Siemens CCDA1415-DN Instruction Manual

Page 1
CCDA1415-DN DAY/NIGHT Dome System
Instruction Manual
Fire & Security Products
Page 2
Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. © 2004 Copyright by Siemens Building Technologies AG
Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich machen oder außerhalb des Zweckes verwenden, zu dem es ihm übergeben worden ist.
We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
70
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 3
Foreword
To prevent damage, and to achieve optimum reproduction of images, please read and follow this Instruction Manual carefully.
WARNING
The camera must be handled with utmost care to avoid damage to the sensitive image sensor. Do not touch the front glass of the image sensor. Connection, commissioning and maintenance must only be carried out by suitably qualified personnel.
Do not remove any covers as this could lead to serious physical injury that
may even result in death through electric shock.
Mains-operated cameras must be connected to earth. Cameras for low-voltage supply must only be connected to fully insulated
class 2 power supply units. Correct and safe operation of this camera is dependent on proper transport, storage, installation and connection, as well as careful operation and maintenance.
Do not run data and power cables adjacent to or in the same conduit as line
voltage mains power.
SensorNet 485 networks require 22 AWG unshielded cable. Do not exceed 32
devices per cable run.
Siemens RS422/RS485 networks require 22 AWG shielded cable. Do not
exceed 10 devices per cable run.
Always terminate the camera dome connected at the end of a RS422/RS485
cable run using termination jumpers.
When using the standard base and wiring cables directly to the dome, ALWAYS
connect the video cable to the dome before you connect the 9-pin cable (which contains power). If you connect the 9-pin cable first, you risk shorting delicate electronics near the connector.
I/O PC board (when used). If a cable clamp is on this board, remove it, as it could damage cable connectors
in the housing during assembly.
Use a jeweler's 2.5 mm (0.1 inch) slotted screwdriver to tighten connector
screws. Do not over tighten these screws.
Use the dust cover when shipping the I/O board back to the manufacturer. It will
protect the spring-finger connector.
When connecting the housing and eyeball assembly to an outdoor housing:
Remove both slot covers to keep the camera from overheating. Keep cables entering the housing away from the heater assembly. Place tubing around the BNC connectors to avoid shorting their metal surface
to the outdoor housing.
Check heater fans. Both fans must be on to prevent overheating.
If disassembling the dome:
Dome contains electrostatic-sensitive devices! Use a ground strap when
handling PC boards. Once disassembled, parts of housing and eyeball assembly are "extremely fragile" and may break. Proceed using extreme care!
71
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 4
Warnings and Cautions
Please review the following warnings and cautions before you begin installation or service.
WARNING!
ALWAYS USE:
Proper safety equipment for the location and type of installation. Proper lift equipment to reach the installation. Safety features of the lift equipment.
BE SURE:
Electrical power is not connected to the dome when connecting wires. Dome
will move when power is applied. Electrical power is not connected to nearby fixtures that you might touch during installation.
WARNING!
DO NOT install this camera dome in hazardous areas where highly combustible or explosive products are stored or used.
WARNING!
EU power requirements: This product runs on 24 V AC. In the EU, it is intended to be powered from a Limited Power Source. A limited power source is a certified source of SELV, and if inherently limited, with 8 amps maximum output current, and a maximum of 100 VA available; or if not inherently limited, fused with a maximum value of 3.3 Amps, meeting section 2.11 of IEC950, and a maximum of 250 VA available. The power supply can be obtained through SIEMENS or through another source where the provider can furnish the verification. This is required to assure electrical safety in the product.
NOTE:
Your attention is drawn to the fact that the contents of this Instruction Manual do not form part of an earlier or existing agreement, commitment or legal relationship nor should they alter such a contract in any way. All the obligations of Siemens are detailed in the relevant sales contract which also contains the complete and solely applicable warranty clause. These contractual warranty conditions are neither extended nor restricted by the information contained within this document. If you require further information, or if particular problems should arise which are not covered by this Instruction Manual, then please contact your local Siemens office and request the information you require.
72
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 5
Contents
1
General Details......................................................................................75
1.1 Electromagnetic Compatibility (EMC) .....................................................75
1.2 Manufacturer's Declaration of Conformity...............................................75
2 Ordering Data ........................................................................................76
3 Scope of Delivery..................................................................................77
4 Technical Data.......................................................................................78
5 About the Dome Camera ...................................................................... 80
5.1 Mounting Base ........................................................................................80
5.2 Housing and Eyeball Assembly ..............................................................80
5.3 Indoor Ceiling Mounting ..........................................................................81
5.4 Indoor Ceiling/Wall Mounting (Optional) .................................................82
5.5 Outdoor Mounting (Optional) ..................................................................83
5.6 Outdoor Mounting Structures (Optional).................................................84
5.7 Data Cable Requirements.......................................................................84
5.8 Power-Up Routine...................................................................................84
5.9 Synchronizing Domes .............................................................................84
6 Indoor Installation.................................................................................85
6.1 Connecting to the Standard Mounting Base...........................................85
6.2 Connecting to a Mounting Base with I/O Board......................................89
7 Using the Dome Configuration Utility.................................................93
7.1 Starting the Dome Configuration Utility...................................................93
7.2 Working with the Dome Configuration Utility ..........................................94
7.3 Entering the Dome's Password...............................................................94
7.4 Restoring Factory Settings......................................................................95
7.5 Exiting the Configuration Utility...............................................................95
8 Configuring Pan, Tilt, Zoom, and Synchronization Options ............96
8.1 Setting the Automatic “Flip” Feature .......................................................96
8.1.1 Changing the Automatic Flip Setting.......................................................96
8.2 Adjusting the Zoom Stop Settings...........................................................97
8.2.1 Changing the Zoom Stop Settings..........................................................97
8.3 Configuring the Line Lock Setting...........................................................97
8.3.1 Changing the Line Lock Setting ..............................................................98
9 Configuring Camera Features .............................................................99
9.1 Overview of Camera Settings .................................................................99
9.2 Adjusting White Balance Settings.........................................................100
9.2.1 Changing Automatic White Balance Settings .......................................101
9.3 Understanding How IR Mode (Black & White) Operates......................101
9.3.1 Changing the IR Mode Setting..............................................................102
9.3.2 Manually Activating or Deactivating the IR Mode .................................102
9.4 Understanding Wide Dynamic Range...................................................103
9.4.1 Changing the Wide Dynamic Range Setting ........................................104
9.5 Working with AGC and Open Shutter Settings.....................................104
9.5.1 Understanding How Advanced Shutter Settings Improve Low-Light
Performance..........................................................................................105
9.5.2 The Relationship between IR Mode and AGC and
Open Shutter Settings...........................................................................106
9.5.3 Configuring AGC and Open Shutter Settings .......................................106
73
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 6
10 Configuring Alarms, Areas, Home, Privacy Settings
and Presets..........................................................................................107
10.1 Overview of Alarms, Areas, Home, North Position,
Preset and Privacy Settings..................................................................107
10.2 Alarm Actions ........................................................................................108
10.2.1 Configuring Alarm Actions.....................................................................109
10.2.2 Configuring Normal Input States for Alarms .........................................110
10.2.3 Setting Alarm Input States ....................................................................110
10.3 Assigning the Dome’s Home Position...................................................111
10.3.1 Setting the North Position .....................................................................112
10.4 Programming Area Boundaries.............................................................113
10.5 Setting Area Boundaries .......................................................................114
10.6 Establishing Privacy Zones...................................................................115
10.6.1 How Privacy Zones are Programmed ...................................................116
10.6.2 Programming Privacy Zones.................................................................117
10.6.3 Removing or Hiding Privacy Zones.......................................................118
10.6.4 Deleting Specific Privacy Zones............................................................119
10.6.5 Deleting All Privacy Zones ....................................................................119
10.6.6 Hiding Privacy Zones ............................................................................119
10.7 Programming Presets ...........................................................................120
10.7.1 Setting Presets......................................................................................120
11 Configuring Text Displayed On-Screen ............................................121
11.1 Overview of On-Screen Text Display Settings......................................121
11.2 Displaying or Hiding Status Information................................................122
11.2.1 Changing the Display of Status Information..........................................122
11.3 Displaying or Hiding All Name Information ...........................................123
11.3.1 Changing the Display of All Name Information .....................................123
11.4 Displaying Diagnostic Tests During Reset............................................124
11.4.1 Changing the Display of Diagnostic Information...................................124
11.5 Displaying Direction Indicators..............................................................125
11.5.1 Changing the Display of Direction Indicators ........................................126
11.6 Configuring Name Information ..............................................................127
11.7 Assigning or Changing Name Information ............................................128
11.7.1 Setting or Changing Names..................................................................128
11.8 Changing the Settings for Text Displayed On-Screen ..........................130
11.8.1 Changing On-Screen Text Appearance................................................131
12 Configuring Language and Password Settings...............................132
12.1 Overview ...............................................................................................132
12.2 Selecting a Language ...........................................................................132
12.2.1 Changing the Language Setting ...........................................................133
12.3 Setting and Enabling the Dome Password ...........................................134
12.3.1 Setting or Changing the Dome Password.............................................134
12.3.2 Enabling or Disabling Password Protection..........................................134
13 Displaying Dome Information ............................................................135
13.1 Understanding the Dome Information Screen.......................................135
13.2 Viewing Dome Operating Statistics.......................................................136
74
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 7
General Details
1 General Details
1.1 Electromagnetic Compatibility (EMC)
This product has been designed for the utilization in general-purpose CCTV applications in a residential, business or industrial environment. Please contact your supplier of this product before you install it in medical and/or intrinsically safe applications or in an industrial EMC environment. To ensure normal operation and to avoid EMC problems, the product must be installed according to the currently valid EMC installation instructions.
1.2 Manufacturer's Declaration of Conformity
EU Directive
The following is applicable for the equipment described in this Instruction Manual: The product fulfils the requirements of EU directive 89/336/EEC on “Electromagnetic compatibility“ as per:
Electromagnetic emission Immunity to electromagnetic interference
EN 61000-6-3 EN 50130-4 +A1+A2 with the basic standard: with the basic standards: EN 55022 Kl.B EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6
The EU conformity certificate which is available for the associated authorities is held at:
Siemens Building Technologies Fire & Security Products GmbH & Co. oHG Siemensallee 84 76187 Karlsruhe
75
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 8
Ordering Data
2 Ordering Data
Designation Order No.
