Siemens AP 118 Technical Product Information

Page 1
GAMMA instabus
Technical Product-Information
August 2017
Control Module Box AP 118 5WG1 118-4AB01
Product- and Applications Description
The AP 118 Control Module Box with a height of 41 mm is designed for installation in a false ceiling, in a raised floor, directly on a wall or in an installation channel or raceway. The Control Module Box is affixed with screws at the two ends of the housing. The Control Module Box offers one mounting location for these modules: 5WG1 260-4AB23 Binary input, quadruple,
AC/DC 12...230V 5WG1 510-2AB23 Binary output (relay), 2 x 10A 5WG1 512-4AB23 Load switch (relay), 1 x 16A 5WG1 520-2AB23 Blind / shutter actuator, 1 x 6A 5WG1 521-4AB23 Blind / shutter actuator, 2 x 6A 5WG1 525-2AB23 Universal dimmer, 1 x 250VA
The mounted module is connected to the bus line via a bus terminal block. The AP 118 Control Module Box provides wiring space with room for two connectors for PE and N conductors. This allows for secure connection of the PE and N con­ductors of the cables inserted into the AP 118 Control Module Box. For strain relief, cables can be secured at the entrance to the wiring space. Line voltage supply and load conductors are terminated at the terminals of the mounted modules.
Application Programs
Example of Application
figure 1: Example of Application
Installation instructions
The Control Module Box may be used for permanent
interior installations, for mounting in dry rooms, in false ceilings, raised floors, and installation channels or raceways.
Υ
The Control Module Box must be mounted and com-
A safety disconnection of the Control Module Box must
For planning and construction of electric installations,
DANGER
missioned by an authorized electrician.
be possible.
the relevant guidelines, regulations and standards of the respective country are to be considered.
Requires no application programs
Siemens AG AP 118, page 1 / 6 Technical Manual Infrastructur e and Cities S ector, Building Technologies Control Products and Systems © Siemens AG 2017 Update: http ://www.siemens.com/gamma P. O. Box 10 09 53, D-93009 Regen sburg Subject to change without furth er notice.
Page 2
GAMMA instabus
Technical Product-Information
August 2017
Control Module Box AP 118 5WG1 118-4AB01
Technical Data
Physical Specifications
housing: plasticdimensions:
Length x Width x Height (in mm): 180 x 50 x 41,1
weight: approx. 100gfire load: approx. 3000 kJmounting: with two screwsone mounting location for RS / RL modules
Connections
Bus line: screwless bus connection block (red-black)
0.6…0.8 mm Ø single core, strip insulation 5mm
Mains power: 230 V AC ± 10 %, 50...60 Hz
terminals of RS / RL modules
Electrical Safety
Degree of pollution (according to IEC 60664-1): 2Type of protection (according to EN 60529): IP 20Overvoltage category (according to IEC 60664-1): IIIBus: safety extra low voltage SELV DC 24 V
Environmental specifications
Climatic withstand capability: EN 50090-2-2Ambient temperature operating: - 5 ... + 45 ↓CAmbient temperature non-op.: - 25 ... + 70 ↓Crelative humidity (non-condensing): 5 % bis 93 %
Mounting and Connecting
General description The Control Module Box is designed for on-surface mounting on ceilings, walls, on the floor or any even surface, as well as installation in installation channels or raceways. The holes for screw fastening of the Control Module Box are located on the ends of the box and are accessible after opening the housing. The Control Mod­ule Box is affixed with two screws.
Mounting
Mounting of the Control Module Box:
- Distance between drill holes for screw fastening: 166 mm (see figure 2-a)
- Pull the latching clamp (A4) away from the lid (A5), lift the lid up, swivel it up and remove it from the hinge (A6).
- Fix the Control Module Box at the fixation points (A2) (see figure 2-b) with screws (e.g. 4.5 x 50 mm, to be sourced separately).
CE norm
figure 2a: Mounting
complies with low voltage regulations
Technical Manual AP 118 , page 2 / 6 Siemens AG
Update: http ://www.siemens.com/gamma © Siemens AG 2017 Control Products and Systems
Subject to change without furth er notice. P. O. Box 10 09 53, D-93009 Regensburg
Infrastructur e and Cities S ector, Building Technologies
Page 3
GAMMA instabus
Technical Product-Information
August 2017
Control Module Box AP 118 5WG1 118-4AB01
A1 Product label A2 Hole for screw fastening of Control Module Box A3 Screws for securing the lid A4 Latching clamp for locking the lid A5 Control Module Box, Lid A6 Hinge for lid A7 Bushing for BUS cables (with strain relief) A8 Bushing for low voltage cables (with strain relief) A9 Control Module Box, base A10 Bus terminal A11 Mounting location for one RS / RL module A12 RS module (to be ordered separately) A13 RL module (to be ordered separately) A14 Clamp for strain relief (cut off from base)
A4
A2
A8
A11
A14
A7
A6
A9
A2
A14
figure 2b: Mounting
Removing the lid of the Control Module Box:
- Remove the screws (A3) securing the lid.
