Siemens CDC-4 Installation Instructions Manual

Page 1
Installation Instruct ions Model CDC-4
Conventional Detector Card
INTRODUCTION The Model CDC-4 from Siemens Industry, Inc., is a card that
allows conventional detectors to be used on the FireFinder-XLS system. It provides four Class A or Class B conventional detec­tion zones. Each zone can support two-wire photoelectric or ionization compatible smoke detectors and an unlimited number of normally open circuit closure devices. The module also supports Siemens Fire Safety flame and beam detectors. The relay base, remote lamp and audible base may also be used with the CDC-4. The CDC-4 uses one network address on the FireFinder-XLS system. It has diagnostic LED indicators showing module status and the status of each zone.
OPERATION Activation of any device on the circuit initiates a zone alarm and
causes any previously programmed functions to operate. Any circuit in an alarm or trouble condition is displayed on the PMI/ PMI-2/PMI-3.
The CDC-4 is designed to function in a local degrade mode during failure of the FireFinder-XLS main processor or during the loss of the system communication network. While in the degrade mode, the CDC-4 can report both alarm and trouble conditions and can activate local outputs on other modules within the same enclosure.
The maximum zone alarm current can be set to either 175mA or 100mA and is set in pairs for zones 1/2 and 3/4. When a compatible detector is selected in the Zeus Programming Tool, the maximum zone alarm current is automatically set by the CDC-4. Detectors requiring the 100mA zone current limit (see table on page 11) cannot be used on the same zone pair as detectors requiring the 175mA zone current limit (see table on pages 7-11).
CDC-4 zones may be configured either as alarm-causing or supervisory-causing, if allowed by the local Authority Having Jurisdiciton.
Do not use shorting devices on circuits with accessories on them. The shorting devices will lower the zone voltage to a point where the accessories will not operate.
Figure 1 CDC-4 Conventional Detector Card
P/N 315-034200-9
Building
Siemens Siemens
Siemens
Siemens Siemens
TT
ecec
hnologies Dihnologies Di
T
ec
hnologies Di
TT
ecec
hnologies Dihnologies Di
IndustryIndustry
Industry
IndustryIndustry
visionvision
vision
visionvision
,,
Inc. Inc.
,
Inc.
,,
Inc. Inc.
Page 2
Any or all of the CDC-4 circuits may be programmed to operate with Alarm Verifica­tion. This allows the automatic verification of alarm conditions caused by smoke detectors in order to prevent nuisance alarms. For further information, refer to the FireFinder-XLS Manual, P/N 315-033744.
When upgrading the firmware in the CDC-4, be sure to check the PC board version. Version 2.0 and above firmware are only compatible with PC board P/N 580-034888. If version 2.0 or above firmware is uploaded into the older version of the CDC-4, the PMI/PMI-2/PMI-3 displays “ROM SW Version Error”. The PC board revision number is printed on the back of the CDC-4 board.
Controls and Indicators The front panel of the CDC-4 contains one reset switch, sixteen LEDs, and three
HNET address switches as shown in Figure 1.
A reset switch is located on the top of the front panel. Pushing the reset switch re­initializes the CDC-4 operation (similar to a cold boot).
The LEDs follow the reset switch and their functions are defined as follows:
POWER (Green) Normally ON. When illuminated, indi-
cates that power for the CDC-4 is applied to the card.
CARD FAIL (Yellow) Normally OFF. When illuminated, indi-
cates that the card microprocessor has failed.
HNET FAIL (Yellow) Normally OFF. When illuminated, indi-
cates that the HNET communication with the CDC-4 has terminated and the card goes into degrade mode (applicable only when card resides in the HNET network).
GND FAULT (Yellow) Normally OFF. When illuminated, indi-
cates that the CDC-4 has detected either a negative or positive ground fault.
ZONE 1 ALARM (Red) Normally OFF. When illuminated indi-
cates that an alarm condition has been detected in Zone 1. It will stay on continuously until the system is reset.
ZONE 1 TROUBLE (Yellow) Normally OFF. When illuminated, indicates
that a trouble condition has been de­tected in Zone 1. It will stay on continu­ously until the condition is cleared.
ZONE 1 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-
cates that there is a break in the Class A wiring in Zone 1.
ZONE 2 ALARM (Red) Normally OFF. When illuminated indi-
Siemens Industry, Inc. Building Technologies Division
cates that an alarm condition has been detected in Zone 2. It will stay on continuously until the system is reset.
