SINAMICS G130
Advanced Operator Panel 30
(AOP30)
Control via the operator
panel
Maintenance and servicing

Siemens AG
Division Process Industries and Drives
Postfach 48 48
90026 NÜRNBERG
GERMANY
03/2018 Subject to change
Copyright © Siemens AG 2004 - 2017.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
indicates that death or severe personal injury will result if proper precautions are not taken.
indicates that death or severe personal injury may result if proper precautions are not taken.
indicates that minor personal injury can result if proper precautions are not taken.
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
The product/system described in this documentation may be operated only by
for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
3
1 Safety information ................................................................................................................................... 5
1.1 General safety instructions ....................................................................................................... 5
1.2 Handling the AOP30 backup battery ........................................................................................ 9
1.3 Handling electrostatic sensitive devices (ESD) ...................................................................... 10
1.4 Industrial security .................................................................................................................... 11
2 General ................................................................................................................................................. 13
3 Mechanical installation .......................................................................................................................... 15
4 Connection ........................................................................................................................................... 19
5 Control via the operator panel ............................................................................................................... 23
5.1 Operator panel (AOP30) overview and menu structure ......................................................... 23
5.2 Menu: Operation screen ......................................................................................................... 25
5.3 Menu: Parameterization .......................................................................................................... 26
5.4 Menu: Fault/alarm memory ..................................................................................................... 27
5.5 Menu commissioning / service ................................................................................................ 28
5.5.1 Drive commissioning ............................................................................................................... 28
5.5.2 Device commissioning ............................................................................................................ 29
5.5.3 Drive diagnostics ..................................................................................................................... 29
5.5.4 AOP settings ........................................................................................................................... 31
5.5.5 AOP diagnostics ..................................................................................................................... 38
5.6 Sprachauswahl/Language selection ....................................................................................... 40
5.7 Operation via the operator panel (LOCAL mode) ................................................................... 40
5.7.1 LOCAL/REMOTE key ............................................................................................................. 41
5.7.2 ON key / OFF key ................................................................................................................... 41
5.7.3 Switching between clockwise and counter-clockwise rotation ............................................... 42
5.7.4 Jog .......................................................................................................................................... 42
5.7.5 Increase setpoint / decrease setpoint ..................................................................................... 42
5.7.6 AOP setpoint ........................................................................................................................... 43
5.7.7 Lock AOP LOCAL mode ......................................................................................................... 44
5.7.8 Acknowledge error from the AOP ........................................................................................... 44
5.7.9 CDS setting via AOP ............................................................................................................... 44
5.7.10 Operator input inhibit / parameterization inhibit ...................................................................... 45
5.8 Faults and alarms ................................................................................................................... 46
5.9 Saving the parameters permanently ....................................................................................... 48
5.10 Parameterization errors .......................................................................................................... 48

Table of contents
Advanced Operator Panel 30 (AOP30)
4 Operating Instructions, 11/2017, A5E00331451A
6 Maintenance and servicing .................................................................................................................... 49
6.1 Replacing the backup battery ................................................................................................ 49
6.2 Downloading new operator panel firmware from the PC ....................................................... 51
7 Technical specifications ........................................................................................................................ 53
Index .................................................................................................................................................... 55

Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
5
General safety instructions
Electric shock and danger to life due to other energy sources
Touching live components can result in death or serious injury.
• Only work on electrical equipment if you are appropriately qualified.
• Always observe the country-specific safety rules for all work.
Generally, the following steps apply when establishing safety:
1. Prepare for disconnection. Notify all those who will be affected by the procedure.
2. Isolate the drive system from the power supply and take measures to prevent it being
switched back on again.
3. Wait until the discharge time specified on the warning labels has elapsed.
4. Check that there is no voltage between any of the power connections, and between any
of the power connections and the protective conductor connection.
5. Check that every auxiliary circuit is de-energized.
6. Ensure that the motors cannot move.
7. Identify all other dangerous energy sources, e.g. compressed air, hydraulic systems or
water. Switch the energy sources to a safe state.
8. Check that the correct drive system is completely locked.
After you have completed the work, restore the operational readiness by following the
above steps in the reverse order.
Electric shock due to connection to an unsuitable power supply
When equipment is connected to an unsuitable power supply, exposed components may
carry a hazardous voltage that might result in serious injury or death.
• Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV
(Protective Extra Low Voltage) output voltages for all connections and terminals of the
electronics modules.

Safety information
1.1 General safety instructions
Advanced Operator Panel 30 (AOP30)
6 Operating Instructions, 11/2017, A5E00331451A
Electric shock due to equipment damage
Improper handling may cause damage to equipment. For damaged devices, hazardous
voltages can be present at the enclosure or at exposed components; if touched, this can
result in death or severe injury.
• Ensure compliance with the limit values specified in the technical data during transport,
storage and operation.
• Do not use any damaged devices.
Electric shock due to unconnected cable shield
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
• Connect cable shields and unused conductors of power cables (e.g. brake conductors)
at least on one side to the grounded housing potential.
Electric shock if there is no ground connection
For missing or incorrectly implemented protective conductor connection for devices with
protection class I, high voltages can be present at open, exposed parts, which when
touched, can result in death or severe injury.
• Ground the device in compliance with the applicable regulations.
Arcing when a plug connection is opened during operation
Opening a plug connection when a system is in operation can result in arcing that may
cause serious injury or death.
• Only open plug connections when the equipment is in a voltage-free state, unless it has
been explicitly stated that they can be opened in operation.
Property damage due to loose power connections
Insufficient tightening torques or vibration can result in loose power connections. This can
result in damage due to fire, device defects or malfunctions.
• Tighten all power connections to the prescribed torque.
• Check all power connections at regular intervals, particularly after equipment has been
transported.

