All rights reserved. No part of this documentation may be reproduced or published in any form or by any
means without prior written permission from the copyright owner.
Subject to alterations without notice.
A publication of PMA Prozeß- und Maschinen- Automation
Postfach 310229
D-34058 Kassel
Germany
Page 3
Introduction
1Introduction
Thank you for buying a KS 50-1 TCont.
This expert line unit offers special functions for tempering and hot-runner
equipment. An optional 20mA current loop or an RS485/422 interface are
available for easy connection of peripheral units including a KS 50-1 TCont to a
machine control system.
The protocol is widely used in the plastics industry and supported by many
injection moulder and extruder manufacturers, e.g. Arburg, Engel and
Krauss-Maffei. Another name for it is ”ARBURG protocol”.
This operating note describes the extended functions and features of
KS 50-1 TCont. For all other functions, refer to operating manual
9499-040-62811 for KS 50-1 Industrial Controller.
1.1 Definitions
A current loop interface transmits serial data by switching on and off a 20mA
current in a conductor loop at the data bit clock. During the rest condition, or
during transmission of ”1” bits, a constant 20 mA current is flowing, whilst the
current flow is intermittent with ”0” bits.
Another name for 20mA current loop interface is TTY interface
(TeleTYpe(writer)).
l
Caution! The unit contains ESD-hazarded components.
ARBRUG is a registered trademark of ARBURG GmbH + CO, D-Loßburg.
.
Operating note KS 50-1 TCont3Definitions
Page 4
Hints on operation
2Hints on operation
2.1 Electrical connections
alternativ
RGND
RXD-B
GND
RXD-A
DATA B
DATA A
TXD-B
TXD-A
RS485 / RS422
+24V DC
OUT5
OUT6
24V GND
+ 20mA
20mA GND
di2
di3
U
TTY
1
(2)
3
4
5
T
6
7
8
9
10
11
12
13
14
15
(16)
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
L
N
Logic
24V AC/DC
U
HC
mA
90...250V
mA
0..10 V*
OUT1
OUT2
OUT3
INP2
di1
INP1
*Safety switch mA i V turned left
g
The controller is provided with flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to
DIN 46 244. Or with screw terminals depending on ordering code.
2 Alternative connection of the RS485/422 bus interface (example)
R = 120...200 OhmT
RT
RGND connection optional
2.3 Connection example
RGNDRGND
DATA B
DATA A
12
13
14
15
(16)
17
10
11
12
13
14
15
DATA B
DATA A
J
12
13
14
15
(16)
17
10
11
12
13
14
15
RGND
DATA B
DATA A
12
13
14
15
(16)
17
10
11
12
13
14
15
PC
R=100 Ohm
converter
RS485-RS232
max. 1000m
”Twisted Pair”
RT
R = 120...200 OhmT
remote/local
L.start
L.stop
STL
process
value
heating
current
mould
di1
di2
di3
INP1
INP2
TTY
OUT1
OUT2
OUT3
STL
tempering unit
heating
cooling
pump
Operating note KS 50-1 TCont5Connection example
Page 6
Operation
KS 50-1
TCont
180
178.
SP.x
Rem
Err
Ada
123OK
3
1
2
3
4
0
5
!
6
"
7
8
§
9
$
%
è
&
3Operation
3.1 Front view
LED colours :
LED 1, 2, 3:yellow
LED OK:green
other LEDs:red
1 Status of switching outputs
OuT.1... 6
2 Lights with limit value 1
(PArA / Lim) not exceeded
3 Process value display
4 Set-point, controller output
5 Signals ConF and PArA level
6 Device in remote mode
7 Self-tuning active
8 Entry in error list
9 Set-point SP.2 or SP.E is
effective
0 Set-point gradient is effective
! Manual/automatic switch-over:
Off:Automatic
On:Manual
(changing possible)
Blinks: Manual
(changing not possible)
(r ConF/ Cntr/ MAn))
" Enter key:
calls up extended
operating level / error list
§ Up/ Down keys:
changing the set-point or the
controller output value
$ Manual mode /spec. function
(→ ConF / LOGI)
% PC connection for
BlueControl (engineering
tool
& Remote/local-switch /
spec. function
(→ ConF / LOGI)
g
g
Front view6Operating note KS 50-1 TCont
In the upper display line, the process
value is always
extended operating level, the bottom display line changes cyclically between
parameter name and parameter value.
