Siemens Expert Series, KS50-1 TCont Operating Note

Page 1
PMA Prozeß- und Maschinen-Automation GmbH
Temperature controller KS 50-1
KS50-1
KS50-1
expert line for tempering units and hot runners
Operating Note
TCont
TCont
English
Valid from: 8403
Page 2

Contents

1 Introduction ............................3
1.1 Definitions..............................3
2 Hints on operation .........................4
2.1 Electrical connections ........................4
2.2 Bus interface.............................4
2.3 Connection example.........................5
3 Operation ..............................6
3.1 Front view ..............................6
3.2 Behaviour after power-on ......................7
3.3 Functions for tempering units ....................7
3.4 Functions for hot-runner ......................10
4 Configuration extensions .....................11
5 Parameter extensions .......................13
6 Communication protocol .....................14
6.1 Data format.............................15
6.2 Protocol structure .........................15
7 Protocol for tempering equipment................16
7.1 Master telegram ..........................16
7.2 Slave telegram ...........................17
7.3 Error messages ...........................18
7.4 Alarm Reset ............................19
8 Protocol for hot-runner systems .................20
8.1 Master telegram ..........................20
8.2 Slave telegram ...........................21
9 ORDERING INFORMATION .................22
10 TECHNICAL DATA .......................23
11 Index ................................27
© PMA Prozeß- und Maschinen-Automation GmbH Printed in Germany (0307)
All rights reserved. No part of this documentation may be reproduced or published in any form or by any
means without prior written permission from the copyright owner.
Subject to alterations without notice.
A publication of PMA Prozeß- und Maschinen- Automation
Postfach 310229
D-34058 Kassel
Germany
Page 3
Introduction
1 Introduction
Thank you for buying a KS 50-1 TCont. This expert line unit offers special functions for tempering and hot-runner equipment. An optional 20mA current loop or an RS485/422 interface are available for easy connection of peripheral units including a KS 50-1 TCont to a machine control system. The protocol is widely used in the plastics industry and supported by many injection moulder and extruder manufacturers, e.g. Arburg, Engel and Krauss-Maffei. Another name for it is ”ARBURG protocol”.
This operating note describes the extended functions and features of KS 50-1 TCont. For all other functions, refer to operating manual 9499-040-62811 for KS 50-1 Industrial Controller.
1.1 Definitions
A current loop interface transmits serial data by switching on and off a 20mA current in a conductor loop at the data bit clock. During the rest condition, or during transmission of ”1” bits, a constant 20 mA current is flowing, whilst the current flow is intermittent with ”0” bits.
Another name for 20mA current loop interface is TTY interface (TeleTYpe(writer)).
l
Caution! The unit contains ESD-hazarded components.
ARBRUG is a registered trademark of ARBURG GmbH + CO, D-Loßburg.
.
Operating note KS 50-1 TCont 3 Definitions
Page 4
Hints on operation
2 Hints on operation
2.1 Electrical connections
alternativ
RGND
RXD-B
GND
RXD-A
DATA B
DATA A
TXD-B
TXD-A
RS485 / RS422
+24V DC
OUT5 OUT6
24V GND
+ 20mA
20mA GND
di2
di3
U
TTY
1
(2)
3
4
5
T
6
7
8
9
10
11
12
13
14
15
(16)
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
L N
Logic
24V AC/DC
U
HC
mA
90...250V
mA
0..10 V*
OUT1 OUT2
OUT3
INP2
di1
INP1
* Safety switch mA i V turned left
g
The controller is provided with flat-pin terminals 1 x 6,3mm or 2 x 2,8mm to DIN 46 244. Or with screw terminals depending on ordering code.
2.2 Bus interface
1 Connection of the TTY bus interface (example)
PC
converter
TTY -RS232
+
-T
+R
-
+20mA
20mA GND
12
13
14
15
(16)
17
10
11
12
13
14
15
+20mA
20mA GND
J
12
13
14
15
(16)
17
max. 1000m
(”Twisted Pair”)
10
11
12
13
14
15
+20mA
20mA GND
12
13
14
15
(16)
17
10
11
12
13
14
15
Electrical connections 4 Operating note KS 50-1 TCont
Page 5
Hints on operation
2 Alternative connection of the RS485/422 bus interface (example)
R = 120...200 OhmT
RT
RGND connection optional
2.3 Connection example
RGND RGND
DATA B
DATA A
12
13
14
15
(16)
17
10
11
12
13
14
15
DATA B
DATA A
J
12
13
14
15
(16)
17
10
11
12
13
14
15
RGND
DATA B
DATA A
12
13
14
15
(16)
17
10
11
12
13
14
15
PC
R=100 Ohm
converter
RS485-RS232
max. 1000m
”Twisted Pair”
RT
R = 120...200 OhmT
remote/local
L.start
L.stop
STL
process value
heating current
mould
di1
di2
di3
INP1
INP2
TTY
OUT1
OUT2
OUT3
STL
tempering unit
heating
cooling
pump
Operating note KS 50-1 TCont 5 Connection example
Page 6
Operation
KS 50-1
TCont
180
178.