Approx. weight (kg)
1/4-inch CCD day-night indoor dome CCDA 1415-DN 470 TV lines, 0.01 lux, 24 V AC
2GF1191-8AA
2.4
Accessories, not included in delivery! Quick-mount socket
with integrated I/O board for the CCDA1415-DN
2GF1191-8BC
0.35
“Top Hat” ceiling housing
for dome camera CCDA 1415-DN
2GF1191-8BD
1.3
Bubble, smoked
for the “Top Hat” housing
2GF1191-8BE
1.0
Bubble, clear
for the “Top Hat” housing
2GF1191-8BF
1.0
Ceiling bracket, adjustable
for the "Top Hat" housing
2GF1191-8BG
2.0
Ceiling bracket, fixed
for the "Top Hat" housing
2GF1191-8BH
1.4
Hard ceiling bracket
for the "Top Hat" housing
2GF1191-8BJ
2.0
Pendant mount, indoor
for dome camera CCDA1415-DN
2GF1191-8BK
1.9
Wall bracket, indoor
for dome camera CCDA1415-DN
2GF1191-8BL
1.4
Wall mount bracket, short
for dome cameras CCDA1415-DN with outdoor housing and CCDA1410-WD
2GF1191-8BM
1.85
Wall mount bracket, long
for dome cameras CCDA1415-DN with outdoor housing and CCDA1410-WD
2GF1191-8BN
2.0
Outdoor pendant mount
for dome cameras CCDA1415-DN with outdoor housing and CCDA1410-WD
2GF1191-8BP
1.9
Pole strap adapter
for long and short wall mounts
2GF1191-8BQ
1.0
Corner bracket adapter
for long and short wall mounts
2GF1191-8BR
1.2
Dome outdoor housing
for dome camera CCDA1415-DN
2GF1190-8BS
2.6 (without dome)
3.9 (with dome)
Bubble, smoked
for dome camera CCDA1410-WD and outdoor housing
2GF1190-8BT
0.75
76
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 9
Scope of Delivery
3 Scope of Delivery
Instruction Manual 1 Dome Camera CCDA1415-DN 1 Ceiling Mount incl. Mounting Base 1 Screws (subpackage) 1 Safety Lanyard 1
Tools Required
Slotted screwdriver
77
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 10
Technical Data
4 Technical Data
Operational
Pan/Tilt: Manual Pan and Tilt speed
1° to 100° per second
(scaled to zoom position) Preset Pan/Tilt speed Max. 220° per second Pan Travel 360° continuous rotation Tilt Travel 105° Pan/Tilt accuracy ± 0.5° Zoom/Focus Accuracy ± 0.5% Total Zoom 184 x Optical Zoom 23 x Digital Zoom 8 x Zoom Pause 23 x or 35 x (default zoom pause) Zoom Stop 23 x, 35 x (default zoom pause), 46 x, 69 x,
92 x (default), 115 x, 138 x, 161 x, 184 x
Electrical
Input voltage 24 to 30 V AC, 50/60 Hz class 2 LPS Design tolerance 20 to 36 V AC, 50/60 Hz Power consumption 16 W Current 1.5 A Surge protection
Video output Series resistor of 3.9 Ohm. Low capacitance
Zener suppressor 6.5 V, 1500 W SensorNet RS485 interface Isolation transformer coupled,
2000 Vrms PTC resettable fuse protects
transformer,
TVS RATED AT 5.6 V, 40 A, 0.1 joules;
10 kA impulse rated gas tube Siemens RS422/RS485 Interface Series resistor of 33 Ohm; TVS rated at
5.6 V, 40 A, 0.1 joules
Alarm Input Series resistor of 33 Ohm; TVS rated at
5.6 V, 40 A, 0.1 joules
Power Line TVS rated at 60 V, 250 A, 1.5 Joule
Cameras
Imager 1/4-inch CCD Scanning System 2:1 Interlace Video Output 1.0 Vpp, 75 Ohm composite Signal to Noise 50 dB (typical) Horizontal Resolution 470 lines at centre Minimum Illumination Better than 1.0 Lux (20 IRE, AGC) on
0.5 Lux with open shutter
0.01 Lux in black and white IR mode
0.009 Lux in black and white mode with
open shutter White Balance Through the Lens (TTL) Autotracing White
Balance (ATW)
78
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 11
Technical Data
Standard
PAL Effective Pixels 752 (H) x 582 (V) Scanning 625 lines 50 Fields 25 Frames Horizontal 15.625 kHz Vertical 50 Hz
Lens
Type Aspherical Focal Length 3.6 to 82.8 mm Aperture f1.6 (Wide) f3.7 (Tele)
4 mm 54.0° (H) x 40.5° (V) 88 mm 2.5° (H) x 1.9° (V)
Viewing Angle 4 mm 54.0° (H) x 40.5° (V)
82.8 mm 2.5° (H) x 1.9° (V) (equivalent to 8 to 80 mm 1/2-inch CCD or 11 to 110 mm on 2/3-inch CCD
Dimensions (D x H) 120 x 205 mm
79
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 12
About the Dome Camera
5 About the Dome Camera
The SIEMENS DAY/NIGHT Dome System CCDA1415-DN comes in black finish, mounts indoors or outdoors, and can communicate with the video controller over Siemens RS422/RS485 network. The dome consists of a mounting base, and a housing and rotating eyeball assembly.
5.1 Mounting Base
The housing and eyeball assembly connects to the base using a twist and lock action, enabling it to be moved easily from one location to another. The base attaches directly to a hard or tile ceiling, or indirectly to walls or ceilings using one of many optional housings and mounting structures. As shown in Fig. 1, two base types are offered: a standard base and a base with I/O board.
Standard Base
With this base, video, data, and power cables are inserted through the base and attached to the top of the housing and eyeball assembly, which is then connected to the base. A lanyard connects between the base and the housing and eyeball assembly to prevent cables from being pulled during disassembly. The base comes in black.
Optional Base with I/O Board
With this base, video, data, and power cables are pre-connected to an I/O PC board. A spring-finger connector on the board makes electrical contact with the housing and eyeball assembly as it connects to the base. The base comes in black (Quick Mount socket).
5.2 Housing and Eyeball Assembly
The housing and eyeball assembly consists of the following:
Housing. The housing contains the dome's power supply, pan motor, and
electronics used to operate the eyeball. The housing provides one alarm input and one alarm output using the standard base, or four alarm inputs and four alarm outputs using the base with I/O board.
Eyeball. With a diameter of 120 mm (4.75 inch), the eyeball contains a camera,
tilt motor, and associated electronics. The eyeball enables the camera to pan and tilt to track a target moving in any direction even as it moves under the
dome. Two slot covers in the eyeball facilitate access to the camera, one of which incorporates an opening for the camera lens. Remove both covers to improve ventilation when the dome is to be used outdoors. Each camera has 23 x optical zoom with continuous auto focus and back light compensation. Electronic zoom provides selectable magnification up to 184 x.
80
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 13
About the Dome Camera
Standard Base
Base with I/O Board
81
Fig. 1 Mounting base and housing and eyeball assembly
5.3 Indoor Ceiling Mounting
Using hardware shipped with the base, the dome attaches directly to indoor ceilings made of sheet rock, wood, metal, or concrete (Fig. 2), or to tile ceiling T-bars where they intersect (Fig. 3).
Fig. 2 Surface mounting to hard
ceilings
Fig. 3 Surface mounting to tile ceilings
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 14
About the Dome Camera
5.4 Indoor Ceiling/Wall Mounting (Optional)
The camera dome attaches to one of the following optional indoor mounting structures (Fig. 4).
2GF1191-8BJ Hard Ceiling Bracket
This bracket enables the Top Hat housing to be recessed in the ceiling. The bracket is mounted to the Top Hat and installed in a hole cut in the ceiling­perfect for sheet rock, plaster, or solid ceilings. The Hard Ceiling Bracket can be installed entirely from below the ceiling.
2GF1191-8BH Fixed Bracket
This bracket enables the Top Hat housing to be recessed in the ceiling or recessed in a 2 foot drop ceiling tile. The bracket is mounted to the Top Hat and installed in a hole cut in the ceiling. The bracket distributes the weight of the dome and Top Hat housing across the T-bar framework of the ceiling. It is also very useful for sheet rock, plaster, or solid ceilings.
2GF1191-8BG Adjustable Bracket
This bracket enables the Top Hat housing to be recessed in drop ceilings that utilize other than 2 foot grids. The bracket distributes the weight of the dome and the Top Hat housing across the T-bar framework of the ceiling.
Fig. 4 Indoor mounting structures (optional)
82
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 15
About the Dome Camera
5.5 Outdoor Mounting (Optional)
NOTE:
This document does not include outdoor installation and service instructions. For these instructions, see manual of Outdoor Housing.
The camera dome attaches to outdoor walls and ceilings using an outdoor housing (Fig. 5) and one of the following optional mounting structures (Fig. 6):
Pendant Mount Pole Mount Corner Bracket. Wall Mount long/short Wall Mount short
The outdoor housing contains a pre-installed mounting base, a cooling fan for hot weather, a heater for cool weather and to prevent icing, and surge protection circuitry to protect against lightning strikes. An environmental PC board is used to pre-wire cables. A round spring-finger connector on the board makes electrical contact with the housing and eyeball assembly as it connects to the base.
NOTE: Do not use the I/O board (designed for indoor use) in place of the environmental board.
Fig. 5 Outdoor housing (optional)
83
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 16
About the Dome Camera
5.6 Outdoor Mounting Structures (Optional)
Fig. 6 Outdoor brackets (optional)
5.7 Data Cable Requirements
Table 1 shows the data cable requirements for Siemens RS422/RS485 and SensorNet RS485 networks.
SensorNet RS485 Siemens RS422/RS485
Cable type 1 unshielded, twisted pair 2/1 shielded, twisted pair Wire gauge 22 AWG 22 AWG Connection Non-polarized Polarized Max. devices on line 32 10
Tab. 1 Data cable requirements
5.8 Power-Up Routine
After power is connected to the dome, the dome performs the following homing routine.
1. After a few seconds, the camera lens tilts up into the housing and eyeball
assembly.
2. The lens tilts downs until it looks at the floor.
3. Eyeball pans slowly.
4. Lens tilts up 90° (home position).
Once the lens is in its home position, you can use the controller to call up the camera and control it.
5.9 Synchronizing Domes
To prevent picture rolling when switching from camera to camera, all domes can be synchronized to a 50 or 60 Hz AC source.
84
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 17
Indoor Installation
6 Indoor Installation
This section explains how to connect the housing and eyeball assembly to a:
Standard mounting base Mounting base with I/O board.
6.1 Connecting to the Standard Mounting Base
This procedure explains how to connect the housing and eyeball assembly to a standard base.
WARNING! Ensure that AC power and electrical signals are off during wire connections!
1. Set dome address (Fig. 7). Recessed at top of housing and eyeball assembly are three rotary address switches. Address range is from 01 to 099. Set switches from most significant bit (MSB) to least significant bit (LSB). For example: For address 066, set SW3 to 0, SW2 to 6, and SW1 to 6.
090909
MSB
LSB
SW3
SW1SW2
Fig. 7 Setting the address switches
85
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 18
Indoor Installation
2. Attach safety lanyard to cap on housing and eyeball assembly (Fig. 8). Use M3 x 6 screw supplied with lanyard.
Only use this location to secure lanyard.
Fig. 8 Attaching safety lanyard
3. WITH POWER OFF, connect the video cable (Fig. 9).
Connect BNC of video micro coax cable to BNC of video cable. Feed cable through access hole in base. Press micro coax connector into mating receptacle in top of housing and
eyeball assembly. A firm snap indicates a tight connection.
4. Set termination jumper JW1 (Fig. 9). Depending upon the dome’s location in the communications line, set jumper JW1 across the appropriate pins as described in the following chart:
Position of dome in communications line Setting Pins
Between other devices Un-terminated 1-2* End of communications line Terminated 2-3
* Pins 1-2 are closest to 9-pin connector.
NOTE:
In some cases, an additional termination of the RS422/RS485 buses may be required.