Safety information
1.1 General safety instructions
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
7
Spread of fire from built-in devices
In the event of fire outbreak, the enclosures of built-in devices cannot prevent the escape of
fire and smoke. This can result in serious personal injury or property damage.
• Install built-in units in a suitable metal cabinet in such a way that personnel are
protected against fire and smoke, or take other appropriate measures to protect
personnel.
• Ensure that smoke can only escape via controlled and monitored paths.
Failure of pacemakers or implant malfunctions due to electromagnetic fields
Electromagnetic fields (EMF) are generated by the operation of electrical power equipment,
such as transformers, converters, or motors. People with pacemakers or implants in the
immediate vicinity of this equipment are at particular risk.
• If you have a heart pacemaker or implant, maintain a minimum distance of 2 m from
electrical power equipment.
Unexpected movement of machines caused by radio devices or mobile phones
When radio devices or mobile phones with a transmission power > 1 W are used in the
immediate vicinity of components, they may cause the equipment to malfunction.
Malfunctions may impair the functional safety of machines and can therefore put people in
danger or lead to property damage.
• If you come closer than around 2 m to such components, switch off any radio devices or
mobile phones.
• Use the "SIEMENS Industry Online Support App" only on equipment that has already
been switched off.
Motor fire in the event of insulation overload
There is a greater load on the motor insulation as result of a ground fault in an IT system. If
the insulation fails, it is possible that death or severe injury can occur as a result of smoke
and fire.
• Use a monitoring device that signals an insulation fault.
• Correct the fault as quickly as possible so the motor insulation is not overloaded.

Safety information
1.1 General safety instructions
Advanced Operator Panel 30 (AOP30)
8 Operating Instructions, 11/2017, A5E00331451A
Fire due to inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating of components with subsequent
fire and smoke. This can cause severe injury or even death. This can also result in
increased downtime and reduced service lives for devices/systems.
• Ensure compliance with the specified minimum clearance as ventilation clearance for
the respective component.
Unrecognized dangers due to missing or illegible warning labels
Dangers might not be recognized if warning labels are missing or illegible. Unrecognized
dangers may cause accidents resulting in serious injury or death.
• Check that the warning labels are complete based on the documentation.
• Attach any missing warning labels to the components, where necessary in the national
language.
• Replace illegible warning labels.
Device damage caused by incorrect voltage/insulation tests
Incorrect voltage/insulation tests can damage the device.
• Before carrying out a voltage/insulation check of the system/machine, disconnect the
devices as all converters and motors have been subject to a high-voltage test by the
manufacturer, and therefore it is not necessary to perform an additional test within the
system/machine.
Unexpected movement of machines caused by inactive safety functions
Inactive or non-adapted safety functions can trigger unexpected machine movements that
may result in serious injury or death.
• Observe the information in the appropriate product documentation before
commissioning.
• Carry out a safety inspection for functions relevant to safety on the entire system,
including all safety-related components.
• Ensure that the safety functions used in your drives and automation tasks are adjusted
and activated through appropriate parameterizing.
• Perform a function test.
• Only put your plant into live operation once you have absolutely guaranteed that the
functions relevant to safety are operating correctly.

Safety information
1.2 Handling the AOP30 backup battery
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
9
Note
Important safety instructions for Safety Integrated functions
If you want to use Safety Integrated functions, you must observe the safety instructions in
the Safety Integrated manuals.
Handling the AOP30 backup battery
Risk of explosion and release of harmful substances
Improper handling of lithium batteries can result in an explosion of the batteries.
Explosion of the batteries and the released pollutants can cause severe physical injury.
Note the following points when handling lithium batteries:
• Replace used batteries in good time; see the chapter "Replacing the backup battery".
• Only replace the lithium battery with an identical battery or with a type recommended by
the manufacturer.
• Do not throw lithium batteries into a fire, do not recharge, do not open, do not short-
circuit, do not reverse the polarity, do not heat above 100 °C and protect from direct
sunlight, moisture and condensation.

Safety information
1.3 Handling electrostatic sensitive devices (ESD)
Advanced Operator Panel 30 (AOP30)
10 Operating Instructions, 11/2017, A5E00331451A
Handling electrostatic sensitive devices (ESD)
Electrostatic sensitive devices (ESD) are individual components, integrated circuits, modules
or devices that may be damaged by either electric fields or electrostatic discharge.
Damage through electric fields or electrostatic discharge
Electric fields or electrostatic discharge can cause malfunctions through damaged
individual components, integrated circuits, modules or devices.
• Only pack, store, transport and send electronic components, modules or devices in their
original packaging or in other suitable materials, e.g. conductive foam rubber or
aluminum foil.
• Only touch components, modules and devices when you are grounded by one of the
following methods:
– Wearing an ESD wrist strap
– Wearing ESD shoes or ESD grounding straps in ESD areas with conductive flooring
• Only place electronic components, modules or devices on conductive surfaces (table
with ESD surface, conductive ESD foam, ESD packaging, ESD transport container).
The necessary ESD protective measures are clearly illustrated in the following diagram:
● a = conductive floor surface
● b = ESD table
● c = ESD shoes
● d = ESD overall
● e = ESD wristband
● f = cabinet ground connection
● g = contact with conductive flooring
Figure 1-1 ESD protective measures

Safety information
1.4 Industrial security
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
11
Note
Industrial Security
Siemens provides products and solutions with industrial security functions that
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement
– and continuously maintain – a holistic, state-of-the-art Industrial
curity concept. Siemens products and solutions only represent one component of such a
The customer is solely responsible for preventing unauthorized access to its plants, systems,
machines and networks. Systems, machines and components should only
the company's network or the internet if and to the extent necessary and with appropriate
security measures (e.g. use of firewalls and network segmentation) in place.
Additionally, Siemens’ guidance on appropriate security measures should
account. For more information about Industrial Security, please visit:
http://www.siemens.com/industrialsecurity).
Siemens’ products and solutions undergo cont
inuous development to make them more
secure. Siemens strongly recommends to apply product updates as soon as available and to
always use the latest product versions. Use of product versions that are no longer supported,
and failure to apply latest updates
may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed at:
http://www.siemens.com/industrialsecurity).
Unsafe operating states resulting from software manipulation
Software manipulation (e.g. viruses, trojans, malware or worms) can cause unsafe
operating states in your system that may lead to death, serious injury, and property
damage.
• Keep the software up to date.
• Incorporate the automation and drive components into a holistic, state-of-the-art
industrial security concept for the installation or machine.
• Make sure that you include all installed products into the holistic industrial security
concept.
• Protect files stored on exchangeable storage media from malicious software by applying
suitable protection measures, e.g. virus scanners.
Note
Industrial security Configuration Manual
You can find a Configuration Manual on the topic of industrial security at this address
(
https://support.industry.siemens.com/cs/ww/en/view/108862708).

