Siemens CP-2ER Operation, Installation, And Maintenance Manual

Page 1
Fire Safety
Model CP-2ER Control Panel
Operation, Installation, and Maintenance Manual
POWER
ON BATTERY WHEN FLASHING
TROUBLE
SUPERVISORY
ALARM
ZONE 1
ALARM
ZONE 2
DISCHARGE
ALARM SILENCED
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-093523-7
Technical Manuals Online! - http://www.tech-man.com
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN
Page 2
Table of Contents
INTRODUCTION.................................................................................................. 1
OPERATION ........................................................................................................ 2
CONNECTION DIAGRAM ................................................................................ 4-5
INSTALLATION AND WIRING............................................................................. 7
POWER LIMITED WIRING .................................................................................. 8
MAINTENANCE AND TESTING .......................................................................... 9
TROUBLESHOOTING THE SYSTEM ................................................................. 9
Technical Manuals Online! - http://www.tech-man.com
Page 3
FACTORY SET POTS–
OPTION DIPSWITCHES
DO NOT RESET
PREDISCHARGE/DISCHARGE SELECT DIPSWITCH
MANUAL DISCHARGE SELECT DIPSWITCH
ABORT STATION OPERATION SELECTION DIPSWITCH
BATTERY CHARGER OPERATING INDICATOR
ZONE 1 AND ZONE 2 TROUBLE INDICATORS
LOCAL AUDIBLE BUZZER
DISCHARGE DELAY SELECTION SWITCH S101
SPECIFIC SUPERVISORY TROUBLE INDICATORS
INDICATORS ON FRONT COVER (VISIBLE WITH DOOR CLOSED)
SERVICE SELECTION JUMPER PLUG P72 (LOCAL) OR P12 (RELEASE)
Figure 1
Model CP-2ER
FACTORY SET POT– DO NOT RESET
BATTERY FAULT INDICATOR
MANUAL SWITCHES GROUND FAULT
INDICATOR FUSES
BATTERY PLUG
POWER SUPPLY
PR-24 MODULE
BATTERIES
2A AC INPUT CIRCUITBREAKER
PR-24 POWER PLUG
GROUND DISCONNECT PLUG
INTRODUCTION
The SIEMENS Model CP-2ER Control Panel is a two-zone local control unit which meets the requirements of NFPA 72 Local for a two-zone releasing device panel approved in accordance with NFPA 12A, 13, and 2001 for cross zone protection. The two initiating zones, Zone 1 and Zone 2, may be connected for either Class A or Class B operation. The two zones are arranged so that both must be acti­vated in order to discharge the agent automatically into the protected area.
As shipped from the factory, the CP-2ER is set to meet the NFPA 72 requirements; that is, an alarm in either of the two initiating zones causes the general alarm to sound. Once the general alarm is silenced, an alarm in the other initiat­ing zone causes the general alarm to sound again.
To set the CP-2ER to meet NFPA 12A, 13, or 2001 require­ments for a releasing panel, place the SERVICE SELEC- TION plug in position P12 (Release). With the plug in this position, both a general alarm associated with the first ini­tiating zone actuation and a predischarge/discharge alarm with actuation of the second initiating zone will sound. The
position of the plug in P12 voids the NFPA 72 Local listing since the general alarm circuit silences upon actuation of the second initiating zone.
The Control Panel provides for the external connection of a supervised manual discharge station for agent release, as well as for several other supervised input and output func­tions. Essentially, every supervised feature has its own sepa­rate fault indicator for ease of troubleshooting the system, should a fault occur.
Displayed through the front cover are the usual visual indi­cators for power, system alarm, and system trouble, as well as several additional specific function indicators. Within the Control Panel are a fire alarm RESET/LAMP TEST switch, an ALARM SILENCE switch, a SUPERVISORY SILENCE switch, a TROUBLE SILENCE switch, and a RELEASE DISCONNECT switch. The separate visual fault indicators are displayed within the panel for all supervised features.
Isolated relay contacts are provided for: System alarm ­DPDT, System trouble - SPDT, Predischarge/discharge ­SPDT and SPST (normally open). For information regarding functional options. refer to the OPERATION section.
Technical Manuals Online! - http://www.tech-man.com
1
Page 4
OPERATION
External Output Loading
It is critical that sufficient battery energy be provided for either 24 hour or 60 hour system operation. All circuit loading is fixed except for the following (See the CON- NECTION DIAGRAM on pages 4-5, also).