NOTE:
You may need a small slotted screwdriver to gently pry jumper loose. Be careful not to damage underlying PC board.
86
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 19
Indoor Installation
Micro Coax Cable
Termination Jum
p
er JW1
Fig. 9 Video cable connection and termination jumper location
5. Connect the 9-pin plug (data and power) to the 9-pin receptacle (Fig. 10).
CAUTION DO NOT connect 9-pin plug unless you have performed step 3 first!
Feed cables access hole in base. Connect data and power wires to the 9-pin plug (refer to charts below). Insert plug into mating receptacle in top of housing and eyeball assembly.
Siemens RS42/RS4852 data and power connections
87
Pin Designation
1-2 must be connected using a jumper cable!
3 24 V AC 4 Masse / common 5 24 V AC 6 RS422 Data In High (+) 7 RS422 Data In Low (–) 8 RS422 Data Out High (+) 9 RS422 Data Out Low (–)
from the controlle
r
to the next dome
The following interface parameters are applicable for the Siemens protocol RS422/RS485:
Data rate in baud
19,200 bits/s
Data format
Start bit 1 Data bit 8 Parity 0 Stop bit 1
Tab. 2 Interface parameters Siemens RS422/RS485
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 20
Indoor Installation
SensorNet RS485 data and power connections
Pin Designation
1 SensorNet (unshielded) 2 SensorNet (unshielded) 3 24 V AC 4 Ground 5 24 V AC
6-9 Not used.
6. Connect 4-pin plug (alarm input/output) to 4-pin receptacle (Fig. 12).
Feed cable through access hole in base. Connect alarm wires to 4-pin plug (refer to chart below). Insert plug into mating receptacle in top of housing and eyeball assembly.
Alarm connections
Pin Designation
1 +12 V DC 2 Alarm Out 3 Alarm In 4 Common
9-pin plug
4-pin plug
Fig. 10 Cable connections
88
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 21
Indoor Installation
7. Connect housing and eyeball assembly to base (Fig. 11).
Align dimple on cap of dome with rib on mounting base. Mate housing and eyeball assembly to base and turn it clockwise until you
hear a click.
L
A
T
C
H
Fig. 11 Connecting housing and eyeball assembly to base
(cables and lanyard not shown)
8. Wait a few seconds for dome to begin its homing routine. Homing routine indicates that address was placed into dome memory and that dome is ready for programming.
6.2 Connecting to a Mounting Base with I/O Board
This procedure explains how to connect the housing and eyeball assembly to the optional mounting base with I/O board.
WARNING! Ensure that AC power and electrical signals are off during wire connections!
CAUTION:
Detach and discard cable clamp if I/O board has one. If not removed, clamp can damage 9-pin connector in housing and eyeball assembly when you attempt to connect it to base.
1. Set data communications jumper JW1. If data lines continue to another dome, set JW1 across pins 1-2 (un-terminated). Otherwise, set JW1 across pins 2-3 (terminated).
2. Connect video cable to BNC connector P8 on I/O board.
3. Connect Siemens RS422/RS485, or SensorNet 485 data wires to connector P1.
89
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 22
Indoor Installation
Siemens RS422/RS485 data connections
90
Pin Designation
1 RS422 Data In High (+) 2 RS422 Data In Low (–) 3 RS422 Data Out High (+) 4 RS422 Data Out Low (–)
5-6 must be connected using a jumper cable!
from the controller
to the next dome
IMPORTANT If the Siemens protocol is used, the SensorNet input must be jumpered!
The following interface parameters are applicable for the Siemens protocol RS422/RS485:
Data rate in baud 19,200 bits/s
Data format Start bit 1
Data bit 8 Parity 0 Stop bit 1
Table 3 Interface parameters Siemens RS422/RS485
SensorNet RS485 data connections
Pin Designation
1-4 not used 5 SensorNet (unshielded) 6 SensorNet (unshielded)
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 23
Indoor Installation
1
P1
P4
P3
P8
P7
JW1
I/O Board
Pin 1
Pin 1
Pin 1
Pin 1
Function
Terminated
Unterminated
Pins
1-2
2-3
Fig. 12 Electrical connections
Connect alarm output cable, if used, to P3 connector.
Pin Designation
1 12 V DC (100 mA max.) 2 12 V DC (100 mA max.) 3 Output P0 (40 mA sync. Max.) 4 Output P1 (40 mA sync. Max.) 5 Output P2 (40 mA sync. Max.) 6 Output P3 (40 mA sync. Max.) 7 Ground 8 Ground
Connect alarm input cable, if used, to P4 connector.
Pin Designation
1 Alarm 3 input (3.5 mA sink) 2 Alarm 2 input (3.5 mA sink) 3 Alarm 1 input (3.5 mA sink) 4 Alarm 0 input (3.5 mA sink) 5 Ground 6 Ground
Connect power to P7 connector.
Pin Designation
1 24 V AC 2 Ground 3 24 V AC
91
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 24
Indoor Installation
4. Reattach I/O board.
5. Connect power to base.
6. Set dome address (Figure 13). Recessed at top of housing and eyeball assembly are three rotary address switches. Address range is from 001 to 099. Set switches from most significant bit (MSB) to least significant bit (LSB). For example: For address 066, set SW3 to 0, SW2 to 6,and SW1 to 6
.
090909
MSB
LSB
SW3
SW1SW2
Figure 13 Setting address switches
7. Connecting the housing and eyeball assembly to the base (Fig. 14).
Align dimple on cap of dome with rib on mounting base. Mate housing and eyeball assembly to base and turn it clockwise until you
hear a click.
8. Wait a few seconds for dome to begin its homing routine. Homing routine indicates that address was placed into dome memory and that dome is ready for programming.
L
A
T
C
H
Fig. 14 Connecting the housing and eyeball assembly to the base
92
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 25
Using the Dome Configuration Utility
7 Using the Dome Configuration Utility
This chapter introduces you to the Dome Configuration Utility. It explains how to start the utility, navigate through the menus, and change settings. It also explains where to find specific information about customizing dome settings. The Dome Configuration Utility is started using a series of keyboard commands (Siemens Control Unit CKA3210 and CKA4810). Depending on the controller and network protocol in use, the commands required to start the configuration utility differ. If the dome is installed together with the Siemens Control Unit CKA3210 or CKA4810, press and hold Cam, then press F1.
The Dome Configuration Utility provides a means to setting features for your camera dome via a text overlay menu. You access this utility using a keystroke combination on your camera controller. The utility provides settings relating to camera functions, alarms, text display, privacy zones, direction indicators and password protection. Some items supplement similar features that may be available through your controller. Refer to your controller operating instructions for information about button locations mentioned in this document.
7.1 Starting the Dome Configuration Utility
The Dome Configuration Utility is started using a series of keyboard commands. Depending on the controller and network protocol in use, the commands required to start the configuration utility differ. If the dome is installed in a Siemens RS422/RS485 environment, press and hold Cam, then press F1.
NOTE:
Other protocols and controllers may be supported. The Appendixes located at the end of this manual provide additional information.
DOME CONFIGURATION MENU
PAN/TILT/ZOOM/SYNC OPTS
CAMERA FUNCT ION S
A
LARMS/AREAS/PRESETS/PZ
ON-SCREEN TE XT DI SPL AY
LANGUAGE / PASSWORD
DOME INFORMATION
RESET TO FACTORY SETTINGS
QUIT WITHOUT SAVING
EXIT AND SAVE CHANGES
Fig. 15 Dome configuration menu
IMPORTANT
If you have password protection enabled for the configuration utility, the Enter Password screen appears first. You must correctly enter the password before the Dome Configuration Menu will appear.
93
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 26
Using the Dome Configuration Utility
7.2 Working with the Dome Configuration Utility
Once the Dome Configuration Menu is displayed, you may select a menu item, and then modify the settings you want to change. The following table summarizes the controller commands for Siemens Control Unit CKA3210 and CKA4810. For combination keystrokes, press and hold each button in sequence, then release.
If you want to … Use …
Move the highlight bar.
Pan/Tilt
Select the highlighted item on the screen.
Focus
Increase the value of the selected setting or display the next choice for the setting
Zoom In
Decrease the value of the selected field, or display the previous choice for the field.
Zoom Out
During naming, move the cursor to the right of the current character in the name.
Zoom In
During naming, move the cursor to the left of the current character in the name.
Zoom Out
Save changes and exit the utility from any screen.
Cam, then F10
7.3 Entering the Dome's Password
A dome password can be used to prevent unauthorized users from starting the configuration utility. The Enter Password screen appears when the command to start the configuration utility is entered, if password protection is enabled.
ENTER PASSWORD
PASSWOR D: ** *** ***
ABCDEFGHIJKLMNOPQRST UVWXYZabcdefghijklmn opqrstuvwxyz 0123456 789/-
CONTINUE
CANCEL
Blank Space Character
Fig. 16 Password
Users must enter the password before the Dome Configuration Menu displays. The password may be from 1 to 8 characters long. To enter the password using Siemens RS422/RS485 protocols:
1. Use the Pan/Tilt control to move the cursor around the character field.
2. Press Focus to enter the highlighted character. If you need to change a character that has been entered:
Zoom In moves the cursor to the right in the Password field. Zoom Out moves the cursor to the left in the Password field.
94
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 27
Using the Dome Configuration Utility
As each character in the password is selected, asterisks (*) appear in the Password field. When you have finished entering the password, select Continue. If the correct password has been entered, the Dome Configuration Menu appears. If the correct password was not entered, the Enter Password screen remains on the monitor. If you do not want to start the configuration utility, select Cancel to return to normal dome operation.
IMPORTANT If you forget the password, contact your Siemens Representative for assistance.
7.4 Restoring Factory Settings
Some screens provide a choice to restore factory settings. This choice applies only to those settings currently displayed on the screen. To reset all configuration settings, choose Reset to Factory Settings from the Dome Configuration Menu. The following prompt appears:
Reset to Factory Settings No
If you want to restore the factory settings, select Yes. If you do not want to restore the factory settings, select No.
IMPORTANT
Selecting Reset to Factory Settings from the Dome Configuration Menu does not change the following settings: Camera Name, Alarm Names, Area Names, Preset Names, Pattern Names, Area Boundaries, Privacy Zones, and Presets. To reset names to the default settings.
7.5 Exiting the Configuration Utility
You may save your changes and exit the utility from any screen by pressing and holding Cam, then pressing F10. From the Dome Configuration Menu, you have two choices for exiting the utility: Exit and Save Changes or Quit Without Saving. Use the Pan/Tilt control to move the highlight bar up and down on the screen.
If you want to keep the changes you made, move the highlight bar to Exit and
Save Changes, and select. The utility closes.
If you want to exit without making changes, move the highlight bar to Quit
Without Saving, and select. The following prompt appears on the screen:
Data Not Saved. Quit Anyway? No
To cancel the changes, select Yes. To keep the changes, select No. If you choose No, the Dome Configuration Menu is displayed.