P/N 315-034200-92
Page 3
ZONE 2 TROUBLE (Yellow) Normally OFF. When illuminated, indicates
HNET
that a trouble condition has been de­tected in Zone 2. It will stay on continu­ously until the condition is cleared.
ZONE 2 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-
cates that there is a break in the Class A wiring in Zone 2.
ZONE 3 ALARM (Red) Normally OFF. When illuminated indi-
cates that an alarm condition has been detected in Zone 3. It will stay on continuously until the system is reset.
ZONE 3 TROUBLE (Yellow) Normally OFF. When illuminated, indicates
that a trouble condition has been de­tected in Zone 3. It will stay on continu­ously until the condition is cleared.
ZONE 3 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-
cates that there is a break in the Class A wiring in Zone 3.
ZONE 4 ALARM (Red) Normally OFF. When illuminated indi-
cates that an alarm condition has been detected in Zone 4. It will stay on continuously until the system is reset.
ZONE 4 TROUBLE (Yellow) Normally OFF. When illuminated, indicates
that a trouble condition has been de­tected in Zone 4. It will stay on continu­ously until the condition is cleared.
ZONE 4 CLASS A OPEN (Yellow) Normally OFF. When illuminated, indi-
cates that there is a break in the Class A wiring in Zone 4.
Three rotary dial switches at the bottom of the front panel are used to set the HNET network address of the CDC-4.
PRE-INSTALLATION The network address switches must be set prior to inserting the card into the CC-5
(refer to Figure 1):
Network Address Switches: Set the three-digit HNET network address for the
HUNDREDS
TENS
ONES
CDC-4 using the three rotary dial address switches located near the bottom of the front panel. (Refer to Figure 1 for the location of the switches.) The address for the CDC-4 must be the same as the address selected for it in the Zeus Programming Tool. To set the address, turn the pointers on each of the three dials to the numbers for the selected address. For example, if the address is 123, set the pointer for the HUNDREDS dial to “1”, set the pointer for the TENS dials to “2”, and set the pointer for the the ONES dial to “3”. The range of allowable addresses is from 001 to 251 (leading zeros must be used).
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-93
Page 4
WIRING
Remove all system power before installation, first battery, then AC. (To power up, connect the AC first, then the battery.)
All device field wiring to the CDC-4 is connected to the terminal blocks of the CC-5 card cage slot in which it is installed.
To Connect the External Wiring:
1. Loosen the screw of the terminal by turning it counter­clockwise.
2. Insert the wire into the side of the terminal block
3. Tighten the screw of the terminal block by turning it clockwise.
Connect +24V from PSC-12 to terminal 17 and -24V from PSC-12 to terminal 18 of the slot in the CC-5 where the CDC will be installed using 12-18 AWG (Refer to Fig.2).
Refer to Figure 3. All circuits are power limited to NFPA 70 per NEC 760. Each detector or group of detectors must use a two-wire circuit of at least 18 AWG, thermoplastic fixture wire, enclosed in conduit. If permitted by local building codes, 18 AWG limited energy, shielded cable without conduit may also be used.
ZONE 1
RETURN)
LINE+ (OUT)
LINE+ (RETURN)
12345678
910111213141516
LINE+ (OUT)
ZONE 3
ONE SLOT OF CC-5 FOR CDC-4
17 18 19 20 21 22 23 24
24V–
24V+
TO 24VDC FROM PSC-12
LINE- (
LINE+ (RETURN)
LINE- (RETURN)
LINE- (OUT)
LINE- (OUT)
LINE+ (OUT)
ZONE 2
LINE+ (RETURN)
LINE+ (OUT)
LINE- (RETURN)
LINE- (RETURN)
LINE+ (RETURN)
ZONE 4
LINE- (OUT)
LINE- (OUT)
Siemens Industry, Inc. Building Technologies Division
The CDC-4 may be connected to existing device loops that have a 3.9K or 4.7K end-of-line resistor (
1
/4W, 5%) or a 50uF,
Figure 2 Wiring 24V Power Lines
50V end-of-line capacitor installed. Always use a 50uF, 50V end-of-line capacitor for new installations and whenever practical in existing detector loops for all detector models except the Siemens PBA-1191, which requires a 4.7K end-of-line resistor, as shown in Figure 3.
Total circuit resistance must not exceed 70 ohms—40 ohms if accessories (relay/ audible bases) are used.
