Siemens CP 1243-1 PCC, SIMATIC S7-1200 Operating Instructions Manual

Page 1

CP 1243-1 PCC

___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
___________________
SIMATIC NET
Operating Instructions
02/2015
C79000
Preface
Application and properties
1
Requirements for use
2
LEDs and connectors
3
Installation, connecting up, commissioning
4
Configuration and operation
5
Diagnostics and upkeep
6
Technical specifications
7
Approvals
A
Dimension drawings
B
Documentation references
C
Siemens Automation
-G8976-C384-01
Page 2
Siemens AG Division Process Industries and Drives Postfach 48 48 90026 NÜRNBERG GERMANY
C79000-G8976-C384-01
Copyright © Siemens AG 2015. All rights reserved

Legal information

Warning notice system
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
Qualified Personnel
personnel qualified
Proper use of Siemens products
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
Disclaimer of Liability
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.
The product/system described in this documentation may be operated only by task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.
Note the following:
documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
for the specific
01/2015 Subject to change
Page 3

Preface

Validity of this manual
CP 1243-1 PCC
This document contains information on the following product:
Article number6GK7 243-1HX30-0XE0 Hardware product version 2 Firmware version V2.0
The CP 1243-1 PCC for Plant Cloud Communication / Data Driven Services is the communications processor for connecting the SIMATIC S7-1200 via a public infrastructure (e.g. DSL) to an operation center.
The integrated Plant Cloud Communication of the CP for connection and transfer of data values to a operation center can be used for the service offer of Industry Services, e.g. Asset Analytics Services. Communication with other cloud servers is not supported. Information on Asset Analytics and Industry Services: Asset Analytics (http://support.automation.siemens.com/WW/view/en/92377679) Industry Services (http://www.industry.siemens.com/services)
The CP transfers the required data to the communications partner, the operation center. To obtain a prediction of the status of your system or your devices, the operation center collects and analyzes the transferred data.
With the help of a firewall, the CP allows protected access to the S7-1200.
The CP can also be used as an additional interface of the CPU for S7 communication.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
3
Page 4
Preface
Product names and abbreviations
Operation center
CP
STEP 7
Figure 1 CP 1243-1 PCC
Behind the top hinged cover of the module housing, you will see the hardware product version to the right of the article number printed as a placeholder "X". If the printed text is, for example, "1 X 3 4", "X" would be the placeholder for hardware product version 2.
You will find the firmware version of the CP as supplied behind the top hinged cover of the housing to the left below the LED field.
You will find the MAC address under the lower hinged cover of the housing.
This abbreviation will be used below instead of the full term "Plant Cloud in the operation center".
The term "CP" is used below instead of the full product name CP 1243-1 PCC.
This short form will be used below for the STEP 7 Basic / Professional configuration tool.
CP 1243-1 PCC
4 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 5
Preface
Purpose of the manual
Current manual release on the Internet
Required experience
Requirements for use of the module
Sources of information and other documentation
SIMATIC NET glossary
This manual describes the properties of this module and supports you when installing and commissioning it.
The required configuration steps are described as an overview and there are explanations of the relationship between firmware functions and configuration.
You will also find information about the diagnostics options of the device.
You will also find the current version of this manual on the Internet pages of Siemens Industry Online Support in the directory with following entry ID:
51297224 (http://support.automation.siemens.com/WW/view/en/51297224)
To install, commission and operate the CP, you require experience in the following areas:
Automation engineering
Setting up the SIMATIC S7-1200
SIMATIC STEP 7 Basic / Professional
You will find the requirements for using the module in the section Hardware requirements (Page 15).
You will find an overview of further reading and references in the Appendix of this manual.
Explanations of many of the specialist terms used in this documentation can be found in the SIMATIC NET glossary.
You will find the SIMATIC NET glossary here:
SIMATIC NET Manual Collection or product DVD
The DVD ships with certain SIMATIC NET products.
On the Internet under the following entry ID:
50305045 (http://support.automation.siemens.com/WW/view/en/50305045)
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
5
Page 6
Preface
License conditions
Note Open source software
Read the license conditions for open source software carefully before using the product.
Security information
Firmware
Training, Service & Support
Trademarks
You will find license conditions in the following documents on the supplied data medium:
DOC_OSS-S7CMCP_74.pdf
DOC_OSS-CP1243-1-PCC_76.pdf
Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. For more information about industrial security, visit
http://www.siemens.com/industrialsecurity.
To stay informed about product updates as they occur, sign up for a product-specific newsletter. For more information, visit http://support.automation.siemens.com.
The firmware is signed and encrypted. This ensures that only firmware created by Siemens can be downloaded to the device.
You will find information on Training, Service & Support in the multi--language document "DC_support_99.pdf" on the data medium supplied with the documentation.
The following and possibly other names not identified by the registered trademark sign ® are registered trademarks of Siemens AG:
SIMATIC, SIMATIC NET, SIMATIC STEP 7, SCALANCE, Operation Center
CP 1243-1 PCC
6 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 7

Table of contents

Preface ................................................................................................................................................... 3
1 Application and properties ....................................................................................................................... 9
2 Requirements for use ............................................................................................................................ 15
3 LEDs and connectors ............................................................................................................................ 17
4 Installation, connecting up, commissioning ............................................................................................ 21
5 Configuration and operation .................................................................................................................. 29
1.1 Properties of the CP .................................................................................................................. 9
1.2 Plant Cloud Communication ..................................................................................................... 9
1.3 Communications services ....................................................................................................... 10
1.4 Other services and properties ................................................................................................. 11
1.5 Configuration limits and performance data ............................................................................. 13
2.1 Hardware requirements .......................................................................................................... 15
2.2 Software requirements ............................................................................................................ 15
3.1 Opening the covers of the housing ......................................................................................... 17
3.2 LEDs ....................................................................................................................................... 18
3.3 Electrical connectors ............................................................................................................... 20
3.3.1 Power supply .......................................................................................................................... 20
3.3.2 Ethernet interface X1P1 .......................................................................................................... 20
4.1 Important notes on using the device ....................................................................................... 21
4.1.1 Notices on use in hazardous areas ........................................................................................ 21
4.1.2 General notices on use in hazardous areas according to ATEX ............................................ 23
4.1.3 Notices regarding use in hazardous areas according to UL HazLoc ..................................... 23
4.2 Installing, connecting up and commissioning ......................................................................... 24
5.1 Note on operation ................................................................................................................... 29
5.2 Configuration in STEP 7 ......................................................................................................... 29
5.3 Address and authentication information ................................................................................. 31
5.4 Configuring data points and messages .................................................................................. 32
5.5 Datapoint types ....................................................................................................................... 33
5.6 CPU scan cycle ....................................................................................................................... 35
5.7 Types of transmission, event classes, triggers, status identifiers ........................................... 36
5.8 Security functions .................................................................................................................... 39
5.8.1 Firewall .................................................................................................................................... 39
5.8.1.1 Firewall sequence when checking incoming and outgoing frames ........................................ 39
5.8.1.2 Notation for the source IP address (advanced firewall mode) ................................................ 39
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
7
Page 8
Table of contents
6 Diagnostics and upkeep ........................................................................................................................ 55
7 Technical specifications ........................................................................................................................ 61
A Approvals ............................................................................................................................................. 63
B Dimension drawings .............................................................................................................................. 67
C Documentation references .................................................................................................................... 69
Index .................................................................................................................................................... 71
5.8.2 Filtering of the system events ................................................................................................ 39
5.9 Time-of-day synchronization .................................................................................................. 40
5.10 SNMP ..................................................................................................................................... 41
5.11 STEP 7 configuration of individual parameters ...................................................................... 43
5.11.1 Communication types and SNMP .......................................................................................... 43
5.11.2 Ethernet interface (X1) > Advanced options .......................................................................... 44
5.11.3 Operation center .................................................................................................................... 44
5.11.3.1 Operation center1 or Operation center2 ................................................................................ 45
5.11.4 Communication with the CPU ................................................................................................ 47
5.11.5 Data point configuration ......................................................................................................... 47
5.11.5.1 Configuring the data point names .......................................................................................... 47
5.11.5.2 Threshold value trigger and Analog value preprocessing ..................................................... 48
5.11.5.3 Analog value preprocessing ................................................................................................... 49
5.11.5.4 Threshold value trigger .......................................................................................................... 52
6.1 Diagnostics options ................................................................................................................ 55
6.2 Downloading firmware ........................................................................................................... 56
6.3 Module replacement .............................................................................................................. 59
7.1 Technical specifications of the CP 1243-1 PCC .................................................................... 61
7.2 Pinout of the Ethernet interface ............................................................................................. 62
CP 1243-1 PCC
8 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 9
1
1.1

Properties of the CP

Application
1.2

Plant Cloud Communication

CP data: Transferring - collecting - analyzing
Access to the analyzed data
Requirements for CP configuration
The CP is intended for operation in an S7-1200 automation system. The CP allows connection of the S7-1200 to Industrial Ethernet or via the Internet to a plant cloud in the operation center.
With the combination of different security functions such as firewall and protocols for data encryption, the CP protects the station and even entire automation cells from unauthorized access and protects the communication between the remote S7 station and the operation centerfrom espionage and manipulation.
To transfer data values of the CP regularly, e.g. diagnostics or maintenance data, to an operation center:
Set up the Plant Cloud Communication to one or two operation centers.
To obtain a prediction of the status of your system or your devices:
Have the transferred data analyzed using this remote computing center/server of the operation center.
To call up the analyzed data, you have the following options available:
Direct access to the analyzed data.
Within the framework of a service contract, you receive regular reports about the status of
your system or your devices.
Remember the following requirements in the CP configuration for Plant Cloud Communication:
Activation of Plant Cloud Communication ("Communication types" parameter group).
IP address assignment: Set the IP address manually or obtain the IP address from a
DHCP server.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
9
Page 10
Application and properties
1.3
Communications services
Plant Cloud Communication
S7 communication and PG/OP communication with the following functions:

