Please remember that Part A of the device manual also belongs to the description
of the CP. Among other things, it contains explanations of the safety notices and
general information that applies to all S7 CPs for Industrial Ethernet.
You will find the references in this Part B of the manual /.../ in the Appendix of the
general Part A of the manual.
The following version of the manual Part A of the manual belongs to this version of
Part B: Release 01/2007
Contents
You can download the general Part from the Internet:
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
1Properties / Services
Application
The CP 343−1 Lean communications processor is designed for operation in a
SIMATIC S7-300 programmable logic controller. It allows attachment of the
S7−300 to Industrial Ethernet and supports PROFINET IO.
A 2-port switch with autocrossing, autonegotiation and autosensing was integrated
in the CP for simple integration in a line or for attaching a further Ethernet device.
Services
The CP supports the following communication services:
SPROFINET IO device
Integration of the SIMATIC S7−300 programmable controller over the CP as
intelligent PROFINET IO device.
1Properties / Services
SS7 communication and PG/OP communication
− PG functions (including routing)
− Operator control and monitoring functions (HMI)
− Server for data exchange on S7 connections configured at one end only
without communication blocks on the S7-300 / C7-300 station
SS5 compatible communication with
− SEND/RECEIVE interface over ISO-on-TCP, TCP and UDP connections
− Multicast over UDP connection
The multicast mode is made possible by selecting a suitable IP address
when configuring connections.
− FETCH/WRITE services (server; corresponding to S5 protocol) via
ISO-on-TCP connections and TCP connections;
The addressing mode can be configured for FETCH/WRITE access as the
S7 or S5 addressing mode.
− LOCK/UNLOCK with FETCH/WRITE services;
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
B3L−5
1Properties / Services
STime-of-day synchronization over Industrial Ethernet using the following
configurable modes:
− SIMATIC mode
The CP receives MMS time frames and synchronizes its local time and the
time of the CPU (accuracy approx. +/− 1 second);
or
− NTP mode (NTP: Network Time Protocol)
The CP sends time-of-day queries at regular intervals to an NTP server and
synchronizes its local time of day and the time of the CPU (accuracy approx.
+/− 1 second).
STime of day for the diagnostic buffer
If a time master exists (using the NTP or SIMATIC mode), the time for the
CP-internal diagnostic buffer is synchronized over the LAN (accuracy approx.
+/− 10 ms)
SAddressing using a factory-set MAC address
The CP can be reached over the default MAC address to allow an IP address to
be assigned.
SSNMP Agent
The CP supports data queries over SNMP in version V1 (Simple NetworkManagement Protocol) according to the MIB II and LLDP MIB standard.
You will find more information on MIB in the manual “Commissioning PC
Stations” on the SIMATIC NET Manual Collection or at the following
SIMATIC NET Internet page:
You can configure how and with which method the CP is assigned the IP
address, the subnet mask and the address of a default router.
It is also possible, as an alternative, to assign the connection configuration to
the CP using STEP 7 or using a block interface in the user program (FB55:
IP_CONFIG) (see /Part A/).
SWeb diagnostics
With the aid of Web diagnostics, you can read out the diagnostic data from a
station connected over the CP to a PG/PC with an Internet browser.
B3L−6
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
1Properties / Services
Configuration
It is possible to download the configuration data to the CP over MPI or
LAN/Industrial Ethernet. You require STEP 7 with NCM S7 for Industrial Ethernet
(NCM IE) with the following version:
Table 1-1
Version STEP 7 / NCM IEFunctions of the CP
V5.2 or higherThe range of functions of the CP 343−1 Lean (CX00) can be
configured.
V5.4 or higherRequirement for configuring the full functionality of the
CP 343−1 Lean (CX10 with firmware V1.0) including PROFINET
IO.
V5.4 Service Pack 2 *)Requirement for configuring the full functionality of the
CP 343−1 Lean (CX10 with firmware V2.0) including Web
diagnostics.