SP.x
Rem
Err
Ada
123OK
3
1
2
3
4
0
5
!
6
"
7 8
§
9
$
%
è
&
3 Operation
3.1 Front view
LED colours :
LED 1, 2, 3: yellow LED OK: green other LEDs: red
1 Status of switching outputs
OuT.1... 6
2 Lights with limit value 1
(PArA / Lim) not exceeded
3 Process value display 4 Set-point, controller output 5 Signals ConF and PArA level 6 Device in remote mode 7 Self-tuning active 8 Entry in error list 9 Set-point SP.2 or SP.E is
effective
0 Set-point gradient is effective ! Manual/automatic switch-over:
Off: Automatic On: Manual
(changing possible)
Blinks: Manual
(changing not possible)
(r ConF/ Cntr/ MAn))
" Enter key:
calls up extended operating level / error list
§ Up/ Down keys:
changing the set-point or the controller output value
$ Manual mode /spec. function
(ConF / LOGI)
% PC connection for
BlueControl (engineering tool
& Remote/local-switch /
spec. function
(ConF / LOGI)
g
g
Front view 6 Operating note KS 50-1 TCont
In the upper display line, the process value is always extended operating level, the bottom display line changes cyclically between parameter name and parameter value.
LED REM - 6 displays the remote/local mode. In mode remote this LED lights and value changes via front keys are locked.
displayed. At parameter, configuration, calibration as well as
Page 7
3.2 Behaviour after power-on
After supply voltage switch-on, the unit starts with the remote mode and goes then into the standby mode. The controller mode is switched off. (SP = OFF).
3.3 Functions for tempering units
KS 50-1 TCont has a lot of possibilities to connect signals coming from and going to the tempering unit.
The process value is connected to INP1.
w
An output signal of a safety temperature limiter (STL) can be attached
w
alternatively to di1 to di3. When responding the STL the controller goes into the switching off mode (stop). The signal is passed on in the protocol (see page 18).
Operation
The operation of the controller can be accomplished in the remote or in local
w
operation. For the change-over the inputs di1 to di3 or the F-key are available. In remote mode values can be given only over the attached interface; inputs via the front are blocked. Vice versa in local mode set-point operations over the interface are not permitted. As answer the device supplies a NAK message.
For local starting and stopping of the tempering unit push-buttons or
w
switches can be selected and attached at the inputs di1 to di3. The function start or stop is released with the change of 0 to 1, independently of the configuration of di.Fn as push-button or switch.
Selected signals for sensor mode, level alarm or flow alarm can be connected
w
to di1 to di3. They are only through-handed in the device, but indicated in the protocol (see page 17).
The alarm for safety temperature - monitoring can be determined with limit 1
w
( Lim.1).
KS 50-1 TCont supplies a continuous signal to control a pump, which can be
w
connected to OUT1 to OUT6. After a stop command the pump is only switched off, if the return flow
w
temperature is fallen below the adjusted limit, which is defined over the set-point SP2.
g
If the inputs for start and stop are not wired, then the same functionality can be achieved in local mode by switching on and off the controller function (for switching off put the set-point SP to OFF; for switching on enter a valid set-point). The start instruction corresponds to the control command (r) in the remote mode, the stop command to the control command (p).
Operating note KS 50-1 TCont 7 Behaviour after power-on
Page 8
Operation
Signal connection types
Signal Connection types Remarks Pt100 / TC – sensor, internal or external INP1 Heating current input, if applicable INP2
STL input from safety temperature limiter di1...3 remote – local – switch-over di1...3, F-Key local – start; push-button function di1...3 local – stop; push-button function di1...3
Sensor operating mode: 0 Input for alarm “level”: 0= ok; 1= alarm di1...3   Input for alarm “flow”: 0= ok, 1= alarm di1...3  
Output heating relay OUT1..3, OUT5..6 Output cooling relay OUT1..3, OUT5..6 Output pump relay OUT1..3, OUT5..6
alarm safety temperature LiM.1 Set-point for return flow temperature SP.2
= internal; 1= external; di1...3  
Signals are only transferred in communication protocol.Alternative connection types
The function flow is described in the following state diagram.
Power down
T1
T7
Standby /Rem Standby/ Loc
T8
T14
T13
T2
Controlling /
T3 T4
Rem
T11
T10
T9
T5
Controlling /
T6
T12
Loc
The implemented actions executed at a change-over of states are shown in the following table.
