The AP 118 Control Module Box with a height of 41 mm
is designed for installation in a false ceiling, in a raised
floor, directly on a wall or in an installation channel or
raceway. The Control Module Box is affixed with screws
at the two ends of the housing.
The Control Module Box offers one mounting location for
these modules:
5WG1 260-4AB23Binary input, quadruple,
AC/DC 12...230V
5WG1 510-2AB23Binary output (relay), 2 x 10A
5WG1 512-4AB23Load switch (relay), 1 x 16A
5WG1 520-2AB23Blind / shutter actuator, 1 x 6A
5WG1 521-4AB23Blind / shutter actuator, 2 x 6A
5WG1 525-2AB23Universal dimmer, 1 x 250VA
The mounted module is connected to the bus line via a
bus terminal block.
The AP 118 Control Module Box provides wiring space
with room for two connectors for PE and N conductors.
This allows for secure connection of the PE and N conductors of the cables inserted into the AP 118 Control
Module Box.
For strain relief, cables can be secured at the entrance to
the wiring space.
Line voltage supply and load conductors are terminated
at the terminals of the mounted modules.
Application Programs
Example of Application
figure 1: Example of Application
Installation instructions
∂ The Control Module Box may be used for permanent
interior installations, for mounting in dry rooms, in
false ceilings, raised floors, and installation channels or
raceways.
Υ
∂ The Control Module Box must be mounted and com-
∂ A safety disconnection of the Control Module Box must
∂ For planning and construction of electric installations,
DANGER
missioned by an authorized electrician.
be possible.
the relevant guidelines, regulations and standards of
the respective country are to be considered.
∂ weight: approx. 100g
∂ fire load: approx. 3000 kJ
∂ mounting: with two screws
∂ one mounting location for RS / RL modules
Connections
∂ Bus line: screwless bus connection block (red-black)
0.6…0.8 mm Ø single core, strip insulation 5mm
∂ Mains power: 230 V AC ± 10 %, 50...60 Hz
terminals of RS / RL modules
Electrical Safety
∂ Degree of pollution (according to IEC 60664-1): 2
∂ Type of protection (according to EN 60529): IP 20
∂ Overvoltage category (according to IEC 60664-1): III
∂ Bus: safety extra low voltage SELV DC 24 V
Environmental specifications
∂ Climatic withstand capability: EN 50090-2-2
∂ Ambient temperature operating: - 5 ... + 45 ↓C
∂ Ambient temperature non-op.: - 25 ... + 70 ↓C
∂ relative humidity (non-condensing): 5 % bis 93 %
Mounting and Connecting
General description
The Control Module Box is designed for on-surface
mounting on ceilings, walls, on the floor or any even
surface, as well as installation in installation channels or
raceways. The holes for screw fastening of the Control
Module Box are located on the ends of the box and are
accessible after opening the housing. The Control Module Box is affixed with two screws.
Mounting
∂ Mounting of the Control Module Box:
- Distance between drill holes for screw fastening:
166 mm (see figure 2-a)
- Pull the latching clamp (A4) away from the lid (A5), lift
the lid up, swivel it up and remove it from the hinge
(A6).
- Fix the Control Module Box at the fixation points (A2)
(see figure 2-b) with screws (e.g. 4.5 x 50 mm, to be
sourced separately).
Subject to change without furth er notice.P. O. Box 10 09 53, D-93009 Regensburg
Infrastructur e and Cities S ector, Building Technologies
2.4.2.11/2
Page 3
GAMMA instabus
Technical Product-Information
August 2017
Control Module Box AP 1185WG1 118-4AB01
A1 Product label
A2 Hole for screw fastening of Control Module Box
A3 Screws for securing the lid
A4 Latching clamp for locking the lid
A5 Control Module Box, Lid
A6 Hinge for lid
A7 Bushing for BUS cables (with strain relief)
A8 Bushing for low voltage cables (with strain relief)
A9 Control Module Box, base
A10 Bus terminal
A11 Mounting location for one RS / RL module
A12 RS module (to be ordered separately)
A13 RL module (to be ordered separately)
A14 Clamp for strain relief (cut off from base)
A4
A2
A8
A11
A14
A7
A6
A9
A2
A14
figure 2b: Mounting
∂ Removing the lid of the Control Module Box:
- Remove the screws (A3) securing the lid.
- Pull the latching clamp (A4) away from the lid (A5), lift
the lid up, swivel it up and remove it from the hinge
(A6).
∂ Mounting the lid of the Control Module Box:
- Hook the lid (A5) into the hinge (A6).
- Push the lid (A5) down until it audibly snaps into the
latching clamp (A4).
- Fasten the screws (A3) to secure the lid.
A10
figure 3: Removing/Mounting the lid of the Control
Module Box
∂ Mounting / Dismounting of RS /RL modules:
A RS module (A13) or an RL module (A14) may be installed at the mounting location (A12) of the Control
Module Box. Mounting of the RS and RL modules is described generically in these mounting and operating
instructions.
Notes on wiring and commissioning of specific modules
may be found in the respective documentation for that
module.