LED REM - 6 displays the remote/local mode. In mode remote this LED lights
and value changes via front keys are locked.
displayed. At parameter, configuration, calibration as well as
Page 7
3.2 Behaviour after power-on
After supply voltage switch-on, the unit starts with the remote mode and goes
then into the standby mode. The controller mode is switched off. (SP = OFF).
3.3 Functions for tempering units
KS 50-1 TCont has a lot of possibilities to connect signals coming from and
going to the tempering unit.
The process value is connected to INP1.
w
An output signal of a safety temperature limiter (STL) can be attached
w
alternatively to di1 to di3. When responding the STL the controller goes into
the switching off mode (stop). The signal is passed on in the protocol (see
page 18).
Operation
The operation of the controller can be accomplished in the remote or in local
w
operation. For the change-over the inputs di1 to di3 or the F-key are
available. In remote mode values can be given only over the attached
interface; inputs via the front are blocked. Vice versa in local mode set-point
operations over the interface are not permitted. As answer the device
supplies a NAK message.
For local starting and stopping of the tempering unit push-buttons or
w
switches can be selected and attached at the inputs di1 to di3. The function
start or stop is released with the change of 0 to 1, independently of the
configuration of di.Fn as push-button or switch.
Selected signals for sensor mode, level alarm or flow alarm can be connected
w
to di1 to di3. They are only through-handed in the device, but indicated in
the protocol (see page 17).
The alarm for safety temperature - monitoring can be determined with limit 1
w
( Lim.1).
KS 50-1 TCont supplies a continuous signal to control a pump, which can be
w
connected to OUT1 to OUT6.
After a stop command the pump is only switched off, if the return flow
w
temperature is fallen below the adjusted limit, which is defined over the
set-point SP2.
g
If the inputs for start and stop are not wired, then the same functionality can be
achieved in local mode by switching on and off the controller function (for
switching off put the set-point SP to OFF; for switching on enter a valid
set-point). The start instruction corresponds to the control command (r) in the
remote mode, the stop command to the control command (p).
Operating note KS 50-1 TCont7Behaviour after power-on
Page 8
Operation
Signal connection types
SignalConnection typesRemarks
Pt100 / TC – sensor, internal or externalINP1
Heating current input, if applicableINP2
STL input from safety temperature limiterdi1...3
remote – local – switch-overdi1...3, F-Key
local – start; push-button functiondi1...3
local – stop; push-button functiondi1...3
Operating note KS 50-1 TCont9Functions for tempering units
Page 10
Operation
3.4 Functions for hot-runner
To operate with the protocol extension for hot-runners only a few additional
inputs and outputs are needed.
In local operation a start-/stop functionality can be achieved by switching on and
off the controller (for switching off put the set-point SP to OFF; for switching
on enter a valid set-point). The start command corresponds to the control
command (r) in the remote mode, the stop command to the control command (a).
The operation of the automatic controller can be switched over from remote
w
to local operation. Therefore the inputs di1 to di3 or the F-key are available.
Functions for hot-runner10Operating note KS 50-1 TCont
Page 11
Configuration extensions
4Configuration extensions
The KS 50-1 TCont configuration values are extended by the following settings
compared with the standard version
Protocol selection
q
.
In configuration menu othr, item Prot is available for definition of the
protocol to be used.
othr
NameRangeDescriptionDefault
ProtProtocol selection for rear interface1
0MODBUS RTU
1Protocol for tempering unit
2Protocol for hot runner
q Output selection
Control of a pump can be selected via parameter PumPin the configuration menu
for OUT.1, OUT.2, OUT.3, OUT.5 or OUT.6 . The default is an active OUT.3.
OUT.1, OUT.2, OUT.3, OUT.5, OUT.6
NameRangeDescriptionDefault
PuMPoutput pump0
0Not active
1Active
q
Self-tuning start
For KS 50-1 TCont, the self-tuning behaviour during start-up was changed.
Self-tuning is suppressed during power-on and called up only when starting
control operation, if permitted (see OrEL).
0Manual self-tuning start via the front panel, or when starting
control operation, if permitted.