1. Class B Supervised General Alarm Audibles TB2, terminals 1 and 2 Rated 24 VDC, 1.5A max
2. Class B Supervised Discharge Audibles TB2, terminals 3 and 4 Rated 24 VDC, 1.5A max
3. Class B Supervised Discharge Circuit TB2, terminals 5 and 6 Rated 24 VDC, 2.0A max
The table below provides a listing of the various visual indi­cators provided within the CP-2ER Control Panel unit. The labels appearing on the unit are printed in capital letters.
SERVICE SELECTION Jumper
The SERVICE SELECTION jumper is provided so that a CP-2ER system can be operated under NFPA 72 Local or NFPA 12A, 13 or 2001.
For NFPA 72 Local Service:
 Do not place SERVICE SELECTION plug in P12 po-
sition. NOTE: Plug may be either in P72 or not used
for 72 Local service.
 Connect 5.6K ohm, 1/2W, end-of-line resistor across
TB2, terminals 3 and 4.
 Connect 1K ohm, 1W, end-of-line resistor across TB2,
terminals 5 and 6.
Initiating Circuit and Local Protective Signaling Panel Operation (Selection Plug Placed on P72).
A single zone alarm results in the following:
1. An alarm lock-in of that zone.
2. A visual alarm condition of that zone.
3. A general alarm condition of the panel which includes: a. Change of state of fire alarm relay contacts (TB3,
terminals 4 through 9).
b. General alarm audible circuit actuated.
Since neither the discharge audible circuit nor the dis­charge device circuit is used, an initiation of the second zone results in only a visual display indicating that the second zone has alarmed.
VISUAL INDICATORS COLOR
Visual Indicators Externally Visible
POWER  Steady on indicates main power is normal. Green
 Flashing on/off indicates panel is operating from the backup battery supply.  System TROUBLE  Indicates a general system trouble. Yellow  System SUPERVISORY  Indicates a general system supervisory Yellow  ALARM ZONE 1 Red  ALARM ZONE 2 Red  Predischarge/DISCHARGE alarm operates in flashing mode upon cross zone Red
(Zone 1 and Zone 2) activation condition until preselected time delay has expired.
Operates in steady mode upon, and following, actual discharge.  Audible ALARM SILENCED indicates that either the general alarm audible Red device or predischarge/discharge audible device circuit has been silenced.
Visual Indicators Internally Visible (Must open panel door to be viewed)
BATTERY FAULT indicates high/low (or open) battery fault condition or open battery circuit. YellowGROUND FAULT Yellow
Abort station circuit fault (ABORT TROUBLE) YellowManual release station circuit fault (MANUAL DISCHARGE TROUBLE) YellowRelease circuit fault (AGENT DISCHARGE TROUBLE) YellowZone 1 initiation circuit fault (ZONE 1 TROUBLE) YellowZone 2 initiation circuit fault (ZONE 2 TROUBLE) Yellow  General alarm audible circuit fault (GENERAL ALARM TROUBLE) YellowPredischarge/discharge audible alarm circuit fault (PREDISCHARGE TROUBLE) Yellow
CYLINDER PRESSURE TROUBLE Yellow  CYLINDER PRESSURE SUPERVISORY Yellow  BATTERY CHARGER Charging current operation Light Red
Internally Operated Switch Functions
 System RESET/LAMP TEST switch (momentary)  Audible ALARM SILENCE switch (momentary)  System audible SUPERVISORY SILENCE switch System audible TROUBLE SILENCE switch  RELEASE DISCONNECT switch
Technical Manuals Online! - http://www.tech-man.com
2
Page 5
If the ALARM SILENCE switch has been operated after initiation of the first zone alarm, a second zone alarm re­sults in reactivating the general alarm audible circuit, which may then be silenced again.
For NFPA 12A, 13, or 2001 Service:
 Place SERVICE SELECTION plug in P12.
Connect TB2, terminals 5 and 6 as shown in the Con­nection Diagram. An open circuit will cause a trouble condition.
Initiating Circuit and Agent Release Operation (Selec­tion Plug Placed on P12). The two initiating zones pro­vided are arranged so that both zones (cross zoning) must be alarmed before the agent release discharge sequence begins.
A single zone alarm condition results in:
1. Alarm lock-in of that zone.
2. Visual alarm indication of that zone.
3. General alarm condition of panel which includes: a. Change of state of fire alarm relay contacts. b. General alarm audible circuit activated.