Safety information
1.4 Industrial security
Advanced Operator Panel 30 (AOP30)
12 Operating Instructions, 11/2017, A5E00331451A

Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
13
The user-friendly AOP30 operator panel is an optional input/output device for SINAMICS
G130 converters. The operator panel can be used for commissioning, operation, and
diagnostic purposes.
The AOP30 communicates with the SINAMICS drive via a serial interface (RS232) using the
PPI protocol. The interface is a point-to-point connection. During communication, the AOP30
is the master and the connected drive is the slave.
The AOP30 is an operator panel with a graphical display and a touch-sensitive keypad. An
RS232 interface is used as the interface to the drive unit. The device can be installed in a
cabinet door (thickness: between 2 mm and 4 mm).
● Display with green backlighting (resolution: 240 x 64 pixels)
● 26-key touch-sensitive keypad
● Connection for a 24 V DC power supply
● RS232 interface
● Time and date memory powered by internal battery backup
● 4 LEDs indicate the operating status of the drive unit:
– RUN: green
– ALARM: yellow
– FAULT: red
– LOCAL/REMOTE: green

General
Advanced Operator Panel 30 (AOP30)
14 Operating Instructions, 11/2017, A5E00331451A

Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
15
The following diagrams and descriptions explain the conditions and procedures involved in
the mechanical installation of the AOP30 operator panel.
Figure 3-1 Dimension drawing of the AOP30 operator panel
Installing the operator panel (cabinet door thickness: 2 mm)
1. Cut out a 141.5 mm x 197.5 mm section in the cabinet door.
2. Fit the AOP30 operator panel in this cutout section from the outside.
3. Apply pressure to the four corners until the snap-in lugs lock into position.

Mechanical installation
Advanced Operator Panel 30 (AOP30)
16 Operating Instructions, 11/2017, A5E00331451A
Installing the operator panel (cabinet door thickness: 2 mm to 4 mm)
The following photos show the tensioning elements for the AOP30 operator panel for
installation in cabinet doors (thickness: 2 mm to 4mm).
Figure 3-2 Tensioning elements for the AOP30 operator panel for installation in cabinet doors
(thickness: 2 mm to 4 mm)

Mechanical installation
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
17
1. Cut out a 141.5 mm x 197.5 mm section in the cabinet door.
2. Fit the AOP30 operator panel in this cutout section from the outside.
3. Hook the tensioning elements into the openings provided.
4. Tighten the screws by hand to secure the tensioning elements.
Device damage caused by screws being tightened excessively
The excessive tightening of the screws used to fix the tension jack can cause damage to
the operator panel housing!
• Tighten the screws used to fix the tension jack only hand-tight.

Mechanical installation
Advanced Operator Panel 30 (AOP30)
18 Operating Instructions, 11/2017, A5E00331451A

Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
19
Figure 4-1 AOP30 interfaces
Table 4- 1 Power supply terminals
Max. connectable cross-section: 2.5 mm²

Connection
Advanced Operator Panel 30 (AOP30)
20 Operating Instructions, 11/2017, A5E00331451A
Note
Connectable voltage supply
Only a protective extra
-low voltage of Class DVC A, (PELV) acc. to EN 61800-5-1 must be
connected to the power supply.
X540: serial interface (RS232)
Table 4- 2 Serial interface (RS232) X540
Connector type: 9-pin SUB D socket
Note
Maximum cable lengths
The maximum cable length is 10 m.
-free communication, you are advised to use a shielded cable and connect
the cable shield to both connector housings.
Device damage caused by interchanged poles of the connected power supply
In the operator panel electronic circuitry, a connected cable shield may possibly be
connected to the signal and P24 ground. If the power supply is connected with incorrect
polarity, the P24 supply via the shield and signal ground will short-circuit. This can cause
device damage.
• Connect the correct poles of the power supply.

Connection
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
21
The AOP30 is connected as follows:
1. Connect the power supply cable to the interface for the electronic power supply (X524).
2. Connect the standard cable to the serial RS232 interface (X540) of the Control Unit.
Figure 4-2 Signal cable between the Control Unit and AOP30
Note
Assignment of the connecting cable
The connection cable to AOP30 may only contain the three contac
ts which are shown in the
drawing; a completely allocated cable may not be used.

Connection
Advanced Operator Panel 30 (AOP30)
22 Operating Instructions, 11/2017, A5E00331451A

Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
23
Operator panel (AOP30) overview and menu structure
Description
The operator panel can be used for the following activities:
● Parameterization (commissioning)
● Monitoring status variables
● Controlling the drive
● Diagnosing faults and alarms
All the functions can be accessed via a menu.
Your starting point is the main menu, which you can always call up using the yellow MENU
key:
Dialog screen for the main menu:
It can be accessed at any time with the
"MENU" key.
Press "F2" or "F3" to navigate through the
menu options in the main menu.
Note
AOP reset
If the AOP no longer reacts, you can trigger an AOP reset by simultaneously pressing the
key and OFF buttons (longer than two seconds) and then releasing the OFF button.

Control via the operator panel
5.1 Operator panel (AOP30) overview and menu structure
Advanced Operator Panel 30 (AOP30)
24 Operating Instructions, 11/2017, A5E00331451A
Menu structure of the operator panel
Figure 5-1 Menu structure of the operator panel

Control via the operator panel
5.2 Menu: Operation screen
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
25
Menu: Operation screen
Description
The operation screen displays the most important status variables for the drive unit:
In the delivery condition, it displays the operating state of the drive, the direction of rotation,
the time, as well as four drive variables (parameters) numerically and two in the form of a bar
display for continuous monitoring.
There are two ways to reach the operation screen:
1. After the power supply has been switched on and the system has ramped up.
2. By pressing the MENU key and F5 "OK"
Figure 5-2 Operation screen
If a fault occurs, the system automatically displays the fault screen (see "Faults and alarms").
In LOCAL control mode, you can choose to enter the setpoint numerically (F2: setpoint).
With F3 "Extras", screen2 and CDS data set (see section CDS setting via AOP (Page 44))
can be selected.
The individual parameters of the operation screen can be selected using F4 "Sel. par." The
corresponding parameter number of the short identifier is displayed using F1 "Help+" and a
description of the parameter can be called up.
When you choose Commissioning / service –> AOP settings –> Define operation screen, you
can adjust the display type and the values displayed as required (see "AOP settings").