95
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 28
Configuring Pan, Tilt, Zoom, and Synchronization Options
8 Configuring Pan, Tilt, Zoom, and Synchronization
Options
When Pan/Tilt/Zoom/Sync Opts is selected from the Dome Configuration Menu, the following screen appears:
PAN/TILT/ZOOM/SYNC OPTS
PROPORTIONAL FLIP OFF/ON 1ST ZOOM STOP X 35/23 MAX TOTAL ZOOM X 46...1 84 LINE LOCK ON/OFF
RESET TO FACTORY SETTINGS
EXIT
Fig. 17 PTZ, Sync options
Use this screen to enable or disable the “automatic flip” feature, configure the zoom stop settings, and set the line lock options.
To change the settings, move the highlight bar to appropriate field and make the
changes.
To change the settings for this screen to the factory defaults, select Reset to
Factory Settings.
To return to the Dome Configuration Menu, select Exit.
8.1 Setting the Automatic “Flip” Feature
Use the automatic (proportional) “flip” feature when you need to track someone who walks directly under the dome and continues on the other side. You start the flip by moving the tilt control to its lower limit and holding for a brief period. When the flip engages, the dome automatically rotates 180°. You may then continue to track the person as long as the tilt control stays in its lower limit. Once the tilt control is released, the dome resumes normal operation. The dome is initially installed with the automatic flip feature disabled. In this situation, the dome stops when the tilt down reaches its lower limit.
8.1.1 Changing the Automatic Flip Setting
1. Select Pan/Tilt/Zoom/Sync Opts from the Dome Configuration Menu. The highlight bar appears on the Proportional Flip setting.
2. Change the setting.
Select On to enable the flip feature. Select Off to disable the flip feature.
The default setting is Off.
3. Select Exit. The Dome Configuration Menu appears.
96
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 29
Configuring Pan, Tilt, Zoom, and Synchronization Options
8.2 Adjusting the Zoom Stop Settings
The SIEMENS DAY/NIGHT Dome CCDA1415-DN includes a 23 x optical zoom camera with 8 x digital zoom capability. The maximum possible zoom is 184 x. Zoom stop settings define how the zoom function is partitioned. Depending on the current zoom level, the camera will either stop at the first zoom stop setting or continue to the maximum zoom setting. The following example explains how zoom stop settings work. The default camera settings are 35 x for the first zoom stop setting and 92 x for the maximum zoom setting. If the current zoom level is less than 35 x, pressing Zoom In continuously causes the zoom to stop at 35 x. If the zoom level is 35 x or greater, pressing Zoom In continuously causes the zoom to stop at the maximum zoom setting of 92 x. The second zoom stop remains in effect until the zoom function is reduced to less than the first zoom stop setting (35 x) and the zoom button is released for one second or longer. To achieve higher zoom levels, change the maximum zoom setting. 2 x is the margin of error for the zoom stop settings.
8.2.1 Changing the Zoom Stop Settings
1. Select Pan/Tilt/Zoom/Sync Opts from the Dome Configuration Menu.
2. To change the first zoom stop, continue with step 3. To change the maximum zoom setting, continue with step 5.
3. Move the highlight bar to 1ST ZOOM STOP X. Change the setting.
Select 23 to set the first zoom stop to 23 x magnification. Select 35 to set the first zoom stop to 35 x magnification.
The default setting is 35 x.
4. To change the maximum zoom setting, continue with step 5. Otherwise, continue with step 6.
5. Move the highlight bar to the Max Total Zoom X setting. Change the value of the setting.
The values for the setting are: 46 x, 69 x, 92 x, 115 x, 138 x, 161 x, and
184 x magnification.
The default setting is 92 x.
6. Select Exit. The Dome Configuration Menu appears.
8.3 Configuring the Line Lock Setting
Use the Line Lock setting to prevent vertical rolling or adjust the appearance of overlay text on color monitors. If you experience problems with vertical video rolling when switching multiple cameras to a single monitor, enabling the Line Lock setting phase locks the video with the AC power line. All cameras connected to the same power supply will be synchronized. This synchronization prevents the video from rolling vertically when cameras are switched. With the Line Lock disabled, the appearance of text displayed on color monitors may be improved. However, the video will no longer be phase locked with the AC power line. Video may roll vertically when switching between cameras.
97
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 30
Configuring Pan, Tilt, Zoom, and Synchronization Options
8.3.1 Changing the Line Lock Setting
1. Select Pan/Tilt/Zoom/Sync Opts from the Dome Configuration Menu.
2. Move the highlight bar to Line Lock. Change the setting.
Select On to enable the line lock. This phase locks the video with the AC
power line to prevent video rolling.
Select Off to disable the line lock. This stops the phase lock, but may
improve the appearance of text displayed on color monitors.
IMPORTANT
Changing the Line Lock setting is not immediate. The dome must reinitialize (reset) for the change to take place.
3. When the configuration utility is exited, the following prompt appears:
DOME MUST RESET TO CHANGE LINELOCK MODE.
RESET DOME NOW? NO
If you do not want to reinitialize the dome, select No. Changes to the Line
Lock setting will not take effect.
If you want to reinitialize the dome, select Yes. Changes to the Line Lock
setting will take effect when the dome finishes the reset.
4. Select Exit. The Dome Configuration Menu appears.
98
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 31
Configuring Camera Features
9 Configuring Camera Features
This chapter describes the settings used to control the camera features. It describes how to change the white balance settings, IR mode, wide dynamic range settings, automatic gain control, and open shutter settings to improve camera performance.
9.1 Overview of Camera Settings
When Camera Functions is selected from the Dome Configuration Menu, the following screen appears:
CAMERA FUNCTIONS
Auto White Bal OFF/ON W Bal Adj: Red 0-511 Blue 0-511 IR Mode OFF/ON/Auto High/Auto Mid/Auto Low WDR OFF/ON AGC/Shutter Max Gain Limit Open Shutter(NTSC)0-28 dB 1/2-1/60 s
RESET TO FACTORY SETTINGS
EXIT
Open Shutter(PAL) 0-29 dB 2/3-1/50 s
Fig. 18 Camera functions
From this screen you can adjust the white balance settings, set the IR mode for the camera, enable or disable Wide Dynamic Range, set the automatic gain control (AGC) feature, adjust the AGC level, and configure the open shutter settings.
To change settings, move the highlight bar to the appropriate field and make the
changes.
To change the settings for this screen to the factory defaults, select Reset to
Factory Settings.
To return to the Dome Configuration Menu, select Exit.
99
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 32
Configuring Camera Features
9.2 Adjusting White Balance Settings
White balance is normally compensated for by the automatic white balance gain control. In some lighting conditions, you may need to manually adjust the red and blue settings for optimal viewing. When Automatic White Balance is enabled, the red and blue setting values are based on feedback from the camera. When Automatic White Balance is disabled, the camera uses the red and blue setting values to control the white balance. When Automatic White Balance is first switched from On to Off, the red and blue values displayed are based on the current feedback from the camera. The red and blue values range from 0 to 511. Changes occur in increments of 5. The following chart illustrates the red and blue settings relationship to white balance.
100
Maximum
Blue
WHITE BALANCE
511
On-screen Colo
r
appears Magenta
(Purple)
Both Red and Blue settings are maximized.
On-screen Color appears Green
0
Minimum
Blue
Minimum
Red
Maximum
Red
511
0
Fig. 19 White balance
As the value for the red setting increases, the image appears more red. As the value decreases, the image appears less red. As the value for the blue setting increases, the image appears more blue. As the value decreases, the image appears less blue. As the values for both the red and blue settings are increased, the image appears more magenta (purple). As the values for both the red and blue settings are decreased, the image appears more green.
Tip: Auto White Bal must be set to Off to manually change the Red and Blue settings.
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 33
Configuring Camera Features
9.2.1 Changing Automatic White Balance Settings
1. Select Camera Functions from the Dome Configuration Menu. The highlight appears on the Auto White Bal setting.
2. Change the setting.
Select Off to manually adjust the red or blue settings. Continue with step 3. Select On for automatic white balance. Continue with step 7.
The default setting is On.
3. Do one of the following:
To change the red setting, move the highlight bar to W Bal Adj: Red,
continue with step 4.
To change the blue setting, continue with step 5.
4. Adjust the red setting. The values range from 0 to 511 and change in increments of 5.
There is no default value for the red setting.
5. Do one of the following:
To change the blue setting, move the highlight bar to Blue,
continue with step 6.
If you are finished making changes, continue with step 7.
6. Adjust the blue setting. The values range from 0 to 511 and change in increments of 5.
There is no default value for the blue setting.
7. Select Exit. The Dome Configuration Menu appears.
9.3 Understanding How IR Mode (Black & White) Operates
SIEMENS DAY/NIGHT Dome CCDA1415-DN provides a black-and-white (B/W) mode to improve camera performance when the light level falls below certain thresholds. This allows clear images to be obtained under low-light conditions. This is referred to as IR Mode. There are five IR Mode settings: Off, On, Auto High, Auto Mid and Auto Low. The following table lists the approximate lux values when the camera is expected to switch between color and B/W modes. Actual values depend on the current zoom setting of the camera and the light source.
IR Mode Setting Camera Performance
B/W Mode
Activated
B/W Mode
Deactivated
Off No B/W capabilities. N/A N/A On Full-time B/W mode. N/A N/A Auto High Cleanest possible picture. No field integration effect. ~30 lux ~135 to 155 lux Auto Mid Minimizes field integration effect. ~3 lux ~20 to 25 lux Auto Low Maximizes color low-light performance. ~0.5 lux ~10 to 12 lux
Table 4 IR Mode Setting
101
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 34
Configuring Camera Features
9.3.1 Changing the IR Mode Setting
1. Select Camera Functions from the Dome Configuration Menu.
2. Move the highlight to the IR Mode field. Change the setting.
Select OFF to disable the IR mode. The camera will operate in color mode
only.
Select ON to enable full-time B/W mode. Select Auto High to enable automatic B/W mode at ~30 lux. Select Auto Mid to enable automatic B/W mode at ~3 lux. Select Auto Low to enable automatic B/W mode at ~0.5 lux.
The default setting is ON.
3. Select Exit. The Dome Configuration Menu appears.
9.3.2 Manually Activating or Deactivating the IR Mode
The IR mode can be manually activated or deactivated using a combination of keyboard commands. This allows you to change between color and B/W modes as needed. To change the mode using Siemens RS422/RS485 protocols: press and hold Cam-button on keyboard, press and hold button F3. Using the manual command has the following affect on the menu settings:
If the current IR Mode setting is... The setting changes to...
IR Mode On IR Mode Off IR Mode Off IR Mode On IR Mode Auto High, Auto Mid, or Auto Low IR Mode On
Tip:
If you need to resume Auto High, Auto Mid, or Auto Low IR mode settings, you must use the Dome Configuration Menu (see "Changing the IR Mode Setting").
102
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 35
Configuring Camera Features
9.4 Understanding Wide Dynamic Range
Wide Dynamic Range (WDR) is a feature that allows clear viewing of both bright and low light areas in a scene. Use this feature if you need to view both indoor and outdoor lighting conditions simultaneously. For example, a dome is installed in the loading dock area of a building. When the door to the loading dock area is closed, the light level remains constant and the interior can be viewed clearly without iris adjustments.
