fault in 230 V (or 110 V) power supply.
Fault Battery Fault in the battery power supply.
Fault External PSU Fault in external power supply unit.
Fault Earth fault Grounding fault.
Fault Set date & time Date and time was not set.
Input Input # Reset Panel has been reset when get signal from input.
Input Input # Level 2 access Panel is into access level 2 when get signal from input.
Input Input # Alarm and fault dialer isolated
Input Input # Manned operation Panel is in 'Manned' mode when get signal from input.
Input Input # Alarm dialer fault The output 'Alarm dialer' is in fault state when get signal from input.
Input Input # Alarm dialer confirmation received Alarm dialer confirmation received when get signal from input.
Input Input # Alert active Panel is in 'Alert' mode when get signal from input.
Sounder outputs were disabled.
Isolation of the output 'Alarm dialer' and 'Fault dialer' when get signal from input.
88 Smart Infrastructure A6V10393190_h_en_--
Page 89
Message Meaning
Input Input # ACK Panel has been acknowledged from input.
Input Input # External PSU fault External PSU fault information received when get signal from input.
ACK Panel has been acknowledged from panel. Reset Panel has been reset from panel. Active
EVAC Active
EVAC sounder NL Fault
EVAC Module
All sounder outputs have been activated in quiescent mode, by pushing the button 'SILENCE / RESOUND'.
Programmed EVAC sounder NL outputs have been activated by pushing the button 'Start' on EVAC module.
With or without EVAC module status is not match with panel’s configure
Input Input # Dependency reset Panel has been reset when get signal from input.
Test Zone # Zone # is in Test state.
Fault Input # Alarm dialer fault
The output 'Alarm dialer' is in fault state when get signal from input.
Input Input # SE ACK function Panel has been acknowledged from input.
Fault Output # 24VDC too low
For output # which is powered by external power, external power voltage is too low.
Smart Infrastructure A6V10393190_h_en_--
89
Page 90
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies
Document ID: A6V10393190_h_en_-- Edition: 2019-09-01