Control via the operator panel
5.3 Menu: Parameterization
Advanced Operator Panel 30 (AOP30)
26 Operating Instructions, 11/2017, A5E00331451A
You can adjust the device settings in the Parameterization menu.
The drive software is modular. The individual modules are called DOs ("drive objects").
The following DOs are available in the SINAMICS G130:
General parameters for the Control Unit
The TM31 terminal module (optional)
the TM150 temperature sensor module (optional)
Parameters with identical functions may exist with the same parameter number in more than
one DO (e.g. p0002).
The AOP30 is used for operating devices that comprise more than one drive so that attention
is focused on one drive (i.e. the "current" drive). The switchover is made in the main menu.
The corresponding function key is labeled "Drive."
This drive determines the following:
● Operation screen
● Fault and alarm displays
● The controller (ON, OFF, …) of a drive
Depending on your requirements, you can choose between two AOP display types:
1. All parameters
All the parameters present in the device are listed here. The DO to which the currently
selected parameter belongs is displayed in curly brackets in the top left of the screen.
2. DO selection
In this display, you can pre-select a DO Only the parameters for this DO are then listed.
(The expert list display in STARTER only uses this DO view)
In both cases, the set access level governs which parameters are displayed. You can set the
access level in the menu for inhibit functions, which can be called up using the key button.
The parameters for access levels 1 and 2 are sufficient for simple applications.
At access level 3 ("Expert"), you can change the structure of the function by interconnecting
BICO parameters.
In the Data set selection menu, you can choose which of the data sets chosen is currently
DISPLAYED on the operator panel.
Data set parameters are indicated by a "c", "d", "m", "e", or "p" between the parameter
number and parameter designator.
When a data set parameter is changed, the data set selection dialog appears.

Control via the operator panel
5.4 Menu: Fault/alarm memory
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
27
Figure 5-3 Data set selection
Explanation of the operator control dialog
● "Max" shows the maximum number of data sets parameterized (and thereby available for
selection) in the drive.
● "Drive" indicates which data set is currently active in the drive.
● "AOP" indicates which particular data set is currently being displayed in the operator
panel.
When you select the menu, a screen appears containing an overview of faults and alarms
that are present.
For each drive object, the system indicates whether any faults or alarms are present. ("Fault"
or "Alarm" appears next to the relevant drive object).
In the graphic below, you can see that at least one active fault/alarm is present for the
"VECTOR" drive object. No faults/alarms are indicated for the other drive objects.
Fault/alarm memory
When you navigate to the line with active
ults and then press the F5 <Diag>
key, the system displays a screen in which
you have to select the current or old
alarms/faults.

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
28 Operating Instructions, 11/2017, A5E00331451A
Display diagnosis
When you navi
gate to the required line and
then press the F5 <OK> key, the corr
sponding faults/alarms are displayed.
The list of current faults is selected here as
Display of current faults
A maximum of eight current faults are di
played along with their fault number and
name of the fault.
To display additional help regarding the
cause of the problem and how to solve it,
cho
<Ack.>. If a fault cannot be acknowledged,
the fault remains.
Menu commissioning / service
5.5.1
This option enables you to re-commission the drive from the main menu.
Only the basic commissioning parameters are queried and stored permanently.
Complete commissioning with motor and encoder data entry is carried out. Following this,
key motor parameters are recalculated from the motor data. The parameter values
calculated during previous commissioning are lost.
In a subsequent motor identification procedure, the calculated values are overwritten.

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
29
The selection screen for motor identification appears.
The actual operating hours of the fan in the power unit is displayed.
After a fan replacement, the operating hours counter for monitoring the fan operating time
must be reset.
Device commissioning
Device commissioning
In this menu, you can enter the device commissioning status directly. This is the only way
that you can reset parameters to the factory setting for example.
Drive diagnostics
Curve recorder
The curve recorder provides a slow trace function, which monitors a signal trend.
A signal selected via a parameter is shown in the form of a curve.
Figure 5-4 Curve recorder
The curve recorder-relevant settings are changed by pressing the F5 key or via the
"Commissioning / Service – AOP settings - Curve recorder-relevant settings" menu.
The value of the parameter selected in the curve recorder-relevant settings is output on the
display in addition to the curve and updated every 0.5 ... 24.5 seconds (parameterizable).
With a slowly running time basis (as of 20 minutes/figure), the time basis value flashes in the
header in the 1 s-cycle alternately with the text "slow X".
Assignment of the function keys F1 to F5 is not normally displayed so that the space can be
fully utilized to display the curve. Pressing a function key shows the key assignments. If no
further key is pressed within 5 seconds, the labeling will disappear again.

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
30 Operating Instructions, 11/2017, A5E00331451A
The curve can be scaled automatically or manually. This is selected with key F3 "scale+" F2 "Auto/Manual" followed by confirmation with F5 "OK."
●
The scaling of the curve changes dynamically, it is oriented to the maximum value (for
example, 12.49) and minimum value (for example, 0.00) visible in the display at the
actual point in time. Scaling can be changed step-by-step by pressing buttons F2 and F3.
If measured value noise is shown with an excessively high resolution as a result of the
automatic scaling, then the resolution can be reduced in four steps by pressing button F2.
As a result, the automatic scaling is deactivated. However, if the measured value leaves
the display area, then this is extended. Automatic scaling can be reselected by pressing
button F3.
●
After selecting manual scaling and confirmation with "OK", a window opens in which the
maximum and minimum limits for scaling can be set.
Figure 5-5 Curve recorder - manual scaling
After setting and applying the limits, you switch to the curve recorder and manual scaling
is used.
If the current measured values are outside the displayable range, the range will
automatically be extended.
Note
Changing the parameter for the curve recorder in manual scaling
When the parameter for the curve recorder is changed the following occurs with manual
scaling:
If the current parameter has lower values than the currently set scaling, the scaling will
be retained.
If the current parameter has higher values than the currently set scaling, the scaling
will be adjusted automatically.
Help on the curve recorder can be opened with key F1.
The curve recorder is exited by pressing the MENU button.

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
31
Note
No recording of data
The values
displayed in the recorder are not recorded and saved, they are only used for
display until the screen form is exited.
AOP settings
Control settings
This defines the settings for the control keys in LOCAL mode (see "Operation / Control via
the operator panel / Operation via the operator panel").
In this menu, you set the lighting, brightness, and contrast for the display.
In this menu, you can switch between five operation screens. You can set the parameters to
be displayed.
Figure 5-6 Define operation screen

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
32 Operating Instructions, 11/2017, A5E00331451A
The following screenshot shows how entries are assigned to the screen positions:
Figure 5-7 Layout of entries on the operation screen
Lists of signals for the operating screen form
The following tables list some of the main signals for the operation screen along with the
associated reference variables and default settings for fast commissioning.