1.3 Communications services

If not obtained automatically from a DHCP server:
– Assignment of the DNS server address.
Activation of the Security functions.
Activation of time-of-day synchronization with "Time from partner", "NTP" or "NTP
(secure)". For the communication with an operation center, give preference to the secure method NTP (secure).
Required from the operator of the operation center:
– Operation center key and a suitable certificate for secure and encrypted transfer of the
data.
– Operation center address (URL address of the operation center).
The following communications services are supported:
The CP is a communications processor of the SIMATIC S7-1200 for system connection to a plant cloud in the operation center.
Secure communication between the CP and operation center is assured by the HTTPS protocol.
For a description of the configurable Security functions, refer to the section Other services and properties (Page 11).
– PUT/GET as client and server for data exchange with remote stations (S7-
300/400/1200/1500)
– PG functions
– Operator control and monitoring functions (HMI)
CP 1243-1 PCC
10 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 11
Application and properties
1.4
Other services and properties
Other services and properties
Data point configuration
IP configuration - IPv4 and IPv6
Time-of-day synchronization
Data buffering: Storage of event data
Data transfer: triggered
Analog value processing

1.4 Other services and properties

Due to the data point configuration in STEP 7, programming program blocks in order to transfer the process data is unnecessary. The individual data points are processed 1:1 in the operation center.
The essential features of IP configuration for the CP:
– The CP supports IP addresses according to IPv4 and IPv6.
For applications in IPv6 networks, an IPv6 address can be used in addition to an IPv4 address.
– IP address assignment:
The IP address, the subnet mask and the address of a gateway can be set manually in the configuration.
As an alternative, the IP address can be obtained from a DHCP server or by other means outside the configuration.
– If Plant Cloud Communication is enabled, the CP can obtain its local time as UTC time
from the operation center or using NTP or NTP (secure). The time of day can be read from the CPU. For the communication with an operation center, give preference to the secure method NTP (secure). The mechanisms are described in the STEP 7 information system.
For information on the format of the time stamp, refer to the section Datapoint types (Page 33).
For more information, refer to the section Time-of-day synchronization (Page 40).
If a connection fails, the CP can buffer the data of events of different classes and transfer them bundled to the operation center.
The Plant Cloud Communication with the operation center is started in the following way:
– Triggered by various selectable criteria.
Analog values can be preprocessed on the CP according to various methods.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
11
Page 12
Application and properties
Online functions
SNMP
Industrial Ethernet Security
Security functions of the CP
Firewall
Operation centers
Logging
1.4 Other services and properties
From an engineering station (ES) on which STEP 7 is installed, you can use the online functions of STEP 7 via the CP to access the S7-1200 CPU if the station is located in the same IP subnet. Online access via the operation center is not possible.
The following online functions are available:
– Downloading project or program data from the STEP 7 project to the station.
– Querying diagnostics data on the station.
– Downloading firmware files to the CP.
As an SNMP agent, the CP supports data queries using SNMP (Simple Network Management Protocol) in version V1.
For more detailed information, refer to section SNMP (Page 41).
With Industrial Ethernet Security, individual devices, automation cells or network segments of an Ethernet network can be protected. The data transfer via the CP can be protected from the following attacks by a combination of different security measures:
Data espionage
Data manipulation
Unauthorized access
Secure underlying networks can be operated via additional Ethernet/PROFINET interfaces of the CPU.
The CP supports the following security functions:
– IP firewall with stateful packet inspection (layer 3 and 4)
– Firewall also for "non-IP" Ethernet frames according to IEEE 802.3 (layer 2)
– Limitation of the transmission speed ("Bandwidth limitation")
– Global firewall rules
Secure communication with one or two operation centers.
To allow monitoring, events can be stored in log files that can be read out using the configuration tool or can be sent automatically to a Syslog server.
CP 1243-1 PCC
12 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 13
Application and properties
NTP (secure)
Protection for devices and network segments
Note Plants with security requirements - recommendation
Use the following options:
1.5
Configuration limits and performance data
Number of CMs/CPs per station
Connection resources
TCP connections
Online functions
S7 connections
PG/OP connections

1.5 Configuration limits and performance data

For secure transfer during time-of-day synchronization
The protection provided by the firewall can cover individual devices, several devices or even entire network segments.
If you have systems with high security requirements, use the secure protocols
NTP (secure) and HTTPS.
If you connect to public networks, you should use the firewall. Think about the services
you want to allow access to the station via public networks. By using the "bandwidth limitation" of the firewall, you can restrict the possibility of flooding and DoS attacks.
For information on configuring the security functions, refer to the section Security functions (Page 39).
You will find further information on the functionality and configuration of the security functions in the information system of STEP 7 and in the manual /2/ (Page 70).
In each S7-1200 station, up to three CMs/CPs can be plugged in and configured; this allows three CP 1243-1 PCC modules.
The CP can establish connections to up to 8 communications partners (S7 stations).
1 connection resource is reserved for online functions.
8 connection resources for S7 connections (PUT/GET)
– 1 connection resource for PG connections
– 3 connection resources for OP connections
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
13
Page 14
Application and properties
Number of data points for the data point configuration
User data
Frame memory (send buffer)
Firewall rules
1.5 Configuration limits and performance data
The maximum number of configurable data points is 200.
The data to be transferred by the CP is assigned to various data points in the STEP 7 configuration.
The size of the user data per data point depends on the data type of the relevant data point. You will find details in the section Datapoint types (Page 33).
The CP has a frame memory (send buffer) for the values of data points configured as an event.
The send buffer has a maximum size of 64 000 events divided into equal parts for all configured communications partners. The size of the frame memory can be set in STEP 7, refer to the section Communication with the CPU (Page 47).
You will find details of how the send buffer works (storing and sending events) as well as the options for transferring data in the section Types of transmission, event classes, triggers, status identifiers (Page 36).
The maximum number of firewall rules in advanced firewall mode is limited to 256.
The firewall rules are divided up as follows:
Maximum 226 rules with individual addresses
Maximum 30 rules with address ranges or network addresses
(e.g. 140.90.120.1 - 140.90.120.20 or 140.90.120.0/16)
Maximum 128 rules with limitation of the transmission speed ("Bandwidth limitation")
CP 1243-1 PCC
14 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 15
2
2.1

Hardware requirements

Application example: Plant Cloud Communication
In the S7-1200 station:
For the configuration of the S7 station with CP:
2.2

Software requirements

Configuration software
Software for online functions
The following list relates to Plant Cloud Communication.
Rails, housing, cabling and other accessories are not taken into account.
Depending on the configuration of your plant, you require the following devices and firmware versions.
CPU with firmware version ≥ V3.0
Engineering station with STEP 7
To configure the CP, the following configuration tool is required:
STEP 7 Basic / Professional V13 SP1 with HSP0112
STEP 7 in the version specified above.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
15
Page 16
Requirements for use
2.2 Software requirements
CP 1243-1 PCC
16 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 17
3
3.1

Opening the covers of the housing

Location of the display elements and the electrical connectors
Opening the covers of the housing
The LEDs for the detailed display of the module statuses are located behind the upper cover of the module housing.
The Ethernet connector is located behind the lower hinged cover of the module.
Open the upper or lower cover of the housing by pulling it down or up as shown by the arrows in the illustration. The covers extend beyond the housing to give you a grip.
Figure 3-1 Opening the covers of the housing
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
17
Page 18
LEDs and connectors
3.2
LEDs
LEDs of the module
LED on the front panel
LEDs below the upper cover of the housing
LED / colors
Name
Meaning
(red / green)
DIAG
LED / colors
Name
Meaning
(red / green)
LINK
(green)
CONNECT
Reserve (empty LED position)
(green)
SERVICE
Note LED colors when the module starts up
When the module starts color mixture. At this point in time, the color of the LEDs is not clear.

3.2 LEDs

The module has various LEDs for displaying the status:
The "DIAG" LED that is always visible shows the basic statuses of the module.
The LEDs below the upper cover provide more detailed information on the module status.
Table 3- 1 LED on the front panel
Table 3- 2 LEDs below the upper cover of the housing
Basic status of the module
Status of the physical connection to Industrial Ethernet
Status of the connection to the operation center
Status of a connection for online functions
up, all its LEDs are lit for a short time. Multicolored LEDs display a
CP 1243-1 PCC
18 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 19
LEDs and connectors
Display of the operating and communications statuses
Symbol LED status
OFF
ON (steady light)
Flashing
Not relevant
DIAG
(red / green)
LINK
(red / green)
CONNECT
(green)
SERVICE
(green)
Meaning
Module startup (STOP → RUN) or error statuses
-
-
Connection to Industrial Ethernet
exists
Connection to communications partners
CPU in RUN
CPU in STOP
CPU in RUN
Connection for online functions
lished
3.2 LEDs
The LED symbols in the following tables have the following significance:
Table 3- 3 Meaning of the LED symbols
-
The LEDs indicate the operating and communications status of the module according to the following scheme:
Power OFF
Startup - phase 1
- Missing STEP 7 project data
-
-
-
- - - Running (RUN) without error
- Backplane bus error
- - Errors: double IP address
- - Connection to Industrial Ethernet
- - No connection to Industrial Ethernet
-
- - -
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
- Connection established to at least one partner,
- Connection established to at least one partner,
- Physical connection established, partner not responding,
- Physical connection established, partner not responding, CPU in STOP
-
Connection for online functions estab-
No connection to engineering station
19
Page 20
LEDs and connectors
DIAG
(red / green)
LINK
(red / green)
CONNECT
(green)
SERVICE
(green)
Meaning
Loading firmware
3.3
Electrical connectors
3.3.1