Fig. 20 Example scene of a loading dock with the door closed
When the door is open, additional light from outside enters the room and distortion occurs. Without WDR, you could adjust the iris of the camera to compensate for the lighting change, however you cannot clearly see both activities inside and outside of the loading dock area simultaneously. For example, if you close the iris, the outside scene will improve, but the interior scene will become too dark to view clearly. In Fig. 21, the car near the loading dock door can be seen clearly, but the interior of the room appears too dark
Fig. 21 Example scene of loading dock with door open and iris close adjustment
If you want to view the interior scene, open the iris to make the dark scene appear brighter. However, this causes the outdoor scene to appear too bright. In Fig. 22, it is difficult to see the car near the loading dock door.
Fig. 22 Example scene with loading dock door open and iris open adjustment
103
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 36
Configuring Camera Features
With WDR enabled, you can see the scenes both inside and outside the loading dock area. In Fig. 23, you can see the boxes stacked inside the loading dock area and the car approaching the door.
Fig. 23 Example scene with loading dock door open and WDR enabled
NOTE:
When WDR is enabled, you may notice a slight flicker to the video image. This is a normal aspect of WDR operation.
9.4.1 Changing the Wide Dynamic Range Setting
1. Select Camera Functions from the Dome Configuration Menu.
2. Move the highlight to the WDR field. Change the setting.
Select OFF to disable wide dynamic range. Use this setting when the light
level is constant or changes in lighting conditions are gradual.
Select ON to enable wide dynamic range. Use this setting when both bright
and low light areas need to be viewed simultaneously.
The default setting is OFF.
3. Select Exit.
9.5 Working with AGC and Open Shutter Settings
The Dome camera CCDA1415-DN provides settings for compensating for low-light scenes in color: Automatic Gain Control and Open Shutter. Automatic Gain Control (AGC) amplifies the video signal in scenes with minimal light. Many low-light scenes result in picture noise. As gain is increased, the picture noise is also amplified. When AGC is enabled, the camera automatically adjusts the gain setting value. When AGC is disabled, no gain is applied to the video signal. This may make the video appear darker on the monitor. The gain setting for the camera differs from the maximum gain (Max Gain) setting available on the Camera Functions menu. The Max Gain setting is an upper limit for how much gain can be increased when AGC is enabled. The trade-off between picture level (brightness) and noise may be adjusted by setting the Max Gain value. Lower values for Max Gain setting may result in a darker picture with less noise. Higher values for Max Gain setting may result in a brighter picture with more noise. In addition to the AGC settings, you can also change the Shutter settings to improve the dome's low-light performance.
104
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 37
Configuring Camera Features
9.5.1 Understanding How Advanced Shutter Settings Improve Low-Light Performance
The camera dome supports the ability to view color images from extremely low­light situations. This feature is called Open Shutter and is only in effect during low­light situations where an image would not be obtainable otherwise. It does not affect the camera performance in normal or bright light situations. When the Open Shutter is enabled and the scene illumination is too low to obtain a clear image at the normal video rate, the camera collects luminance information from multiple fields. As it does so, the current video information is retransmitted until new information is available from the camera. Under these conditions, moving objects will appear blurred, and still images may appear blurred, choppy, and with more static than video obtained under normal lighting conditions. The Shutter Limit value sets the video update time in fractions of a second. Depending on the lighting conditions, the video information may be updated more frequently, but no slower than the limit set.
180
msec
250 msec
250
msec
Red Light Red Light Red Light Green Light
Fig. 24 Graphical view of Shutter Limit settings
In this example, the dome receives information about the color of the traffic light. While the light is red, the image is relatively static. With the shutter limit set to 1/4 second (250 milliseconds), updated red light information is transmitted at 1/4 second intervals. When the light changes from red to green, updated light color information becomes available. The dome must now transmit information about the green light. This update occurs as soon as the green light information is available. This may occur before the 1/4-second interval elapses. In this example, the light changed to green after 180-milliseconds. Thereafter the green light information is transmitted at 1/4-second intervals until new light color information becomes available. If the traffic light changes from red to green in the middle of the field integration interval (125 ms), you may get the impression that both the red and the green lights light up simultaneously. This situation is illustrated in Fig. 25.
125
msec
250
msec
125
msec
Red Light Red Light Red/Green Light Green Light
Fig. 25 Mixed field integration
Adjusting the Shutter Limit sets the update time used to maintain the image quality. If you want to videotape an incident in low-light conditions, you may find that tape quality is not acceptable. To ensure that the videotape quality is acceptable for possible prosecution purposes, you may want to test the Shutter Limit settings under the expected lighting conditions.
105
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 38
Configuring Camera Features
9.5.2 The Relationship between IR Mode and AGC and Open Shutter Settings
The current IR Mode setting affects which AGC and Open Shutter settings are available. The following table lists which AGC/Shutter modes are available based upon the IR Mode setting:
IR Mode Setting AGC Off AGC On Open Shutter
Off Yes Yes Yes On Yes Yes Yes
Auto High Yes Yes No
Auto Mid No No Yes
Auto Low No No Yes
Table 5 IR Mode and AGC and Open Shutter Settings
When AGC Off is the current setting, the Max Gain and Limit fields are not
displayed.
When AGC On is the current setting, the Max Gain field is displayed and may be
modified. The Limit field is not displayed.
When Open Shutter is the current setting, both the Max Gain and Limit fields are
displayed and may be modified.
9.5.3 Configuring AGC and Open Shutter Settings
Tip: The current IR Mode setting affects which AGC and Shutter settings are available.
1. Select Camera Functions from the Dome Configuration Menu.
2. Move the highlight to AGC/Shutter mode field. The highlight appears in the first field (AGC/ Mode).
3. Select one of the following:
Select AGC On to set AGC to automatic mode. This allows you to adjust
the maximum AGC gain setting (in decibels). Continue with step 4.
Select AGC Off to set the AGC to minimum level. You cannot adjust the
maximum AGC gain or shutter limit settings. Continue with step 7.
Select Open Shutter to enable field integration. This allows you to adjust
the maximum AGC gain and shutter limit settings. Continue with step 4.
The default setting is Open Shutter.
4. Move the highlight to Max Gain field. Change the setting.
5. If you need to change the shutter limit setting, continue below. Otherwise, continue with step 7.
6. Move the highlight to the Limit field. Change the setting.
The default setting is 1/3 for PAL.
7. Select Exit. The Dome Configuration Menu appears.
106
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 39
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10 Configuring Alarms, Areas, Home, Privacy Settings
and Presets
This chapter describes settings associated with Alarms, Areas, the Home Position, Privacy Zones, and Presets. It explains how to set a default action to run when a dome alarm occurs, as well as how to define the normal alarm input states. It describes how to set a default position for the dome and assign a dome position that corresponds with North. It also explains how to program Areas, Privacy Zones, and Presets.
10.1 Overview of Alarms, Areas, Home, North Position, Preset and Privacy Settings
When Alarms/Areas/Home/Presets/PZ is selected from the Dome Configuration Menu, the following screen appears:
ALARMS/AREAS/HOME/PRESETS/PZ
SET ALARM ACTIONS
SET ALARM STATES
SET HOME POSITION
SET NORTH PO SI T IO N
AREA BOUNDARIES
PRIVACY ZONES
PRESETS
EXIT
Fig. 26 Alarms/Areas/Home/Presets and Pan Zoom
From this menu you can choose to configure alarm actions, configure normal states for alarm inputs, assign the “home position”, establish the north position for the dome, set area boundaries, set privacy zones, and program presets.
To make changes, select a menu item to display the associated settings. To change the settings, move the highlight bar to appropriate field and make the
changes.
To return to the Dome Configuration Menu, select Exit.
107
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 40
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.2 Alarm Actions
IMPORTANT
When used in Siemens RS422/485 networks, the dome camera can be configured to respond to all available alarm inputs. The dome cannot transmit alarm input states to the host controller. So if alarm states are to be transmitted to the host controller, the alarm device must be directly connected to the host controller.
The dome provides alarm inputs. By connecting alarm devices - such as smoke alarms, twilight sensors, or motion sensors - to these inputs, you can enhance the usability of your video surveillance system. You can further improve your video surveillance by assigning a dome action (a preset or pattern) to start whenever an alarm input changes from normal to abnormal. When Set Alarm Actions is selected from Alarms/Areas/Home/Presets/PZ screen, the following screen appears:
SET ALARM ACTIONS
INTERNAL ALARMS
INPUT NO. ACTIO N
1 NO ACTI ON 2 PRESET 1-96 3 PATTERN 1-3 4 NO ACTI ON
SEND INPUTS TO HOST? YES / NO
EXIT
Fig. 27 Set alarm actions.
Use this screen to assign a preset or pattern to occur whenever the alarm's input state changes from normal to abnormal. You may also choose to have no action occur when the alarm's input state changes. Alarms can be processed internally by the dome, externally by the controller, or both. You may choose to send changes in the input state to the host controller. If the changes in input state are sent to the host controller, the host actions have higher priority than the associated dome actions.
NOTE:
An active internal alarm only resets when the input state changes to “normal.” A manual reset is not available.
108
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 41
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.2.1 Configuring Alarm Actions
IMPORTANT
Some controller types allow you to define the alarm actions for dome cameras directly on the controller. Please refer to the appropriate Appendix for additional information on the controller types that support this function. Use either the dome configuration utility or the controller to set the alarm actions - never use both simultaneously at the same input.
Use only the dome configuration utility or the controller to assign the alarm actions.
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Set Alarm Actions. The Set Alarm Action screen appears.
3. Move the highlight bar to the appropriate alarm input. Change the setting.
Select Preset to use a preset as the alarm action. Continue with step 4. Select Pattern to use a pattern as the alarm action. Continue with step 4. Select No Action if you do not want to set an alarm action. Continue with
step 6.
4. Move the highlight bar to the Action Number field and select the action number.
For preset, select the number from 1 through 64. Continue with step 5.
i
NOTE: The protocol (or controller) used may support fewer presets.
For pattern, select the number from 1 through 3 for the pattern you want to
assign. Continue with step 5. If the selected pattern is not programmed, the dome runs the Apple Peel pattern.
5. If you need to make additional changes to the alarm actions for this dome, repeat steps 3 and 4. When finished, continue with step 6.
6. Move the highlight bar to Send Inputs to Host?
Is not possible to send alarm contact status back to the controller.
Choose No.
The default setting is Yes.
7. Select Exit to return to the Alarm/Areas/Home/PZ screen.
8. When the Alarm/Areas/Home/PZ screen appears, select Exit. The Dome Configuration menu appears.
109
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 42
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.2.2 Configuring Normal Input States for Alarms
IMPORTANT
Some controller types allow you to define the normal input states for dome cameras directly on the controller. Use only the dome configuration utility or the controller to assign the normal input states.
The normal input state for an alarm is the state that the device maintains when an alarm is not occurring. For example, you have a smoke detector connected to a dome input. Under normal circumstances, the smoke detector should not be detecting smoke. When smoke is detected, the alarm input changes states (from open to closed) and an alarm is issued. To configure the normal state for the alarm, select Set Alarm States from the Alarm/Areas/Home/Presets/PZ screen. The following screen appears:
SET ALARM STATES
INPUT NO. NORMAL STATE
1 OPEN / CLOSED 2 OPEN / CLOSED 3 OPEN / CLOSED 4 OPEN / CLOSED
EXIT
Fig. 28 Set alarm states
Use this screen to assign open or closed as the normal state for the dome alarm inputs. When an input state changes from normal to abnormal and an internal alarm action is associated with the input, the alarm is triggered. The normal state is used by both internal alarms and controller defined alarms.