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
33
Table 5- 1 List of signals for the operation screen - VECTOR object
Scaling (100 %=...) See
table below
Factory setting (entry no.)
Speed setpoint upstream of ramp-function
(1) r1114 NSETP 1/min p2000
Power smoothed (3) r0032 PACTV kW r2004
Actual speed value smoothed
Absolute actual current, smoothed
Converter output voltage smoothed
Control factor smoothed r0028 AUSST % Reference modulation
Field-producing current component
Torque-producing current component
Degree of thermal overload
r0036 LTI2T % 100 % = Shutdown
Speed actual value motor encoder
Speed setpoint after the filter
Output frequency r0066 F_OUT Hz Reference frequency
Control factor r0074 AUSST % Reference modulation
Torque-generating actual current
For further diagnostic purposes
Fixed speed setpoint effective
Active motorized potentiometer setpoint
I component of speed controller
1)
If a temperature sensor has not been installed, a value of –200 °C is displayed.

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
34 Operating Instructions, 11/2017, A5E00331451A
Normalization for VECTOR object
Table 5- 2 Normalization for VECTOR object
Default for quick commissioning
p2000 = Maximum speed (p1082)
Reference voltage 100% = p2001 p2001 = 1000 V
p2002 = Current limit (p0640)
p2003 = 2 x rated motor torque
r2004 = (p2003 x p2000 x π) / 30
100 % = Maximum output voltage without overload
Table 5- 3 List of signals for the operation screen – TM31 object
In this menu, the following settings can be made:
You can select here the parameter whose signal is to be displayed in the form of a trend
curve in the curve recorder.
(factory setting: No), serves for the better display of rapidly changing quantities.
●
Only the measured values are displayed as points, without a connecting line between
the points.
●
The measured values are connected with a vertical line.
●
The measured values are connected with a line, offset at the center.

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
35
(factory setting: 2 minutes/screen)
The rate of the signal acquisition in minutes per screen is set. The value can be changed in
integer multiples of 2. If an odd value is entered, the value will be rounded up. After changing
the time basis the recording is started again.
Values are still recorded, even if the display screen is exited. When the screen is
entered again, the recorded prehistory is displayed.
●
The recording is stopped when the curve recorder is exited.
(factory setting: Auto), specifies the representation of the trend
Scaling is done automatically (making the best possible use of the display height).
●
Scaling is done manually by entering the range limits MIN/MAX. If, in this mode,
values that are outside the defined window occur, the limit is automatically adapted for
the display so that actual measured values can always be recorded.
Setting the date/time (for date stamping of error messages)
In this menu, you set the date and time.
You can also set whether and/or how the AOP and drive unit are to be synchronized.
Synchronization of the AOP with the drive enables error messages to be date- and timestamped.
Note
Display format for the time
The drive unit displays the time in parameter r3102 in the UTC format (days/milliseconds
since 1970
Under "Additional settings", settings for synchronization can be made:
(factory setting: None)
●
None
The times for the AOP and drive unit are not synchronized.
– If you activate this option, the AOP and drive unit are synchronized immediately
whereby the current AOP time is transferred to the drive unit.
– The current AOP time is transferred to the drive unit every time the AOP is started.
– Depending on the set synchronization interval, the current AOP time is transferred to
the drive unit.

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
36 Operating Instructions, 11/2017, A5E00331451A
Note
Flashing "S"
If the AOP detects a difference between RAM and ROM during synchronization to the
drive unit, this is indicated by a flashing "S" at the top right in the display or, if operator
input and/or parameter ass
ignment has been disabled, by a flashing key symbol.
– If you activate this option, the AOP and drive unit are synchronized immediately
whereby the current drive unit time is transferred to the AOP.
– The current drive unit time is transferred to the AOP every time the AOP is started.
– Depending on the set synchronization interval, the current drive unit time is transferred
to the AOP.
Note
Time-of-day master
The time in the drive must be set by a clock master (e.g. SIMATIC).
The interval for time synchronization is set from 1 hour (factory setting) to 99 hours.
For the interval, the time in the AOP from the time of the last change of the interval is
decisive.
No
The time does not automatically change over to daylight-saving time.
Yes
Selection is only possible if synchronization is set to "None" or "AOP -> Drive".
The time is then automatically set to summer or winter time.
After the changeover - for synchronization "AOP -> Drive" - synchronization is
immediately carried out, irrespective of the synchronization interval set.
Changes to the synchronization must be saved with "Save".
In this menu, the date format can be set:
●
: North American date format

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
37
In this menu, you can toggle the display of the DO-name between the standard abbreviation
(e.g., VECTOR) and a DO-name of your choice (e.g. motor_1).
The "User-defined DO-name" stored in parameter p0199 is displayed instead of the
standard DO abbreviation.
●
The standard DO abbreviation is displayed.
In this menu, the reference variable for the bar-type display of parameter r0027 (absolute
actual current value smoothed) can be changed over in the operating screen forms.
The bar display of parameter r0027 in the operating screen form is displayed with
reference to parameter p0305 (rated motor current).
●
The bar display of parameter r0027 in the operating screen form is displayed with
reference to parameter p2002 (reference current).
When you choose this menu option, the AOP factory settings for the following are restored:
● Language
● Display (brightness, contrast)
● Operating screen
● Control settings
Note
Restoring the factory setting
When you reset pa
rameters, all settings that are different to the factory settings are reset
immediately. This may cause the cabinet unit to switch to a different, unwanted operational
status.
For this reason, you should always take great care when resetting parameters.

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
38 Operating Instructions, 11/2017, A5E00331451A
In this menu, the battery symbol can be activated so that it is displayed in the operating
screen form. When the display is activated, then the battery symbol is shown instead of the
time of day seconds display. It displays the battery voltage in 20 % steps. If the display was
received in the last 20 %, then the battery symbol flashes in order to indicate that the battery
must be replaced.
The battery symbol is shown at the top right of the operating screen form - at the
time of day seconds display.
●
The battery symbol is not displayed in the operating screen form.
AOP diagnostics
Software/database version
You can use this menu to display the firmware and database versions.
The database version must be compatible with the drive software status (you can check this
in parameter r0018).
For service purposes, the contents of the database are displayed in the screen form.
In this menu, you can display the battery voltage numerically (in Volts) or as a bar display.
The battery ensures that the data in the database and the current time are retained.
When the battery voltage is represented as a percentage, a battery voltage of ≤ 2.30 V is
equal to 0%, and a voltage of ≥ 3 V to 100%.
The data is secure up to a battery voltage of 2.30 V.
● If the battery voltage is ≤ 2.45 V, the message "Battery weak - replace soon" is displayed
in the status bar.
● If the battery voltage is ≤ 2.30 V, the system displays the following message: "Battery
defect - replace immed."
● If the time and/or database are not available after the system has been switched off for a
prolonged period due to the voltage being too low, the loss is established by means of a
CRC check when the system is switched on again. This triggers a message instructing
the user to replace the battery and then load the database and/or set the time.
For instructions on how to change the battery, see "Maintenance and servicing".