1Manual self-tuning start via the front panel, when starting
control operation, if permitted, and when detecting
oscillation.
Operating note KS 50-1 TCont11
Page 12
Configuration extensions
Input selection
q
For configuration menu LOGI additional menus for selecting typical digital
inputs for tempering equipment are available.
LOGI
NameRangeDescriptionDefault
StBSource for safety temperature limiter signal0
0interface only
2di1 switches
3di2 switches
4di3 switches
L.StaSource for local function start0
0interface only
2di1 switches
3di2 switches
4di3 switches
L.StoSource for local function stop0
0interface only
2di1 switches
3di2 switches
4di3 switches
SEnSSource for sensor operating mode (internal, external)0
0interface only
2di1 switches
3di2 switches
4di3 switches
LEvLSource for level alarm0
0interface only
2di1 switches
3di2 switches
4di3 switches
FloSource for flow alarm0
0interface only
2di1 switches
3di2 switches
4di3 switches
12Operating note KS 50-1 TCont
Page 13
Parameter extensions
5Parameter extensions
The KS 50-1 TCont parameters are extended by the following settings compared
to the standard version.
Self-tuning switch-off
q
For Cntrcontrol and adaptation, parameter OrEl is used to permit self-tuning.
Cntr
NameRangeDescriptionDefault
OrElEnable self-tuning at control operation start0
0Self-tuning permitted
1Self-tuning not permitted
+
g
g
g
Hints on self-tuning
To meet the special requirements of fast control loops, e.g. with tempering units,
the following information should be taken into account.
By setting the input filter for measurement input 1 ( Para / InP.1 / t.F1)toa
filter time
the input variable.
To improve the optimization result, the control range should be limited to the
actual range. For this purpose, the min. and max. control range limit must be
matched, e.g. with a range of 20°C ... 150°C, value rnG.L = 20and rnG.H =
150 in Conf / Cntrmust be set.
The minimum cycle times t1 and t2 should be as low as possible. If a defined
min. pulse duration must not be exceeded, changing during self-tuning can be
prevented via configuration parameter Adt0 = 1. Please, note that the shortest
pulses result from ¼ x t1 or¼xt2.
≥ 15 s, input variable fluctuations can be reduced, i.e. earlier settling of
Operating note KS 50-1 TCont13
Page 14
Communication protocol
6Communication protocol
KS50-1 TCont supports a simple protocol for injection moulders and extruders
widely used in the plastics industry, which is used for connecting peripheral
equipment and easy simple data exchange. This protocol, which is also called
”ARBURG” protocol, is designed according to the specification of the Arburg
company.
g
This protocol is also supported by other machine manufacturers, e.g. Engel,
Krauss-Maffei, etc. Any adaptation required can be done by changing the
Baudrate or the parity.
Communication is according to the master / slave principle. KS 50-1 is always
slave and polled for a message by the machine control system. Exchanging
messages is done in half-duplex operation.
The transmission parameters are adjustable via the front panel or via
BlueControl
Baudrate (bAud):
q
2400 ,
w
,
4800
w
9600,
w
19200 Bits/s
w
q Parity (PrtY):
,
Even
w
Odd,
w
None
w
.
q Address settings (Addr):
1to32
w
q
Byte format (fixed):
Number of data bits: 8
w
Number of stop bits: 1
w
Number of start bits: 1
w
The LSB is sent first.
Exchanging messages is subjected defined time conditions:
w
Character delay timeT1:< 50 ms
(The max. possible time which can pass between sending of the start bits of
two successive bytes a message)
w
Acknowledgement delay timeT2: <100ms
(The max. possible time which can pass between the end of an inquiry sent by
the master and reception of the first character of the slave reply)
14Operating note KS 50-1 TCont
Page 15
Communication protocol
6.1 Data format
For transmission of block length and checksum, the hexadecimal format is used,
whilst set-points and process values are transmitted in BCD format. For
transmission, hexadecimal values are converted into ASCII. For simplification,
values above 9 (A-F) are coded as 3Ah - 3Fh instead of 41h-46h (ASCII A-F).
