Siemens Schweiz AG User Manual OEM CE1U2353en01a
HVAC Products Table of contents 22. November 2006
Legend
1 Overview of OEM settings
The table below shows all available settings up to the heating engineer level. However,
certain operating lines may be hidden, depending on the type of unit.
E = enduser I = commissioning F = heating engineer O = OEM
BZ = operating line
Operating line
User level
Function
Default value
Minimum
Max
Unit
Time of day and date
1 E Hours/minutes - 00:00 23:59 hh:mm
2 E Day/month - 01.01 31.12 dd.mm
3 E Year - 2004 2099 yyyy
5 F Start of summertime 25.03 01.01 31.12 dd.mm
6 F End of summertime 25.10 01.01 31.12 dd.mm
Operator section
20 E Language
German ¦ …
22 F Info
Temporarily ¦ Permanently
26 F Operation lock
Off ¦ On
27 F Programming lock
Off ¦ On
30 O Data:read
No ¦ Yes
31 O Data:write
No ¦ Yes
40 I Used as
Room unit 1 ¦ Room unit 2 ¦ Operator unit ¦Service unit
54 F Readjustment room sensor 0.0 -3 3 °C
70 F Software version - 0 99.9 Wireless
120 I Binding
No ¦ Yes
121 I Test mode
Off ¦ On
130 I Room unit 1
Missing ¦ Ready ¦ No reception ¦ Change batt
131 I Room unit 2
Missing ¦ Ready ¦ No reception ¦ Change batt
132 I Outside sensor
Missing ¦ Ready ¦ No reception ¦ Change batt
133 I Repeater
Missing ¦ Ready ¦ No reception
No
Off
- -
- -
- -
- -
4/26
Siemens Schweiz AG User Manual OEM CE1U2353en01a
HVAC Products Overview of OEM settings 22. November 2006
Operating line
134 I Operator unit
135 I Service unit
138 I Delete all devices
User level
Function
Missing ¦ Ready ¦ No reception ¦ Change batt
Missing ¦ Ready ¦ No reception ¦ Change batt
No ¦ Yes
Default value
Minimum
Max
- -
- -
No -
Unit
Time prog heating circuit 1
500 E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa
¦Su
Mo - Su -
501 E 1st phase on 6:00 00:00 24:00 hh:mm
502 E 1st phase off 22:00 00:00 24:00 hh:mm
503 E 2st phase on 24:00 00:00 24:00 hh:mm
504 E 2st phase off 24:00 00:00 24:00 hh:mm
505 E 3st phase on 24:00 00:00 24:00 hh:mm
506 E 3st phase off 24:00 00:00 24:00 hh:mm
516 E Default values
No ¦ Yes
No -
Time prog heating circuit 2
520 E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa
¦Su
Mo - Su -
521 E 1st phase on 6:00 00:00 24:00 hh:mm
522 E 1st phase off 22:00 00:00 24:00 hh:mm
523 E 2st phase on 24:00 00:00 24:00 hh:mm
524 E 2st phase off 24:00 00:00 24:00 hh:mm
525 E 3st phase on 24:00 00:00 24:00 hh:mm
526 E 3st phase off 24:00 00:00 24:00 hh:mm
536 E Default values
No ¦ Yes
No -
Time program 3 / HCP
540 E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa
¦Su
Mo - Su -
541 E 1st phase on 6:00 00:00 24:00 hh:mm
542 E 1st phase off 22:00 00:00 24:00 hh:mm
543 E 2st phase on 24:00 00:00 24:00 hh:mm
544 E 2st phase off 24:00 00:00 24:00 hh:mm
545 E 3st phase on 24:00 00:00 24:00 hh:mm
546 E 3st phase off 24:00 00:00 24:00 hh:mm
556 E Default values
No ¦ Yes
No -
Time program 4 / DHW
560 E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa
¦Su
Mo - Su -
561 E 1st phase on 6:00 00:00 24:00 hh:mm
562 E 1st phase off 22:00 00:00 24:00 hh:mm
563 E 2st phase on 24:00 00:00 24:00 hh:mm