Functions for tempering units 8 Operating note KS 50-1 TCont
Page 9
Operation
Transi tion
T1 Power down Standby/Rem Power on none - start-initialization
T2 Standby/Rem Controlling/
T3 Controlling/
T4 Controlling/
T5 Standby/Loc Controlling/
T6 Controlling/
T7 Standby/Rem Standby/Loc r/l-switch-
T8 Standby/Loc Standby/Rem r/l-switch-
T9 Controlling/
T10 Controlling/
T11 Controlling/
T12 Controlling/
T13 Standby/Rem Controlling/
T14 Controlling/
previous state
Rem
Rem
Loc
Rem
Loc
Rem
Loc
Rem
following state
Rem
Standby/Rem Control
Standby/Rem Control
Loc Standby/Loc local stop
Controlling/ Loc
Controlling/ Rem
Standby/Rem STL active remote as T4
Standby/Loc STL active local as T4
Rem
Controlling/ Rem
event condition action
- controller switched off
- remote mode
- no self-tuning
Control command (r)
command (k)
command (p)
local start signal
signal
over
over r/l-switch-
over r/l-switch-
over
identifier (R)
identifier (R)
remote - switch on pump
- switch on controller
- start self-tuning, if applicable
- control to set-point
remote - if X > SP2: cooling
- then switch off controller
- switch off pump
remote - if X > SP2: cooling
- then switch off controller
- witch off pump
local as T2
local as T4
local toggle to local
remote toggle to remote
local toggle to local
remote toggle to remote
remote -Acknowledge/delete the
existing alarms
- continue with T2
remote - Acknowledge/delete the
existing alarms
- continue with T2 (however without self-tuning)
Operating note KS 50-1 TCont 9 Functions for tempering units
Page 10
Operation
3.4 Functions for hot-runner
To operate with the protocol extension for hot-runners only a few additional inputs and outputs are needed.
In local operation a start-/stop functionality can be achieved by switching on and off the controller (for switching off put the set-point SP to OFF; for switching on enter a valid set-point). The start command corresponds to the control command (r) in the remote mode, the stop command to the control command (a).
The operation of the automatic controller can be switched over from remote
w
to local operation. Therefore the inputs di1 to di3 or the F-key are available.
Functions for hot-runner 10 Operating note KS 50-1 TCont
Page 11
Configuration extensions
4 Configuration extensions
The KS 50-1 TCont configuration values are extended by the following settings compared with the standard version
Protocol selection
q
.
In configuration menu othr, item Prot is available for definition of the protocol to be used.
othr
Name Range Description Default Prot Protocol selection for rear interface 1
0 MODBUS RTU 1 Protocol for tempering unit 2 Protocol for hot runner
q Output selection
Control of a pump can be selected via parameter PumPin the configuration menu for OUT.1, OUT.2, OUT.3, OUT.5 or OUT.6 . The default is an active OUT.3.
OUT.1, OUT.2, OUT.3, OUT.5, OUT.6
Name Range Description Default PuMP output pump 0
0 Not active 1 Active
q
Self-tuning start
For KS 50-1 TCont, the self-tuning behaviour during start-up was changed. Self-tuning is suppressed during power-on and called up only when starting control operation, if permitted (see OrEL).
Cntr
Name Range Description Default Strt Self-tuning start 0
0 Manual self-tuning start via the front panel, or when starting
control operation, if permitted.
1 Manual self-tuning start via the front panel, when starting
control operation, if permitted, and when detecting oscillation.
Operating note KS 50-1 TCont 11
Page 12
Configuration extensions
Input selection
q
For configuration menu LOGI additional menus for selecting typical digital inputs for tempering equipment are available.
LOGI
Name Range Description Default StB Source for safety temperature limiter signal 0
0 interface only 2 di1 switches 3 di2 switches 4 di3 switches
L.Sta Source for local function start 0
0 interface only 2 di1 switches 3 di2 switches 4 di3 switches
L.Sto Source for local function stop 0
0 interface only 2 di1 switches 3 di2 switches 4 di3 switches
SEnS Source for sensor operating mode (internal, external) 0
0 interface only 2 di1 switches 3 di2 switches 4 di3 switches
LEvL Source for level alarm 0
0 interface only 2 di1 switches 3 di2 switches 4 di3 switches
Flo Source for flow alarm 0
0 interface only 2 di1 switches 3 di2 switches 4 di3 switches
12 Operating note KS 50-1 TCont
Page 13
Parameter extensions
5 Parameter extensions
The KS 50-1 TCont parameters are extended by the following settings compared to the standard version.
Self-tuning switch-off
q
For Cntrcontrol and adaptation, parameter OrEl is used to permit self-tuning.
Cntr
Name Range Description Default OrEl Enable self-tuning at control operation start 0
0 Self-tuning permitted 1 Self-tuning not permitted
+
g
g
g
Hints on self-tuning
To meet the special requirements of fast control loops, e.g. with tempering units, the following information should be taken into account.
By setting the input filter for measurement input 1 ( Para / InP.1 / t.F1)toa filter time the input variable.
To improve the optimization result, the control range should be limited to the actual range. For this purpose, the min. and max. control range limit must be
matched, e.g. with a range of 20°C ... 150°C, value rnG.L = 20and rnG.H = 150 in Conf / Cntrmust be set.
The minimum cycle times t1 and t2 should be as low as possible. If a defined min. pulse duration must not be exceeded, changing during self-tuning can be prevented via configuration parameter Adt0 = 1. Please, note that the shortest pulses result from ¼ x t1 or¼xt2.