Upon initiation of both zones, the agent discharge delay sequence begins. The discharge delay period may be preselected by rotating the Discharge Delay Selection switch S101 to one of the following time-in periods: 0, 5, 10, 15, 20, 25, 30, 35, 40, or 45 second delay. (Refer to Option No. 1 below.)
As the discharge delay period begins (both zones alarmed), and the general alarm audible circuit is de-energized, the predischarge relay contacts (TB3, terminals 10 through
14) change state (See Option No. 4). The predischarge au­dible circuit, along with its associated visual indicator, is cycled at a 2 Hz rate with a 50% duty cycle during the selected discharge delay period. At the conclusion of the discharge delay period, the agent release circuit is ener­gized for approximately 1 minute, while the discharge au­dible is energized in a steady-on condition until either it is silenced or the panel is reset to a non-alarm condition.
MANUAL SWITCHES
System RESET/LAMP TEST
Upon initiation of either Zone 1 or Zone 2 and/or op­eration of the manual DISCHARGE PRESSURE switch, the Control Panel locks into an alarm condi­tion. This alarm condition may only be reset by opera­tion of the internal momentary RESET/LAMP TEST switch. While this switch is held in the Reset position, all indicating lamps, except POWER and charge cur- rent operation BATTERY CHARGER are lit. It should be noted that the Control Panel cannot be reset while the manual DISCHARGE PRESSURE switch is in the closed position.
ALARM SILENCE
The internal momentary ALARM SILENCE switch is operated to silence an existing energized audible alarm circuit. The general alarm audible circuit may be op­tionally silenced by momentary operation of the ALARM SILENCE switch at any time after it has become en­ergized. The predischarge/discharge audible alarm circuit may be optionally silenced by momentary op­eration of the same ALARM SILENCE switch, but only after the selected predischarge period has timed out.
Silencing the general alarm circuit prior to operation of the predischarge audible circuit does not inhibit the predischarge circuit audible from its normal operation. To silence the discharge audible circuit in this case requires a second ALARM SILENCE switch activa­tion. After silencing either the general alarm circuit and/ or the discharge audible circuit, both remain silenced until the panel is reset (if alarm condition cleared). Silence operation of either alarm circuit does not change the state of the general alarm relay contacts. Operation of the ALARM SILENCE switch, when the panel is not in an alarm state, has no effect.
SUPERVISORY SILENCE
Operation of the SUPERVISORY SILENCE switch to its Silence position results in silencing the internal su­pervisory buzzer when the panel is in a supervisory condition, as indicated by the supervisory light on the front panel. Operation of the SUPERVISORY SI- LENCE switch to its Silence position when a panel supervisory condition does not exist causes the su­pervisory buzzer to operate as it does when the SU- PERVISORY SILENCE switch is in Silence position and the panel supervisory condition is cleared to a normal supervisory condition.
TROUBLE SILENCE
Operation of the TROUBLE SILENCE switch to its Silence position results in silencing the internal trouble buzzer when the panel is in a trouble condition, as indicated by the trouble light on the front panel. Op­eration of the TROUBLE SILENCE switch to its Si­lence position when a panel trouble condition does not exist causes the trouble buzzer to operate as it does when the TROUBLE SILENCE switch is in Si­lence position and the panel trouble condition is cleared to a normal supervisory condition.
RELEASE DISCONNECT
The RELEASE DISCONNECT switch is a normally closed single pole switch in series with the release circuit output. Moving the switch from its normally closed position during a non-discharge or circuit activation condition causes an open circuit trouble indication of the release circuit. This prevents the associated dis­charge devices from activating.
Technical Manuals Online! - http://www.tech-man.com
3
Page 6
SIEMENS Model CP-2ER CONNECTION DIAGRAM
Approved for Manual or Automatic alarm for the following categories: Local control unit in accordance with NFPA 72 Local; suitable for NFPA connection; suitable also for releasing device service in accordance with NFPA 12A, 13, and 2001. Refer to Note 3e.
DISCHARGE
CIRCUIT RATED:
24VDC, SUPV. 1.4mA
ALARM 2.0A MAX
N O CYLINDER SUPERVISORY SWITCH, P/N 500-878709
2.2K
1/2W EOL
N C ABORT STATION MODEL AW-1
MANUAL DISCHARGE
5.6K
1/2W EOL
MANUAL DISCHARGE PRESSURE SWITCH, P/N 500-486536
STATION MODEL MH-51
W,
-
W
1.78K
1/2W EOL
P/N 140-016124
+
CLASS B CONNECTION
NOTE: Both zones 1 and 2 may be connected as either Class A or Class B.