10.2.3 Setting Alarm Input States
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Set Alarm States.
3. Select the appropriate input line, and then change the setting.
Select Open if the alarm normal input state is open. Select Closed if the alarm normal input state is closed.
The default setting is Open.
NOTE:
In most cases, the normal input state for a dome's input should match the contact type of the connected switch.
4. Repeat step 3 for each input requiring change. When finished, continue with step 5.
5. Select Exit to return to the Alarms/Areas/Home/Presets/PZ screen.
6. When the Alarms/Areas/Home/Presets/PZ screen appears, select Exit. The Dome Configuration Menu appears.
110
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 43
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.3 Assigning the Dome’s Home Position
The home position is a preset or pattern that automatically runs after a designated period of dome inactivity. Use this option if you want a specific area to be under surveillance after an operator stops moving the dome. To assign the home position, select Set Home Position from the Alarms/Areas/Home/Presets/PZ screen. The following screen appears:
SET HOME POSITION
HOME POSITION NO ACTION
RETURN TIM E M IN S 1-60 (10)
EXIT
PRESET 1-9 6 PATTERN 1-3
Fig. 29 Set home position
Tip:
When a pattern is selected as the home position, the pattern runs until stopped manually by issuing a camera command, such as Tilt or Focus.
Setting the Home Position
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Set Home Position. The highlight bar appears on the Home Position setting.
3. Select a setting.
Select Preset to use a preset as the home position. Continue with step 4. Select Pattern to use a pattern as the home position. Continue with step 4. Select No Action if you do not want to set a home position. Continue with
step 5.
4. Move the highlight bar to the Number field, and select a number.
For preset, select the number from 1 through 64. Continue with step 5.
i
NOTE: The protocol used may support fewer presets.
For pattern, select the number from 1 through 3 for the pattern you want to
assign. Continue with step 5. If the selected pattern is not programmed, the dome runs the Apple Peel pattern.
5. Move the highlight bar to Return Time Mins. Set the amount of time that the dome must remain inactive before returning to the home position.
The setting ranges from 1 to 60 minutes.
6. Select Exit to return to the Alarms/Areas/Home/Presets/PZ screen.
NOTE: If you selected a preset that has not been programmed, preset programming automatically starts.
7. When the Alarms/Areas/Home/Presets/PZ screen appears, select Exit. The Dome Configuration Menu appears.
111
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 44
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.3.1 Setting the North Position
Direction indicators permit you to understand the approximate pointing position of the dome to an established reference point. This reference point is called “North” and may correspond to magnetic north (if it is known) or some other landmark or fixture. When the dome is initially installed, “North” defaults to a pre-defined position (0° pan/tilt). You may program the “North” position to be any point along the dome's pan axis (also called azimuth).
Programming
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Set North Position.
The Set North Position screen appears:
SET NORTH POSITION
PAN to new north positi on
ZOOM to mark north position
FOCUS quits w/o changing
Fig. 30 Set North position
3. Point the dome to the new North position. When satisfied with the view, save the setting, or cancel the change.
4. The Alarms/Areas/Home/Presets/PZ screen appears. Select Exit. The Dome Configuration Menu appears.
112
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 45
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.4 Programming Area Boundaries
If the dome is installed in a location where you can see numerous departments or other identifiable objects, you might want to consider programming area boundaries. Areas are programmed start- and end-points of a camera's field of view. Each area is a part of a circular viewing area that extends around the dome. The ending point of one area is the starting point for the next area. The ending point of the last area cannot go past the starting point of the first area. In this example, the area that includes the vending machines cannot extend past the starting point of the area that includes the emergency exit. If your controller supports areas, these are separate from the areas you can program with the dome. You should not use both the controller and the configuration utility to define areas.
V
ending Machines
Lockers
Entrance
Emergency
Exit
Area
1
Area
8
Area
2
Area
7
Area
5
Area
6
Area
3
Dom
Area
4
Areas appear smaller when zoomed in.
Areas appear larger when
zoomed out.
Fig. 31 An example of areas found in a break room
The zoom level also affects how large areas appear. When you zoom in to an area, the area may appear to be small. When you pan the dome, area boundaries may appear to be close. However, if you zoom out, the area appears to be larger. When you pan the dome, the area boundaries appear further apart. With this in mind, it will be easier to establish area boundaries if the zoom level is small than if the zoom level is large.
NOTE: When defining areas, each area is assigned a standard name.
113
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 46
Configuring Alarms, Areas, Home, Privacy Settings and Presets
To program areas, select Area Boundaries from the Alarms/Areas/Home/Presets/PZ screen. The following screen appears:
A
REA BOUNDARIES
PAN to start of BOUND 1-16
PAN RIGHT ONLY
ZOOM to mark BOUNDARY FOCUS saves and exits
Fig. 32 Setting Area Boundaries
If no boundary is set, pressing Focus quits without making any changes. The dome supports up to 16 areas.
IMPORTANT
If areas were previously programmed, you cannot restore the previously programmed boundaries by selecting Quit Without Saving from the Dome Configuration Menu once you begin making changes the boundaries.
10.5 Setting Area Boundaries
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Move the highlight bar to Area Boundaries, then select. The Area Boundaries screen appears.
3. Adjust the camera to the starting point of the first area, and press Zoom to mark the boundary.
4. Adjust the dome to the right until the ending point of the area is seen. If you attempt to move left, an error message appears. See the note for information.
5. Mark the end-point of the area. The area number automatically advances.
6. Repeat steps 4 and 5 for each area you want to establish.
NOTE:
You will receive an error message under the following conditions:
If you attempt to program an area boundary that passes the starting point of the first area If you move the camera left after establishing the first boundary.
Return to step 2 and start again.
7. When the last area boundary is set, save the changes. A message appears confirming that the areas have been successfully saved. Press Focus to continue.
8. When the Alarms/Areas/Home/Presets/PZ screen appears, select Exit. The Dome Configuration Menu appears.
114
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 47
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.6 Establishing Privacy Zones
Privacy Zones are “masked” sections of the dome’s viewing area. These masks prevent operators of the surveillance system who do not have access to the dome password from viewing these designated zones. Each zone has four sides, and the zones may overlap to form irregular shapes. The Privacy Zones move in relation to the dome pan/tilt position. In addition, the apparent size of the Privacy Zone adjusts automatically as the zoom level is adjusted. Up to eight Privacy Zones may be established for a dome. Privacy Zones are useful for high security areas. For example, you might establish a Privacy Zone around a safe’s combination. However, you could view people approaching or opening the safe. In addition, the appearance of the configuration menus changes slightly when Privacy Zones are active. Both the first and last lines of the menus will appear in enlarged text when Privacy Zones are active. The menus change to one-sized text if Privacy Zones are hidden or deleted. To program Privacy Zones, select Privacy Zones from the Alarms/Areas/Home/Presets/ PZ screen. The following screen appears:
PRIVACY ZONES
A
DD PRIVACY ZONES
DELETE SPECIFIC ZONE
DELETE ALL ZON E S
HIDE ALL ZONES? NO/YES
EXIT
Fig. 33 Setting Privacy Zones
From this screen you can establish up to eight Privacy Zones, delete individual or all Privacy Zones, or hide all Privacy Zones. Further information can be found in the following chapters.
115
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 48
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.6.1 How Privacy Zones are Programmed
Privacy Zones are established by selecting three points on the display image to mask. The fourth point on the Privacy Zone is automatically generated by mirroring the longest axis between the three selected points Fig. 34 illustrates how Privacy Zones are programmed.
+
+
+
+
Point 1
Point 4 mirrors the longest axis.
Point 2
Point 3
Fig. 34 Privacy Zone programming example
The dome’s firmware prevents you from establishing a zone that is too small or too large (greater than 90-degrees pan or tilt from the starting point). Fig. 35 illustrates the Privacy Zone programming screen:
NEW PRIVACY ZONE
Navigate to corner 1(2, 3)
ZOOM to Mark Corner
FOCUS to Abandon Zone
Fig. 35 Privacy Zone Programming screen
The circled arrows represent the target area on the screen for creating the Privacy Zone. Normally, this target area remains in the center of the screen. Using the Pan/Tilt control moves the target area by panning or tilting the dome. If the dome reaches its maximum tilt position, the Privacy Zone may still be established in the upper part of the display. When this occurs, the arrows move relative to the movement of the Pan/Tilt control until the top of the display area is reached. The boundary points on the Privacy Zone are selected by pressing Zoom. Once a boundary point is selected, the arrows “blink” until the target area is moved to a valid area. Once the target moves to a valid area, the arrows stop blinking. If you move the target more than 90-degrees from a selected point, the arrows begin to blink again, indicating that the boundary is too large. If you attempt to establish a boundary point while the arrows are blinking you will receive an error message: Zone is Too Small or Zone is Too Large. If this happens, you must start programming from the beginning. Pressing Focus Far returns you to the Privacy Zone programming screen. If you attempt to program more than eight Privacy Zones, the following message appears:
116
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 49
Configuring Alarms, Areas, Home, Privacy Settings and Presets
Maximum Allowed Number of Zones Defined
Pressing Focus Far returns to the Program Privacy Zones screen. To program a new zone, you must delete at least one of the eight existing Privacy Zones:
IMPORTANT
Areas of the Privacy Zone may be exposed during rapid pan / tilt movements of the dome. To compensate for this limitation, you may want to program the Privacy Zone to be 20 to 25% larger than the area you want to mask.
10.6.2 Programming Privacy Zones
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Privacy Zones.
3. The Program Privacy Zones screen appears. Select Add Privacy Zone.
4. Use the Pan/Tilt control to position the arrows over the boundary point. Press Zoom to create.
5. Repeat step 4 to create boundary points 2 and 3.
Tip:
Remember, if the arrows are blinking, you are not in a valid target area. Only select a point if the arrows are not blinking.
6. After the third boundary point is created, the fourth boundary point is automatically calculated. The new Privacy Zone appears on the screen. To program additional Privacy Zones, repeat steps 3 through 5. When finished, continue with step 7.
7. Select Exit to return to Alarms/Areas/Home/Presets/PZ screen.
8. When the Alarms/Areas/Home/Presets/PZ screen appears, select Exit.
117
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 50
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.6.3 Removing or Hiding Privacy Zones
If you made an error during programming or no longer require Privacy Zones, individual zones or all Privacy Zones may be deleted. To temporarily remove the Privacy Zones, you may disable their appearance by changing the Hide All Zones setting to Yes. To delete individual Privacy Zones, you must adjust the position of the arrows to the area of the screen where the zone is recognized by the firmware. If multiple Privacy Zones are close together or overlap, the arrows blink, indicating that the selection is not allowed.
Navigate to zone
ZOOM to delete zone
FOCUS quits w/o changing
Zone 2
Zone 1
A
rrows blink to indicate this is
an invalid selection.
Zone 3
Fig. 36 Deleting Privacy Zones – Invalid Selection
Three Privacy Zones are illustrated. Zones 1 and 2 are overlapping. Zone 1 and 3 are in close proximity. In this situation, the arrows blink because the target area is the same distance from all three zones. To ensure that the correct Privacy Zone is deleted, place the arrows clearly in the zone you want to delete Fig. 37 illustrates a valid selection.