Power supply

Power supply
3.3.2

Ethernet interface X1P1

Ethernet interface

3.3 Electrical connectors

Firmware being loaded. The "DIAG" LED flashes alternating red and green.
Firmware was successfully loaded.
Errors:
Error loading firmware
Internal error of the CP
remedy: Power OFF → ON
The CM is supplied with power from the backplane bus. It does not require a separate power supply.
The Ethernet connector is located behind the lower hinged cover of the module. The interface is an RJ-45 jack according to IEEE 802.3.
The pin assignment and other data relating to the Ethernet interface can be found in the section Technical specifications (Page 61).
CP 1243-1 PCC
20 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 21
4
4.1

Important notes on using the device

Safety notices on the use of the device
Overvoltage protection
NOTICE
Protection of the external power supply
4.1.1

Notices on use in hazardous areas

WARNING
EXPLOSION HAZARD
Note the following safety notices when setting up and operating the device and during all associated work such as installation, connecting up or replacing the device.
If power is supplied to the module or station over longer power cables or networks, the coupling in of strong electromagnetic pulses onto the power supply cables is possible. This can be caused, for example by lightning strikes or switching of higher loads.
The connector of the external power supply is not protected from strong electromagnetic pulses. To protect it, an external overvoltage protection module is necessary. The requirements of EN61000-4-5, surge immunity tests on power supply lines, are met only when a suitable protective element is used. A suitable device is, for example, the Dehn Blitzductor BVT AVD 24, article number 918 422 or a comparable protective element.
Manufacturer: DEHN+SOEHNE GmbH+Co.KG Hans Dehn Str.1 Postfach 1640 D-92306 Neumarkt, Germany
DO NOT OPEN WHEN ENERGIZED.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
21
Page 22
Installation, connecting up, commissioning
WARNING
WARNING
EXPLOSION HAZARD
WARNING
EXPLOSION HAZARD
WARNING
WARNING
4.1 Important notes on using the device
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a Limited Power Source (LPS).
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1 must be connected to the power supply terminals. The power supply unit for the equipment power supply must comply with NEC Class 2, as described by the National Electrical Code (r) (ANSI / NFPA 70).
If the equipment is connected to a redundant power supply (two separate power supplies), both must meet these requirements.
DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT.
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2 OR ZONE 2.
The device may only be operated in an environment with pollution degree 1 or 2 (see IEC 60 664-1).
When used in hazardous environments corresponding to Class I, Division 2 or Class I, Zone 2, the device must be installed in a cabinet or a suitable enclosure.
CP 1243-1 PCC
22 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 23
Installation, connecting up, commissioning
4.1.2

General notices on use in hazardous areas according to ATEX

WARNING
Requirements for the cabinet/enclosure
WARNING
WARNING
4.1.3

Notices regarding use in hazardous areas according to UL HazLoc

WARNING
EXPLOSION HAZARD
4.1 Important notes on using the device
To comply with EU Directive 94/9 (ATEX95), the enclosure or cabinet must meet the requirements of at least IP54 in compliance with EN 60529.
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air ambient in excess of 50 °C, only use cables with admitted maximum operating temperature of at least 80 °C.
Take measures to prevent transient voltage surges of more than 40% of the rated voltage. This is the case if you only operate devices with SELV (safety extra-low voltage).
DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non­hazardous locations only.
This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations only.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
23
Page 24
Installation, connecting up, commissioning
4.2
Installing, connecting up and commissioning
Prior to installation and commissioning
CAUTION
Read the system manual "S7-1200 Programmable Controller"
Pulling/plugging the module
NOTICE
Turning off the station when plugging/pulling the module

4.2 Installing, connecting up and commissioning

Prior to installation, connecting up and commissioning, read the relevant sections in the system manual "S7-1200 Programmable Controller", refer to the documentation in the Appendix.
When installing and connecting up, keep to the procedures described in the system manual "S7-1200 Programmable Controller".
Before pulling or plugging the module, always turn off the power supply to the station.
CP 1243-1 PCC
24 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 25
Installation, connecting up, commissioning
Dimensions for installation
S7-1200 devices
Width A
Width B *
CPU 1211C, CPU 1212C
90 mm
45 mm
CPU 1214C
110 mm
55 mm
CM 1241 RS-232 and CM 1241 RS-485
30 mm
15 mm
CM 1243-5, CM 1242-5 (PROFIBUS master / slave)
30 mm
15 mm
CP 1242-7
30 mm
15 mm
CP 1243-1
30 mm
15 mm
* Width B: The distance between the edge of the housing and the center of the hole in the DIN rail mounting clip
DIN rail clamps, control panel installation
4.2 Installing, connecting up and commissioning
Figure 4-1 Dimensions for installation of the S7-1200
Table 4- 1 Dimensions for installation (mm)
CPU (examples)
Communications inter­faces (examples)
You will find detailed dimensions of the module in the section Dimension drawings (Page 67).
All CPUs, SMs, CMs and CPs can be installed on the 35 mm DIN rail in the cabinet. Use the pull-out DIN rail mounting clips to secure the device to the rail. These mounting clips also lock into place when they are extended to allow the device to be installed in a switching panel. The inner dimension of the hole for the DIN rail mounting clips is 4.3 mm.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
25
Page 26
Installation, connecting up, commissioning
Installation location
NOTICE
Installation location
Device position / permitted temperature range
Installation location
Requirement: Configuration prior to commissioning
4.2 Installing, connecting up and commissioning
The module must be installed so that its upper and lower ventilation slits are not covered, allowing adequate ventilation. Above and below the device, there must be a clearance of 25 mm to allow air to circulate and prevent overheating.
Remember that the permitted temperature ranges depend on the position of the installed device.
Horizontal installation of the rack:
-20 °C to +70 °C
Vertical installation of the rack:
-20 °C to +60 °C
One requirement for the commissioning of the module is the completeness of the STEP 7 project data (see below, step 5).
CP 1243-1 PCC
26 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 27
Installation, connecting up, commissioning
Installing, connecting up and commissioning the module
Note Connection with power off
Only wire up the S7
Step
What to do
Notes and explanations
1
The slots to the left of the CPU are permitted.
2
Secure the DIN rail.
3
specifications (Page 61).
4
Turn on the power supply.
5
6
them closed during operation.
4.2 Installing, connecting up and commissioning
-1200 with the power turned off.
Table 4- 2 Procedure for installation and connecting up
Mount the CP on the DIN rail and connect it to
the module to its right.
Connect the Ethernet cable to the CP. You will find the pinout of the interface in the section Technical
The remaining steps in commissioning involve
downloading the STEP 7 project data.
Close the front covers of the module and keep
Use a 35 mm DIN rail.
The STEP 7 project data of the CP is transferred when you load to the station. To load the station, connect the engineer­ing station on which the project data is located to the Ethernet interface of the CPU.
You will find more detailed information on loading in the follow­ing sections of the STEP 7 information system:
"Loading project data"
"Using online and diagnostics functions"
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
27
Page 28
Installation, connecting up, commissioning
4.2 Installing, connecting up and commissioning
CP 1243-1 PCC
28 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 29
5
5.1

Note on operation

NOTICE
Closing the front panels
5.2

Configuration in STEP 7

Configuration in STEP 7
STEP 7 online help in "Support Packages"
Requirement for configuring the Plant Cloud Communication
To ensure interference-free operation, keep the front panels of the module closed during operation.
You configure the modules and networks in SIMATIC STEP 7. You will find the required version in the section Software requirements (Page 15).
You can configure a maximum of three CMs/CPs per station.
The current online help topics dealing with the CP and the security functions are available in the STEP 7 information system under the entry "Support Packages".
One requirement for configuring communication between CP and operation center is the programming of the assigned CPU and the input and output data of the station.
PLC tags must also be created to assign the user data to be transferred to the data points. When assigning the PLC tags to your communications partners, you can select both operation centers.
For more detailed information, refer to the following sections.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
29
Page 30
Configuration and operation
Required information for the Plant Cloud Communication
Overview of the configuration steps in STEP 7
5.2 Configuration in STEP 7
The following information is required for the STEP 7 configuration of the CP:
Address of the operation center The URL address of the operation center.
DNS server address(es)
You require the DNS server address if you address the operation center using a name that can be resolved by DNS and the DNS is not operated by the network provider. You configure DNS in the parameter group "DNS configuration":
– If you do not specify an address, the DNS server address is obtained automatically
from the network provider (recommended procedure).
– If you want to use a different DNS server, enter its IP address. In this case, DNS
servers of the network provider are not taken into account.
Follow the steps below when configuring:
1. Create a STEP 7 project.
2. Insert the required SIMATIC stations.
3. Insert the CPs and the required input and output modules in the stations.
4. Create an Ethernet network.
5. Connect the stations to the Ethernet subnet.
6. Configure the inserted CPs.
7. Save and compile the project.
8. Download the project data to the stations.
Using the "Download to device" function, the STEP -7 project data including the configuration data of the CPs is downloaded to the relevant CPU.
You will find further information on the individual steps in the following sections and in the help system of STEP 7.
CP 1243-1 PCC
30 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 31
Configuration and operation
5.3
Address and authentication information
IP address of the CP
Address and authentication information for the Plant Cloud Communication
Parameters in the "Operation center" parameter group
Parameters in the "Security" -> "Operation center" parameter group
Importing the certificate with encrypted transfer

