AP 257/41 Wind sensor 5WG1 257-3AB41
Product and Applications Description
The AP 257/41 wind sensor contains the sensor and the electronic systems for wind data analysis and bus inter­facing in one compact enclosure. The wind speed can be sent to the bus in the EIS5 format and monitored respectively for up to 3 limit values. Limit values can be selected as parameters or as communica­tion objects. Additionally the maximum wind speed can be recorded, stored, requested and reset. In addition, 8 AND-gates and 8 OR-gates are available with 4 inputs each for logical combinations. If the wind speed is measured at different locations / facades the logic gates may be used e.g. for the logical combination of the wind alarms from several wind sensors to an over­all alarm. The voltage supply of the electronics takes place via AC 20 V or DC 24 V safety extra-low voltage (SELV). For the transmission of this voltage, the white / yellow twisted pair of the bus cable can be used.
Application Program
The AP 257/41 wind sensor has to be used together with the application program “0701 CO wind sensor 910101” which can be configured and loaded with the Engineer­ing Tool Software (ETS) from version ETS2 V1.3. But it is recommended to use the engineering tool software ETS3, since it presents a graphically optimal display of the setting menus of the wind sensor.
Installation Instructions
If the wind sensor should be damaged, it must not be commissioned.
V
WARNING
Technical Specifications
Sensors
Wind sensor
- Measuring range: 0 ... 70 m/s
- Resolution: < 10% of the measuring range
Voltage supply
Bus voltage: via the bus line
Bus current: 9 mA
Sensor electronics: AC 20 V +
10% max. 110 mA, residual ripple < 10%, max. per-
+ missible cable length 100 m
Power consumption: at AC 20 V: max. 2.2 VA; at DC 24 V: max. 2.64W
Connections
Voltage supply: plug terminals for solid conductors or
finely stranded conductors 0.5 ... 1.5mm²
Bus connection: screw-less bus terminal, single-core
0.6...0.8 mm single-core, insulation strip length 5 mm.
Mechanical data
Housing: plastic
Dimensions: approx. 118mm x 96mm x 77mm (LxWxH)
Weight: approx. 145 g
Mounting: Mast or wall mounting
Electric safety
Protection type (according to EN 60529): IP44
Bus: safety extra low voltage (SELV) DC 24 V
Device complies with EN 50090-2-2
EMC requirements
complies with EN 50090-2-2
Environmental conditions
Ambient temperature during operation: - 30 ... + 50 °C
Storage temperature: - 20 ... + 70 °C
rel. humidity (not condensing): 5 ... 93 %
Markings
KNX EIB
CE mark
complies with the EMC regulations (residential and func­tional buildings), and low voltage regulations
:
10% 50/60 Hz or DC 24 V
The device must be mounted and commissioned by an authorised electrician.
For planning and construction of electric installations, the relevant guidelines, regulations and standards of the respective country are to be considered.
Siemens AG AP 257/41, 4 pages Technical Manual Industry Sector, Building Technologies Electrical Installation Technology © Siemens AG 2008 Update: http://www.siemens.com/gamma P.O.Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
2.13.5.1/1
Page 2
GAMMA instabus
Technical Product Information
March 2008
AP 257/41 Wind sensor 5WG1 257-3AB41
Location and Function of the Display and Operat­ing Elements
Figure 1
1 Slot for cable connection to the lid of the enclosure 2 Plug terminal for voltage supply AC 20 V / DC 24 V 3 Opening for voltage supply cable 4 Opening for bus cable 5 Slot for bus terminal 6 Commissioning button: for switching over between
normal mode / addressing mode
7 Commissioning LED: for display of normal mode /
addressing mode (off / on)
Mounting and wiring
Location
Select a position on the building where wind can be recorded by the sensor without impairment. There must be at least 60 cm free space under the wind sensor to allow for correct wind measurements and to prevent the sensor being snowed in case of snow. The wind sensor must be mounted on a mast or a vertical wall (see fig. 2) and be aligned horizontally across (see fig. 3).
