Siemens QFA3212.FWxN, QFA32SS.FWxN, FA3212.EWxN, QFA32SS.EWxN, FA3232.EWxN Installation Instructions Manual

Page 1
Installation Instructions
Series
2200 and 3200 Relative
and Temperature Room Units
CAUTION
Docume nt No. 129-104
Decemb er 11, 2017
Product Description
These room units measure relative humidity and temperature in the occupied space in which they are install ed. Models wit h display allow users to view the measured temperature value. A version with temperature setpoint adjustment is also off ered.
The effective sensing range is 32°F to 122°F (0°C to 50°C), and the setpoi nt range is 55°F to 95°F (13°C to 35°C). The humidity measuring range is 0 to 100% RH.
Hardware is included for installation on drywall or on a 2” × 4” electrical box.
Product Numbers
QFA3212.FWxN QFA32SS.FWxN QFA3212.EWxN QFA32SS.EWxN QFA3232.EWxN
Accessories
AQA2200-INTL Room Unit Back Plate
(10-pack)
563-102 GSKT KIT Room Sensor Insulating
Gasket (10-pack) (For hollow wall installations)
Expected Installation Time
20 minutes
Required Tools
Sizes 1 and 2 Phillips screwdrivers
Small and medium flat-blade screwdrivers
1/16-inch hex key
Medium-duty electric drill
3/16-inch (4.8 mm) drill bit
One-inch (25 mm) hole saw
Small level
Tape measure
Marker or pencil
Prerequisites
Review these instructions before beginning.
Installed: appropriate field wiring within the
maximum wiring run length for the individual equipment controller. The maximum recommended length is 750 feet (229 m) for 18 AWG; 300 feet (91 m) for 22 AWG.
All wiring must comply with National Electric Code (NEC) and local regulations.
Caution Notations
Equipm ent damage or l oss of data may occur if you do not follow a procedure as specified.
Item Number 129-104, Rev. JA
Figure 1. Typical Temperature Room Unit.
Page 1 of 4
Page 2
Document No. 129-104 Installation Instructions December 11, 2017
Mounting Information
Always mount the room unit vertically. Locate the room unit:
according to design specifications and local regulations.
where the air circulates around it freely (not in recessed areas or behind doors).
allowing a minimum of 4 inches (10 cm) free space above and below for proper airflow, the front cover removal tool, and the computer communicati on cabl e.
away from drafts caused by doors, windows, outside walls, air registers, pipes, return air plenums, etc.
away from heat sources such as strong lights, fireplaces, direct sunlight, etc.
on an inside wall (preferably), about 5 feet (1.5 m) above the finished floor, or per code (ANSI, ADA, or local regulation).
Drywall Mounting (No Rough-in), Typical
Base Plate Mounting and Wiring
1. Mark the center (cable) hole and the mounting hole locations, using t he room unit base plate as a template. See Figure 3.
Figure 2. Insulating Gasket.
4. Pull about three inches (75 mm) of the cable through the hole in the base plate.
5. Mount the room unit base plate on the wall, noting the UP arrow:
NOTE: If required, position the back plate behind
the room unit base, aligning the top and bottom mounting holes, prior to mounting to the wall:
a. Install the two mounting screws prov ided, but
do not tighten. b. Level the room unit base plate for appearance. c. Ti ghten the two mounting screws to the room
unit base plate.
6. Cut the cable, leaving about three inches (75 mm) on the room unit side of the drywall. Ensure that pin Number 1 connects to the same wire at each end of the cable.
2. Drill two 3/16-inch (4.8 mm) mounting holes and mount the two plastic wall anchors flush to below the wall surface for stable mounting of the device.
3. Cut a 1-inch (25 mm) center hole with a hole saw.
NOTE: It is recommended that you use the
optional Insulating Gasket* on the back of the Unit Base for hollow wall install ati ons.
When applying the adhesive-backed gasket to the back of the unit base, orient the gasket so that the cut-out arrow portion of the gasket is in the upper lefthand quadrant of the unit base. The sensor base has an UP arrow mol ded into the surf ace in the same quadrant location (see Figure 6).
*Insulating gasket s are sold in 10-packs (Part Number 563-102 GSKT KIT).
Page 2 of 4 Siemens Industry, Inc.
NOTE: See Figure 2 for details on optional Gasket
application.
Figure 3. Drywall Mounting (No Rough-in), Typical.