5.3 Address and authentication information

Since the CP always establishes the connection to the operation center, a dynamic IP address can be assigned to the CP by the Internet service provider.
The following information is required for the STEP 7 configuration of the CP for the Plant Cloud Communication with the operation center :
Operation center address
URL address via which the operation center is connected to the Internet.
Operation center number
The operation center number for the relevant operation center is assigned automatically by the system when Plant Cloud Communication is enabled.
Operation center key
You obtain the Operation center key from the operator of the operation center. Copy the key to the input box "Operation center key".
To be able to use encrypted transfer, you need to load the relevant certificate in the certificate manager of STEP 7. You receive the certificate from the provider of the operation center.
To import the certificate, follow these steps:
1. Save the certificate from your operation center operator in the file system of the
engineering station.
2. In STEP 7, select the entry "Global security settings > Certificate manager" in the "Project
tree".
3. Change to the "Trusted certificates and root certification authorities" tab.
4. Select any row in the table "Trusted certificates and root certification authorities".
5. Select the "Import" entry in the shortcut menu.
6. In the dialog that follows, select the required certificate.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
31
Page 32
Configuration and operation
5.4
Configuring data points and messages
Data point-related communication with the CPU
Requirement: Created PLC tags and/or data blocks (DBs)
Note Number of PLC tags
Remember the maximum possible number of PLC tags the can be used for data point configuration in the section
Access to the memory areas of the CPU

5.4 Configuring data points and messages

No program blocks need to be programmed for the CP to transfer user data between the station and communications partner. The data areas in the memory of the CPU intended for communication with the partner are configured data point-related on the CP. Each data point is linked to a PLC tag or a data block on the CPU.
PLC tags or DBs must first be created in the CPU program to allow configuration of the data points.
The PLC tags for data point configuration can be created in the standard tag table or in a user-defined tag table. All PLC tags intended to be used for data point configuration must have the attribute "Visible in HMI".
Address areas of the PLC tags are input, output or bit memory areas on the CPU.
The formats and S7 data types of the PLC tags that are compatible with the protocol-specific data point types of the CP can be found in the section Datapoint types (Page 33).
The values of the PLC tags or DBs referenced by the data points are read and transferred to the communications partner by the CP.
Data received from the communications partner is written by the CP to the CPU via the PLC tags or DBs.
Configuration limits and performance data (Page 13).
CP 1243-1 PCC
32 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 33
Configuration and operation
Configuring the data points and messages in STEP 7
5.5
Datapoint types

5.5 Datapoint types

You configure the data points in STEP 7 in the editor for the data point and message configuration. You can find this using the project tree:
Project > directory of the relevant station > Local modules > CP 1200
Figure 5-1 Configuring data points and messages
You will find more information on configuration in the following sections and in the STEP 7 information system.
During the configuration of the user data to be transferred by the CP, each data point is assigned a protocol-specific data point type. The data point types supported by the CP along with the compatible S7 data types are listed below. They are grouped according to format (memory requirements).
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
33
Page 34
Configuration and operation
Supported data point types of the CP
Note Plant Cloud in the operation center cannot process ARRAY
The Plant Cloud in the operation center does not support the ARRAY this data type are discarded by the operation center. Make sure that you take this into account in the configuration of the data points.
Format (memory re­quirements)
Data point type
S7 data types
Address area Bit
Digital input
BOOL
I, Q, M, DB
Byte
Digital input
BYTE
I, Q, M, DB
Integer with sign (16 bits)
Analog input
INT
I, Q, M, DB
Counter (16 bits)
Counter input
WORD, UINT
I, Q, M, DB
Integer with sign (32 bits)
Analog input
DINT
I, Q, M, DB
Counter (32 bits)
Counter input
DWORD, UDINT
I, Q, M, DB
Floating-point number with sign (32 bits)
Floating-point number with sign (64 bits)
Block of data (1 ... 64 bytes)
1)
For the possible formats of the ARRAY data type, refer to the following section.
Block of data (ARRAY)
Time stamp in UTC format
5.5 Datapoint types
data type. Transfers of
Table 5- 1 Supported data point types and compatible S7 data types
Analog input REAL Q, M, DB
Analog input LREAL Q, M, DB
Data ARRAY 1) DB
With the ARRAY data type, contiguous memory areas up to a size of 64 bytes can be transferred.
Compatible components of ARRAY are the following uniform S7 data types with a size between 1 and 32 bytes:
BYTE, CHAR (in total up to 64 times per block of data)
INT (in total up to 32 times per block of data)
DINT, UDINT (in total up to 16 times per block of data)
If the array is modified later, the data point must be recreated.
Time stamps are transferred in UTC format (48 bits) and contain the time difference in milliseconds since 01.01.1970.
CP 1243-1 PCC
34 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 35
Configuration and operation
5.6
CPU scan cycle
Structure of the CPU scan cycle
High-priority read jobs
Write jobs
Low-priority read jobs - proportion
Cycle pause time
Duration of the CPU scan cycle

5.6 CPU scan cycle

The cycle (including the pause) with which the CP scans the memory area of the CPU is made up of the following phases:
For data points of the type "Input", which are configured with the "High priority" setting in the data point configuration in "General > Priority in the scan cycle", the PLC tags are all read in one scan cycle.
In every cycle, the values of a certain number of unsolicited write jobs are written to the CPU. The number of tags written per cycle is specified for the CP in the "Communication with the CPU" parameter group with the "Max. number of write jobs" parameter. The tags whose number exceeds this value are then written in the next or one of the following cycles.
For data points of the type "Input", which are configured with the "Low priority" setting in the data point configuration in "General > Priority in the scan cycle", the values of a part of the PLC tags are read in every scan cycle.
The number of tags read per cycle is specified for the CP in the "Communication with the CPU" parameter group with the "Max. number of read jobs" parameter. The tags that exceed this value and can therefore not be read in one cycle are then read in the next or one of the following cycles.
This is the waiting time between two scan cycles. It is used to reserve adequate time for other processes that access the CPU via the backplane bus of the station.
Since no fixed time can be configured for the cycle and since the individual phases cannot be assigned a fixed number of objects, the duration of the scan cycle is variable and can change dynamically.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
35
Page 36
Configuration and operation
5.7
Types of transmission, event classes, triggers, status identifiers
Classification of the data points and storage of the values
No event (static value)
Event
The image memory
The send buffer

5.7 Types of transmission, event classes, triggers, status identifiers

The values of data points are stored in the image memory of the CP and transferred only when called by the operation center. Events are also stored in the send buffer and can be transferred unsolicited. All data points are therefore classified as follows:
All the current values of the configured data points are stored in the image memory. New values of a data point overwrite the last stored value in the image memory.
The values are sent after being queried by the communications partner. Refer to "Transfer after call" in the section "Types of transmission".
The send buffer is the data buffer on the CP for storing the values of events. The send buffer has a maximum size of 64 000 events. The configured number of events is divided equally among all configured and enabled communications partners. The "Data buffer size" parameter for the size of the send buffer is described in the section Communication with the CPU (Page 47).
Data points that are not configured as an event ("Transfer after call") are entered in the image memory (process image of the CP).
The values of data points configured as an event are also entered in the image memory of the CP. The value of the event is sent unsolicited to the operation center.
The values of events are also entered in the send buffer of the CP.
If a connection to a communications partner is interrupted, the values of the events are retained in the buffer. When the connection returns, the buffered frames are sent.
The frame memory operates chronologically; in other words, the oldest frames are sent first (FIFO principle). When the maximum number of events is reached and the frames could not be sent, the oldest values are overwritten.
CP 1243-1 PCC
36 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 37
Configuration and operation
Types of transmission
Transfer after call
Event class
Event classes
Every value triggered
Current value triggered
Trigger
Threshold value trigger
Time trigger
Event trigger
Resetting the trigger bit in the bit memory area / DB
5.7 Types of transmission, event classes, triggers, status identifiers
Depending on your CP type, you have the following transmission types available:
The current value of the data point is entered in the image memory of the CP. New values of a data point overwrite the last stored value in the image memory.
After being called by the communications partner, the current value at the time is transferred.
The value is entered in the send buffer as an event and transferred unsolicited to the communications partner when the trigger fires.
You will find details of the event classes and triggers in the following sections.
The type of transmission is specified for each data point in the data point configuration in STEP 7 with the "Type of transmission" or "Event class" parameter.
The process data of the various event classes is handled as follows:
Each value change is entered in the send buffer in chronological order.
Only the current value at the time the trigger condition was met is entered in the image memory and overwrites the last value stored there.
Various trigger types are available for starting event-driven transfer:
The value of the data point is transferred when this reaches a certain threshold. The threshold is calculated as the difference compared with the last stored value, refer to the section Threshold value trigger (Page 52).
The value of the data point is transferred at configurable intervals or at a specific time of day.
The value of the data point is transferred when a configurable trigger signal is fired. For the trigger signal, the edge change (0 → 1) of a trigger bit is evaluated that is set by the user program. When necessary, a separate trigger bit can be configured for each data point.
If the memory area of the trigger bit is in the bit memory or in a data block, the trigger bit is reset to zero when the data point is transferred.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
37
Page 38
Configuration and operation
Generation of events if a data point status changes
Status IDs of data points
Bit
7 6 5 4 3 2 1
0
Flag name EXISTENT
Meaning
ble
Bit status
(always 0)
1 1 1 1 1 1 1
5.7 Types of transmission, event classes, triggers, status identifiers
With data points that were configured as an event, the change to the status bit of the status identifiers described below also leads to an event being generated.
Example: If the status "RESTART" of a data point configured as an event changes to "Value updated" when the station starts up, this causes an event to be generated.
The status IDs listed in the following tables are transferred for each data point in each frame in 1 byte.
The meaning relates to the bit status in the last row of each table.
Table 5- 2 Byte assignment of the status byte for data points
- NON_
- Data point does not exist or S7 address unreacha-
SB Substituted
Substitute value
LOCAL_ FORCED
Local oper­ator control
CY CARRY
Counted value over­flow before reading the value
OVER_ RANGE
Analog value: Val­ue range exceeded
RESTART ONLINE
Value not updated after start
Value is invalid
CP 1243-1 PCC
38 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 39
Configuration and operation
5.8
Security functions
5.8.1