Control via the operator panel
5.5 Menu commissioning / service
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
39
In this screen, you can check whether the keys are functioning properly. Keys that you press
are represented on a symbolic keyboard on the display. You can press the keys in any order.
You cannot exit the screen (F4 – "back") until you have pressed each key at least once.
Note
Exit keyboard test
Alternatively, you can exit the keyboard test screen by pressing any key and holding it down.
A screenshot is created by simultaneously pressing keys "1" and "+/-" - and then the display
flashes 2 times, one after the other. A maximum of 8 screenshots can be managed.
The list of the saved screenshots is displayed in the "Screenshots" menu item.
The screenshot is selected from the list and is displayed by pressing F5.
While the screenshot is being displayed, the identifier and the time stamp are displayed
flashing in the title line every 5 seconds.
By pressing any function key F1 ... F5, the function key assignment is displayed for 5
seconds.
● The display is exited by pressing F4 and the list of screenshots is redisplayed.
● By pressing the F5 key once and then pressing F5 "Clear" again to confirm, the displayed
screenshot will be deleted and the list of screenshots will be displayed again.
To clear all of the screenshots, in the list of screenshots, press F5 for longer than 1 second and confirm the following prompt with "Yes".
If there are gaps in the list of screenshots, then they are populated with new screenshots
from the top to the bottom. When the list is full, then the oldest chronological entry in the list
is overwritten.
Note
Battery buffering
The screenshots are saved to the memory, buffered by a battery
after the power supply has been switched
-off and switched-on again.
When the AOP30 is switched off and the battery is too weak
- a buffer time of approximately 30 minutes applies.

Control via the operator panel
5.6 Sprachauswahl/Language selection
Advanced Operator Panel 30 (AOP30)
40 Operating Instructions, 11/2017, A5E00331451A
In this screen, you can check that the four LEDs are functioning properly.
For service purposes, the database statistics are displayed in the screen form.
Sprachauswahl/Language selection
The operator panel downloads the texts for the different languages from the drive.
You can change the language of the operator panel via the "Sprachauswahl/Language
selection" menu.
Note
Additional languages for the display
Languages in addition to the current availabl
e languages in the display are available on
Operation via the operator panel (LOCAL mode)
You activate the control keys by switching to LOCAL mode. If the green LED in the
LOCAL/REMOTE key does not light up, the key is not active.
Note
OFF in REMOTE
If the "OFF in REMOTE" function is activated, the LED in the LOCAL
For LOCAL master control, all of the supplementary setpoints are deactivated.
After the master control has been transferred to the operator panel, the BICO
interconnections at bit 0 to bit 10 of the control word of the sequence control are not effective
(refer to function diagram 2501).
Note
Message "Other device has master control"
If STARTER has master control, then when pressing the LOCAL
"Other device has master control" message is displayed, and the master control transfer is
rejected.

Control via the operator panel
5.7 Operation via the operator panel (LOCAL mode)
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
41
LOCAL/REMOTE key
Activating the LOCAL mode:
: LED does not light up: the ON, OFF, JOG, direction reversal, faster, and
slower keys are not active.
Settings: MENU – Commissioning/Service – AOP Settings – Control Settings
Save LOCAL mode
: The "LOCAL" or "REMOTE" operating mode is saved when the power supply is
switched off and restored when the power supply is switched back on.
●
: "LOCAL" or "REMOTE" operating mode is not saved. "REMOTE" is active when the
supply voltage is switched back on.
: The OFF key functions in REMOTE mode even if the drive is being controlled by
external sources (fieldbus, customer terminal strip, NAMUR terminal strip).
WARNING This function is not an EMERGENCY STOP function!
●
: The OFF key only functions in LOCAL mode.
LOCAL/REMOTE also during operation
: You can switch between LOCAL and REMOTE when the drive is switched on (motor
is running).
●
: Before the system switches to LOCAL, a check is carried out to determine whether
the drive is in the operational status. If so, the system does not switch to local and
outputs the error message "Local mode during operation not possible". Before the system
switches to REMOTE, the drive is switched off and the setpoint is set to 0.
: always active in LOCAL when the operator input inhibit is deactivated.
: in the factory setting, acts as OFF1 = ramp-down at the deceleration ramp (p1121);
when n = 0: voltage disconnection (only if a main contactor is installed)
The OFF key is effective in the LOCAL mode and when the "OFF in REMOTE" function is
active.
Settings: Menu – Commissioning / Service – AOP Settings – Control Settings
Red OFF key acts as
: (factory setting: OFF1)
●
: Ramp-down on the deceleration ramp (p1121)
●
: Immediate pulse block, motor coasts to a standstill
●
: Ramp-down on the emergency stop ramp (p1135)

Control via the operator panel
5.7 Operation via the operator panel (LOCAL mode)
Advanced Operator Panel 30 (AOP30)
42 Operating Instructions, 11/2017, A5E00331451A
Switching between clockwise and counter-clockwise rotation
Settings: MENU – Commissioning/Service – AOP Settings – Control Settings
Switching between CCW/CW
: Switching between CW/CCW rotation by means of the CW/CCW key possible in
LOCAL mode
●
: The CW/CCW key has no effect in LOCAL mode
For safety reasons, the CW/CCW key is disabled in the factory setting (pumps and fans must
normally only be operated in one direction).
In the operation status in LOCAL mode, the current direction of rotation is indicated by an
arrow next to the operating mode.
Note
Activation of CCW/CW changeover
You have to make additional settings when switching between CW/CCW rotation.
Settings: MENU – Commissioning/Service – AOP settings – Control settings
JOG key active
: The jog key is effective in the LOCAL mode in the state "ready to power-up" (not in
"operation"). The speed that is set in parameter p1058 is approached.
●
: The JOG key has no effect in the LOCAL mode
Increase setpoint / decrease setpoint
You can use the Increase and Decrease keys to enter the setpoint with a resolution of 1% of
the maximum speed.
You can also enter the setpoint numerically. To do so, press F2 in the operation screen. The
system displays an field for entering the required speed. Enter the required value using the
numeric keypad. Press F5 "OK" to confirm the setpoint.
When you enter values numerically, you can enter any speed between the minimum speed
(p1080) and the maximum speed (p1082).