-
+
CLASS A CONNECTION
W,
RATED 15 VDC
3.4mA SUPV
RATED 15 VDC
1.5mA SUPV
RATED 15 VDC
1.8mA SUPV
ZONE 2 INITIATING CIRCUIT RATED 17.6 - 22.5 VDC
SUPV 12mA ALARM 120mA
ZONE 1 INITIATING CIRCUIT RATED 17.6 - 22.5 VDC
SUPV 12mA ALARM 120mA
TB1
14
13
12
11
10
9
8
7
6
5
4
3
2
1
TB2
+
6
-
5
+
4
-
3
DISCHARGE AUDIBLES
2
-
+
1
GENERAL ALARM AUDIBLES
INPUT: 120V, 50/60 HZ, 2A MAX
NEUTRAL
DISCHARGE DEVICE: REFER TO AGENT DISCHARGE DEVICES TABLE
IF THIS CIRCUIT IS NOT USED, CONNECT A 1K, 1W RESISTOR ACROSS THE TERMINALS
24 VDC LISTED POLARIZED AUDIBLE DEVICES
5.6K , 1/2W EOL
W
RESISTORS
AUDIBLE CIRCUITS 19 VDC (MIN), 28 VDC (MAX)
SUPV 1.2mA ALARM 1.5A MAX
P1
POWER SUPPLY
1
2
3
P/N 140-016124
TYPICAL CONNECTION TO FIRE ALARM SYSTEM
(When CP-2ER panels are arranged for NFPA Releasing Service)
CP-2ER
TO LISTED
FIRE ALARM
CONTROL
PAN EL
TROUBLE CONTACTS MUST BE CONNECTED AS SHOWN SO AS NOT TO INTERFERE WITH AN ALARM CONDITION.
ALARM ALARM
TROUBLE TROUBLE
1 15 53 36 6
Technical Manuals Online! - http://www.tech-man.com
1.78K
1/2W EOL
W
CP-2ER
EOL DEVICE
BATTERIES 24 VDC
Charging Current Normal: 300mA, 24 VDC Charging Current Max: 560mA Load Current Max: 3.3A
24 HR: P/N 175-084476 (5 AH) 60 HR: P/N 175-084477 (10 AH)
4
P2
4.0A with self­interrupting solenoid, P/N 500-890181
Page 7
TB3
15
DO NOT USE
14
5K1
5K2
13
12
11
PREDISCHARGE/DISCHARGE OPERATED CONTACTS RATED 120 VAC/24 VDC, 3A SEE NOTE BELOW
10
9
3K2
3K1
8
7
6
GENERAL ALARM OPERATED CONTACTS RATED 120 VAC/24 VDC, 3A SEE NOTE BELOW
5
4
4K2
NOTE:
3
2
The contacts are shown in supervisory condition
TROUBLE OPERATED CONTACTS RATED 120 VAC/24 VDC, 3A SEE NOTE BELOW
1
(5K and 3K relay de-energized; 4K relay energized).
noitacilppA
31APFN
noitcaerP(
)eguleD
A21APFN42-VSHA/NCDV42enOsmho8
)nolaH(
1002APFNA/NPXE42-SHCECDV42enOsmho01
)002-MF(
.sdionelos
snemeiS
ledoM
A/NrennikS
A/N
A/N
A/N
42-3VSH
42-C-SSPC
42-C-3SSPC
A/N
6-CEYPC
21-CEYPC
42-CEYPC
A/N A/N A/N
rodneV
rebmuNtraP
52XBL2VL
OCSA
701A012BT
OCSA
701A0128R
OCSA
701A0128
42-SHCE
OCSA
*6-235812VH
ETITPANS
ETITPANS
**5F4A-BN2-A3282N/P
6F2A-60X-A3282N/P .dettimreptonsielbatehtnidebircsedtondionelosynA
.desuebtsumsdionelosV6detcennocseiresruoF*
NOTES:
1. To obtain proper agent releasing operation, both audible circuits must be utilized.
2. All external circuits on TB1 and TB2 are supervised.
3. See OPERATION, INSTALLATION, AND P/N 315-093523
for details regarding:
MAINTENANCE MANUAL,
a. Abort Mode Selection b. Manual Discharge Mode Selection c. Time Delay Adjustment d. 5K Relay Operation Selection e. Service Selection: Removing the plug from position P72 will void
NFPA 72 Local approval
4. Jumper terminal 11 to terminal 12 of TB1 when abort station is not used.
5. Place EOL resistor across associated terminals when designated
devices are not used.