Navigate to zone
ZOOM to delete zone
FOCUS quits w/o changing
Zone 2
Zone 1
Zone 3
A
rrows stop blinking indicating
this is a valid selection.
Fig. 37 Deleting Privacy Zone – Valid Selection
By moving to the left, the arrows stop blinking when the target area enters Zone 1. Pressing Zoom allows you to delete Zone 1. If you do not want to delete the zone, press Focus.
118
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 51
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.6.4 Deleting Specific Privacy Zones
To delete individual Privacy Zones, use the following procedure.
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Privacy Zones. The Program Privacy Zones screen displays.
3. Select Delete Specific Zones.
4. Position the arrows in the Privacy Zone that you want to delete. Press Zoom to delete. If you do not want to delete the zone, press Focus.
5. Repeat steps 3 and 4 for each Privacy Zone you want to delete. When finished, select Exit.
6. When the Alarms/Areas/Home/Presets/PZ screen appears, select Exit. The Dome Configuration Menu appears.
10.6.5 Deleting All Privacy Zones
To delete all Privacy Zones, use the following procedure. To delete individual Privacy Zones:
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Privacy Zones. The Program Privacy Zones screen displays.
3. Select Delete All Zones. The following prompt appears on-screen:
You are about to delete
All Privacy Zones
Cancel
Continue
4. To delete all Privacy Zones, select Continue. If you do not want to delete all Privacy Zones, select Cancel. The Program Privacy Zones screen displays.
5. Select Exit to return to Alarms/Areas/Home/Presets/PZ screen. When the Alarms/Areas/Home/Presets/PZ screen appears, select Exit.
10.6.6 Hiding Privacy Zones
If you want to temporarily disable the appearance of Privacy Zones, you may “hide” them. This allows you to keep the Privacy Zones that have been programmed while disabling their appearance on-screen. To hide all Privacy Zones:
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Privacy Zones. The Program Privacy Zones screen displays.
3. Select Hide All Zones. Change the setting.
Select Yes to hide all Privacy Zones. Select No to make all Privacy Zones active.
The default setting is No.
4. Select Exit to return to Alarms/Areas/Home/Presets/PZ screen.
5. When the Alarms/Areas/Home/Presets/PZ screen appears, select Exit.
119
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 52
Configuring Alarms, Areas, Home, Privacy Settings and Presets
10.7 Programming Presets
If you need to view specific places routinely, you should program presets. A preset is a programmed video scene with automatic pan, tilt, zoom, focus and iris settings. Once programmed, entering the number and pressing a button on your controller automatically calls up the preset. In addition, presets may be assigned to alarm actions or as the “home” position for the dome. As many as 60 presets, whose positions are saved in the dome’s firmware, may be programmed. Positions from 65 up to 96 are not supported yet.
10.7.1 Setting Presets
1. Select Alarms/Areas/Home/Presets/PZ from the Dome Configuration Menu.
2. Select Presets. The Select Preset to Program screen appears:
SELECT PRESET TO PROGRAM
PRESET NUMBER PRESET NAME
1-96 PRESET 1-96
FOCUS FAR to program preset
EXIT
Fig. 38 Setting Presets
3. Select the number for the preset that you want to program. The Presets screen appears.
PRESETS
PRESET X
Position camera with PAN
TILT, ZOOM and IRIS
FOCUS FAR to save and exit
EXIT
Fig. 39 Presets screen
4. Adjust the camera until you see the scene you want to use as the preset. Adjust the zoom and iris settings as necessary. When satisfied with the scene, save the preset.
5. Repeat steps 3 and 4 for each preset you want to program. When finished, select Exit.
6. When the Alarms/Areas/Home/Presets/PZ screen appears, select Exit.
120
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 53
Configuring Text Displayed On-Screen
11 Configuring Text Displayed On-Screen
This chapter describes how to modify settings related to text displayed by the dome. It includes settings for displaying dome status information, names, diagnostics, and pointing direction. It also provides instructions for programming names and configuring text display options.
11.1 Overview of On-Screen Text Display Settings
When On-Screen Text Display is selected from the Dome Configuration Menu, the following screen appears:
ON-SCREEN TEXT DISPLAY
STATUS DISP L AY ON/OFF DISABLE ALL NAMES? YES/NO DIAGNOSTIC DISPLAY ON/OFF DIRECTION INDICATOR ON/OFF
NAME CONFIGURATION MENU
TEXT ATTRIBUTE OPTIONS
EXIT
Fig. 40 OSD setup
Use this screen to display dome status information, enable or disable the display of all name information, display diagnostic information after a dome reset, and display direction information about where the dome is pointing. You may also start the Name Configuration Menu and the Text Attribute Options screens.
To change the settings, move the highlight bar to appropriate field and make the
changes.
To return to the Dome Configuration Menu, select Exit.
121
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 54
Configuring Text Displayed On-Screen
11.2 Displaying or Hiding Status Information
You can choose to display the status of the zoom setting, auto focus, and auto iris. This information will appear in the upper left corner of the monitor. The information only appears when there is a change in the status of any item and remains on the screen for 5 seconds. If “D” appears next to the zoom factor, the digital zoom is active (zooms greater than 23 x).
ZOOM X 92 D
A
UTO IRIS OFF
A
UTO FOCUS ON
Fig. 41 Zoom, Auto Iris and Auto Focus Status Information
NOTE:
Status information and name information are always displayed separately. If
Disable All Names? is set
to
YES, the status information will remain visible only if Status Display is ON.
11.2.1 Changing the Display of Status Information
1. Select On-Screen Text Display from the Dome Configuration Menu. The highlight bar appears on Status Display.
2. Change the setting.
Select On to display dome status information on the monitor. Select Off to prevent dome status information from appearing on the
monitor.
The default setting is Off.
3. Select Exit. The Dome Configuration Menu appears.
122
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 55
Configuring Text Displayed On-Screen
11.3 Displaying or Hiding All Name Information
The dome provides the ability to display the dome name, the area where the dome is pointing, the name of the preset or pattern that is running, and alarm names. When the display of camera or area names is enabled, the information appears on the screen continuously. Preset, pattern, and alarm names appear only while they are active.
CAMERA NAME PRESET NAME/PATTERN NAME
ALARM NAME
AREA NAME
Fig. 42 Display Locations for Name Information
You may choose to disable displaying all name information, or you may choose to display selected or all name information.
11.3.1 Changing the Display of All Name Information
1. Select On-Screen Text Display from the Dome Configuration Menu.
2. Move the highlight to Disable All Names?
3. Change the setting.
Select Yes to disable the appearance of all name information. Select No to enable the appearance of all or some name information. Then
continue
The default setting is No.
4. Select Exit. The Dome Configuration Menu appears.
123
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 56
Configuring Text Displayed On-Screen
11.4 Displaying Diagnostic Tests During Reset
You can choose to have dome diagnostic tests run whenever the dome resets. The diagnostic information displayed includes:
Communications Loopback Test Camera Loopback Test Motor Circuit Test.
If you do not want diagnostic information to appear when the dome resets, a screen displaying the firmware version numbers for the Boot and Application code and the maximum optical zoom for the dome appears.
IMPORTANT
If the diagnostic test function is activated, there may be a temporary loss of communication in the network while the dome diagnostic tests are running.
11.4.1 Changing the Display of Diagnostic Information
1. Select On-Screen Text Display from the Dome Configuration Menu.
2. Move the highlight to Diagnostic Display.
3. Change the setting.
If you want diagnostic tests to run when the dome resets, select On. If you do not want diagnostic tests to run when the dome resets, select Off.
This choice displays the firmware versions whenever the dome resets.
The default setting is Off.
4. Select Exit. The Dome Configuration Menu appears.
124
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 57
Configuring Text Displayed On-Screen
11.5 Displaying Direction Indicators
Direction Indicators let you know the approximate pointing direction of the dome in relation to an established point called “North”. When enabled, the Direction Indicators appear along the top edge of the display. In addition, a tilt elevation indicator also appears along the left edge of the display. The value of the tilt elevation indicator is relative to the “virtual horizon” of 0° tilt. By default, the display of Direction Indicators is disabled.
NE E60
12
125
Fig. 43 Screen locations for Direction Indicators
In this example, the current pointing position is 60° from North. The tilt elevation is 12° above the virtual horizon. Panning to the left points the dome towards the Northeast. Panning to the right points the dome towards the East. If you tilt below the virtual horizon, the negative values will be displayed along the left edge (for example, -25). The elevation values range from +25° to -90°.
If you pan to a position that corresponds to a well-known navigational heading, the label corresponding to the heading appears in the center position. Fig. 44 illustrates the navigational headings and their corresponding degrees from North.
N
45°
135°
180°
90°
270°
315°
225°
NE
E
SE
S
SW
NW
W
Tilt elevation/declination
from Horizontal
Dome
Pointing direction around the Pan axis (0 to 359°)
Fig. 44 Navigational headings and corresponding degrees from North
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 58
Configuring Text Displayed On-Screen
In this illustration, the black circle in the center represents the dome, the dotted circle represents the pan axis, and the arrowheads represent panning the dome to the right.
Figure 45 represents pointing the dome precisely at 225° from North (Southwest) with a tilt of 25° below the virtual horizon. Panning to the left points the dome towards the South. Panning to the right points the dome towards the West.
S
W
SW
-25
Figure 45 Pointing the dome precisely Southwest with a tilt elevation of -25°
11.5.1 Changing the Display of Direction Indicators
1. Select On-Screen Text Display from the Dome Configuration Menu.
2. Move the highlight to Direction Indicator.
3. Change the setting.
Select On to display the direction information. Select Off to prevent the direction information from displaying.
The default setting is Off.
4. Select Exit. The Dome Configuration Menu appears.
126
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 59
Configuring Text Displayed On-Screen
11.6 Configuring Name Information
Use the Name Configuration Menu to select which name information appears on­screen. To display this screen, select Name Configuration Menu from the On­Screen Text Display screen. The following screen appears:
NAME CONFIGURATION MENU
CAMERA NAM E ON/OFF AREA NAME ON/OFF PRESET NAM E ON/OFF PATTERN NAME ON/OFF ALARM NAME OFF/ON
FOCUS FAR to pr ogram names
RESET PROGRAMMABLE NAMES
EXIT
Fig. 46 Name Configuration menu
You can choose to enable or disable the display of camera, area, preset, pattern, and alarm names from this screen. You can reset all programmable names to their default settings.
Changing the Display of Selected Name Information
1. Select On-Screen Text Display from the Dome Configuration Menu. The On­Screen Text Display appears.
2. Move the highlight to Name Configuration Menu and select. The Name Configuration Menu appears.
3. Move the highlight bar to the item whose display setting you want to change.
4. Change the setting.
Choose On to display name information on the monitor. Choose Off to prevent name information from appearing on the monitor.
The default settings are Off for Camera, Areas, Presets, and Patterns, and On for Alarms.
5. Repeat steps 3 and 4 for each item you want to change.
6. Do one of the following:
To reset all programmable names to their default values, select Reset
Programmable Names. Continue with step 7.