Firewall

5.8.1.1
Firewall sequence when checking incoming and outgoing frames
5.8.1.2
Notation for the source IP address (advanced firewall mode)
5.8.2

Filtering of the system events

Communications problems if the value for system events is set too high

5.8 Security functions

Note the range and application of the security functions of the CP, refer to the section Other services and properties (Page 11).
Each incoming or outgoing frame initially runs through the MAC firewall (layer 2). If the frame is discarded at this level, it will not be checked by the IP firewall (layer 3). This means that with suitable MAC firewall rules, IP communication can be restricted or blocked.
If you specify an address range for the source IP address in the advanced firewall settings of the CP, make sure that the notation is correct:
Separate the two IP addresses only using a hyphen.
Correct: 192.168.10.0-192.168.10.255
Do not enter any other characters between the two IP addresses.
Incorrect: 192.168.10.0 - 192.168.10.255
If you enter the range incorrectly, the firewall rule will not be used.
If the value for filtering the system events is set too high, you may not be able to achieve the maximum performance for the communication. The high number of output error messages can delay or prevent the processing of the communications connections.
In "Security > Log settings > Configure system events", set the "Level:" parameter to the value "3 (Error)" to ensure the reliable establishment of the communications connections.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
39
Page 40
Configuration and operation
5.9
Time-of-day synchronization
Procedure for time-of-day synchronization
Note Special feature of time-of-day synchronization using NTP
If the "Accept time from non accepts the
If the option is disabled, the response is as follows:
If the CP receives a time of day frame from an unsynchronized NTP server with stratum 16, the time of day is not set according servers is displayed as "NTP master" in the diagnostics; but rather only as being "reachable".
NTP (secure) with security functions enabled
Note Ensuring a valid time of day
If you use security use the NTP
Configuration

5.9 Time-of-day synchronization

The CP supports the three methods of time-of-day synchronization:
Time from partner
In this case, the time of day is synchronized by the operation center. This method is enabled automatically if the Plant Cloud Communication and Security functions are enabled in "Communication types" in STEP 7.
To be able to receive the time of day from the operation center, "Operation center" and "Operation centers" need to be fully configured.
NTP or NTP (secure)
If Plant Cloud Communication is disabled, the time of day can only be synchronized using NTP or NTP (secure). Here, configure the synchronization mode, the local time zone of the station, the synchronization interval and the addresses of the NTP servers.
time from NTP servers that are not directly synchronized with stratum 16.
In the extended NTP configuration, you can create and manage additional NTP servers including those of the type NTP (secure).
The secure method NTP (secure) uses authentication with symmetrical keys according to the hash algorithms MD5 or SHA-1.
functions, a valid time of day is extremely important. It is recommended to
(secure) method.
-synchronized NTP servers" option is enabled, the CP also
to the frame. In this case, none of the NTP
For information on configuration, refer to the STEP 7 online help of the "Time-of-day synchronization" parameter group.
CP 1243-1 PCC
40 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 41
Configuration and operation
5.10
SNMP
SNMP (Simple Network Management Protocol)
Range of performance of the CP as an SNMP agent

5.10 SNMP

SNMP is a protocol for managing networks and nodes in the network. To transmit data, SNMP uses the connectionless UDP protocol.
The information on the properties of SNMPcompliant devices is entered in MIB files (MIB = Management Information Base).
The CP supports data queries over SNMP in the following version:
SNMPv1 (standard)
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
41
Page 42
Configuration and operation
MIB II
Siemens Automation MIB
Access permissions using community name
Type of access
Community name *)
Read access
public
*) Note the use of lowercase letters!
5.10 SNMP
It returns the contents of MIB objects of the standard MIB II according to RFC 1213 and the Siemens Automation MIB.
The CP supports the following groups of MIB objects:
– System
– Interfaces
The "Interfaces" MIB object provides status information about the CP interfaces.
– IP (IPv4 and IPv6)
– ICMP
– TCP
– UDP
– SNMP
The other groups of the MIB II standard are not supported:
– Address Translation (AT)
– EGP
– Transmission
The following exceptions / restrictions apply to the CP.
Write access is permitted only for the following MIB objects of the system group:
– sysContact
– sysLocation
– sysName
A set sysName is sent as the host name using DHCP option 12 to the DHCP server to register with a DNS server.
For all other MIB objects / MIB object groups, only read access is possible for security reasons.
Traps are not supported by the CP.
The CP uses the following community names to control the access rights in the SNMP agent:
Table 5- 3 Access rights in the SNMP agent
Read and write access private
CP 1243-1 PCC
42 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 43
Configuration and operation
5.11
STEP 7 configuration of individual parameters
Note Information in STEP 7 and in the manual
If there are discrepancies between the following descriptions and the information in STEP 7 / Professional V13, the information in this document is valid.
5.11.1

Communication types and SNMP

"Communication types" parameter group
Enable Plant Cloud Communication
Activate online functions
Enabling S7 communication
"SNMP" parameter group
Enable SNMP

5.11 STEP 7 configuration of individual parameters

Below, you will find information on the configuration of individual functions grouped according to parameter groups in STEP 7.
In this parameter group, you enable the communication type of the CP.
To minimize the risk of unauthorized access to the station via Ethernet, you need to enable the communications services that the CP will execute individually. You can enable all options but at least one option should be enabled.
Enables communication with the operation center on the CP. Two operation centers can be configured.
Enables access to the CPU for the online functions via the CP (diagnostics, loading project data etc.). If the function is enabled, the engineering station can access the CPU via the CP.
If the option is disabled, you have no access to the CPU via the CP with the online functions. Online diagnostics of the CPU with a direct connection to the interface of the CPU however remains possible.
Enables the functions of S7 communication with a SIMATIC S7 on the CP.
If you configure S7 connections to the relevant station, and these run via the CP, you will need to enable this option.
Enables communication using SNMP on the CP.
If security functions are enabled, you will find the entry in "Security".
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
43
Page 44
Configuration and operation
5.11.2

Ethernet interface (X1) > Advanced options

TCP connection monitoring
TCP connection monitoring time
TCP keepalive monitoring time
5.11.3

Operation center

Operation center
Enable operation center
Operation center number
5.11 STEP 7 configuration of individual parameters
The setting made here applies globally to all TCP connections of the CP.
Note the option of overwriting the value configured here for individual operation centers, refer to the section Operation center1 or Operation center2 (Page 45).
If there is no data traffic within the connection monitoring time, the CP sends a keepalive to the communications partner.
Permitted range: 0 ... 65535 s
Default setting: 180 s; if you enter 0 (zero), the function is deactivated.
The monitoring time is configured for the Ethernet interface as the default for all TCP connections. The default value can be adapted individually for each connection in "Operation center".
After sending a keepalive, the CP expects a reply from the communications partner within the keepalive monitoring time. If the CP does not receive a reply within the configured time, it terminates the connection.
Permitted range: 0 ... 65535 s
Default setting: 1 s; if you enter 0 (zero), the function is deactivated.
The monitoring time is configured for the Ethernet interface as the default for all TCP connections. The default value can be adapted individually for each connection in "Operation center".
Selecting the option enables communication with the configured operation center on the CP. You have option of configuring two operation centers.
The Operation center number in this parameter group is set by the system. It is required for data point configuration.
CP 1243-1 PCC
44 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 45
Configuration and operation
5.11.3.1
Operation center1 or Operation center2
Connection to operation center
Operation center address
Connection monitoring
TCP connection monitoring time
TCP keepalive monitoring time
5.11 STEP 7 configuration of individual parameters
The URL address of the operation center.
When the function is enabled, the connection to the communications partner (operation center) is monitored by sending keepalive frames.
The TCP connection monitoring time is set for all TCP connections of the CP in the parameter group of the Ethernet interface, see also the section Ethernet interface (X1) > Advanced options (Page 44). The setting applies to all TCP connections of the CP.
Here in the parameter group "Operation center", the globally set TCP connection monitoring time can be set separately for the operation center. The value set here overwrites the global value for the operation center that was set in the "Ethernet interface (X1) > Advanced options > TCP connection monitoring" parameter group.
Only with TCP: If there is no data traffic within the connection monitoring time, the CP sends a keepalive to the communications partner.
– Permitted range: 0 ... 65535 s
– Default setting: 180 s; if you enter 0 (zero), the function is deactivated.
The monitoring time is configured for the Ethernet interface as the default for all TCP connections. The default value can be adapted individually for each connection in "Operation center" and this overwrites the global value for this partner that was set in the parameter group "Ethernet interface (X1) > Advanced options > TCP connection monitoring".
Only with TCP: After sending a keepalive, the CP expects a reply from the communications partner within the keepalive monitoring time. If the CP does not receive a reply within the configured time, it terminates the connection.
– Permitted range: 0 ... 65535 s
– Default setting: 1 s; if you enter 0 (zero), the function is deactivated.
The monitoring time is configured for the Ethernet interface as the default for all TCP connections. The default value can be adapted individually for each connection in "Operation center".
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
45
Page 46
Configuration and operation
Advanced settings
Operation center
Monitoring time for operation center
Connection monitoring time
Reconnection delay
Report operation center status
5.11 STEP 7 configuration of individual parameters
Description of the operation center e.g. name of the server.
If the CP does not receive a response from the communications partner (operation center) within the configured time, the CP interprets this as a fault/error on the partner. With 0, after 5 minutes the lack of a response is interpreted as a connection problem.
If the establishment of an HTTPS connection to the communications partner (operation center) fails, this is interpreted as a connection problem.
Value for the wait time until the next connection establishment following an unsuccessful attempt to establish a connection.
The reconnection delay is the waiting time between repeated attempts to establish the connection by the CP when the operation center is not reachable or the connection has aborted.
A value is configured for the waiting time before the next connection establishment attempt.
With the value 0, the attempts until successful connection establishment are made as default at the following intervals: 3 x 60 s, 3 x 120 s, 4 x 900 s, 23 x 3 600 s (1 hour), 1 x 86 400 s (1 day).
If the "Report operation center status" function is enabled, the CP signals the status of the communication to the operation center.
– Bit 0 of "PLC tag for operation center status" (data type WORD) is set to 1 if the
operation center can be reached.
– Bit 1 is set to 1 if all the paths to the operation center are OK (useful with redundant
paths).
– Bits 2-3 indicate the status of the send buffer (frame memory).
The following values are possible:
- 0: send buffer OK
- 1: send buffer threatening to overflow (more than 80 % full).
- 3: send buffer has overflowed (fill level 100 % reached).
As soon as the fill level drops below 50%, bits 2 and 3 are reset to 0.
Bits 4 to 15 of the PLC tags are not used and do not need to be evaluated in the program.
CP 1243-1 PCC
46 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 47
Configuration and operation
5.11.4