6. TB2, terminals 3, 4, 5, and 6 are not used for 72 Local Service.
7. Refer to OPERATING INSTRUCTIONS, P/N 315-193524.
8. To use power limited wiring to NFPA 70, NEC, the audible circuits,
terminals 1-4 of TB2 must use the PLM-35 module. Refer to In­structions P/N 315-093495. Initiating circuits, TB1, terminals 1-14, are power limited as they are.
9. For a list of COMPATIBLE NOTIFICATION APPLIANCES, refer to
P/N 315-096363.
DETECTORS
May use up to 30 smoke detectors (selected from any of the compatible detectors listed below) or may use shorting devices, detector relays, or remote lamps (Refer to the related detector instructions).
COM PATIBL E DE TECTORS
DETECTOR
COMPATIBILITY
IDENTIFIER
DI-3/3H DI-4A DI-6
SECIVEDEGRAHCSIDTNEGA
forebmuN
sdioneloS
seireSni
CDV42enOsmho3
CDV42enO
CDV42enO
CDV42enO
xaM eniL
ecnatsiseR
smho3
smho3
smho3
DI-A3/A3H DI-B3/B3H
DT-3P DT-11 PE-3/3T PE-11/11T
DB-3S DB-4 DB-4 DB-3S AD-3I/3ILP AD-3RI/3RP SA-3I/3P DB-3S DB-11 DB-3S DB-11 DB-3S w ith DB-ADPT
CDV42enO CDV42enO CDV42enO
CDV42enO
CDV6ruoF
CDV21owT
CDV42enO
smho8 smho8 smho8
mho1
smho3
smho3
smho3
CP-2ER is t h e c ompa t ibilit y ide n t if ie r
DESIGNATION RATING CIRCUIT
F1 F2
AD-11P
F3
CDV6ehtfonoitanibmocynahtiwdionelosCDV21enoximotdettimreptonsitI**
F4
BASE
COMPATIBILITY
IDENTIFIER
5A 2A 2A 3A
Battery General Alarm Audibles Discharge Audibles Discharge Circuit
INSTALLATION
WIRING
INSTRUCTIONS
P/N 315-081943-17 P/N 315-085257-11 P/N 315-085257-11 P/N 315-081943-17 P/N 315-093234-6 P/N 315-086591-7 P/N 315-086593-6 P/N 315-084401-5 P/N 315-095429-2 P/N 315-090875-7 P/N 315-094198-9 P/N 315-094198-9 P/N 315-095659-7
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
Technical Manuals Online! - http://www.tech-man.com
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN
5
P/N 575-293737-8
Page 8
OPTIONS
S
g
1. Discharge Delay Selection Switch S101
5
witch
S101
Dial
Setting
Dial setting
Rotate to change settin
Discharge Delay
Period (seconds)
Closure of the Manifold Discharge Monitor (mechani­cal release) will result in an instant discharge.
b. Position II Closed; I Open
Operation of the MANUAL DISCHARGE station re- sults in immediate discharge, regardless of delay period selected.
NOTE: Opening the closed manual station contacts
(or resetting) restores the control panel to a non-alarm state if the initiating zones have not been activated.
0 1 2 3 4 5 6 7 8 9
0
5 10 15 20 25 30 35 40 45
2. Abort Station Operation Selection Dipswitch PS1
a. Position I Closed; II and Ill Open
When used, abort function is operational if, and only if, one, but not two, of the associated initiating de­vice circuits has activated. Release of the ABORT station switch, after both initiating device circuits have activated, results in the regular preselected discharge delay sequence as selected on S101.
b. Position II Closed; I and Ill Open
Discharge may be aborted at any time before se­lected discharge delay period has expired and dis­charge has begun. Release of the ABORT station switch after both initiating device circuits have acti­vated results in continuation of the unexpired dis­charge delay period as selected on S101.
c. Position III Closed; I and II Open
Discharge may be aborted at any time before se­lected discharge delay period has expired. Release of the ABORT station switch after both initiating de- vice circuits have activated results in a complete dis­charge delay period as selected on S101.
3.