B1 RS module
B2 RL module
B3 Type label (with space for physical address of the
module)
B4 Mounting location for RS / RL module in AP 118
Control Module Box or AP 641 Room Control Box
B5 Bus connection module with bus connection pins
for bus terminal block, LED for indicating normal
operating mode (LED off) or addressing mode (LED
on), Learning button and contacts to RS module
B6 Insertion point for bus connection module of the RS
module
B7 Snap-in point for bus connection module of the RS
module
B8 Learning button for switching between normal
operating mode and addressing mode and for receiving the physical address
B9 LED for indicating normal operating mode (LED off)
or addressing mode (LED on); returns to normal operating mode automatically after receiving the physical address
figure 5: mounting of a RS module
B10 Bus connection pins of the module for connection
of the bus terminal block in the respective mounting
location
∂ Dismounting an RS module:
B11 Insertion point for bus terminal
B12 Bus connection block for single core conductors
with 0,6...0,8 mm Ø
B13 Hinge joint for mounting hinge of the RL module
B14 Terminals
- AP 118: Remove the lid of the Control Module Box.
- Remove the wiring from the terminals (B14).
- Remove the bus terminal (B12).
- To remove the RS module (B1), insert a screw driver
between the module and the mounting location siding
and push it up to release it from the snap-in hooks. Do
∂ Mounting of a RS module:
- AP 118: Remove the lid of the Control Module Box.
-Insert the bus connection module (B5) in such a way
into the insertion point (B6) for the bus connection
module that the bus connection pins (B10) point to the
insertion point for the bus terminal (B11).
- Press the bus connection module (B5) down until it
snaps into the locking position (B7).
this on both sides.
- Pull the RS module (B1) from the mounting location
(B4).
- If an RL module (B2) shall be inserted into the mounting
location, detach the bus connection module (B5) from
the snap-in point (B7), swivel it up and pull it out of the
insertion point (B6).
Mount the lid again.
-Insert the RS module (B1) from the top with the terminals (B14) pointing away from the bus terminal insertion point (B11). The type label (B3) is on top.
-Insert the bus terminal (B12) of the mounting location
(B4) onto the bus connection pins (B10) of the bus connection module (B5).
-For assignment of the Physical Address press the learning button (B8) for a maximum of 2 seconds. The addressing mode is indicated when the LED is on (B9). It
returns to normal operating mode (LED Off) automatically after receiving the physical address.
Subject to change without furth er notice.P. O. Box 10 09 53, D-93009 Regensburg
Infrastructur e and Cities S ector, Building Technologies
2.4.2.11/4
Page 5
GAMMA instabus
C2
C2.2 C2.1
C2.3
Technical Product-Information
August 2017
Control Module Box AP 1185WG1 118-4AB01
figure 6: dismounting an RS module
∂ Mounting of an RL module:
- AP 118: Remove the lid of the Control Module Box.
- Insert the RL module (B2) into the hinge (B13) of the
mounting location (B4). The terminals (B14) point away
from the insertion point for the bus terminal (B11). The
type label (B3) is on top.
- Swivel the RL module (B2) down until it audibly snaps
into the mounting location (B4).
- Insert the bus terminal (B12) of the mounting location
(B4) onto the bus connection pins (B10) of the RL module (B2).
Wiring
Slipping off/on bus connection blocks
figure 8: dismounting an RL module
- For assignment of the Physical Address press the learning button (B8) for a maximum of 2 seconds. The addressing mode is indicated when the LED is on (B9). It
returns to normal operating mode (LED Off) automatically after receiving the physical address.
- Mount the lid again.
The bus connection block (C2) is situated on the back of
the actuator (C1).
It consists of two components (C2.1 and C2.2) with four
terminal contacts each. Take care not to damage the two
test sockets (C2.3) by accidentally connecting them to
the bus cable or with the screw driver (e.g. when attempting to unplug the bus connection block).
figure 7: mounting of an RL module
∂ Dismounting an RL module:
- AP 118: Remove the lid of the Control Module Box.
- Remove the wiring from the terminals (B14).
- Remove the bus terminal (B12).
- To remove the RL module (B2), insert a screw driver
between the module and the mounting location on the
bus terminal side and push it up to release it from the
snap-in hooks.
- Swivel the RL module (B2) up, pull it down out of the
hinge (B13) and remove it from the mounting location
(B4).
- Mount the lid again.
Slipping off bus connection blocks
- Carefully put the screw driver to the wire insertion slit
of the bus connection block’s grey component (C2.2)
and
- pull the bus connection block (C2) from the module .
Note
Don’t try to remove the bus connection block from the
bottom side. There is a risk of shorting-out the device!
Slipping on bus connection blocks
- Slip the bus connection block (C2) onto the guide slot
of the module and
- press the bus connection block (C2) down to the stop.
figure 9: Slipping off/on bus connection blocks
Connecting bus cables
- The bus connection block (D1) can be used with single
core conductors Ø 0.6…0.8 mm.
- Remove approx. 5 mm of insulation from the conductor (D2) and plug it into the bus connection block (D1)
(red = +, grey = -)