Control via the operator panel
5.7 Operation via the operator panel (LOCAL mode)
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
43
Setpoint entry in LOCAL mode is unipolar. You can change the direction of rotation by
pressing the key that allows you to switch between CW/CCW rotation.
● CW rotation and "Increase key" mean:
The displayed setpoint is positive and the output frequency is increased.
● CCW rotation and "Increase key" mean:
The displayed setpoint is negative and the output frequency is increased.
AOP setpoint
Settings: MENU – Commissioning/Service – AOP Settings – Control Settings
Save AOP setpoint
: In LOCAL mode, the last setpoint (once you have released the INCREASE or
DECREASE key or confirmed a numeric entry) is saved.
The next time you switch the system on in LOCAL mode, the saved value is selected.
This is also the case if you switched to REMOTE in the meantime or the power supply
was switched off.
When the system is switched from REMOTE to LOCAL mode while the drive is switched
on (motor is running), the actual value that was last present is set as the output value for
the motorized potentiometer setpoint and saved.
If the system is switched from REMOTE to LOCAL mode while the drive is switched off,
the motorized potentiometer setpoint that was last saved is used.
●
: On power-up in LOCAL mode, the speed is always set to the value entered under
"AOP starting setpoint". When the system is switched from REMOTE to LOCAL mode
while the drive is switched on (motor is running), the actual value that was last present is
set as the output value for the AOP setpoint.
AOP setpoint ramp-up time
AOP setpoint ramp-down time
(factory setting: 10 s)
●
: set as ramp-up/ramp-down time (p1120/p1121).
Changing the ramp-up/ramp-down times does not affect the settings for parameters
p1120 and p1121 because this is an AOP-specific setting.
(factory setting: 0.000 rpm)
The AOP starting setpoint is the speed setpoint which is active when the drive is switched on
(with AOP30 - "ON" key). This setpoint is valid on condition that the system setting "Save
setpoint" is set to "NO".
Note
Internal ramp-function generator
The internal drive ramp
-function generator is always active.

Control via the operator panel
5.7 Operation via the operator panel (LOCAL mode)
Advanced Operator Panel 30 (AOP30)
44 Operating Instructions, 11/2017, A5E00331451A
Lock AOP LOCAL mode
Settings: MENU – Commissioning/Service – AOP settings – Control settings
Save AOP local mode
: Deactivates the "Control via operator panel" function, thereby disabling the
LOCAL/REMOTE key.
●
: Activates the LOCAL/REMOTE key.
Note
Lock LOCAL
LOCAL functionality can also be inhibited on the drive by means of the p0806 parameter (BI:
Inhibit master control).
Acknowledge error from the AOP
Settings: MENU – Commissioning/Service – AOP Settings – Control Settings
Acknowledge error from the AOP
: Errors can be acknowledged via the AOP.
●
: Errors cannot be acknowledged via the AOP.
CDS setting via AOP
Settings: MENU – Commissioning/Service – AOP settings – Control settings
CDS changeover via AOP
: In the LOCAL mode, in the operating screen form the active CDS can the changed
by one. This is helpful, if operation via an AOP would not be possible due to the fact that
a standard telegram is active.
When CDS0 or 2 is active, "CDS+1" switches to CDS1 or CDS3.
When CDS1 or 3 is active, "CDS-1" switches to CDS0 or CDS2.
●
: In the LOCAL mode, in the operating screen form the active CDS cannot be changed
by one.

Control via the operator panel
5.7 Operation via the operator panel (LOCAL mode)
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
45
Operator input inhibit / parameterization inhibit
To prevent users from accidentally actuating the control keys and changing parameters, you
can activate an operator input / parameters disable using a key pushbutton. Two key icons
appear in the top right of the display when these inhibit functions are enabled.
Table 5- 4 Display of operator input/parameters disable
Operator input inhibit + parameters disable
Figure 5-8 Set inhibit functions
The "Operator input inhibit" setting can be changed directly via <F5> "Change" once you
have selected the selection field.
When "Parameterization inhibit" is activated, you have to enter a numeric password (repeat
this entry). You must also enter this password when deactivating "Parameterization inhibit".
(factory setting: not active)
●
: The parameters can still be viewed, but a parameter value cannot be saved
(message: "Note: operator input inhibit active"). The OFF key (red) is enabled. The
LOCAL, REMOTE, ON (green), JOG, CW/CCW, INCREASE, and DECREASE keys are
disabled.
(factory setting: not active)
●
: Parameters cannot be changed unless a password is entered. The
parameterization process is the same as with the operator input inhibit. If you try and
change parameters, the message "Note: Parameterization inhibit active" is displayed. All
the control keys can, however, still be actuated.

Control via the operator panel
5.8 Faults and alarms
Advanced Operator Panel 30 (AOP30)
46 Operating Instructions, 11/2017, A5E00331451A
(factory setting: Expert):
The different parameters required for this complex application are filtered so that they can be
displayed as clearly as possible. You select them according to the access level.
An expert level, which must only be used by expert personnel, is required for certain actions.
Note
Copy from RAM to ROM
When the operator input inhibit or parameterization inhibit is activated, a "Copy from RAM to
ROM" is automatically executed to back the parameter settings up in non-volatile memory on
the memory card.
Faults and alarms
Indicating faults and alarms
If a fault occurs, the drive displays the fault and/or alarm on the operator panel. Faults are
indicated by the red "FAULT" LED and a fault screen is automatically displayed. You can use
the F1 Help function to call up information about the cause of the fault and how to remedy it.
You can use F5 Ack. to acknowledge a stored fault.
Alarms are indicated by means of the yellow "ALARM" LED. The system also displays a note
in the status bar providing information on the cause.
A fault is a message from the drive indicating an error or other exceptional (unwanted) status
that causes the drive to shutdown. This could be caused by a fault within the converter or an
external fault triggered, for example, by the winding temperature monitor for the motor. The
faults are displayed and can be reported to a higher-level control system via PROFIBUS. In
the factory default setting, the message "converter fault" is also sent to a relay output. Once
you have rectified the cause of the fault, you have to acknowledge the fault message.
An alarm is the response to a fault condition identified by the drive. It does not result in the
drive being switched off and does not have to be acknowledged. Alarms are "self
acknowledging", that is, they are reset automatically when the cause of the alarm has been
eliminated.