15 s, input variable fluctuations can be reduced, i.e. earlier settling of
Operating note KS 50-1 TCont 13
Page 14
Communication protocol
6 Communication protocol
KS50-1 TCont supports a simple protocol for injection moulders and extruders widely used in the plastics industry, which is used for connecting peripheral equipment and easy simple data exchange. This protocol, which is also called ”ARBURG” protocol, is designed according to the specification of the Arburg company.
g
This protocol is also supported by other machine manufacturers, e.g. Engel, Krauss-Maffei, etc. Any adaptation required can be done by changing the Baudrate or the parity.
Communication is according to the master / slave principle. KS 50-1 is always slave and polled for a message by the machine control system. Exchanging messages is done in half-duplex operation. The transmission parameters are adjustable via the front panel or via
BlueControl
Baudrate (bAud):
q
2400 ,
w
,
4800
w
9600,
w
19200 Bits/s
w
q Parity (PrtY):
,
Even
w
Odd,
w
None
w
.
q Address settings (Addr):
1to32
w
q
Byte format (fixed):
Number of data bits: 8
w
Number of stop bits: 1
w
Number of start bits: 1
w
The LSB is sent first.
Exchanging messages is subjected defined time conditions:
w
Character delay time T1:< 50 ms (The max. possible time which can pass between sending of the start bits of two successive bytes a message)
w
Acknowledgement delay time T2: <100ms (The max. possible time which can pass between the end of an inquiry sent by the master and reception of the first character of the slave reply)
14 Operating note KS 50-1 TCont
Page 15
Communication protocol
6.1 Data format
For transmission of block length and checksum, the hexadecimal format is used, whilst set-points and process values are transmitted in BCD format. For transmission, hexadecimal values are converted into ASCII. For simplification, values above 9 (A-F) are coded as 3Ah - 3Fh instead of 41h-46h (ASCII A-F).
6.2 Protocol structure
1 2 3 4 5 6 ... n n+1 n+2 Address Length
Identificaton Message Checksum
Byte 1: Device address of instruments 1 – 32, default 1
Master slave (range: B1h...D1h, B0h: reserved)
Slave master (range: 31h...51h, 30h: reserved)
Byte 2-4: Block length; each message contains 3 bytes, which include
(ASCII-coded) the binary number of bytes of the overall message (including checksum bytes). When receiving, the correct number of bytes is checked (range: 30h,30h,37h ... 3Fh,3Fh,3Fh)
Byte 5: Identification marks the message type,(range: 41h, 7Fh), see below
Byte 6-n: Information bytes, see below
Byte n+1,n+2: Checksum; every message is completed by 2 checksum bytes, which
are also counted in the block length bytes. The checksum bytes are the (ASCII-coded) 8 bit wide sum of all bytes of the message including block length bytes, checksum bytes not included. (range: 30h,30h...3Fh,3Fh)
g
Hexadecimal numbers are coded in form xxh, e.g. 41h means decimal 65 or ‘A’ in ASCII.
Operating note KS 50-1 TCont 15 Data format
Page 16
Protocol for tempering equipment
7 Protocol for tempering equipment
The protocol for tempering equipment is selected via parameter ProT =1.
7.1 Master telegram
The following telegrams sent by the master are supported by KS 50-1 TCont.
… 4 5 6 ... 12 13+14 ... Identification Message Check sum
Byte 5: Identification: 41h (‚A‘) and 52h (‚R‘) is supported.
Byte 6-9: Set-point (= SP) in 0,1 degrees Celsius
(3 digits before, 1 digit behind the decimal point); negative temperatures up to –99 degrees Celsius are possible (1st byte = 2Dh)
Range: -99,9 ... 999,9 °C Examples: 12,3 °C 30h 31h 32h 33h
-5,6 °C 2Dh 30h 35h 36h
Byte 10: Mould type = parameter set:
60h (`): is supported (self-tuning acc. to KS 50-1 TCont setting) 61h (a)...6Ah(j): commands are accepted; function as 60h
Byte 11: Control commands = operating mode:
61h (a), 6Bh (k): Switch-off function;
cooling down to return flow temperature, switch off feedback signals: (k) cooling, (p) switched off
70h (p): Switch-off function;
heating off, cooling down to return flow temperature, cooling off, pump off, switch off feedback signals: (k) cooling, (p) switched off
72h (r ): Switch-on function;
pump on, self-tuning on (if permitted), closed-loop control (normal operation) feedback signals: (r ) closed-loop control
73h (s): Switch-off function;
cooling down to return flow temperature, switch off feedback signals: (s) cooling, (p) switched off
Byte 12: Reserved, always 20h
Byte 13,14: Checksum
Master telegram 16 Operating note KS 50-1 TCont
Page 17
Protocol for tempering equipment
7.2 Slave telegram
With correctly received master telegram, the following reply telegram is sent by KS 50-1 TCont :
...4 5 6 ... 17 17+18 ... Identification Message Checksum
Byte 5: Identification: 41h (‚A‘) and 72h (‚r‘) are supported.