Manual Discharge Operation Selection Dipswitch PS2
a. Position I Closed; II Open
Operation of the MANUAL DISCHARGE station re- sults in a discharge delay period, as selected, be­fore actual discharge begins, provided the delay se­lected is 30 seconds or less. When the discharge delay selector is set for more than 30 seconds, the MANUAL DISCHARGE switch operation gives a 30­second delay period maximum.
4. Predischarge/Discharge Delay Operation Selection (TB3, Terminals 10 through 14) Dipswitch PS3
a. Position I Closed; II Open
Relay contacts change state on any of the following conditions without any delay period.
 Both initiating device circuits have activated. 
MANUAL DISCHARGE station has been operated.
 Normally open MANIFOLD DISCHARGE moni-
tor switch has closed.
b. Position II Closed; I Open
Relay contacts change state at conclusion of se­lected discharge delay period when operated by activating both initiating device circuits, by activat­ing manual discharge station, or by operating the Manifold Discharge (mechanical release).
5. New York Option
To meet the requirements of the City of New York Fire Prevention Directive 3-74 and the New York Board of Standards and Appeals, it is necessary to modify the CP-2ER Control Panel by deactivating the 10K ohm resistor R174.
When R174 is not operational, certain responses of the control unit are altered: the general alarm sounds when the first of the two zones alarms. When the second zone alarms, two possible sequences may be followed:
a. If the ABORT switch is not pressed.
1) Discharge audibles operate in a pulsing manner and the general alarm circuit is silenced.
2) A 30 second discharge delay is provided by set­ting switch S101 at 6.
3) After the delay period, when the agent is re­leased, the discharge audibles sound in a steady manner.
b. If the ABORT switch is depressed before the 30
second time-in period ends.
1) The discharge audibles are silenced during the 90 second abort duration period. NOTE: The 90 second delay period associated
with the external abort switch is provided by others.
Technical Manuals Online! - http://www.tech-man.com
6
Page 9
2) The general alarm audibles sound in a steady manner (as if only one zone had alarmed).
3) After the 90 second abort delay period ends, the internal 30 second discharge delay begins. At that time the general alarm audibles silence, and the discharge audibles begin to pulse as de­scribed in No. 1a above.
Mounting Control Units (Refer to Figure 2)
Securely fasten the control unit to a shock and vibration free surface in a clean, dry area. It must be mounted far­ther than 3 feet, but less than 6 feet, from the floor. The location should be easily visible, readily accessible for main­tenance, and should allow sufficient clearance to open the hinged front door.
INSTALLATION AND WIRING
The reliability of any system depends to a great extent on the proper installation of the control units, detectors, asso­ciated equipment, and wiring. These instructions outline the requirements for a satisfactory installation. Careful completion of each detail will provide an automatic fire and smoke detection system that is dependable and gives reli­able operation.
Connection instructions are mounted inside the cover of the CP-2ER. Additional wiring information is provided in the manual. Any questions regarding the equipment or in­stallation should be directed to Siemens Building Tech­nologies, Inc. or an authorized representative; do not make any alteration without first consulting one of the above.
Local regulations or codes generally require all wiring to, from, and between units to be carried in 1/2-3/4 inch con­duits. Knockouts are provided in the top and bottom of the control unit. No. 18 AWG, 300V insulation, color coded wire is recommended for the detector circuits. A larger size may be used if desired; e.g., 16 AWG. For the power input, audible, and release circuits, use at least 14 AWG, 300V wire.
Power Requirements
The Model CP-2ER Control Unit is designed to be operated from a 120 VAC power source with the neutral line grounded. The 120 VAC input powers all internal circuitry. The AC volt­age may vary between the limits of 102 and 132 volts, and the limits should not be exceeded. The CP-2ER ungrounded
Technical Manuals Online! - http://www.tech-man.com
Figure 2
Mounting Data
7
Page 10
leg must be connected, through a separate circuitbreaker or fuse, directly to the power supply. No other equipment should be supplied from this separate circuitbreaker or fuse. Wire must be run continuously from power source to termi­nals in the control unit. A 24V battery provides emergency power. Refer to the CONNECTION DIAGRAM on pages 4­5, for terminal connections.
Installation of Conduit and Outlet Boxes
Install outlet boxes and run conduit between boxes and control unit. Use 4 inch octagonal boxes for ionization, photoelectric, flame, and plug-in thermal detectors. The depth of the boxes should be determined by the NEC re­quirements for the number and size of conductors used. Do not mount boxes in direct air flow from air conditioning or ventilating system supply registers.