6.2 Protocol structure
123456...nn+1n+2
AddressLength
IdentificatonMessageChecksum
Byte 1:Device address of instruments 1 – 32, default 1
Byte 2-4:Block length; each message contains 3 bytes, which include
(ASCII-coded) the binary number of bytes of the overall message
(including checksum bytes). When receiving, the correct number of
bytes is checked
(range: 30h,30h,37h ... 3Fh,3Fh,3Fh)
Byte 5:Identification marks the message type,(range: 41h, 7Fh), see below
Byte 6-n:Information bytes, see below
Byte n+1,n+2:Checksum; every message is completed by 2 checksum bytes, which
are also counted in the block length bytes. The checksum bytes are the
(ASCII-coded) 8 bit wide sum of all bytes of the message including
block length bytes, checksum bytes not included.
(range: 30h,30h...3Fh,3Fh)
g
Hexadecimal numbers are coded in form xxh, e.g. 41h means decimal 65 or ‘A’
in ASCII.
Operating note KS 50-1 TCont15Data format
Page 16
Protocol for tempering equipment
7Protocol for tempering equipment
The protocol for tempering equipment is selected via parameter ProT =1.
7.1 Master telegram
The following telegrams sent by the master are supported by KS 50-1 TCont.
… 456...1213+14
...IdentificationMessageCheck sum
Byte 5:Identification: 41h (‚A‘) and 52h (‚R‘) is supported.
Byte 6-9:Set-point (= SP) in 0,1 degrees Celsius
(3 digits before, 1 digit behind the decimal point);
negative temperatures up to –99 degrees Celsius are possible
(1st byte = 2Dh)
Range: -99,9 ... 999,9 °C
Examples: 12,3 °C → 30h 31h 32h 33h
-5,6 °C → 2Dh 30h 35h 36h
Byte 10:Mould type = parameter set:
60h (`):is supported (self-tuning acc. to KS 50-1 TCont setting)
61h (a)...6Ah(j): commands are accepted; function as 60h
Byte 11:Control commands = operating mode:
61h (a), 6Bh (k):Switch-off function;
cooling down to return flow temperature, switch off
feedback signals: (k) cooling, (p) switched off
70h (p): Switch-off function;
heating off, cooling down to return flow temperature,
cooling off, pump off, switch off
feedback signals: (k) cooling, (p) switched off
72h (r ): Switch-on function;
pump on, self-tuning on (if permitted),
closed-loop control (normal operation)
feedback signals: (r ) closed-loop control
73h (s): Switch-off function;
cooling down to return flow temperature, switch off
feedback signals: (s) cooling, (p) switched off
Byte 12:Reserved, always 20h
Byte 13,14:Checksum
Master telegram16Operating note KS 50-1 TCont
Page 17
Protocol for tempering equipment
7.2 Slave telegram
With correctly received master telegram, the following reply telegram is sent by
KS 50-1 TCont :
...456...1717+18
...IdentificationMessageChecksum
Byte 5:Identification: 41h (‚A‘) and 72h (‚r‘) are supported.
Byte 6-9:
Process value (= In.1)in0,1°C
(3 digits before, 1 digit behind the decimal point);
Negative temperatures up to –99 °C are possible (1
Range: -99,9 ... 999,9 °C
Examples:12,3 °C → 30h 31h 32h 33h
Bit 0:controller mode1: local0: remote
Bit 1:sensor mode1: internal; (selection via SEns)
Bit 2:inadmissible
set-point1: fault
Bit 3:(fixed)0
Bit 4:1: common alarm occurred
Bit 5, 6, 7: (fixed)1, 1, 0
st
byte = 2Dh)
st
byte = 2Dh)
(see status alarms1)
Byte 15:Status alarms 1
Bit 0:sensor break1: sensor break detected (FbF.1)
Bit 1:heating defective1: HCA error (HCA or Loop)
Bit 2:cooling defective0, not supported.