Control via the operator panel
5.8 Faults and alarms
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
47
Every fault and alarm is entered in the fault/alarm buffer along with time the error occurred.
The time stamp refers to the system time (r2114).
You can call up an overview screen that displays the current status of faults and/or alarms
for every drive object in the system by choosing MENU – Fault memory / alarm memory.
A context menu featuring the "Back" and "Quit" options appears when you press F4 "Next".
The function required can be selected using F2 and F3 and executed by pressing F5 "OK".
The "Acknowledge" function sends an acknowledgement signal to each drive object.
The red FAULT LED extinguishes once all the faults have been acknowledged.
Figure 5-9 Fault screen
You can use F5 Ack. to acknowledge a stored fault.
Figure 5-10 Alarm screen
Alarms that are no longer active are removed from the alarm memory with F5 Clear.

Control via the operator panel
5.9 Saving the parameters permanently
Advanced Operator Panel 30 (AOP30)
48 Operating Instructions, 11/2017, A5E00331451A
Saving the parameters permanently
Description
If parameters are changed using the operator panel (confirm with OK in the Parameter
editor), the new values are initially stored in the volatile memory (RAM) of the drive. An "S"
flashes in the top right of the AOP display until they are saved to a permanent memory. This
indicates that at least 1 parameter has been changed and not yet stored permanently.
Two methods are available for permanently saving parameters that have been changed:
● To store the parameters permanently, choose <MENU> <Parameterization> <OK>
<Permanent parameter transfer>.
● When confirming a parameter setting with OK, press the OK key for more than 1 s. The
system displays a message asking you whether the setting is to be saved in the
EEPROM.
If you press "Yes", the system saves the setting in the EEPROM. If you press "No", the
setting is not saved permanently and the "S" starts flashing to indicate this fact.
For both options,
changes that have not yet been saved permanently are stored in the
EEPROM.
If a fault occurs when reading or writing parameters, a popup window containing the cause of
the problem is displayed.
The system displays:
Parameter write error (d)pxxxx.yy:0xnn
and a plain-text explanation of the type of parameterization error.

Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
49
Replacing the backup battery
Replacing the backup battery
Figure 6-1 Replacing the backup battery

Maintenance and servicing
6.1 Replacing the backup battery
Advanced Operator Panel 30 (AOP30)
50 Operating Instructions, 11/2017, A5E00331451A
1. Disconnect the 24 V DC power supply cable.
2. Disconnect the communication cable on the operator panel.
3. Open the cover of the battery compartment.
4. Remove the old battery.
5. Insert the new battery.
6. Carry out any other work by reversing the sequence.
Table 6- 1 Technical specifications of the backup battery
CR2032 3 V lithium battery
Service life (in backup mode) > 1 year at 70 °C; >1.5 years at 20 °C
Service life (in operation)
Note
Replace battery within one minute
The battery must be replaced within one minute to ensure that no AOP settings ar
Note
Battery disposal
The battery must be disposed of in accordance with the applicable country
guidelines and regulations.

Maintenance and servicing
6.2 Downloading new operator panel firmware from the PC
Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
51
Downloading new operator panel firmware from the PC
Description
Firmware might need to be loaded to the AOP if the AOP functionality needs to be upgraded.
If, once the drive has powered up, the memory card is found to contain a newer version of
the firmware, a message will appear on the AOP30 prompting you to load the new firmware.
You should click "YES" in response to this prompt.
The firmware will then be loaded automatically on the operator panel and the following dialog
screen will appear.
Figure 6-2 Dialog screen: loading firmware
If the firmware cannot be loaded successfully, it can be loaded using the following manual
method.
The load program LOAD_AOP30 and the firmware file can be found on the CD.
1. Establish the RS232 connection from the PC to the AOP30.
2. Provide the supply voltage (24 VDC).
3. Start the LOAD_AOP30 program on the PC.
4. Choose the PC interface (COM1, COM2).
5. Choose and open the firmware (AOP30.H86).
6. Follow the instructions in the status window of the program and connect the power supply
for the AOP30 while pressing the red key (O).
7. The load procedure is started automatically.
8. Switch the power on (switch the power supply off and then back on).

Maintenance and servicing
6.2 Downloading new operator panel firmware from the PC
Advanced Operator Panel 30 (AOP30)
52 Operating Instructions, 11/2017, A5E00331451A

Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
53
Table 7- 1 Technical specifications
24 V DC (20.4 V to 28.8 V)
Current requirements
- Without backlighting
- With maximum backlighting
RS232 interface, PPI protocol
Storage and transport temperature
Degree of protection IP20 (inside cabinet)
IP55 (outside cabinet)
Certification cULus
Product standard EN 61800-5-1
Dimensions Information on this can be found in the "Mechanical installa-

Technical specifications
Advanced Operator Panel 30 (AOP30)
54 Operating Instructions, 11/2017, A5E00331451A

Advanced Operator Panel 30 (AOP30)
Operating Instructions, 11/2017, A5E00331451A
55
Acknowledge error from the AOP, 44
AOP
Setpoint ramp-down time, 43
Setpoint ramp-up time, 43
Starting setpoint, 43
AOP setpoint, 43
CDS changeover via AOP, 44
Changing the language, 40
Decrease Key, 42
Downloading the firmware (operator panel), 51
LOCAL/REMOTE key, 41
Lock AOP LOCAL Mode, 44
Menu
AOP diagnostics, 38
AOP30 settings, 31
Basic Commissioning, 28
Battery status, 38
Battery symbol, 38
Commissioning / service, 28
Complete commissioning, 28
Control settings, 31
Curve recorder, 29
Curve recorder settings, 34
Database contents, 38
Database statistics, 40
Database version, 38
Date format, 36
Define operation screen, 31
Device commissioning, 29
Display settings, 31
DO name display mode, 37
Drive commissioning, 28
Drive diagnostics, 29
Fault/alarm memory, 27
Keyboard test, 39
LED test, 40
Motor identification, 29
Operation screen, 25
Reset AOP settings, 37
Reset fan operating time, 29
Scaling to motor current, 37
Screenshots, 39
Setting the date, 35
Setting the time, 35
Software Version, 38
Sprachauswahl/Language selection, 40
Structure, 24
OFF Key, 41
ON Key, 41
Operation screen, 25
Operator input inhibit / parameters inhibit key, 45
Operator panel
Overview, 23
Parameterization errors, 48

Index
Advanced Operator Panel 30 (AOP30)
56 Operating Instructions, 11/2017, A5E00331451A
Safety instructions
General safety instructions, 5
Saving the parameters permanently, 48
Switching between clockwise and counter-clockwise
rotation, 42