Communication with the CPU

Communication with the CPU > "Data buffer size"
Data buffer size
5.11.5

Data point configuration

5.11.5.1
Configuring the data point names
Character set for data point names
5.11 STEP 7 configuration of individual parameters
Here, you set the size of the send buffer for events.
A maximum of 64 000 events divided up equally among all the communications partners can be buffered.
You will find details of how the send buffer works (storing and sending events) as well as the options for transferring data in the section Ethernet interface (X1) > Advanced options (Page 44).
When a data point is created, the name of the PLC tag is initially adopted. In the "General" tab of the data point you can change the name of the data point.
When assigning the name, only the following ASCII characters can be used: ASCII characters 0x20 ... 0x7e with the exception of the characters listed below.
The following characters are forbidden since they do not adhere to the syntax rules of the operation center for OPC items:
0x27 (apostrophe)
0x2e (period)
0x2f (slash)
0x5b and 0x5d (square brackets)
0x5c (backslash)
0x7c (pipe)
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
47
Page 48
Configuration and operation
5.11.5.2
Threshold value trigger and Analog value preprocessing
Sequence of processing Threshold value trigger and Analog value preprocessing
Note Threshold value trigger: Calculation only after "Analog value preprocessing"
Note that the analog value preprocessing is performed before the check for a configured threshold value.
This affects the value that is configured for the threshold value trigger, refer to the section Threshold value trigger
Restricted preprocessing options if mean value generation is configured
If you preprocessing options are not available:
No Threshold value trigger if Mean value generation is configured
If mean value generation analog value event involved.
Sequence of analog value processing
-
-
5.11 STEP 7 configuration of individual parameters
(Page 52).
configure mean value generation for an analog value event, the following
Unipolar transfer Error suppression time Smoothing
is configured, no threshold value trigger can be configured for the
Analog inputs that are configured as an event are processed on the CP in the following sequence:
1. Reading the data from the input area of the CPU
2. Analog value preprocessing (part 1)
Processing involves the following steps:
– Mean value generation
3. Threshold value calculation (if Threshold value trigger is configured)
4. Analog value preprocessing (part 2)
5. Storage of the value in the send buffer
Mean value generation configured: Calculation and then continued at point 4.
No mean value generation configured: Continue with "Unipolar transfer".
– Unipolar transfer (if configured)
– Error suppression time (if configured)
– Smoothing (if configured)
– Adjustment to the start of measuring range and end of measuring range (if configured)
Transfer of the value to the partner if trigger and threshold value conditions are met.
CP 1243-1 PCC
48 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 49
Configuration and operation
5.11.5.3
Analog value preprocessing
Unipolar transfer
Smoothing factor
5.11 STEP 7 configuration of individual parameters
Depending on the data point type, the functions for analog value preprocessing described below are supported.
If unipolar transfer is enabled, negative values of analog inputs are corrected to zero.
Exception: The value -32768 / 8000 inputs is transferred. With a software input, on the other hand, all values lower than zero are corrected to zero.
If mean value generation is active, this parameter has no effect.
Analog values that fluctuate quickly can be smoothed with this function.
The smoothing factors are calculated according to the following formula as with S7 analog input modules.
where
= smoothed value in the current cycle
y
n
= value acquired in the current cycle n
x
n
k = smoothing factor
as fault ID for wire break of live zero hardware analog
h
The following values can be configured for the module as the smoothing factor.
1 = No smoothing
4 = Weak smoothing
32 = Medium smoothing
64 = Strong smoothing
If mean value generation is active, this parameter has no effect.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
49
Page 50
Configuration and operation
Error suppression time
Recommendation for finished values that were preprocessed by the CPU:
Mean value generation
5.11 STEP 7 configuration of individual parameters
An analog value in the overflow range (32767 / 7FFFh) or underflow range (-32768 / 8000h) is not transferred for the duration of the error suppression time. This also applies to live zero inputs. The value in the overflow/underflow range is only sent after the error suppression time has elapsed, if it is still pending.
If the value returns to the measuring range before the error suppression time elapses, the current value is transferred immediately.
A typical use case for this parameter is the suppression of peak current values when starting up powerful motors that would otherwise be signaled to the control center as a disruption.
The suppression is adjusted to analog values that are acquired by the S7 analog input modules as raw values. These modules return the specified values for the overflow or underflow range for all input ranges (also for live zero inputs).
If mean value generation is active, this parameter has no effect.
If the CPU makes preprocessed finished values available in bit memory or in a data block, suppression is only possible or useful if these finished values also adopt the values listed above 32767 / 7FFF case, the parameter should not be enabled for preprocessed values.
or -32768 / 8000h in the overflow or underflow range. If this is not the
h
With this parameter, acquired analog values are transferred as mean values.
The current values of an analog data point are acquired cyclically and totaled. The number of acquired values per time unit depends on the read cycle of the CPU and the CPU scan cycle of the CP. The mean value is calculated from the accumulated values as soon as the transfer is triggered by a time trigger. Following this, the accumulation starts again so that the next mean value can be calculated.
The mean value can also be calculated if the transmission of the analog value message is triggered by a request from the communications partner. The duration of the mean value calculation period is then the time from the last transmission (for example triggered by the trigger) to the time of the request. Once again, the accumulation restarts so that the next mean value can be calculated.
CP 1243-1 PCC
50 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 51
Configuration and operation
Overflow range / underflow range
Note Fault suppression time > 0 configured
If you have configured an error suppression time and then enable mean value generation, the value of the error suppression time is grayed out but no longer used. If mean value generation is enabled, the
Set start of measuring range / Set end of measuring range
Note Evaluation of the value even when the option is disabled
If you enable one or both options and configure a value and then disable the option later, the grayed out value is nevertheless evaluated.
To disable the two options, delete the previously configured values "Start of measuring range" or "End of measuring range" from the input boxes and then disable the relevant option.
Recommendation for quickly fluctuating analog values:
5.11 STEP 7 configuration of individual parameters
Acquisition of a value in the overflow or underflow range results in the mean calculation being stopped immediately. The value 32767 / 7FFF invalid mean value for the current mean value calculation period and sent when the next analog value frame is triggered. The calculation of a new mean value is then started. If the analog value remains in the overflow or underflow range, this new value is again saved immediately as an invalid mean value and sent when the next frame is triggered.
error suppression time is set to 0 (zero) internally.
or -32768 / 8000h is saved as an
h
In these two input boxes, you set a limit value at the start of the measuring range and at the end of the measuring range and if these limits are violated, the transfer of a frame is triggered. Configuration of a threshold value trigger is necessary for this function.
The range of the value that can be configured as a decimal number corresponds to the measuring range of the analog module (-32768 ... 32767).
By configuring these two values, you specify that the values of this analog value are transferred as a frame only in the following situations:
When the threshold value trigger fires
When the value of "Set start of measuring range" is exceeded
When the value of "Set end of measuring range" is undershot
The parameters "Set start of measuring range" and Set end of measuring range" are pointless for measured values that have already been preprocessed in the CPU.
If the analog value fluctuates quickly, it may be useful to smooth the analog value first if the "Set start of measuring range" and "Set end of measuring range" parameters are enabled. This avoids a frame being sent every time a limit value is violated if the analog value
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
fluctuates close to one of the two limit values for a longer period of time.
51
Page 52
Configuration and operation
5.11.5.4
Threshold value trigger
Threshold value trigger: How the integrattion calculation works
The calculation cycle
5.11 STEP 7 configuration of individual parameters
The CP calculates the value for the threshold value trigger after the analog value preprocessing, refer to the section Threshold value trigger and Analog value preprocessing (Page 48).
To calculate the threshold value trigger, the integration method is used.
In the integration threshold value calculation, it is not the absolute value of the deviation of the process value from the last stored value that is evaluated but rather the amount of the integrated deviation.
The integration threshold value calculation works with a cyclic comparison of the integrated current value with the last stored value. The calculation cycle in which the two values are compared is 500 milliseconds. (Note: The calculation cycle must not be confused with the scan cycle of the CPU memory areas).
The deviations of the current process value are totaled in each calculation cycle. The trigger is set only when the totaled value reaches the configured value of the threshold value trigger and a new process value is entered in the send buffer.
CP 1243-1 PCC
52 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 53
Configuration and operation
Time [s]
(calculation cycle)
Process value
stored in the
send buffer
Current process
value
Absolute deviation
from the stored
value
Integrated devia-
tion
0
20.0
20.0 0 0
1.0 19.8
-0.2
0.1
1.5 20.2
+0.2
0.3
2.0 20.5
+0.5
0.8
2.5 20.3
+0.3
1.1
3.0 20.4
+0.4
1.5
3.5
20.5
20.5
+0.5
2.0
4.0 20.4
-0.1
-0.1
4.5 20.1
-0.4
-0.5
5.0 19.9
-0.6
-1.1
5.5 20.1
-0.4
-1.5
6.0
19.9
19.9
-0.6
-2.1
5.11 STEP 7 configuration of individual parameters
The method is explained based on the following example in which a threshold value of 2.0 is configured.
Table 5- 4 Example of the integration calculation of a threshold value configured with 2.0
0.5 20.3 +0.3 0.3
In this example, a value of 2.0 was configured for the threshold value trigger.
With the changes in the process value shown in the example, the threshold value trigger fires twice, if the value 2.0 is reached:
At the time 3.5 s: The value of the integrated deviation is at 2.0. The new process value stored in the send buffer is 20.5.
At the time 6.0 s: The value of the integrated deviation is at 2.1. The new process value stored in the send buffer is 19.9.
In this example, if a deviation of the process value of approximately 0.5 should fire the trigger, then with the behavior of the process value shown here a threshold value of approximately 1.5 ... 2.5 would need to be configured.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
53
Page 54
Configuration and operation
5.11 STEP 7 configuration of individual parameters
CP 1243-1 PCC
54 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 55
6
6.1