Byte 6-9:
Process value (= In.1)in0,1°C (3 digits before, 1 digit behind the decimal point);
Negative temperatures up to –99 °C are possible (1 Range: -99,9 ... 999,9 °C Examples: 12,3 °C 30h 31h 32h 33h
-5,6 °C 2Dh 30h 35h 36h
Byte 10-13: Duty cycle in%(=Ypid);
negative polarity sign for cooling (1 Range: -100 ... 100 %
Examples: 12 % 30h 30h 31h 32h
-34 % 2Dh 30h 33h 34h
Byte 14: Status bit feedback
Bit 0: controller mode 1: local 0: remote Bit 1: sensor mode 1: internal; (selection via SEns) Bit 2: inadmissible
set-point 1: fault Bit 3: (fixed) 0 Bit 4: 1: common alarm occurred
Bit 5, 6, 7: (fixed) 1, 1, 0
st
byte = 2Dh)
st
byte = 2Dh)
(see status alarms1)
Byte 15: Status alarms 1
Bit 0: sensor break 1: sensor break detected (FbF.1) Bit 1: heating defective 1: HCA error (HCA or Loop)
Bit 2: cooling defective 0, not supported. Bit 3: level alarm 0, (optionally adjustable
via LEvL )
Bit 4: flow alarm 0, (optionally adjustable via Flo) Bit 5: temperature >
safety limit 1: yes (optional Stb or Lim.1) Bit 6, 7: (fixed) 1, 0
Operating note KS 50-1 TCont 17 Slave telegram
Page 18
Protocol for tempering equipment
Byte 16: Status alarms 2
Bit 0: pump defective: 0; not supported Bit 1: phase failure: 0; not supported Bit 2: system error 1: input STL has responded
Bit 3, 4, 5, 6, 7: (fixed) 0, 0, 0, 1, 0
Byte 17: Status feedback
6Bh (k) switch-off: cooling down to return flow temperature 6Fh (o) during control operation: self-tuning busy 70h (p) switch-off: heating, cooling, pump switched off 72h (r ) control operation 73h (s) switch-off: cooling down to return flow temperature
Byte 18-19: Checksum
(Stb) or instrument error (E.1, E.2)
7.3 Error messages
With parity or framing errors, or with undefined characters, no reply is provided. If the checksum in the master telegram is faulty, or with an error in the message, KS 50-1 TCont sends a NAK message.
Not Acknowledge message structure:
1234567 Address Length Identification check sum
Byte 1: device address, e.g. 31h device no. 1 Byte 2-4: length (message is 7 bytes long: 30h, 30h, 37h) Byte 5: identification: 7Fh “Not Acknowledge” Byte 6-7: checksum
g
The message is also sent, if an invalid value was sent, because e.g. set-point changing via the interface is not possible during local mode.
Error messages 18 Operating note KS 50-1 TCont
Page 19
Protocol for tempering equipment
7.4 Alarm Reset
During remote mode, a pending STL alarm can be acknowledged and deleted via command ”Alarm Reset”..
Master telegram:
q
Structure of the alarm reset message:
...4 5 6 ... 12 13+14 ... Identification Message Checksum
Byte 5: Instead of identification 41h (‚A‘), identification 52h (‚R‘) Alarm Reset
is sent. Sending and handling of the remaining parameters are as in the standard protocol (see page 16)
Slave telegram
q
...4 5 6 ... 17 18+19 ... Identification Message Checksum
Byte 5: Identification 72h (‚r‘) instead of 41h (‚A‘) is sent. The remaining
functions are as in the standard protocol (see page 17 ).
Operating note KS 50-1 TCont 19 Alarm Reset
Page 20
Protocol for hot-runner systems
8 Protocol for hot-runner systems
Selecting the hot-runner protocol is done via setting ProT =2. With a hot-runner system, KS 50-1 TCont covers one channel.
8.1 Master telegram
The structure of the inquiry telegram is:
...4 5 6 ... 10 11+12 ... Identification Message Checksum
Byte 5: Identification: 41h (‚A‘) is supported.
Byte 6-9:
Set-point with command for closed-loop control: (= SP)in0,1 °C
(3 digits before, 1 digit behind the decimal point); Negative temperatures up to –99 °C are possible (1
Output value with command for positioning: in % (= Yman)
(3 digits before, 1 digit behind the decimal point)
Byte 10: Control commands
72h (r): closed-loop control (normal operation),
in °C; instrument in automatic mode; after control function switch-off, self-tuning is done, if permitted
73h (s): positioning,
in %; instrument in manual mode
61h (a): switch off channel
control function switched off
Byte 11-12: Checksum
st
byte = 2dh)
g
Special case: first message after control system start-up: system can read up to 25 channels per device address. Therefore, the message contains up to 25 times the set-point or output value, and the control command. However, a KS 50-1 TCont only uses the values for channel 1 from the message, and indicates in the reply that only one channel is provided.
