Siemens CC-5 Installation Instructions Manual

Installation Instructions Model CC-5
System Cardcage for NCCNT WAN
INTRODUCTION The Model CC-5 Cardcage from Siemens Industry, Inc. (see Figure 1) has five card
slots and occupies two positions on the studs in the backbox or on the optional CAB-MP Mounting Plate. The CC-5 is used for mounting all system circuit card assemblies. It has two removable terminal block connectors at the top and one removable terminal block connector at the bottom of each card slot. All field-wiring connections are made directly to the top of the cardcage while internal power is connected to the bottom of the cardcage. The two removable terminal block connec­tors at the top of each slot are arranged in two rows. The lower row is labeled 1 through 8 and the upper row is labeled 9 through 16. These removable terminal block connectors are used for connecting power limited external equipment. The removable terminal block connector located at the bottom of each slot is labeled 17 through 24 and is used for connecting internal power.
Figure 1 CC-5 Card Cage
OPERATION The CC-5 provides a central point for mounting circuit card assemblies. If a card
requires power, it is applied through the removable terminal block at the bottom of the cardcage. All external devices for the card are connected to the card through the two removable terminal blocks at the top of the cardcage. The circuit card assemblies are connected to the HNET bus through the connectors on the cardcage.
PRE-INSTALLATION The CC-5 is shipped with the card guides removed. The card guides are keyed to
assist in installation. They can be installed either before or after the cardcage is installed in the enclosure. For ease of installation, the card guides have been de­signed to be installed after the field wiring has been completed.
P/N 315-099319-4
Note: Board shown without card guides installed.
Siemens Industry, Inc.
Building Technologies Division
Card Guide Installation (Figure 2)
The upper and lower card guides are keyed differently and are not interchangeable.
Ensure that the card guide keys fit easily into the holes in the motherboard to prevent damage.
1. The upper card guide has a label on each slot that can be used to identify
2. Insert the upper card guide and secure with the captive screws.
3. Insert the lower card guide and secure with the captive screws.
UPPER CARD GUIDE
LABELS
GUIDE PIN
the module installed in the slot. If desired, complete the label before inserting the upper card guide.
LOWER CARD GUIDE
CAPTIVE SCREWS
INSTALLATION
GUIDE PIN HOLE
CAPTIVE SCREW RETAINERS
Figure 2 Card Guide Installation
Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.)
The CC-5 mounts at the back of the enclosure on the studs in the backbox or on the optional Mounting Plate (CAB-MP). The Mounting Plate may be located either “IN” or “OUT” of the enclosure to perform this installation procedure. If the Mounting Plate is located “IN” the enclosure you will have to gain access to it by opening the enclosure Inner and Outer doors. If the Mounting Plate is located outside of the enclosure, place it in front of you so that the word “TOP” is at the top and away from you.
Siemens Industry, Inc. Building Technologies Division
P/N 315-099319-42
Each row of studs in the backbox or each Mounting Plate can hold a maximum of
TOP
two CC-5 cardcages. There are three possible locations for mounting the CC-5.
1. Flush left in the backbox or on the Mounting Plate in positions 1-2.
2. In the center of the row in the backbox or on the Mounting Plate in posi­tions 2-3.
3. Flush right in the backbox or on the Mounting Plate in positions 3-4.
When only one cardcage is to be installed, it is normally installed on the left side of a row or on the Mounting Plate.
There is a top and bottom to the Mounting Plate. The top is where the word “TOP” is stamped on the Mounting Plate. When the cardcage is mounted correctly on the Mounting Plate it will be flush on the top, bottom, and left with the Mounting Plate and the two screw holes in the center of the cardcage motherboard will be over threaded posts.
1. Install four 10-32 screws in the threaded posts at the top left of Position 1, top right of Position 2, bottom left of Position 1, and the bottom right of Position 2 on the Mounting Plate. Screw each of the 10-32 screws into the threaded posts 5-6 turns. (Refer to Figure 3.)
2. Place the cardcage over the four screws on the Mounting Plate and slide it down or towards you to rest on the four screws. (Refer to Figure 4.) When the cardcage is in the correct position it will be flush with the top, bottom, and left side of the Mounting Plate.
3. Install the two 10-32 screws in the center of the cardcage motherboard near the left and right edge.
4. Tighten the six screws.
POSITION 1 POSITION 3 POSITION 4
CC-5 TOP THREADED POSTS
CC-5 BOTTOM THREADED POSTS
POSITION 1 POSITION 3 POSITION 4
POSITION 2
CAB-MP
POSITION 2
Figure 3 Location Of The CC-5 On The Optional CAB-MP