Bit 3:level alarm0, (optionally adjustable
via LEvL )
Bit 4:flow alarm0, (optionally adjustable via Flo)
Bit 5:temperature >
safety limit1: yes (optional Stb or Lim.1)
Bit 6, 7:(fixed)1, 0
Operating note KS 50-1 TCont17Slave telegram
Page 18
Protocol for tempering equipment
Byte 16:Status alarms 2
Bit 0:pump defective:0; not supported
Bit 1:phase failure:0; not supported
Bit 2:system error1: input STL has responded
Bit 3, 4, 5, 6, 7: (fixed)0, 0, 0, 1, 0
Byte 17:Status feedback
6Bh (k)switch-off: cooling down to return flow temperature
6Fh (o)during control operation: self-tuning busy
70h (p)switch-off: heating, cooling, pump switched off
72h (r )control operation
73h (s)switch-off: cooling down to return flow temperature
Byte 18-19:Checksum
(Stb) or instrument error (E.1, E.2)
7.3 Error messages
With parity or framing errors, or with undefined characters, no reply is provided.
If the checksum in the master telegram is faulty, or with an error in the message,
KS 50-1 TCont sends a NAK message.
is sent. Sending and handling of the remaining parameters are as in the
standard protocol (see page 16)
Slave telegram
q
...456...1718+19
...IdentificationMessageChecksum
Byte 5:Identification 72h (‚r‘) instead of 41h (‚A‘) is sent. The remaining
functions are as in the standard protocol (see page 17 ).
Operating note KS 50-1 TCont19Alarm Reset
Page 20
Protocol for hot-runner systems
8Protocol for hot-runner systems
Selecting the hot-runner protocol is done via setting ProT =2.
With a hot-runner system, KS 50-1 TCont covers one channel.
8.1 Master telegram
The structure of the inquiry telegram is:
...456...1011+12
...IdentificationMessageChecksum
Byte 5:Identification: 41h (‚A‘) is supported.
Byte 6-9:
• Set-point with command for closed-loop control: (= SP)in0,1 °C
(3 digits before, 1 digit behind the decimal point);
Negative temperatures up to –99 °C are possible (1
• Output value with command for positioning: in % (= Yman)
(3 digits before, 1 digit behind the decimal point)
Byte 10:Control commands
72h (r):closed-loop control (normal operation),
in °C; instrument in automatic mode;
after control function switch-off, self-tuning is done,
if permitted
73h (s):positioning,
in %; instrument in manual mode
61h (a):switch off channel
control function switched off
Byte 11-12:Checksum
st
byte = 2dh)
g
Special case: first message after control system start-up: system can read up to 25
channels per device address. Therefore, the message contains up to 25 times the
set-point or output value, and the control command.
However, a KS 50-1 TCont only uses the values for channel 1 from the message,
and indicates in the reply that only one channel is provided.
Master telegram20Operating note KS 50-1 TCont
Page 21
Protocol for hot-runner systems
8.2 Slave telegram
The structure of the slave telegram is.
...456...1213+14
...IdentificationMessageChecksum
Byte 5:Identification: 41h (‚A‘) is supported.
Byte 6:Status device
Bit 01: power supply failure during operation
(e.g. heating current alarm)
Bit 1, 2(fixed) 0 0
Bit 31: other internal error, e.g. E.1, E.2 ...
Bit 4, 5, 6, 7: (fixed)0110
Byte 7-10:Channel 1
• Process value with command for closed-loop control: (= In.1)in0,1
degrees Celsius
(3 digits before, 1 digit behind the decimal point); negative
temperatures up to –99 degrees Celsius are possible (1st byte = 2Dh)
Bit 01: switched on ( C.Off =0)
Bit 11: lowering on (with SP.2 =1)
Bit 20: closed-loop control (automatic),
1: positioning (manual mode)
Bit 3(fixed) 0
Bit 4, 5, 6, 7 : (fixed)0110
Byte 12:Channel 1 : status alarms 2
Bit 01: lead break, e.g.: LooP =1
Bit 11: only undercurrent, e.g. HCA =1
Bit 21: sensor defective, e.g. FbF.1 , Sht.1 , POL.1
Bit 30
Bit 4, 5, 6, 7 : (fixed)0110
Span start, end of span: anywhere within measuring
range
Scaling:selectable -1999...9999
Linearization:16 segments, adaptable
with BlueControl
Table 1 Thermocouple ranges
ThermocoupleRangeAccuracyResolution (Ô)
LFe-CuNi (DIN)-100...900°C-148...1652°Fß 2K0.1 K
JFe-CuNi-100...1200°C-148...2192°Fß 2K0.1 K
KNiCr-Ni-100...1350°C-148...2462°Fß 2K0.2 K
NNicrosil/Nisil-100...1300°C-148...2372°Fß 2K0.2 K
SPtRh-Pt 10%0...1760°C32...3200°Fß 2K0.2 K
RPtRh-Pt 13%0...1760°C32...3200°Fß 2K0.2 K
special-25 … 75 mV
0.1%0.01%
Table 2 Resistance transducers
TypeSensor current RangeAccuracyResolution (Ô)
Pt1000,2mA-200...850°C-328...1562°Fß 1K0.1K
Pt1000-200...850°C-328...1562°Fß 2K0.1K
Resistance
4500
ß 0.1%0.051%
Operating note KS 50-1 TCont23Slave telegram
Page 24
TECHNICAL DATA
Table 3 Current and voltage
RangeInput resistanceAccuracyResolution (Ô)
0-10 Volt
If the universal output OUT3 is used there may
be no external galvanic connection between
measuring and output circuits!