Master telegram 20 Operating note KS 50-1 TCont
Page 21
Protocol for hot-runner systems
8.2 Slave telegram
The structure of the slave telegram is.
...4 5 6 ... 12 13+14 ... Identification Message Checksum
Byte 5: Identification: 41h (‚A‘) is supported.
Byte 6: Status device
Bit 0 1: power supply failure during operation
(e.g. heating current alarm) Bit 1, 2 (fixed) 0 0 Bit 3 1: other internal error, e.g. E.1, E.2 ... Bit 4, 5, 6, 7: (fixed)0110
Byte 7-10: Channel 1
Process value with command for closed-loop control: (= In.1)in0,1 degrees Celsius (3 digits before, 1 digit behind the decimal point); negative temperatures up to –99 degrees Celsius are possible (1st byte = 2Dh)
Output variable (3 digits before, 1 digit behind the decimal point)
with command for positioning: in % (= Ypid)
Byte 11: Channel 1 : status alarms 1
Bit 0 1: switched on ( C.Off =0) Bit 1 1: lowering on (with SP.2 =1) Bit 2 0: closed-loop control (automatic),
1: positioning (manual mode) Bit 3 (fixed) 0 Bit 4, 5, 6, 7 : (fixed)0110
Byte 12: Channel 1 : status alarms 2
Bit 0 1: lead break, e.g.: LooP =1 Bit 1 1: only undercurrent, e.g. HCA =1 Bit 2 1: sensor defective, e.g. FbF.1 , Sht.1 , POL.1 Bit 3 0 Bit 4, 5, 6, 7 : (fixed)0110
Byte 13-14: Checksum
Operating note KS 50-1 TCont 21 Slave telegram
Page 22
ORDERING INFORMATION
9 ORDERING INFORMATION
KS 50-1 TCont
Flat pin connectors Screw terminals
KS5 0 1 0
0 1
3
90..250V AC, 3 relays 0 24VAC / 18..30VDC, 3 relays 1
90..250V AC, 2 relays + mA/V/logic 2 24VAC / 18..30VDC, 2 relays + mA/V/logic 3
RS485/422 + U + di2/3 + OUT5/6
TTY + U + di2/3 + OUT5/6
T
T
1
3
Standard configuration 0 Configuration to specification 9 no manual 0 manual german D manual english E
46
Standard (CE certified) 0 UL-certified (on request) U
Accessories delivered with the controller Operating instructions (if selected in ordering code)
2 mounting clamps
w
operating note in 15 languages
w
Optional accessories and ordering information
Description Order no.
Current converter 50A AC 9404-407-50001 PC adapter, for connecting the BlueControl
software to the BluePort Standard rail adapter 9407-998-00061 Operating manual KS 50-1 (Standard) German 9499-040-62818 Operating manual KS 50-1 (Standard) English 9499-040-62811 Operation notes TCont
Operation notes TCont
German English
9407-998-00001
9499-040-64418 9499-040-64411
BlueControl (Engineering-Tool) Mini Download www.pma-online.de BlueControl (Engineering-Tool) Basic 9407-999-11001 BlueControl (Engineering-Tool) Expert 9407-999-11011
Slave telegram 22 Operating note KS 50-1 TCont
Page 23
TECHNICAL DATA
10 TECHNICAL DATA
INPUTS
SURVEY OF THE INPUTS
Input Used for:
INP1 x (process value) INP2 Heating current, ext. set-point di1 Operation disabled, switch-over to di2 di3
PROCESS VALUE INPUT INP1
Resolution: > 14 Bit Decimal point: 0 to 3 decimals Limiting frequency: adjustable 0.000...9999 s Scanning cycle: 100 ms Measured value
correction:
Thermocouples
Input impedance: 1 M Effect of source resistance:
second setpoint SP.2, external setpoint SP.E, fixed output value Y2, manual operation, controller off, disabling of manual key, reset of stored alarms, boost, parameters 1/2, safety temperature limiter, start/stop with local operation, sensor operating mode, level alarm, flow alarm
2-point or offset correction
1 V/
Cold junction compensation
Max. additional error
Sensor break monitoring
0.5 K
Sensor current: 1A Operating sense configurable
Resistance thermometer
Connection: 3-wire Lead resistance: max. 30 Ohm Input circuit monitor: Break and short circuit
Resistance measuring range
The BlueControl software can be used to match the input to the sensor KTY 11-6 (characteristic is stored in the controller).