Diagnostics options

LEDs of the module
STEP 7: The "Diagnostics" tab in the Inspector window
STEP 7: Diagnostics functions in the "Online > Online and diagnostics" menu
The following diagnostics options are available.
For information on the LED displays, refer to the section LEDs (Page 18).
Here, you can obtain the following information on the selected module:
Entries in the diagnostics buffer of the CPU
Information on the online status of the module
Using the online functions, you can read diagnostics information from the CP from an engineering station on which the project with the CP is stored. You obtain the following static information on the selected module:
General information on the module
Diagnostics status
Information on the Ethernet interface:
– Network
– Ethernet interface
– Statistics
Information on Plant Cloud Services:
– Operation center
– List of data points
– Protocol diagnostics
– Device-specific event
Security
The information under the "Security" entry is not used for the CP.
If you want to operate online diagnostics with the station via the CP, you need to select Activate online functions, see section Communication types and SNMP (Page 43).
You will find further information on the diagnostics functions of STEP 7 in the STEP 7 information system.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
55
Page 56
Diagnostics and upkeep
6.2
Downloading firmware
New firmware versions of the CP
Loading the firmware with the online functions of STEP 7 via a WAN
Requirements:
Procedure:

6.2 Downloading firmware

If a new firmware version is available for the module, you will find this on the Internet pages of Siemens Industry Online Support under the following entry ID:
51297224 (http://support.automation.siemens.com/WW/view/en/51297224)
On the Internet page, select the "Entry list" tab and the "Download" entry type. There you will find the available firmware files.
There are three different ways of loading a new firmware file on the CP:
Saving the firmware file on the memory card of the CPU
You will find a description of the procedure for loading on the memory card of the CPU on the Internet page of Industry Online Support shown above.
Loading the firmware with the online functions of STEP 7 via a WAN
Downloading the firmware via the Web server of the CPU (as of CPU firmware version
V4.0)
The last two methods are described below.
The CP can be reached using its IP address.
The engineering station and the CP are located in the same subnet.
The new firmware file is stored on your engineering station.
1. Connect the engineering station to the network.
2. Open the relevant STEP 7 project on the engineering station.
3. Select the CP or the CPU of the station whose CP you want to update with new firmware.
4. Enable the online functions using the "Connect online" icon.
5. In the "Connect online" dialog, select the Ethernet interface "PN/IE" in the "Type of PG/PC interface" list box.
6. Select the slot of the CP or the CPU.
Both methods are possible.
7. Connect using the "Connect" button.
The "Connect online" wizard guides you through the remaining steps in installation.
You will find further information on the online functions in the STEP 7 information system.
CP 1243-1 PCC
56 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 57
Diagnostics and upkeep
Downloading the firmware via the Web server of the CPU
Requirements in the CPU configuration
Connection establishment with HTTP
Connection establishment with HTTPS
Connection establishment with HTTP
http
6.2 Downloading firmware
Follow the steps below to connect to the Web server of the CPU from the engineering station and to download the CP's new firmware file to the station.
1. Open the corresponding project on the engineering station.
2. Select the CPU of the station involved in STEP 7.
3. Select the "Web server" entry.
4. In the parameter group "General", select the "Enable Web server for this interface"
option.
5. With a CPU version V4.0 or higher, create a user in the user management with the name
"admin".
You need to assign the right to perform firmware updates in the access level.
The procedure for establishing a connection to the Web server depends on whether you have enabled or disabled the "Allow access only using HTTPS" option in the "General" parameter group:
Procedure if the "Allow access only using HTTPS" option is disabled
Procedure if the "Allow access only using HTTPS" option is enabled
These two variants are described in the following sections.
Requirement: The new firmware file is stored on your engineering station.
You will find the requirements for access to the Web server of the CPU (permitted Web browser) and the description of the procedure in the STEP 7 information system under the keyword "Information about the Web server".
1. Connect the PC on which the new firmware file is located to the CPU via the Ethernet
interface.
2. Enter the address of the CPU in the address box of your Web browser:
address>
3. Press the Enter key.
The start page of the Web server opens.
4. Click on the "Download certificate" entry at the top right of the window.
The "Certificate" dialog opens.
://<IP
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
57
Page 58
Diagnostics and upkeep
https
Connection establishment with HTTPS
http
Loading firmware
6.2 Downloading firmware
5. Download the certificate to your PC by clicking the "Install certificate ..." button.
The certificate is loaded on your PC.
You will find information on downloading a certificate in the help of your Web browser and in the STEP 7 information system under the key words "HTTPS" or "Access for HTTPS (S7-1200)".
6. When the connection has changed to the secure mode HTTPS ("
://<IP address>/..." in the address box of the Web server), you can continue as described in the next section "Downloading firmware".
If you terminate the connection to the Web server, the next time you can log in with the Web server without downloading the certificate using HTTP.
1. Connect the PC on which the new firmware file is located to the CPU via the Ethernet interface.
2. Enter the address of the CPU in the address box of your Web browser:
s://<IP
address>
3. Press the Enter key.
The start page of the Web server opens.
4. Continue as described in the following section "Downloading firmware".
1. Log in on the start page of the Web server as an administrator.
– User name: admin
– Password: No password necessary
2. After logging in, select the entry "Module status" in the navigation panel of the Web server.
3. Select the CP in the module list.
4. Select the "Firmware" tab lower down in the window.
5. Browse for the firmware file on your PC using the "Browse..." button and download the file to the station using the "Run update" button.
CP 1243-1 PCC
58 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 59
Diagnostics and upkeep
6.3
Module replacement
Module replacement
CAUTION
Read the system manual "S7-1200 Programmable Controller"

6.3 Module replacement

Prior to installation, connecting up and commissioning, read the relevant sections in the system manual "S7-1200 Programmable Controller" (refer to the documentation in the Appendix).
When installing and connecting up, keep to the procedures described in the system manual "S7-1200 Programmable Controller".
Make sure that the power supply is turned off when installing/uninstalling the devices.
The STEP -7 project data of the CP is stored on the local CPU. If there is a fault on the device, this allows simple replacement of the CP without needing to download the project data to the station again.
When the station starts up again, the new CP reads the project data from the CPU.
Siemens Automation
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
59
Page 60
Diagnostics and upkeep
6.3 Module replacement
CP 1243-1 PCC
60 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 61
7
7.1

Technical specifications of the CP 1243-1 PCC

Technical specifications

Article number
6GK7 243-1HX30-0XE0
Attachment to Industrial Ethernet
Transmission speed
10/100 Mbps
Permitted cable lengths (Ethernet)
(Alternative combinations per length range) *
Electrical data
Power supply
From the S7-1200 backplane bus
5 VDC
Current consumption (typical)
From the S7-1200 backplane bus
250 mA
Effective power loss (typical)
From the S7-1200 backplane bus
1.25 W
Permitted ambient conditions
stalled horizontally
stalled vertically
During storage
-40 ℃ to +70 ℃
During transportation
-40 ℃ to +70 ℃
Relative humidity
During operation
≤ 95 % at 25 °C, no condensation
Table 7- 1 Technical specifications of the CP
Quantity 1 Design RJ-45 jack Properties 100BASE-TX, IEEE 802.3-2005, half duplex/full duplex, autocrossover, autonego-
tiation, galvanically isolated
0 to 55 m
0 to 85 m
0 to 100 m
Ambient temperature During operation with the rack in-
Max. 55 m IE TP Torsion Cable with IE FC RJ45 Plug 180
Max. 45 m IE TP Torsion Cable with IE FC RJ45 + 10 m TP Cord via
IE FC RJ45 Outlet
Max. 85 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable with IE FC RJ45 Plug 180
Max. 75 m IE FC TP Marine/Trailing/Flexible/FRNC/Festoon/Food Cable + 10 m TP Cord via IE FC RJ45 Outlet
Max. 100 m IE FC TP Standard Cable with IE FC RJ45 Plug 180
Max. 90 m IE FC TP Standard Cable + 10 m TP Cord via IE FC RJ45 Outlet
During operation with the rack in-
-20 °C to +70 °C
-20 °C to +60 °C
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
61
Page 62
Technical specifications
Technical specifications
Design, dimensions and weight
Module format
Compact module for S7-1200, single width
Degree of protection
IP20
Weight
122 g
Dimensions (W x H x D)
30 x 110 x 75 mm
Switch panel
Product functions **
* **
7.2
Pinout of the Ethernet interface
Pinout of the Ethernet interface
View of the RJ-45 jack
Pin
Signal name
Assignment
1
TD
Transmit data +
2
TD_N
Transmit data -
3
RD
Receive data +
4
GND
Ground 5 GND
Ground
6
RD_N
Receive data -
7
GND
Ground
8
GND
Ground