Each detector zone can be wired Class A or Class B individually.
The screw terminals can accommodate one 12 -18 AWG or two 16-18 AWG.
All unused zones must be terminated with a 50uF capacitor (Terminals 1 and 4 for Zone 1, Terminals 5 and 8 for Zone 2, Terminals 9 and 12 for Zone 3, and Terminals 13 and 16 for Zone 4).
P/N 315-034200-94
Page 5
ZONE 1
2
CLASS A**
ZONE
CLASS B
+
EOL
*
50uF , 50V
P/N 100-115588
***
IN CANADA,
*
MOUNT USING MODEL EL-33
NOTES:
1. All circuits can be Class A or Class B.
2. All circuits are power limited to NFPA 70 per NEC 760.
3. All circuits are supervised.
4. Refer to the UL Compatible Two-Wire Detector List for the maximum number of detectors per zone.
5. Do not mix smoke detectors with the PBA-1191.
6. Do not mix different manufacturer’s smoke detectors on the same zone.
7. Max resistance: 70 ohms/ circuit, 40 ohms/circuit if accessories (relay/audible bases) are used.
8. Do not use shorting devices on circuits with accessories on them.
PBA-1191
_
_
+
ABCDEF
9. Only one device accessory per circuit is guaranteed to activate on the CDC-4.
10. When mixing different model detectors on a zone, do not install more detectors than the smallest number shown in the “Number of Detectors Per Zone” column of the compatibility table. For example, if installing Siemens PE-11 and PE-3 detectors on the same zone, do not install more than fifteen detectors on that zone. When configuring the zone in Zeus, enter the model name of the detector with the smallest number (PE-3 in this example).
11. Positive and negative ground fault detected at <20K ohms for terminals 1-16.
_
++
EOL
50uF , 50V
P/N 100-115588
+
LINE+ (OUT)
LINE+ (RETURN)
1 2 3 4 5 6 7 8
**OPERATES IN FULL CONFORMANCE WITH STYLE 6 (ULC DCLA)
***OPERATES IN FULL CONFORMANC E W ITH STYLE 4 (U LC DCLB)
LINE- (RETURN)
LINE- (OUT)
Figure 3 CDC-4 Detector Zones
LINE+
NC NC
EOLR
4.7K, 1/4W
P/N 140-820188
LINE-
ZONE 3
LINE+
9 10 11 12 13 14 15 16
LINE-
DO NOT
USE
P/N 100-115588
EOL
50uF, 50V
+
ZONE 4
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-95
Page 6
INSTALLATION The CDC-4 plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin
DIN connectors and can occupy any slot in the card cage. (Refer to Figure 4.)
Insert the CDC-4 card into the card guides rightside up (lettering on the front panel is legible).
Slide the card in until the card edge connectors contact the receptacles on the motherboard.
Verify that the DIN connectors of the card and the card­cage aligned properly. The card can only plug in one direction to the card cage, if it does not align, DO NOT FORCE the card.
Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the card until the connectors seat in the receptacles on the motherboard. Secure with the captive screws.
Power up the system and verify that the CDC-4 power LED turns ON.
Figure 4 Installing The CDC-4
INITIATING DEVICES Refer to the UL Compatible Two-Wire Detector List for the number of detectors that
may be used on a CDC-4 zone.
Refer to Figure 3 for initiating device wiring. All circuits are power limited to NFPA 70 per NEC 760. Each detector or group of detectors must use a two-wire circuit of at least 18 AWG, thermoplastic fixture wire, enclosed in conduit. If permitted by local building codes, 18 AWG limited energy, shielded cable without conduit may also be used.
Total circuit resistance must not exceed 70 ohms—40 ohms if accessories (relay/ audible bases) are used.
If the smoke detector has an alarm verification function, the circuit must not be programmed for alarm verification.
See NFPA 72 Standard for the number of normally open contact devices allowed.
See UL Compatible Two-Wire Detectors for the list of compatible devices.
For specific wiring and installation information, read the instructions provided with each device.