The control unit, and all detectors and alarm circuit con­duit, must be properly grounded. Insure that all conduit has clean threads and makes good electrical contact be­tween the control unit and outlet boxes.
Installation of Detector Bases
Wiring (Refer to CONNECTION DIAGRAM)
Run wire in accordance with wiring diagram. Use at least No. 18 AWG, 300V insulation, color coded wire for the detector circuits. Wiring between control unit and first de­tector base, and all subsequent detector bases, must be continuous; no splices, wire nuts, solder, or any other type connection is permissible. On rare occasions an excep­tion may be necessary due to an extremely long run. In this case, the splice must be soldered.
The wire interconnecting the detector bases is continu­ously supervised by a small electrical current flow through the circuit to the end-of-line resistor (1.78K ohms) mounted in the base of the last detector. In order to keep this super­vision complete, no parallel branching of wires is permis­sible. Every base, except the last one, will have one set of incoming and one set of outgoing wires.
Installing Bases
Mount end-of-line resistor between appropriate terminals of last base on circuit, as indicated on the CONNECTION DIAGRAM. Mount all bases to outlet boxes. Manual sta­tions, thermal detectors, air duct detectors, etc., are to be connected to the circuit at this time. Please refer to wiring diagrams for the specific equipment for connection de­tails.
Wiring Test
NOTE: It is suggested that electrical tests be conducted
jointly by the installer and the manufacturers tech­nician or representative. Written notice is requested 15 days prior to the tests so that the services of the technician may be scheduled.
The installation of the wiring should be checked as follows:
1. Detectors should not be in their bases. Temporary jump­ers should be inserted in all bases if not already in­stalled. Install end-of-line resistor to appropriate termi­nals of last detector on circuit for Class B wiring. For Class A wiring, install the end-of-line resistor between terminals 2 and 3 for Zone 1 and between terminals 5 and 6 for Zone 2. Wiring from bases should NOT be connected to the Control Panel at this time.
2. Check the wiring of the detector circuit with an ohm­meter. Resistance reading between wires connected to terminals 1 and 4 of the Control Panel or terminals 5 and 8 for the other zone should be approximately 1.8K ohms. Short the detector lines together and megger the combined lines to chassis and conduit. There should be at least 10 meg resistance reading between wires and conduit or ground.
3. Connect wires to appropriate terminals of the Model CP-2ER.
4. Remove the temporary jumpers from the bases. The manufacturers Service Representative will then install the detectors and check sensitivity.
System Operation Test
CAUTION: Be sure to prevent release of the agent.
1. See that the CP-2ER control unit is in normal standby operation.
2. To test for supervision of initiating circuit, remove the detector connected to the last device and check that proper trouble indicators respond in the system. Re­connect detector.
3. To test operation of initiating circuit, actuate a detec­tor. Check that system fire indicators and alarm relay contacts respond to the alarm.
4. Test operation of detector circuit: Activate each detec­tor and manual station, one at a time, resetting each, and check that detector base lamp and control unit alarm controls operate. Each ionization detector may be activated by blowing smoke into the chamber. The manual station on the front panel should be checked independently.
5. Check all basic system operational functions, particu­larly the operation of the time delay functions, prior to arming the agent releasing circuits.
POWER LIMITED WIRING
Effective May 1, 1995, all power-limited fire protective sig­naling conductors must be separated a minimum of 1/4 inch from all of the following items located within a control panel: electric light, power, Class 1, and non-power limited fire protective signaling conductors .
To meet these requirements, the following guidelines must be observed when installing modules and wiring to this control panel.
Technical Manuals Online! - http://www.tech-man.com
8
Page 11
NOTE: If power-limited wiring is not used within this en-
N = NON-POWER LIMITED TERMINALS
closure, then the following guidelines do not ap­ply. In that case, be sure to follow standard wiring practices.
Wiring Entering the Enclosure
Non-power Limited Wiring
Wiring to the following CP-2ER terminations is considered non-power limited and must enter the enclosure through the knockout specified below (See Figure 3). Wiring be­tween the knockout specified and the termination must be the shortest route, and must not overlap any other wiring.
MODULE TERMINATION
CP-2ER TB-2 (All positions) 3 or 4 CP-2ER TB-3 (All positions) 3 or 4
ENCLOSURE
KNOCKOUT
Wiring in the Enclosure
Non-power Limited Wiring
Wiring from the batteries and power supply is considered non-power limited. To maintain the required separation, route the wires as shown in Figure 3.