OUTPUTS
SURVEY OF THE OUTPUTS
OutputUsed for
Control output for
OUT1 OUT2
(relay)
OUT3
(relay or logic)
OUT3
(continuous)
OUT5 OUT6
(optocoupler)
heating/cooling or open/close,
limit contacts, alarms, end of
program, pump control *
as OUT1 and OUT2
Control output, process value,
set-point, control deviation,
transmitter supply 13 V / 22 mA
as OUT1 and OUT2
CONTROL INPUT DI1
Configurable as direct or invers switch or
push-button! Connection of a potential-free
contact suitable for switching „dry“ circuits.
Switched voltage:2.5 V
Switched current:50µA
CONTROL INPUTS DI2, DI3
Configurable as switch or push-button !
Optocoupler input for active triggering
Nominal voltage:24 V DC external
Current sink (IEC 1131 Type 1)
Logic “0”-3...5 V
Logic “1”15...30 V
Current requirement:approx. 5 mA
* All logic signals can be OR-linked !
RELAY OUTPUTS OUT1, OUT2
Contacts:2 NO contacts with
common connection
Max. contact rating:500 VA, 250 VAC, 2A at
48...62 Hz, resistive load
Min. contact rating:6V, 1 mA DC
Operating life (electric):800,000 duty cycles with
max. rating
OUT3 USED AS RELAY OUTPUT
Contacts:Potential-free changeover
contact
Max. contact rating:500 VA, 250 VAC, 2A at
48...62 Hz, resistive load
Min. contact rating:5V, 10 mA AC/DC
Operating life (electric):600,000 duty cycles with
max. rating
Slave telegram24Operating note KS50-1 TCont
Page 25
TECHNICAL DATA
Galvanic isolations:
Safety isolation
Functional isolation
Process value input INP1
Mains supplySupplementary input INP2
Digital input di1
Relay outputs OUT1,2RS485 /422 interface
TTY interface
Relay output OUT3Digital inputs di2, 3
Universal output OUT3
Transmitter supply U
OUT5, OUT6
Note: If the relays OUT1...OUT3 operate
external contactors, these must be fitted with
RC snubber circuits to manufacturer
specifications to prevent excessive switch-off
voltage peaks.
T
Error:
20 mV (0.2%)
≤
OUT3 used as transmitter supply
Output:22 mA /≥13 V
OUT3 used as logic output
Load≤500
Load > 500
Ω
Ω
0/≤20 mA
0/> 13 V
OUTPUTS OUT5, OUT6
Galvanically isolated opto-coupler outputs.
Grounded load: common positive control
voltage.
Output rating: 18...32 VDC; ≤ 70 mA
Internal voltage drop: ≤ 1V with I
Protective circuit: built-in against short circuit,
overload, reversed polarity (free-wheel diode
for relay loads).
max
POWER SUPPLY
Depending on version:
OUT3 AS UNIVERSAL OUTPUT
Galvanically isolated from the inputs.
Freely scalable
Resolution:11 bit
Time constant of the D/A converter
90:
T
Limiting frequency of the continuous
controller:> 2 Hz
Current output
0/4...20 mA, configurable.