Physical measuring range: 0...4500 Ohm Linearization segments: 16
Current and voltage signals
r Table 3 (page 24 )
Span start, end of span: anywhere within measuring
range Scaling: selectable -1999...9999 Linearization: 16 segments, adaptable
with BlueControl
Table 1 Thermocouple ranges
Thermocouple Range Accuracy Resolution (Ô) L Fe-CuNi (DIN) -100...900°C -148...1652°F ß 2K 0.1 K J Fe-CuNi -100...1200°C -148...2192°F ß 2K 0.1 K K NiCr-Ni -100...1350°C -148...2462°F ß 2K 0.2 K N Nicrosil/Nisil -100...1300°C -148...2372°F ß 2K 0.2 K S PtRh-Pt 10% 0...1760°C 32...3200°F ß 2K 0.2 K R PtRh-Pt 13% 0...1760°C 32...3200°F ß 2K 0.2 K
special -25 … 75 mV
0.1% 0.01%
Table 2 Resistance transducers
Type Sensor current Range Accuracy Resolution (Ô) Pt100 0,2mA -200...850°C -328...1562°F ß 1K 0.1K Pt1000 -200...850°C -328...1562°F ß 2K 0.1K Resistance
4500
ß 0.1% 0.051%
Operating note KS 50-1 TCont 23 Slave telegram
Page 24
TECHNICAL DATA
Table 3 Current and voltage
Range Input resistance Accuracy Resolution (Ô) 0-10 Volt
0-20 mA
~ 110 k 49 (voltage requirement ß 2.5 V)
Decimal point: adjustable Input circuit monitor:: 12.5% below span start
(2mA, 1V)
SUPPLEMENTARY INPUT INP2
Resolution: > 14 Bit Scanning cycle:
Accuracy:
Heating current measurement
via current transformer
Measuring range: 0...50mA AC Scaling: adjustable; -1999...0.000...9999 A
Current measurement range
Input resistance: Span: configurable within
Scaling: adjustable -1999...9999 Input circuit monitor: 12.5% below span start
100 ms better 0.1%
approx. 120
0 to 20mA
(4...20mA 2mA)
ß 0.1 % 0.6 mV ß 0.1 %
1.5 µA
TRANSMITTER SUPPLY UT
Output: 22 mA /≥18 V
If the universal output OUT3 is used there may be no external galvanic connection between measuring and output circuits!
OUTPUTS
SURVEY OF THE OUTPUTS
Output Used for
Control output for OUT1 OUT2 (relay)
OUT3
(relay or logic)
OUT3 (continuous)
OUT5 OUT6
(optocoupler)
heating/cooling or open/close,
limit contacts, alarms, end of
program, pump control *
as OUT1 and OUT2
Control output, process value,
set-point, control deviation,
transmitter supply 13 V / 22 mA
as OUT1 and OUT2
CONTROL INPUT DI1
Configurable as direct or invers switch or push-button! Connection of a potential-free contact suitable for switching „dry“ circuits.
Switched voltage: 2.5 V Switched current: 50µA
CONTROL INPUTS DI2, DI3
Configurable as switch or push-button ! Optocoupler input for active triggering
Nominal voltage: 24 V DC external Current sink (IEC 1131 Type 1) Logic “0” -3...5 V Logic “1” 15...30 V Current requirement: approx. 5 mA
* All logic signals can be OR-linked !
RELAY OUTPUTS OUT1, OUT2
Contacts: 2 NO contacts with
common connection
Max. contact rating: 500 VA, 250 VAC, 2A at
48...62 Hz, resistive load Min. contact rating: 6V, 1 mA DC Operating life (electric): 800,000 duty cycles with
max. rating
OUT3 USED AS RELAY OUTPUT
Contacts: Potential-free changeover
contact
Max. contact rating: 500 VA, 250 VAC, 2A at
48...62 Hz, resistive load Min. contact rating: 5V, 10 mA AC/DC Operating life (electric): 600,000 duty cycles with
max. rating
Slave telegram 24 Operating note KS50-1 TCont
Page 25
TECHNICAL DATA
Galvanic isolations:
Safety isolation Functional isolation
Process value input INP1
Mains supply Supplementary input INP2
Digital input di1
Relay outputs OUT1,2 RS485 /422 interface
TTY interface
Relay output OUT3 Digital inputs di2, 3
Universal output OUT3 Transmitter supply U OUT5, OUT6
Note: If the relays OUT1...OUT3 operate external contactors, these must be fitted with RC snubber circuits to manufacturer specifications to prevent excessive switch-off voltage peaks.
T
Error:
20 mV (0.2%)
OUT3 used as transmitter supply
Output: 22 mA /≥13 V
OUT3 used as logic output
Load≤500 Load > 500
Ω Ω
0/≤20 mA 0/> 13 V
OUTPUTS OUT5, OUT6
Galvanically isolated opto-coupler outputs. Grounded load: common positive control voltage. Output rating: 18...32 VDC; 70 mA Internal voltage drop: 1V with I Protective circuit: built-in against short circuit, overload, reversed polarity (free-wheel diode for relay loads).
max
POWER SUPPLY
Depending on version:
OUT3 AS UNIVERSAL OUTPUT
Galvanically isolated from the inputs.