Figure 3
Mounting
The supplied combined wall / mast holder is fixed at the rear of the enclosure on delivery. To remove it, please use a screwdriver and remove the holder on the right and the left, as shown in figs. 4 and
5. Slide the holder out towards the bottom.
Figure 4
Figure 5
Mounting on a wall: Fasten the holder vertically with the even side to the wall, with the crescent-shaped bar to the top (see fig. 6).
Figure 2
Figure 6
Technical Manual AP 257/41, 4 pages Siemens AG Industry Sector, Building Technologies Update: http://www.siemens.com/gamma © Siemens AG 2008 Electrical Installation Technology Subject to change without prior notice P.O.Box 10 09 53, D-93009 Regensburg
2.13.5.1/2
Page 3
GAMMA instabus
Technical Product Information
March 2008
AP 257/41 Wind sensor 5WG1 257-3AB41
Mounting on a mast / pole: Fasten the holder vertically with the curved side to the mast / pole and the bar to the bottom (see fig. 7).
Figure 7
View of the rear wall and drilling scheme: Dimensioning of the rear of the enclosure with holder: see fig. 8, Drilling scheme: see fig. 9.
Figure 8
Be careful not to tear open the cable connection be­tween the circuit board in the bottom part and the circuit board in the lid (cable with plug). Guide the bus connection through the rubber seals at the bottom part of the wind sensor and connect the wire pairs for the voltage supply and the bus to the provided terminals while taking polarity into account (see fig. 2).
Fastening the wind sensor: Close the enclosure by putting the lid over the lower part. The lid must snap into place on the left and the right with a clear “click”. Check that the lid and lower part are properly snapped into place! Fig. 11 shows the cor­rectly closed wind sensor from below.
Figure 11
Now slide the enclosure into the mounted holder from above. The pegs of the holder must slot into the rails of the enclosure (see fig. 12).
Figure 12
Figure 9
Preparing the wind sensor: The lid of the wind sensor is slotted in on the right and the left at the lower edge. Remove the lid from the wind sensor (see fig. 10).
If needed, the wind sensor can be pulled out of the holder in an upwards direction.
Caution: Do not open the wind sensor if water (rain) can get into the inside. A few drops are enough to damage the elec­tronics. Take care that the connections are correctly made. A wrong connection can destroy the electronics of the wind sensor. During assembly care should be taken that the tempera­ture sensor (small circuit board on the lower part of the enclosure) is not damaged. The cable connection be­tween the circuit board in the bottom part and the circuit board in the lid may not be torn off or bent while making
Figure 10
Siemens AG AP 257/41, 4 pages Technical Manual Industry Sector, Building Technologies Electrical Installation Technology © Siemens AG 2008 Update: http://www.siemens.com/gamma P.O.Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
the connection. The wind measurement value is first transmitted 60 seconds after initiating the supply voltage.
2.13.5.1/3
Page 4
GAMMA instabus
Technical Product Information
March 2008
AP 257/41 Wind sensor 5WG1 257-3AB41
Maintenance The wind sensor should be regularly checked (twice per year) for soiling and cleaned if necessary. In case of strong pollution, the wind sensor may cease to function.
During maintenance and cleaning, the wind sensor should always be separated from the bus and the supply voltage for safety purposes.
General Notes
Any faulty devices should be returned to the local Siemens office.
If you have further questions concerning the product please contact our technical support:
+49 (0) 180 50 50-222 " +49 (0) 180 50 50-223
! www.siemens.com/automation/support-request
Space for notes
Technical Manual AP 257/41, 4 pages Siemens AG Industry Sector, Building Technologies Update: http://www.siemens.com/gamma © Siemens AG 2008 Electrical Installation Technology Subject to change without prior notice P.O.Box 10 09 53, D-93009 Regensburg
2.13.5.1/4
Loading...