- Pull the latching clamp (A4) away from the lid (A5), lift the lid up, swivel it up and remove it from the hinge (A6).
Mounting the lid of the Control Module Box:
- Hook the lid (A5) into the hinge (A6).
- Push the lid (A5) down until it audibly snaps into the latching clamp (A4).
- Fasten the screws (A3) to secure the lid.
A10
figure 3: Removing/Mounting the lid of the Control
Module Box
Mounting / Dismounting of RS /RL modules:
A RS module (A13) or an RL module (A14) may be in­stalled at the mounting location (A12) of the Control Module Box. Mounting of the RS and RL modules is de­scribed generically in these mounting and operating instructions. Notes on wiring and commissioning of specific modules may be found in the respective documentation for that module.
A14
A7
A13
A10
A1
A12
A8
A9
A14
figure 4: mounting / dismounting of RS/RL modules
Siemens AG AP 118, page 3 / 6 Technical Manual Infrastructur e and Cities S ector, Building Technologies Control Products and Systems © Siemens AG 2017 Update: http ://www.siemens.com/gamma P. O. Box 10 09 53, D-93009 Regen sburg Subject to change without furth er notice.
Page 4
GAMMA instabus
Technical Product-Information
August 2017
Control Module Box AP 118 5WG1 118-4AB01
Mounting of RS / RL modules
B1 RS module B2 RL module B3 Type label (with space for physical address of the
module)
B4 Mounting location for RS / RL module in AP 118
Control Module Box or AP 641 Room Control Box
B5 Bus connection module with bus connection pins
for bus terminal block, LED for indicating normal operating mode (LED off) or addressing mode (LED on), Learning button and contacts to RS module
B6 Insertion point for bus connection module of the RS
module
B7 Snap-in point for bus connection module of the RS
module
B8 Learning button for switching between normal
operating mode and addressing mode and for re­ceiving the physical address
B9 LED for indicating normal operating mode (LED off)
or addressing mode (LED on); returns to normal op­erating mode automatically after receiving the phys­ical address
figure 5: mounting of a RS module
B10 Bus connection pins of the module for connection
of the bus terminal block in the respective mounting location
Dismounting an RS module:
B11 Insertion point for bus terminal B12 Bus connection block for single core conductors
with 0,6...0,8 mm Ø
B13 Hinge joint for mounting hinge of the RL module B14 Terminals
- AP 118: Remove the lid of the Control Module Box.
- Remove the wiring from the terminals (B14).
- Remove the bus terminal (B12).
- To remove the RS module (B1), insert a screw driver between the module and the mounting location siding and push it up to release it from the snap-in hooks. Do
Mounting of a RS module:
- AP 118: Remove the lid of the Control Module Box.
-Insert the bus connection module (B5) in such a way into the insertion point (B6) for the bus connection module that the bus connection pins (B10) point to the insertion point for the bus terminal (B11).
- Press the bus connection module (B5) down until it snaps into the locking position (B7).
this on both sides.
- Pull the RS module (B1) from the mounting location (B4).
- If an RL module (B2) shall be inserted into the mounting location, detach the bus connection module (B5) from the snap-in point (B7), swivel it up and pull it out of the insertion point (B6).
Mount the lid again.
-Insert the RS module (B1) from the top with the termi­nals (B14) pointing away from the bus terminal inser­tion point (B11). The type label (B3) is on top.
-Insert the bus terminal (B12) of the mounting location (B4) onto the bus connection pins (B10) of the bus con­nection module (B5).
-For assignment of the Physical Address press the learn­ing button (B8) for a maximum of 2 seconds. The ad­dressing mode is indicated when the LED is on (B9). It returns to normal operating mode (LED Off) automati­cally after receiving the physical address.
- Mount the lid again.