564 E 2st phase off 24:00 00:00 24:00 hh:mm
565 E 3st phase on 24:00 00:00 24:00 hh:mm
566 E 3st phase off 24:00 00:00 24:00 hh:mm
5/26
Siemens Schweiz AG User Manual OEM CE1U2353en01a
HVAC Products Overview of OEM settings 22. November 2006
Operating line
576 E Default values
User level
Function
No ¦ Yes
Default value
Minimum
Max
No -
Unit
Holidays heating circuit 1
641 E Preselection
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8
Periode 1 -
642 E Start --.-- 01.01 31.12 dd.mm
643 E End --.-- 01.01 31.12 dd.mm
648 E Operating level
Frost protection ¦ Reduced
Frost protection -
Holidays heating circuit 2
651 E Preselection
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8
Periode 1 -
652 E Start --.-- 01.01 31.12 dd.mm
653 E End --.-- 01.01 31.12 dd.mm
658 E Operating level
Frost protection ¦ Reduced
Frost protection -
Holidays heating circuit P
661 E Preselection
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8
Periode 1 -
662 E Start --.-- 01.01 31.12 dd.mm
663 E End --.-- 01.01 31.12 dd.mm
668 E Operating level
Frost protection ¦ Reduced
Frost protection -
Heating circuit 1
710 E Comfort cooling setpoint 20.0 BZ 712 BZ 716 °C
712 E Reduced setpoint 16 BZ 714 BZ 710 °C
714 E Frost protection setpoint 10.0 4 BZ 712 °C
716 F Comfort setpoint max 35.0 BZ 710 35 °C
720 E Heating curve slope 1.50 0.10 4.00 721 F Heating curve displacement 0.0 -4.5 4.5 °C
726 F Heating curve adaption
Off ¦ On
Off -
730 E Summer/winter heating limit 18 − − − / 8 30 °C
732 F 24-hour heating limit -3 − − − / -10 10 °C
740 I Flow temp setpoint min 8 8 BZ 741 °C
741 I Flow temp setpoint max 80 BZ 740 95 °C
750 F Room influence 20 − − − / 0 100 %
760 F Room temp limitation − − − − − − / 0.5 4 °C
770 F Boost heating 5 − − − / 0 20 °C
780 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint -
790 F Optimum start control max 0 0 360 min
791 F Optimum stop control max 0 0 360 min
800 F Reduced setp increase start − − − − − − / -30 10 °C
801 F Reduced setp increase end -15 -30 BZ 800 °C
820 F Overtemp prot pump circuit
Off ¦ On
On -
830 F Mixing valve boost 10 0 50 °C
6/26
Siemens Schweiz AG User Manual OEM CE1U2353en01a
HVAC Products Overview of OEM settings 22. November 2006
Operating line
832 F Actuator:type
User level
Function
2-position ¦ 3-position
Default value
Minimum
Max
Unit
3-position -
833 F Switching differential 2-pos 2 0 20 °C
834 F Actuator: running time 120 30 873 s
835 O Mixing valve Xp 32 1 100 °C
836 O Mixing valve Tn 120 10 873 s
850 I Floor curing function
851 I Floor curing setp manually 25 0 95 °C
861 F Excess heat draw
Off ¦ Heating mode ¦ Always
872 F With prim contr/system pump
No ¦ Yes
900 I Optg mode changeover
Protection ¦ Recuced
Always
Yes
Protection
Heating circuit 2
1010 E Comfort cooling setpoint 20.0 BZ 1012 BZ 1016 °C
1012 E Reduced setpoint 16 BZ 1014 BZ 1010 °C
1014 E Frost protection setpoint 10.0 4 BZ 1012 °C
1016 F Comfort setpoint max 35.0 BZ 1010 35 °C
1020 E Heating curve slope 1.50 0.10 4.00 1021 F Heating curve displacement 0.0 -4.5 4.5 °C
1026 F Heating curve adaption