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-96
Page 7
ELECTRICAL RATINGS
)ybdnats(egnaregatloV CDV8.22-7.12
uSxamenozrepAm4
tnerruCyrosivrep
tnerruCmralAxamenozrepAm571xamenozrepAm001
tnerruCenalPkcaBV420
imreTwercS
tnerruCV42lan
tnerruCenalPkcaBV2.6xamAm051
tnerruCybdnatSV42
stiucriCgnitaitinI
ylppuSrewoP
yrosivrepuS
xamenozrepAm8+Am011
mralA
xamenozrepAm023+Am011
yrosivrepuS
xamenozrepAm8+Am051
mralA
xamenozrepAm023+Am051
yrosivrepuS
xamenozrepAm8+Am011
mralA
repuS
mralA
xamenozrepAm082+Am011
yrosiv
xamenozrepAm8+Am051
xamenozrepAm082+Am051
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-97
Page 8
UL COMPATIBLE TWO-WIRE DETECTORS
The detectors listed in the following tables are compatible with the CDC-4 (UL identifier CDC). The CDC-4 and all Siemens detectors shown below are ULC listed. Contact the manufacturer for listing information on models other than Siemens.
rerutcafunaMrotceteD
rotceteDLU
ledoM
reifitnedI
esaB
ledoM
esaBLU
reifitnedI
forebmuN
U
srotceteD
detsiLCL
enoZreP
snemeiS 2911-FD2911-FD0911-BFD0911-BFD4Y snemeiS 3-ID
s
nemeiS 3B-ID
H3-ID
3A-ID
H3A-ID
H3B-ID
3-ID
H3-ID
3A-ID
H3A-ID
3B-ID
H3B-ID
snemeiS A4-IDA4-IDST4-BD
snemeiS 6-ID6-IDST
S3-BDS3-BD03
I3-DAI3-DA03
ST4-BD
FT4-BD
4-BD
FT4-BD
FT4-BD ST4-BD
FT4-BD
03 03 03
03 03
03 03
03
Y Y Y Y
Y Y
Y
Y
snemeiS 531-P3-TD531-P3-TDS3-BDS3-BDdetimilnUY snemeiS 11-TD11-TD11-BD
snemeiS 121IH121IHE11-BD
snemeiS 121HO121HOE11-BD
BD
11-
TPDA/wS3-BD
S3-BD
E11-BD
11-BD
11-BD
E11-BD
11-BD
11-BD
03
Y
03 03
03 03
03
Y Y
Y Y
sne
meiS 121PO121POE11-BD
11-BD
E11-BD
11-BD
03 03
Y Y
snemeiS 1911-ABP1911-ABP1911-BBP1911-BBP1Y snemeiS 3-EP
T3-EP
snemeiS 3-EP
T3-EP
3-EP
T3-EP
3-EP
T3-EP
snemeiS 11-EP11-EP11-BD
snemeiS T11-EPT11-EP11-BD
rerutcafunaMrotceteD
ledoM
rotceteDLU
reifitnedI
S3-BDS3-BD51
PLI3-DAPLI3-DA51
11-BD
P11-DA
RP11-DA
P11-DA
RP11-DA
11-BD
TPDA/wS3-BD
esaB
ledoM
S3-BD
esaBLU
reifitnedI
51
51 03
03 03
03 03
forebmuN
srotceteD
Y Y
Y Y
Y
Y
detsiLCLU
enoZreP
stcudorPriA
N-W2-WRN-W2-WR002-18654002-1865406N
slortnoCdna
stcudorPriA
P-W2-WRP-W2-WR002-18654002-18
65403N
slortnoCdna
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-98
Page 9
rerutcafunaMrotceteD
rotceteDLU
ledoM
reifitnedI
esaB
ledoM
esaBLU
reifitnedI
forebmuN
detsiLCLU
srotceteD
enoZreP
ollopA 051-00055
ot
ot
351-00055
051-00055 351-00055
ollopA 052-00055052-00055002-18654
ollopA 053-00055053-00055002-18654
ollopA 083-00055083-00055002-18654
002-18654 022-18654 722-18654 032-18654 132-18654 232-18654
002-18654 022-18654 722-18654 032-18654 132-18654 232-18654
002-18654
022
-18654 722-18654 032-18654 132-18654 232-18654
022-18654 722-18654 032-18654 132-18654 232-18654
002-18654
022-18654
4 722-18654 032-18654 132-18654 232-18654
022-1865 722-18654 032-18654 132-18654 232-18654
002-18654 022-18654 722-18654 03
2-18654
132-18654 232-18654
022-18654
722-18654
032-18654
132-18654