Page 3
7. Terminate the wires to the termination blocks on the
CAUTION:
room unit's base plate. (See Figure 6.)
8. Feed the extra cable back through the hole.
Unit Set-up
Figure 4. Circuit Board
(Located inside Room Unit Cover.
1. If the device has a switch, determine if voltage or
current output is needed.
Document No. 129-104
Installation Instructions
December 11, 2017
Figure 5. Changing Display to °C.
3. Snap the room unit cover to the room unit base plate by first hooking the room unit front to the top latches, and then rotating the cover downward until it latches.
4. Loosen the safety set screw at the bottom of the base one or two revoluti ons to lock the cover to the base. Be careful not to loosen too far as the screw can be completely removed from the base.
Electrical Box and Rough-in Mounting, Typical
For current, set t he switch in the down position (I).
For voltage, set the switch in the up position (V).
NOTE: The output setting applies to all outputs
(humidity, t em perature, and setpoint).
2. If selecting voltage, set the jumper:
Use the top and middle pins for 0 to 5V.
Use the bottom and mi ddle pins f or 0 to 10V.
NOTE: If the jumper is missing or removed, the
output voltage will default to 0 to 10V.
NOTE: The factory default for displayed temperature
units is °F. To change the display to °C, snip the wire jumper (0 Ohm resistor R64) on the back of the PCA.
1. If a locator is attached to the rough-in device, remove the locator by removing the two screws and lightly rocking the locator to pull it free.
2. Untie the twist tie and pull about three inches (75 mm) of the room unit cable through the hole in the base plate.
3. Mount the room unit base plate on the wall, noting
the UP arrow:
a. Install the two room unit mounting screws
provided, but do not tighten.
b. Level the room unit base plate for appearance
only.
c. Ti ghten the two mounting screws to the room
unit base plate.
Over-tightening may cause the room unit base plate to crack or bend.
4. Continue with Drywall Mounting (No Rough-in),
Typical, Steps 6 through 8, and Unit Set-up.
Page 3 of 4
Page 4
Document No. 129-104
CAUTION:
CAUTION:
Units with Blank Fr ont
Units with Displa y
Installation Instructions December 11, 2017
To prevent equipment dam age, do the following:
If the room unit is powered by AC:
AC Supply must be type NEC Class 2 and earth grounded at the secondary neutral.
Room Unit ACN (GND) must be con nected to the controll er common.
If the controller has a floating common, that common must be connected to the same earth ground point as the controller AC supply.
If the room unit is powered by isolated DC:
Where power is current limited up to 300 mA, it is not required to earth ground the controller isolated common.
Figure 6. Typical Wiring Base.
(All terminals may not be present.) Pin No. Function
Room Unit DC-(GND) must be connected
to the controller common.
Follow manufacturer’s Installation Instructions and Wiring Guidelines for connecting the controller to the Room Unit.
For Siemens Controll ers:
APOGEE Controllers with common already earth grounded are TXIO used on PXC Modular, PXC Compact 36 Expansion and P1 BIM or PTM used on MBC and RBC. These do not require the earth ground wire to be connected to the controller.
APOGEE Controllers with floating common
are PXC Compact 16/24/36, MEC, PXM, LON TEC and PPM. These require the earth ground wire to be connected to the controller.
1 DC+ or ACH 2 DC- or ACN (GND) 3 Temp Output 4 Humidity Output 5* Passive Temp 6* Passive Temp Common
1 DC+ or ACH 2 DC- or ACN (GND) 3 Temp Output 4 Humidity Output 5* Passive Temp 6* Passive Temp Common 7 Setpoint Out put 8 Override 9 Override Common
* Not available on “SS” models.
NOTE: If active temperature (0 to 5V/0 to 10V/4 to
20 mA) (Pin 3) rather than passive/resistive temperature is used, Passive Temp Common (Pin 6) does not need to be termi nated.
The install ation is now complete.
Information in this publication is based on curr ent specifications. The company reserves the rig ht to make changes in specifications and models as design i mprovements are introduced. APOGEE is a r egistered trademark or Siemens Industry, Inc. Other pr oduct or company names mentioned herein may be th e t rademarks of their respective owners. © 2017 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 USA + 1 847-215-1000
Your feedback is i mportant to us . If you have comments about this document, please send them toSBT_technical.editor.us.sbt@siemens.com
Document No. 129-104
Printed in the USA
Page 4 of 4