Freely scalable Resolution: 11 bit Time constant of the D/A converter
90:
T Limiting frequency of the continuous
controller: > 2 Hz
Current output
0/4...20 mA, configurable. Signal range: 0...approx. 21.5mA Load :
500
Load effect: 0.02%/100 Resolution: Error:
≤22µ ≤40µ
Voltage output
0/2...10V configurable Signal range: 0...11 V Load:
2k Load effect: none Resolution:
11 mV (0.1%)
50 ms
A (0.1%) A (0.2%)
AC SUPPLY
Voltage: 90...260 V AC Frequency: 48...62 Hz Power consumption: approx. 7.0 VA
UNIVERSAL SUPPLY 24 V UC
AC voltage: 20,4...26,4 V AC Frequency: 48...62 Hz DC voltage: 18...31 V DC Power consumption: approx. 7 VA (W)
BEHAVIOUR WITH POWER FAILURE
Configuration, parameters, and adjusted set-points, control mode: non-volatile storage in EEPROM
BLUEPORTFRONT INTERFACE
Connection of PC via PC adapter (see
„Accessories“). The BlueControl used to configure, set parameters, and operate the KS 50-1 TCont.
software is
Operating note KS 50-1 TCont 25 Slave telegram
Page 26
TECHNICAL DATA
BUS INTERFACE
Galvanically isolated. Screened cables must be used.
RS 485 / 422
Physical: RS 485/422 Transmission speed:
Parity:
2400, 4800, 9600, 19.200 Bit/s
Even, odd, none Address range: 1...32 Number of
32 controllers/segm:
TTY (20 mA CURRENT LOOP)
Physical: 20 mA current loop Transmission speed:
Parity:
2400, 4800, 9600, 19.200 Bit/s
Even, odd, none Address range: 1...32 Voltage drop:
2.2V
Protocols
MODBUS RTU, protocol for tempering units*, protocol for hot runner systems* * according to Arburg specification
ENVIRONMENTAL CONDITIONS
Protection modes
Front panel: IP 65 Housing: IP 20 Terminals: IP 00
Frequency: 10...150 Hz Unit in operation: 1g or 0.075 mm Unit not in operation: 2g or 0.15 mm
Shock test Ea (DIN IEC 68-2-27)
Shock: 15g Duration: 11ms
Electromagnetic compatibility
Complies with EN 61 326-1
Meets the immunity requirements for
w
continuous, unattended operation Meets the radiation requirements of Class B
w
for rural areas In case of surge interference, increased
w
measurement errors must be expected
GENERAL
Housing
Material: Makrolon 9415
flame-retardant
Flammability class:: UL 94 VO, self-extinguishing
Plug-in module, inserted from the front
Safety tests
Complies with EN 61010-1 (VDE 0411-1): Over voltage category II Contamination class 2 Working voltage range 300 V Protection class II
Certifications
Permissible temperatures
UL certification (applied for)
For specified
0...60°C
accuracy: Warm-up time:
< 15 minutes Temperature effect:: < 100ppm/K For operation: -20...65°C
Electrical connections
w
Flat-pin connectors 1 x 6.3 mm or 2 x 2.8 mm to DIN 46 244
w
Screw terminals
Mounting
For storage: -40...70°C
Panel mounting with two fixing clamps at
Humidity
75% yearly average, no condensation
top/bottom or left/right Close mounting possible
Mounting position: not critical
Shock and vibration
Vibration testFc (DIN 68-2-6)
Weight: 0.27kg
Slave telegram 26 Operating note KS50-1 TCont
Page 27

Index

11 Index
Index
Address settings ............14
Alarm Reset ..............19
ARBURG protocol ...........3
Baudrate ................14
Bus interface .............4,26
Byte format ...............14
Communication protocol .....14-15
Connection of the TTY bus interface . . 4
Current and voltage signals ......23
Data format ...............15
Definitions ................3
Electrical connections ........4,26
Error messages .............18
flow alarm ................7
Front interface .............25
Front view ................6
Frontansicht ...............6
Galvanic isolations ...........25
Heating current ............24
hot-runner ...............10
Housing.................26
input INP2 ...............24
Input selection .............12
INPUTS ................23
Introduction ...............3
level alarm ................7
local...................17
local operation .............10
Master telegram ............20
Master telegram ............16
ORDERING INFORMATION.....22
Output selection ............11
OUTPUTS ...............24
Parity ..................14
POWER SUPPLY ...........25
Protocol for hot-runner systems . . 20 - 21 Protocol for tempering equipment. 16 - 19
Protocol selection............11
Protocol structure............15
Protocols ................26
pump ...................7
Relay outputs .............24
remote .................17
Resistance thermometer ........23
return flow temperature .........7
safety temperature limiter ........7
Self-tuning ...............11
Self-tuning switch-off .........13
sensor mode ...............7
Signal connection types .........8
Slave telegram .........17,21 - 26
state diagram...............8
TECHNICAL DATA .......23-26
Thermocouples ............23
Transmitter supply ...........24
27 Operating note KS 50-1 TCont
Page 28
Subject to alterations without notice © PMA Prozeß- und Maschinen-Automation GmbH Änderungen vorbehalten P.O.B. 310 229, D-34058 Kassel, Germany Sours réserve de toutes modifications Printed in Germany 9499-040-64418 (0307)
A5 auf A6 gefaltet, 2-fach geheftet, SW-Druck, Normalpapier 80g weiß
Loading...