232-18654
06 06 04 04 04 06
06 06 0
4
04 04 06
03 03 52 52 52 03
02 02 51 51 51 02
N
N
N
N
rerutcafunaMrotceteD
sdrawdE B0526
sdrawdE B9626
sdrawdE B0726
rotceteDLU
ledoM
reifitnedI
esaB
ledoM
esaBLU
reifitnedI
forebmuN
detsiLCLU
srotceteD
enoZreP
100 B0526 B0526
100
100
100 B9626 B9626 B9
626
100
100
100
100 B0726 B0726 B0726
10
0
100
100
100-B9426 100-B1526
A100-B1526
100-B9426 100-B1526
A100-B1526
300-B1526 100-B9426
100-B1526
A100-B1526
300-B1526
100 100 100
100 100 100 100
100 100 100 100
55 55 55
5 5 5 5
5 5 5 5
Y Y Y
Y Y Y Y
Y Y Y Y
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-99
Page 10
rerutcafunaMrotceteD
ledoM
rotceteDLU
reifitnedI
esaB
ledoM
esaBLU
reifitnedI
forebmuN
detsiLCLU
srotceteD
enoZreP
langiSortcelE
C02401SA/NA/N07N
)LSE(
langiSortcelE
RC02411SA/NA/N07N
)LSE(
langiSortcelE
TRC02411SA/NA/N07N
)LSE(
elE
langiSortc
TC02401SA/NA/N07N
)LSE(
langiSortcelE
C52401SA/NA/N07N
)LSE(
langiSortcelE
RC52411SA/NA/N07N
)LSE(
langiSortcelE
TRC5
2411SA/NA/N07N
)LSE(
langiSortcelE
TC52401SA/NA/N07N
)LSE(
langiSortcelE
C924A01SA/NA/N53N
)LSE(
langiSortcelE
TC924A01SA/NA/N53N
)LSE(
l
angiSortcelE
TFA/C115A01SA/NA/N53N
)LSE(
langiSortcelE
TFA/C815A01SA/NA/N53N
)LSE(
langiSortcelE
)LSE(
w(
langiSortcelE
)LSE(
langiSortcelE
)LSE(
l
angiSortcelE
)LSE(
langiSortcelE
TXB/B125
A01SA/NA/N53N
)FFO1wS/
TXRC125
A11SA/NA/N53N
)FFO1wS/w(
TXB/B825
A01SA/NA/N53N
)FFO1wS/w(
TXRC825
A11SA/NA/N53N
)FFO1wS/w(
U11601SU10600S07N
)LSE(
langiSortcelE
DU11601SU1060
0S07N
)LSE(
langiSortcelE
DU11601S01U90600S07N
)LSE(
langiSortcelE
TU11601SU10600S07N
)LSE(
langiSortcelE
21601SU10600S07N
)LSE(
langi
SortcelE
DU21601SU10600S07N
)LSE(
langiSortcelE
DU21601S01U90600S07N
)LSE(
langiSortcelE
5U31601SU10600S07N
)LSE(
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-910
Page 11
rerutcafunaMrotceteD
rotceteDLU
ledoM
reifitnedI
esaB
ledoM
esaBLU
reifitnedI
forebmuN
detsiLCLU
srotceteD
enoZreP
ikihcoH 531-DCD3-DH022-4SN
022-6SN
ikihcoH 531-DCD3-DH422-4SN
422-6SN
ikihcoH 091-DCD3-DH022-4SN
0
22-6SN
ikihcoH 091-DCD3-DH422-4SN
422-6SN
ikihcoH F42-HIS3-DHD22-SH
22M-ABY
ikihco
H F42-HIS3-DH422-BSH35-BH02Y
3-BH02
5-BH02
3-BH02
5-BH02
3-BH 3-BH
N
02
N
02
N
02
N
02 02
02
Y Y
ikihcoH F42-HIS3-DHR422-CSH37-BH02Y ikihcoH F42-HIS3-DHD422-SH
oH 42-JIS3-DH022-4SN
ikihc
ikihcoH 42-JIS3-DH422-4SN
ikihcoH F42-KLS
3-DHD22-S
HF42-KLS
422M-ABY
022-6SN
422-6SN
H
22M-ABY
5-BH 5-BH
3-BH51
5-BH51
3-BH 3-BH
02 02
Y Y
Y
51
Y Y
51 02
02
Y Y
Y
ikihcoH F42-KLS
3-DHD422-SH
HF42-KLS
ikihcoH F42-KLS
3-D
H422-BSH35-BH02
HF42-KLS
ikihcoH F42-KLS
3-DHR422-CSH37-BH02
LF42-KLS
ikihcoH LF42-KLS3-DH2-BSH
ikihc
oH H42-RLS
3-DH022-4SN
V42-RLS
ikihcoH H42-RLS
3-DH422-4SN
V42-RLS
ikihcoH 538-R
LS
3-DH022-4SN
W538-RLS
ikihcoH 538-RLS
3-DH422-4SN
W538-RLS
ikihcoH H538-RLS
ikihcoH H538-RLS
WH
538-RLS
5-DH422-4SN
5-DH022-4SN
WH538-RLS
5-BH
422M-ABY
5-BH
02 02
Y Y
Y
02