*) To use the CP with V5.4 Service Pack 1, you will need to install Hotfix 2, the corresponding hardware
update and a block setup. You will find more information at the following Internet page:
http://www4.ad.siemens.de/WW/news/en/24463868
Programming − Using Blocks
For some communications services, there are pre-programmed blocks (FCs/FBs)
available as the interface in your STEP 7 user program.
You will find a detailed description of these blocks in the NCM S7 for Ethernet
manuals.
Notice
We recommend that you always use the latest block versions for all module types.
You will find information on the latest block version and links to download the
current blocks in our Customer Support area on the Internet:
http://www4.ad.siemens.de/WW/news/en/8797900
If you are using older block types, this recommendation only applies if you also
have the latest firmware version.
You will find further information and Internet addresses in the Preface of the
General Part of this manual.
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
B3L−7
2Requirements for Use
2Requirements for Use
General Operation
The CP can be operated in the following device families:
SS7−300 stations with the CPU types
− Standard
− Compact
− Modular
SC7 control systems in C7 packaging system
The following tables show the devices with which the CP can be operated with this
range of functions:
Notice
The tables list the CPUs and devices approved at the time of printing this manual.
S7-300 CPUs or C7 or C7 control systems approved later and not listed in the
table also support the range of functions described here.
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
B3L−9
2Requirements for Use
Table 2-2Use of the CP in C7 Control Systems
C7
C7−6136ES7 613−1CA01−0AE03
6ES7 613−1CA02−0AE3
C7−633 DP6ES7 633−2BF02−0AE03
C7−635 Keys6ES7 635−2EC01−0AE3
6ES7 635−2EC02−0AE3
C7−635 Touch6ES7 635−2EB01−0AE03
6ES7 635−2EB02−0AE3
C7−636 Keys6ES7 636−2EC00−0AE03
6ES7 636−2EC00−0AE3
C7−636 Touch6ES7 636−2EB00−0AE3
Order Number
B3L−10
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
3Installation and Commissioning
3Installation and Commissioning
3.1Procedure / Steps
StepExplanation / Meaning
1. Install the CP on the S7 standard rail.
2. Establish the connection via the enclosed bus
connector to the backplane bus.
Note
The CP cannot be used in an extension rack that is connected via the IM 365! Reason: The required
communication bus is not connected to the extension rack via the IM 365.
3. Connect the CP to the power supply.Follow the steps as described in detail in /1/ when
Slots 4 to 11 are permitted for the CP in racks 0 to 3
(connected by IM 360/361).
Proceed as in the sections dealing with setup and
wiring, described in detail in /1/.
wiring between the power supply and the CPU.
Notes
SThe CPU, CP and IM (if one exists) must be connected to the same power supply.
SOnly wire up the S7-300 / C7-300 with the power switched off!
4. Attach the CP to Industrial Ethernet.
5. The remaining steps in commissioning involve
downloading the configuration data.
To download the configuration, you can connect
the PG as follows:
Svia MPI
Svia Industrial Ethernet
For further details, refer to the general Part A of
this manual:
− addressing the first time (IP address
assignment / node initialization);
− downloading the defined configuration
The PG/PC requires a LAN attachment, for
example via a CP 1613 or CP 1411 and must have
the necessary software (for example the S7-1613
package or SOFTNET IE). The TCP/IP protocol
must be installed. The protocol used must then be
applied to the S7ONLINE access point.
6. User diagnostics for commissioning and to
analyze problems.
The following options are available:
SThe LED displays on the CP
SHardware diagnostics and troubleshooting with
STEP 7
SCommunication diagnostics with STEP 7 / NCM
Diagnostics
SStandard information using HW Config
SWeb diagnostics
SIf applicable, evaluation of the alarm block
FB54 in the user program
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
B3L−11
3Installation and Commissioning
Slider for setting
the chassis
ground contact
Figure 3-1Connectors of a CP 343−1 Lean with the Front Panel Open
Ground/Chassis Ground Concept
Notice
Please note the instructions regarding the grounding and chassis ground concept
in the SIMATIC S7 installation guides; see “SIMATIC S7 Programmable Controller
S7−300 − Installation and Hardware: Installation Manual” /1/.