POWER
LIMITED
1
PLM-35
TB1
P
2
CP-2ER
P1
N
POWER SUPPLY
3
P2
N
4
TB3
N
TB2
N
Wiring Entering the Enclosure
Power Limited Wiring
Wiring to the following CP-2ER terminations is considered power limited and must enter the enclosure through the knockout specified below (See Figure 3).
MODULE TERMINATION
CP-2ER TB-1 (All positions) 1 or 2
ENCLOSURE
KNOCKOUT
PLM-35
If the PLM-35 module is required, mount it on the left side wall of the enclosure as shown in Figure 3 (Refer to PLM-35 Installation Instructions, P/N 315-093495).
MAINTENANCE AND TESTING
To insure proper and reliable operation, refer to NFPA 72 Local, 12A, or 2001, as appropriate, for applicable main­tenance and testing schedule and instructions.
CAUTION: Make sure that release circuits and shunt
trips are disconnected before testing.
Notify facility personnel and the fire depart­ment that a system test is being performed so that any alarm soundings can be ignored during the test.
_
NOTE: P = POWER LIMITED TERMINALS
_
+
+
Figure 3
CP-2ER Power Limited Wiring
TROUBLESHOOTING THE SYSTEM
Refer to OPERATION section for identity of troubles by lamp indicator. Refer to ratings on specific circuit termi­nals for manual voltage readings. (See CONNECTION DIAGRAM on pages 4-5.)
A system trouble condition causes the following panel indications and conditions:
1. Illumination of the front panel visual trouble indicator.
2. Sounding of the internal trouble buzzer.
3. Change of state of the trouble relay contacts (TB3, terminals 1 through 3).
Technical Manuals Online! - http://www.tech-man.com
9
Page 12
When the panel is in an on battery condition, the front panel visual trouble indicator on the internal trouble buzzer (Items 2 and 3 above) operate in a pulsing manner with two short On periods followed by a longer Off period. An additional system trouble is indicated by four short On periods followed by a longer Off period. In both these in­stances, the trouble relay contacts (Item 3 above) remain in a steady change of state condition.
A system trouble may result from any of the following fault conditions:
1. On battery condition as described above.
2. Battery fault. a. High or low battery voltage condition. b. Disconnected or open battery lines (includes an
open or battery fuse F1, rated 5 amps).
3. Ground fault condition of any external wiring. Panel ground fault condition may be alleviated by temporary removal of ground fault connection plug P3.
4. Abort station fault. TB1, terminals 7 and 8, open circuit.
5. Manual discharge station. TB1, terminals 5 and 6, open circuit or not terminated with 5.6K ohm resistor.
6. With Class B wiring: Zone 1 and/or Zone 2 initiating circuits. TB1, between terminals 1 and 4 or between terminals 5 and 8 open circuited, or not terminated with a 1.78K ohm resistor. With Class A wiring: Zone 1 and/or Zone 2 initiating circuits. TB1, between terminals 2 and 3 or between terminals 6 and 7 open circuited, or not terminated with a 1.78K ohm resistor.
Wiring resistance between terminals 1 and 2, 3 and 4, 5 and 6, or 7 and 8 exceeds acceptable limits (Refer to CONNECTION DIAGRAM on pages 4-5).
7. General alarm audible alarm circuit. TB2, terminals 1 and 2, open circuited or not termi­nated with a 5.6K ohm resistor.
NOTE:
A trouble condition may result from a low line resis­tance value as well as from a high line value.
8. Predischarge/discharge audible alarm circuit. TB2, terminals 3 and 4 open circuited or not termi­nated with 5.6K ohm resistor. (See Item 7 above.)
9. Agent release (discharge devices) circuit. Terminals 5 and 6, open circuit condition.
10. Cylinder pressure circuit. TB1, terminals 13 and 14, open circuit or line not ter­minated with 2.2K ohm resistor.
11.
System Reset switch S1 not in normal closed position.
12. RELEASE DISCONNECT switch in off-normal (down) position.
Each of the above circuits, except Item 11, has its own individual trouble indicating light located at various points on the panel PC boards. A system Supervisory will result if there is a short circuit condition (cylinder pressure) on TB1, terminals 13 and 14.
Recommended Spare Parts
Fuse Rating Part No.
F1 5A 105-210734 F2
F3 F4 3A 105-215996
2A 105-210758
Technical Manuals Online! - http://www.tech-man.com
P/N 315-093523-7
10
Loading...