If you do not want to reset the programmable names, continue with step 8.
7. The following prompt appears on the screen:
RESET PROGRAMMABLE NAMES NO
To reset all names to the default value, select Yes. The Name
Configuration Menu displays. “Programmable Names Have Been Reset” appears at the bottom of the screen.
To cancel resetting of names, select No. The Name Configuration Menu
displays.
The default selection is No.
8. Do one of the following:
To change programmable name information. continue with Assigning or
Changing Name Information.
To return to the On-Screen Text Display settings screen select Exit.
Continue with step 9.
9. Select Exit. The Dome Configuration Menu appears.
127
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 60
Configuring Text Displayed On-Screen
11.7 Assigning or Changing Name Information
With the Name Configuration Menu displayed, you can select a menu item to begin name programming. Names for each selection can be up to 19 characters long. The following characters are available:
A-Z (upper case) a-z (lower case) 0-9 Blank Space Minus Sign (-) Forward Slash (/)
11.7.1 Setting or Changing Names
1. Select On-Screen Text Display from the Dome Configuration Menu.
2. Select Name Configuration Menu. The Name Configuration Menu appears.
3. Select the name setting you want to change. The choices are Camera Name, Area Name, Preset Name, Pattern Name, and Alarm Name.
If you choose Camera Name, continue with step 6. If you choose Area Name, Preset Name, Pattern Name, or Alarm Name,
continue with step 4.
4. The Select Name to Program screen appears.
NAMEN AUSWÄHLEN
ZIEL N U M M ERA KTUELLER N A M E
1-96ZIEL 1-96
BEEND EN
FO KUS W EIT ZUR N A M EN PRO G R.
/ BEREIC H / A REA L/ A LA RM
1-3BEREICH 1-3 1-16AREAL 1-16 1-4ALARM 1-4
Fig. 47 Select Name screen
NOTE: The grey text refers to other options which may be displayed on the screen.
5. Press Zoom to change the number. When the item whose name you want to change appears press Focus Far.
NOTE:
If Presets, Patterns, or Areas have been programmed, the dome automatically points to the starting position of the associated selection each time the number is advanced.
128
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 61
Configuring Text Displayed On-Screen
6. The Name Programming screen appears.
NAME PROGRAMMING
CAMERA
NAME: CAMERA.............
ABCDEFGHIJKLMNOPQRST UVWXYZabcdefghijklmn opqrstuvwxyz 0123456 789/-
UNDO CHANGES AND QUIT
EXIT
/PRESET/PATTERN/AREA/ALARM
Blank Space character
Fig. 48 Example Name Programming Screen
7. Move the blinking highlight around the available characters. When the correct character is highlighted, press Focus to select it. If you make a mistake, Zoom In moves the cursor one space right, and Zoom Out moves the cursor one space left in the name.
8. Repeat step 7 until the name is complete.
9. Do one of the following:
To save the name changes, select Exit. To discard the name changes, select Undo Changes and Quit.
10. Do one of the following:
If you were changing the camera name, continue with step 12. If you were changing the name of an area, preset, pattern or alarm, the
Select Name to Program screen appears. Continue with step 11.
11. Do one of the following:
To make additional changes to the same type of name selected in step 3,
repeat steps 4 through 10.
To return to the Name Configuration Menu, select Exit, and continue with
step 12.
12. Do one of the following:
To make additional name changes, repeat steps 3 through 11. To return to On-Screen Text Display, select Exit. Continue with step 13.
13. Select Exit. The Dome Configuration Menu appears.
129
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 62
Configuring Text Displayed On-Screen
11.8 Changing the Settings for Text Displayed On-Screen
You may customize the way text is displayed on-screen. You have the choice of displaying text as translucent (slightly clear) or solid, with or without outlines. To change these settings, select Text Attribute Options from the On-Screen Text Display screen. The following screen appears:
TEXT ATTRIBU TE OPTIONS
CHARACTER OUTLI NE ON/OFF TRANSLUCENT NAMES ON/OFF
EXIT
Fig. 49 Menu screen
Fig. 50 Examples of text attributes
If the video background is light, enable character outlines. If on-screen text obscures the video being displayed, enable translucent names. Character outlines and translucent names may be used together to best suit your video environment.
IMPORTANT:
When Privacy Zones are active, the text is automatically displayed as solid. If you change the setting to display the text as translucent, the change remains ineffective until the Privacy Zones are either hidden or deleted.
130
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 63
Configuring Text Displayed On-Screen
11.8.1 Changing On-Screen Text Appearance
1. Select On-Screen Text Display from the Dome Configuration Menu.
2. Move the highlight to Text Attribute Options and select. The Text Attribute Options screen appears. The highlight bar appears on Character Outline.
3. Change the setting.
Select On to display text with an outline around each character. Select Off to display without an outline around each character.
The default setting is On.
4. Do one of the following:
If you want to change the appearance of the text overlay characters for
dome names and status information, move the highlight bar to Translucent Names. Continue with step 5.
If you are finished making changes, continue with step 6.
5. Change the Translucent Names setting.
Select On to display text associated with dome names and status
information as translucent (slightly clear).
Select Off to display text associated with dome names and status
information as solid.
The default setting is On.
6. Select Exit to return to the On-Screen Text Display screen.
7. Select Exit. The Dome Configuration Menu appears.
131
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 64
Configuring Language and Password Settings
12 Configuring Language and Password Settings
This chapter explains how to change the language for dome messages and text, and how to set and enable the dome password.
12.1 Overview
When Language / Password is selected from the Dome Configuration Menu, the following screen appears:
LANGUAGE / PASSWORD
LANGUAGE SELECTION
SET PASSWORD
PASSWORD PROTECTION OFF
EXIT
/ON
Fig. 51 Language / password
From this screen, you can choose the language for the menus, status information, and prompts from the dome. You can also set and enable the use of the dome password.
To make changes, select a menu item to display the associated settings. To change the settings, move the highlight bar to appropriate field and make the
changes.
To return to the Dome Configuration Menu, select Exit.
12.2 Selecting a Language
The dome supports menus, status information and prompts in English, Spanish, French, German, Italian, and Portuguese. When the dome is initially installed, the language setting is English.
IMPORTANT
If Portuguese is selected, the characters “ã” and “õ” cannot be displayed on the screen owing to a limited functionality of the text overlay chip.
132
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 65
Configuring Language and Password Settings
12.2.1 Changing the Language Setting
1. Select Language/Password from the Dome Configuration Menu.
2. Select Language Selection. The Language Selection screen appears:
LANGUAGE SELECTION
ENGLISH SPANISH
FRENCH GERMAN
ITALIAN
PORTUGUESE
EXIT
Fig. 52 Language selection
3. Move the highlight bar to the preferred language setting.
The default setting is English.
4. Select the highlighted language. The following screen appears:
DOME MUST RESET TO CHANGE LANGUAGE
SELECT CONTINUE TO RESET
CONTINUE
CANCEL
Fig. 53 Language selection
The highlight bar appears on Cancel.
NOTE:
Changing of the language setting will not affect names that were configured previously. Only standard names, like for instance Preset 1, will be changed accordingly.
5. Do one of the following:
To continue with changing the language, select Continue. The dome
automatically resets. To verify the language change, continue with step 5. Otherwise continue with step 6.
To cancel the language change, select Cancel. The Language Selection
screen appears. You may choose a different language, or select Exit to return to the Language / Password screen. Continue with step 6.
6. Start the Dome Configuration Menu. The menu will appear in the new language setting.
133
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 66
Configuring Language and Password Settings
12.3 Setting and Enabling the Dome Password
To prevent unauthorized use of the configuration utility, you may choose to enable password protection. There are two parts to using passwords with your dome: setting a password and enabling password use. The dome password can be from 1 to 8 characters long. The characters available depend on the current language setting.
12.3.1 Setting or Changing the Dome Password
1. Select Language/Password from the Dome Configuration Menu.
2. Select Set Password. The Set Password screen appears.
SET PASSWORD
PASSWORD: ** *** ***
ABCDEFGHIJKLMNOPQRST UVWXYZabcdefghijklmn opqrstuvwxyz 0123456 789/-
CONTINUE
CANCEL
Blank Space character
Fig. 54 Password
3. Move the blinking highlight around the available characters. When the correct character is highlighted, press Focus.
4. If you make a mistake, press Zoom In to move the cursor one space right or Zoom Out to move the cursor one space left.
5. Repeat step 3 until the password is complete. When finished, select Continue.
6. You must successfully enter the password twice. Use the procedure in step 3 to enter the password again. When finished, select Continue.
NOTE:
If the two passwords are not identical, the procedure must be repeated. Return to step 3 and start again.
7. The Language/Password screen appears. Select Exit. The Dome Configuration Menu appears.
12.3.2 Enabling or Disabling Password Protection
Password protection must be enabled before passwords can be used. To enable or disable the dome password:
1. Select Language/Password from the Dome Configuration Menu.
2. Move the highlight bar to Password Protection.
3. Change the setting.
Select On to enable password protection. Select Off to disable password protection.
The default setting is Off.
4. Select Exit. The Dome Configuration Menu appears.
134
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 67
Displaying Dome Information
13 Displaying Dome Information
This chapter explains how to display dome information and operating information.
13.1 Understanding the Dome Information Screen
The Dome Information screen provides essential information about the SpeedDome Ultra VI camera dome if service is required. When you view this screen, you can determine the dome type, mnemonic, software version, serial number, and manufacture date.
DOME INFO RMATION
N A M E: SIEM EN S C C D A 1 4 1 5 -D N Mnemonic: D/N So ftwa re Ver:0701-4008-0100 Devic e Typ e :24770105 SN:01234567890123456789 Manufa c ture Da te :06082001 Dome Sta tistics
EXI T
Fig. 55 Dome information
The information that appears on the Dome Information screen cannot be changed or altered. This feature is provided for information purposes only.
NOTE: The manufacture date is displayed in the format month-day-year (MMDDYYYY).
Select Dome Statistics to display additional information. Select Exit to return to the Dome Configuration Menu.
135
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Page 68
Displaying Dome Information
13.2 Viewing Dome Operating Statistics
When Dome Statistics is selected from the Dome Information screen, the following information is displayed:
DOME STATISTICS
PanStat TiltStat ZoomStat R 000000C9 00000085 00000011 L 0000006A 00000074 00000012 M 000001B5 00000089 00000048 T 00000013 00000017 0000000E
Pwr/Run Pwr/Run
O 00007615 W 00000000 P 00000000 U 00000000
EXIT
Fig. 56 Dome statistics
From this screen, you can identify the operating statistics for various features of the dome. The information represents either runtime in seconds or number of occurrences (displayed in hexadecimal values). The following table describes the abbreviations used.
Abbreviation Description
R Time moving right in seconds. L Time moving left in seconds. M Total move time in seconds. T Total target count. O Operating time in seconds. P Power failure reset count.
W Watchdog reset count. The watchdog tracks software problems that cause
the dome to hang. This number should be zero.
U User reset count. This represents the resets initiated by the dome operators.
Tab. 6 Abbreviations
When you are finished viewing the dome statistics, select Exit to return to the Dome Information screen.
136
Siemens Building Technologies
BE_CCDA1415-DN.doc
Fire & Security Products 05.2004
Loading...