7.2 Pinout of the Ethernet interface

Installation options Standard DIN rail
For details, refer to the IK PI catalog, cabling technology
You will find further characteristics and performance data in the section Application and
properties (Page 9).
The table below shows the pin assignment of the Ethernet interface. The pin assignment corresponds to the Ethernet standard 802.3-2005, 100BASE-TX version.
Table 7- 2 Pin assignment of the Ethernet interface
CP 1243-1 PCC
62 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 63
A
Current approvals on the Internet
Other approvals
You will also find the current approvals for the product on the Internet pages of Siemens Industry Online Support under the following entry ID:
51297224 (http://support.automation.siemens.com/WW/view/en/51297224) → "Entry list" tab, entry type "Certificates"
SIMATIC NET products are regularly submitted to the relevant authorities and approval centers for approvals relating to specific markets and applications.
If you require a list of the current approvals for individual devices, consult your Siemens contact or check the Internet pages of Siemens Industry Online Support:
10805878 (http://support.automation.siemens.com/WW/view/en/10805878)
Under this entry, go to the relevant product and select the following settings: "Entry list" tab > entry type "Certificates".
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
63
Page 64
Approvals
Approvals issued
Note Issued approvals on the type plate of the device
The specified approvals apply only when the corresponding mark is printed on the product. You can check which of the following approvals have been granted for your markings on the type plate.
EC declaration of conformity
product by the
The CP has the following approvals and meets the following standards:
The CP meets the requirements and safety objectives of the following EU directives and it complies with the harmonized European standards (EN) for programmable logic controllers which are published in the official documentation of the European Union.
EC directive 2006/95/EEC "Electrical Equipment Designed for Use within Certain Voltage Limits" (Low Voltage Equipment Directive)
EN 60950-1 Information Technology Equipment - Safety
EC Directive 2004/108/EC "Electromagnetic Compatibility" (EMC Directive)
– Emission
EN 61000-6-4:2007: Industrial area
– Immunity
EN 61000-6-2:2005: Industrial area
The EC Declaration of Conformity is available for all responsible authorities at:
Siemens Aktiengesellschaft Industry Automation Industrielle Kommunikation SIMATIC NET Postfach 4848 D-90327 Nürnberg Germany
You will find the EC Declaration of Conformity for this product on the Internet at the following address:
51297224 (http://support.automation.siemens.com/WW/view/en/51297224) → "Entry List" tab
Filter settings: Entry type: "Certificates" Certificate Type: "Declaration of Conformity" Search items(s): <name of the module>
CP 1243-1 PCC
64 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 65
Approvals
ATEX
WARNING
Installation guidelines
ATEX approval: II 3 G Ex nA IIC T4 Gc
Relevant standards:
EN 60079-0:2006: Potentially explosive atmosphere - general requirements
EN 60079-15:2005: Electrical apparatus for explosive gas atmospheres; type of
protection 'n'
The device is suitable for use in environments with pollution degree 2.
The device is suitable for use only in environments that meet the following conditions:
Class I, Division 2, Group A, B, C, D and areas where there is no risk of explosion
Class I, Zone 2, Group IIC and areas where there is no risk of explosion
The product meets the requirements if you keep to the following during installation and operation:
The notes in the section Important notes on using the device (Page 21)
The installation instructions in the document /1/ (Page 69)
Over and above this, the following conditions must be met for the safe deployment of the CP:
Install the modules in a suitable enclosure with degree of protection of at least IP54 to
EN 60529 and take into account the environmental conditions for operation of the devices.
If the rated temperatures of 70°C at the cable entry or 80°C at the branching point of the
wires are exceeded, the permitted temperature range of the selected cable must be suitable for the actual measured temperatures.
Measures must be taken to prevent the rated voltage being exceeded by more than 40%
due to transient disturbances.
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
65
Page 66
Approvals
cULus HAZ.LOC.
FM
C-Tick
EAC (Eurasian Conformity)
Underwriters Laboratories Inc. meets
Underwriters Laboratories, Inc.: UL 508 Listed (industrial control devices)
UL 1604 (Hazardous Location)
Canadian Standards Association: CSA C22.2 No 142 (process control equipment)
CSA C22.2 No. 213 (Hazardous Location)
APPROVED for Use in:
Cl. 1, Div. 2, GP. A, B, C, D T4A; Ta = -20 °C...60 °C
Cl. 1, Zone 2, GP. IIC T4; Ta = -20 °C...60 °C
Factory Mutual Research (FM): Approval Standard Class Number 3600 and 3611 approved for use in: Class I, Division 2, Group A, B, C, D, Temperature Class T4A, Ta = 60 °C Class I, Zone 2, Group IIC, Temperature Class T4, Ta = 60 °C
The CP meets the requirements of the AS/NZS 2064 standards (Class A)
Customs union of Russia, Belarus and Kazakhstan
Declaration of the conformity according to the technical regulations of the customs union (TR CU)
CP 1243-1 PCC
66 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 67
B
Note
All
dimensions in the drawings of the CP are in millimeters.
Figure B-1 Front view and side view left
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
67
Page 68
Dimension drawings
Figure B-2 From above
CP 1243-1 PCC
68 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 69
C
Where to find Siemens documentation
/1/
You will find the article numbers for the Siemens products of relevance here in the
following catalogs:
– SIMATIC NET Industrial Communication / Industrial Identification, catalog IK PI
– SIMATIC Products for Totally Integrated Automation and Micro Automation, catalog
ST 70
You can request the catalogs and additional information from your Siemens representative.
You will find SIMATIC NET manuals on the Internet pages of Siemens Automation
Customer Support:
Link to Customer Support (http://support.automation.siemens.com/WW/view/en)
Enter the entry ID of the relevant manual as the search item. The ID is listed below some of the reference entries in brackets.
As an alternative, you will find the SIMATIC NET documentation on the pages of Product Support:
10805878 (http://support.automation.siemens.com/WW/view/en/10805878)
Go to the required product group and make the following settings:
"Entry list" tab, Entry type "Manuals / Operating Instructions"
You will find the documentation for the SIMATIC NET products relevant here on the data
medium that ships with some products:
– Product CD / product DVD or
– SIMATIC NET Manual Collection
SIMATIC S7-1200 Programmable Controller System Manual Siemens AG Current issue under the following entry ID: 34612486 (http://support.automation.siemens.com/WW/view/en/34612486)
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
69
Page 70
Documentation references
/2/
SIMATIC NET Industrial Ethernet Security Basics and Application configuration manual Siemens AG Entry ID: 18701555 (http://support.automation.siemens.com/WW/view/en/18701555)
CP 1243-1 PCC
70 Operating Instructions, 02/2015, C79000-G8976-C384-01
Page 71
A
C
D
E
F
G
H
I
M
N
O
P
R
Abbreviations/acronyms, 4 Analog value preprocessing, 49 Article number, 3
Communication with the CPU, configuration, 32 Connection resources, 13 CPU firmware, 15
Data buffering, 14 Data point configuration, 32 Dimensions, 25 DNS, 30
Encryption, 10 ES - engineering station, 12 Ethernet interface
Assignment, 62 Event classes, 37 Events, 36
Image memory, 36 IP address assignment
Obtaining from DHCP server, 11 Setting manually, 11
IP configuration
IPv4, IPv6, 11
MAC address, 3 MIB, 41
NTP, 40 NTP (secure), 40
Online diagnostics, 43, 55 Online functions, 12, 55 Online help (STEP 7), 29 Operating statuses (LED displays), 19
Firewall, 12 Firmware version, 3 Frame memory, 14
Glossary, 5
Hardware product version, 3
CP 1243-1 PCC Operating Instructions, 02/2015, C79000-G8976-C384-01
Siemens Automation
PG/OP connections, 13 Plant Cloud Communication
Address and authentication information, 31 Importing a certificate, 31 Requirement for configuration, 29
Requirements for CP configuration, 9 Plant Cloud Services, 55 Priority of the read jobs, 35 Process image, 36 Product name, 4 PUT/GET, 13
Read jobs, 35 Replacing a module, 59
71
Page 72
Index
S
T
W
Requirements for CP configuration
Plant Cloud Communication, 9
Reset trigger bit, 37
S7 connections
Enable, 43
Resources, 13 S7 data types, 32 Safety notices, 21 Security, 12 Send buffer, 14, 36 Service & Support, 6 SIMATIC NET glossary, 5 SNMP, 12, 41 Status IDs - data points, 38 STEP 7 information system, 29 STEP 7 version, 15
Threshold value trigger, 52 Time stamp, 34 Time-of-day synchronization, 11 Training, 6
Write jobs, 35
CP 1243-1 PCC
72 Operating Instructions, 02/2015, C79000-G8976-C384-01
Loading...