Off ¦ On
Off -
1030 E Summer/winter heating limit 18 − − − / 8 30 °C
1032 F 24-hour heating limit -3 − − − / -10 10 °C
1040 I Flow temp setpoint min 8 8 BZ 1041 °C
1041 I Flow temp setpoint max 80 BZ 1040 95 °C
1050 F Room influence 20 − − − / 0 100 %
1060 F Room temp limitation − − − − − − / 0.5 4 °C
1070 F Boost heating 5 − − − / 0 20 °C
1080 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint -
1090 F Optimum start control max 0 0 360 min
1091 F Optimum stop control max 0 0 360 min
1100 F Reduced setp increase start − − − − − − / -30 10 °C
1101 F Reduced setp increase end -15 -30 BZ 1100 °C
1120 F Overtemp prot pump circuit
Off ¦ On
On -
1130 F Mixing valve boost 10 0 50 °C
1132 F Actuator:type
2-position ¦ 3-position
3-position -
1133 F Switching differential 2-pos 2 0 20 °C
1134 F Actuator: running time 120 30 873 s
1135 O Mixing valve Xp 32 1 100 °C
1136 O Mixing valve Tn 120 10 873 s
1150 F Floor curing function
Siemens Schweiz AG User Manual OEM CE1U2353en01a
HVAC Products Overview of OEM settings 22. November 2006
Operating line
User level
Function
Default value
Minimum
Max
Unit
1151 F Floor curing setp manually 25 0 95 °C
1161 F Excess heat draw
Off ¦ Heating mode ¦ Always
1172 F With prim contr/system pump
No ¦ Yes
1200 I Optg mode changeover
Protection ¦ Recuced
Always
Yes
Protection
Heating circuit P
1300 E Operating mode
Protection ¦ Automatic ¦ Reduced ¦ Comfort
Automatic -
1310 E Comfort cooling setpoint 20.0 BZ 1012 BZ 1016 °C
1312 E Reduced setpoint 16 BZ 1014 BZ 1010 °C
1314 E Frost protection setpoint 10.0 4 BZ 1012 °C
1316 F Comfort setpoint max 35.0 BZ 1010 35 °C
1320 E Heating curve slope 1.50 0.10 4.00 1321 F Heating curve displacement 0.0 -4.5 4.5 °C
1326 F Heating curve adaption
Off ¦ On
Off -
1330 E Summer/winter heating limit 18 − − − / 8 30 °C
1332 F 24-hour heating limit -3 − − − / -10 10 °C
1340 F Flow temp setpoint min 8 8 BZ 1041 °C
1341 F Flow temp setpoint max 80 BZ 1040 95 °C
1350 F Room influence 20 − − − / 0 100 %
1360 F Room temp limitation − − − − − − / 0.5 4 °C
1370 F Boost heating 5 − − − / 0 20 °C
1380 F Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint
Down to reduced setpoint -
1390 F Optimum start control max 0 0 360 min
1391 F Optimum stop control max 0 0 360 min
1400 F Reduced setp increase start − − − − − − / -30 10 °C
1401 F Reduced setp increase end -15 -30 BZ 1100 °C
1420 F Overtemp prot pump circuit
1451 I Floor curing setp manually 25 0 95 °C
1455 F Floor curing setp current 0 0 95 °C
1456 F Floor curing day current 0 0 32 °C
1461 F Excess heat draw
Off ¦ Heating mode ¦ Always
1172 F With prim contr/system pump
No ¦ Yes
1500 I Optg mode changeover
Protection ¦ Recuced
Always
Yes
Protection
Domestic hot water
1610 E Nominal setpoint 55 BZ 1612 BZ 1614 OEM °C
1612 F Reduced setpoint 40 8 BZ 1610 °C
1614 O Nominal setpoint max 65 8 80 °C
1620 I Release
24h/day ¦ Time programs HCs ¦ Time program 4/DHW
Time programs HCs -
8/26
Siemens Schweiz AG User Manual OEM CE1U2353en01a
HVAC Products Overview of OEM settings 22. November 2006