Signal range:0...approx. 21.5mA
Load :
500
≤
Load effect:0.02%/100
Resolution:
Error:
≤22µ
≤40µ
Voltage output
0/2...10V configurable
Signal range:0...11 V
Load:
≥ 2k
Load effect:none
Resolution:
11 mV (0.1%)
≤
50 ms
Ω
Ω
A (0.1%)
A (0.2%)
Ω
AC SUPPLY
Voltage:90...260 V AC
Frequency:48...62 Hz
Power consumption:approx. 7.0 VA
UNIVERSAL SUPPLY 24 V UC
AC voltage:20,4...26,4 V AC
Frequency:48...62 Hz
DC voltage:18...31 V DC
Power consumption:approx. 7 VA (W)
BEHAVIOUR WITH POWER FAILURE
Configuration, parameters, and adjusted
set-points, control mode: non-volatile storage in
EEPROM
BLUEPORTFRONT INTERFACE
Connection of PC via PC adapter (see
„Accessories“). The BlueControl
used to configure, set parameters, and operate
the KS 50-1 TCont.
software is
Operating note KS 50-1 TCont25Slave telegram
Page 26
TECHNICAL DATA
BUS INTERFACE
Galvanically isolated.
Screened cables must be used.
RS 485 / 422
Physical:RS 485/422
Transmission speed:
Parity:
2400, 4800, 9600, 19.200 Bit/s
Even, odd, none
Address range:1...32
Number of
32
controllers/segm:
TTY (20 mA CURRENT LOOP)
Physical:20 mA current loop
Transmission speed:
Parity:
2400, 4800, 9600, 19.200 Bit/s
Even, odd, none
Address range:1...32
Voltage drop:
≤ 2.2V
Protocols
MODBUS RTU, protocol for tempering units*,
protocol for hot runner systems*
* according to Arburg specification
ENVIRONMENTAL CONDITIONS
Protection modes
Front panel:IP 65
Housing:IP 20
Terminals:IP 00
Frequency:10...150 Hz
Unit in operation:1g or 0.075 mm
Unit not in operation: 2g or 0.15 mm
Shock test Ea (DIN IEC 68-2-27)
Shock:15g
Duration:11ms
Electromagnetic compatibility
Complies with EN 61 326-1
Meets the immunity requirements for
w
continuous, unattended operation
Meets the radiation requirements of Class B
w
for rural areas
In case of surge interference, increased
w
measurement errors must be expected
GENERAL
Housing
Material:Makrolon 9415
flame-retardant
Flammability class::UL 94 VO, self-extinguishing
Plug-in module, inserted from the front
Safety tests
Complies with EN 61010-1 (VDE 0411-1):
Over voltage category II
Contamination class 2
Working voltage range 300 V
Protection class II
Certifications
Permissible temperatures
UL certification (applied for)
For specified
0...60°C
accuracy:
Warm-up time:
< 15 minutes
Temperature effect:: < 100ppm/K
For operation:-20...65°C
Electrical connections
w
Flat-pin connectors 1 x 6.3 mm or 2 x 2.8
mm to DIN 46 244
w
Screw terminals
Mounting
For storage:-40...70°C
Panel mounting with two fixing clamps at
Humidity
75% yearly average, no condensation
top/bottom or left/right
Close mounting possible
Mounting position: not critical
Shock and vibration
Vibration testFc (DIN 68-2-6)
Weight:0.27kg
Slave telegram26Operating note KS50-1 TCont
Page 27
Index
11Index
Index
Address settings ............14
Alarm Reset ..............19
ARBURG protocol ...........3
Baudrate ................14
Bus interface .............4,26
Byte format ...............14
Communication protocol .....14-15
Connection of the TTY bus interface . . 4
Current and voltage signals ......23
Data format ...............15
Definitions ................3
Electrical connections ........4,26
Error messages .............18
flow alarm ................7
Front interface .............25
Front view ................6
Frontansicht ...............6
Galvanic isolations ...........25
Heating current............24
hot-runner ...............10
Housing.................26
input INP2 ...............24
Input selection .............12
INPUTS ................23
Introduction ...............3
level alarm ................7
local...................17
local operation .............10
Master telegram ............20
Master telegram ............16
ORDERING INFORMATION.....22
Output selection ............11
OUTPUTS ...............24
Parity ..................14
POWER SUPPLY ...........25
Protocol for hot-runner systems . . 20 - 21
Protocol for tempering equipment. 16 - 19