N N
02
05-BH02
N2-BSH
02
3-BH02
022-6SN
02
5-BH02
422-6SN
02
3-BH51
022-6SN
51
5-BH51
422-6SN
51
5-BH51
422-6SN
51
3-BH51
022-6SN
W022-6SN
51 51
N N
N N
N N
N N
N N
N N
N N
N N
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-911
Page 12
rerutcafunaMrotceteD
rotceteDLU
ledoM
reifitnedI
esaB
ledoM
esaBLU
reifitnedI
forebmuN
detsiLCLU
srotceteD
enoZreP
rosneSmetsyS
TA0042A A/NA/N1N
)KRB(
rosneSmetsyS
TIA0042A A/NA/N1N
)KRB(
esohthtiwsrotcetedesehtximtonoD.sledomgniwollofehtrofAm001otdetsujdasitimiltnerrucenoZ
htiwelbitapmoce
gniriwehtneewtebecnatsiserenileh
detsiLCLU
htraenslanimret
rerutcafunaMrotceteD
rasrotcetedesehT.)4dna3senoZro2dna1senoZ(riapenozemasehtnoevobadetsil
T.888430-085N/PdraobCPhtiwrehgihdna0.2noisivererawmrif
.smho03deecxetontsumsecivedgnitrohsynadna4-CDCe
rotceteDLU
ledoM
reifitnedI
esaB
ledoM
esaBLU
reifitnedI
forebmuN
srotceteD
enoZreP
rosneSmetsyS
)KRB(
rosneSmetsyS
1511A dnaPL011B
A52Y
PL611B
0041A A/NA/N03Y
)KRB(
rosneSmetsyS
)KRB(
rosneSmetsyS
1541A B1
04B,104B
A52Y
B604Bdna
*HD1541A 004HDA 52N
)KRB(
rosneSmetsyS
)KRB(
1512A dnaPL011B
A52Y
PL611B
rosneSmetsyS
T0032A A/NA/N52N
)KRB(
rosneSmetsyS
0042A A/NA/N52Y
)KRB(
rosneSmetsyS
HT0042A A/NA/N52Y
)KRB(
rosneSmetsyS
)KRB(
rosneSmetsyS
1542A B104B,104B
a
A52Y
B604Bdn
*1542A 004HDA 52Y
)KRB(
rosneSmetsyS
)KRB(
rosneSmetsyS
)KRB(
rosneSmetsyS
)KRB(
rosneSmetsyS
)KRB(
HT1542A B104B,104B
1545A dna104B
*I004HD
HD1541(
)004HD/w
HD1542(
)004HD/w
AA/NA/N52N
AA/NA/N52N
*P004HD
A52N
B604Bdna
A52N
B1
04B
.gnisuoh004HDhtiw1542ehtsiP004HDledoM.gnisuoh004HDhtiwHD1541ehtsiI004HDledoM*
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-912
Page 13
CYBER SECURITY DISCLAIMER
Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept.
It is, however, necessary to implement and maintain a comprehensive, state-of-the­art security concept that is customized to individual security needs. Such a security concept may result in additional site-specific preventive action to ensure that the building comfort, fire safety, security management or physical security system for your site are operated in a secure manner. These measures may include, but are not limited to, separating networks, physically protecting system components, user awareness programs, defense in depth, etc.
For additional information on building technology security and our offerings, contact your Siemens sales or project department. We strongly recommend customers to follow our security advisories, which provide information on the latest security threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security-advisories.htm
Siemens Industry, Inc. Building Technologies Division
P/N 315-034200-913
Page 14
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
Siemens Canada, Ltd. 1577 North Service Road East Oakville, Ontario L6H 0H6 Canada
P/N 315-034200-9Document ID A6V10239127
Loading...