Behind the hinged panel on the left of the device, you will see a slider with which
you can connect or disconnect the chassis ground of the 24 V power supply with
reference ground.
SSlider pushed in: chassis and reference ground connected (note: the slider
must be felt to lock in place).
SSlider pulled out: No connection between chassis and reference ground.
Attachment to Industrial
Ethernet:
2 x 8-pin RJ-45 jack
B3L−12
When shipped: Slider pushed in
Use a screwdriver to set the slider.
Note
An Ethernet cable can also be inserted and removed with the power supply on.
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
3Installation and Commissioning
Note
The hinged front panel must be kept closed during operation.
The module must be installed so that its upper and lower ventilation slits are not
covered, allowing adequate ventilation.
Warning
!
When used under hazardous conditions (zone 2), the devices must be installed in
an enclosure.
To comply with ATEX100a (EN 60079−15), this enclosure must meet the
requirements of at least IP54 in compliance with EN 60529.
WARNING − EXPLOSION HAZARD: DO NOT DISCONNECT EQUIPMENT
WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.
Warning
!
The device is designed for operation with safety extra-low voltage (SELV). This
means that only safety extra-low voltages (SELV) complying with
IEC950/EN60950/ VDE0805 may be connected to the power supply terminals.
The power unit for supplying the device must comply with NEC Class 2 as
described by the National Electrical Code(r) (ANSI/NFPA 70).
The power of all connected power units in total must correspond to a limited power
source (LPS).
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
B3L−13
4Displays
4Displays
The display on the front panel consists of 8 LEDs that indicate the operating mode
and the communication status.
Front panel:
The LEDs have the following meaning:
SSF:Group error
SBF:Bus fault PROFINET IO
SDCV5:DC 5 V power supply via the backplane bus (green = OK)
SRX/TX: Acyclic data exchange, for example Send/Receive
(not relevant for PROFINET IO data)
SRUN:RUN mode
SSTOP:STOP mode
SP1 / P2: Link status of Ethernet port 1 / port 2
SF
BF
DC5V
RX/TX
RUN
STOP
P1
P2
B3L−14
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
LEDs for displaying the mode
The different combinations of the LEDs on the front panel indicate the status:
4Displays
SF(red)BF (red)RUN
(green)
STOP
(yellow)
CP Operating Mode
SStarting up after power “ON”
or
−
−−−SNo LAN cable plugged in
SStopped (STOP)with errors
In this state, the CPU or intelligent
modules in the rack remain accessible
using PG functions.
Starting up (STOP->RUN)
Running (RUN)
Stopping (RUN->STOP)
Stopped (STOP)
In the STOP mode configuring and performing
diagnostics on the CP remain possible.
or
SDuplicate IP address detected
−
−
−The CP is configured as a PROFINET IO
device; there is no data exchange with the
PROFINET IO controller
Module fault / system error
Downloading firmware.
Firmware was successfully downloaded.
Firmware could not be downloaded.
Legend:(colored) onoff(colored) flashing“−” any
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
B3L−15
4Displays
LEDs for displaying the CP communication status
In addition to the LEDs that signal the CP state, the following LEDs provide
information about the status of the CP interface to Industrial Ethernet.
Table 4-1
LED
RX/TX (green)The CP is sending/receiving over Industrial
P1 / P2
(green / yellow)
P1 / P2
(green / yellow)
Legend:(colored) onoff(colored) flashing“−” any
DisplayMeaning
Ethernet
Note:
Sending / receiving over PROFINET IO is
not signaled here.
Port has no connection to
Industrial Ethernet.
greenExisting connection over port to
Industrial Ethernet (LINK status).
green /
yellow
yellowContinuous data transfer at the port over
LED flashes yellow (constant light green):
Port sending/receiving over
Industrial Ethernet or PROFINET IO.
Note:
All received / sent frames are signaled for
each specific port including those simply
forwarded by the switch.
Industrial Ethernet (for example
PROFINET IO).
B3L−16
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
5Performance Data
5Performance Data
5.1Number of Possible Connections over Ethernet
Table 5-1
CharacteristicExplanation / Values
Permitted number of simultaneous connections in
total over Industrial Ethernet