Technical Manual AP 118, page 4 / 6 Siemens AG
Update: http ://www.siemens.com/gamma © Siemens AG 2017 Control Products and Systems
Subject to change without furth er notice. P. O. Box 10 09 53, D-93009 Regensburg
Infrastructur e and Cities S ector, Building Technologies
Page 5
GAMMA instabus
C2
C2.2 C2.1
C2.3
Technical Product-Information
August 2017
Control Module Box AP 118 5WG1 118-4AB01
figure 6: dismounting an RS module
Mounting of an RL module:
- AP 118: Remove the lid of the Control Module Box.
- Insert the RL module (B2) into the hinge (B13) of the mounting location (B4). The terminals (B14) point away from the insertion point for the bus terminal (B11). The type label (B3) is on top.
- Swivel the RL module (B2) down until it audibly snaps into the mounting location (B4).
- Insert the bus terminal (B12) of the mounting location (B4) onto the bus connection pins (B10) of the RL mod­ule (B2).
Wiring
Slipping off/on bus connection blocks
figure 8: dismounting an RL module
- For assignment of the Physical Address press the learn­ing button (B8) for a maximum of 2 seconds. The ad­dressing mode is indicated when the LED is on (B9). It returns to normal operating mode (LED Off) automati­cally after receiving the physical address.
- Mount the lid again.
The bus connection block (C2) is situated on the back of the actuator (C1). It consists of two components (C2.1 and C2.2) with four terminal contacts each. Take care not to damage the two test sockets (C2.3) by accidentally connecting them to the bus cable or with the screw driver (e.g. when at­tempting to unplug the bus connection block).
figure 7: mounting of an RL module
Dismounting an RL module:
- AP 118: Remove the lid of the Control Module Box.
- Remove the wiring from the terminals (B14).
- Remove the bus terminal (B12).
- To remove the RL module (B2), insert a screw driver between the module and the mounting location on the bus terminal side and push it up to release it from the snap-in hooks.
- Swivel the RL module (B2) up, pull it down out of the hinge (B13) and remove it from the mounting location (B4).
- Mount the lid again.
Slipping off bus connection blocks
- Carefully put the screw driver to the wire insertion slit of the bus connection block’s grey component (C2.2) and
- pull the bus connection block (C2) from the module .
Note
Don’t try to remove the bus connection block from the bottom side. There is a risk of shorting-out the device!
Slipping on bus connection blocks
- Slip the bus connection block (C2) onto the guide slot of the module and
- press the bus connection block (C2) down to the stop.
figure 9: Slipping off/on bus connection blocks
Connecting bus cables
- The bus connection block (D1) can be used with single core conductors Ø 0.6…0.8 mm.
- Remove approx. 5 mm of insulation from the conduc­tor (D2) and plug it into the bus connection block (D1) (red = +, grey = -)
Siemens AG AP 118, page 5 / 6 Technical Manual Infrastructur e and Cities S ector, Building Technologies Control Products and Systems © Siemens AG 2017 Update: http ://www.siemens.com/gamma P. O. Box 10 09 53, D-93009 Regen sburg Subject to change without furth er notice.
Page 6
GAMMA instabus
F1
F2
Technical Product-Information
August 2017
Control Module Box AP 118 5WG1 118-4AB01
Disconnecting bus cables
- Unplug the bus connection block (D1) and remove the bus cable conductor (D2) while simultaneously wig­gling it.
25...35 mm
5 mm
D2
D2.4
D1
D2
D2.4
figure 10: Connecting / Disconnecting bus cables
Connecting/disconnecting mains and load circuit:
Connect wires
- The load circuits are connected via screwless plug-in
terminals (E1).
- Remove approx. 9…10 mm of insulation from the wire
(E 1.1) and plug it into the terminal (E1).
- The terminals are designed for connection of two wires
allowing to loop through the terminal block.
Dimension drawing
Dimension in mm
Note: The maximum permissible terminal load current is 16A.
Remove wires
- Press the terminal interlocking of the terminal (F1)
with a screw-driver and remove the wire (F2) from the terminal (F1).
E1
figure 11: Connecting/disconnecting mains and load
circuit
General Notes
The operating instructions must be handed over to the
client.
Any faulty device is to be sent together with a return
delivery note of the local Siemens office.
For any technical questions, please consult:
& +49 (911) 895-7222 6 +49 (911) 895-7223
) support.automation@siemens.com www.siemens.com/automation/support-request
Technical Manual AP 118, page 6 / 6 Siemens AG
Infrastructur e and Cities S ector, Building Technologies
Update: http ://www.siemens.com/gamma © Siemens AG 2017 Control Products and Systems
Subject to change without furth er notice. P. O. Box 10 09 53, D-93009 Regensburg