Siemens ALCC Installation Instructions Manual

Page 1
Installation Instruct ions Model ALCC
Audio Level Conversion Card
INTRODUCTION The Model ALCC from Siemens Industry, Inc., is an
Audio Level Conversion Card that contains two audio channels. Each channel is capable of accepting speaker­level audio at 70VRMS from Siemens amplifier models ZAC-30 (MXL) and ZAC-40 (XLS/Desigo Fire Safety Modular/Cerberus PRO Modular). There is a single output channel of line-level audio for connection to the AIC (Audio Input Card).
The ALCC adds system-wide live emergency paging capability to networked XLS/Desigo Fire Safety Modular/Cerberus PRO Modular Voice systems as well as an all-call function for XLS/Desigo Fire Safety Modular/Cerberus PRO Modular-based MXL/XLS/ Desigo Fire Safety Modular/Cerberus PRO Modular hybrid systems. Located on the receiving end in up to 63 remote XLS/Desigo Fire Safety Modular/Cerberus PRO Modular nodes, the ALCC converts the audio signal generated by the amplifiers located in the primary and secondary paging stations into a form that is compatible with AICs located in the remote stations.
The ALCC is transparent to the host system. As such, it supports all styles of wiring supported by ZAC-40 (XLS/ Desigo Fire Safety Modular/Cerberus PRO Modular) as well as ZAC-30 (MXL) amplifiers. It provides supervision by constantly monitoring its two audio channels, reporting faults both visually and through the down­stream AIC. Furthermore, the ALCC contains audio detection and channel selection circuitry that prioritizes incoming audio, enables the appropriate channel, closes the AIC audio active contact, or cuts the output of the ALCC to generate an AIC trouble, depending on the presence of incoming audio or circuit faults. Finally, all XLS/Desigo Fire Safety Modular/Cerberus PRO Modular functions are configured in the Zeus program­ming tool via standard logic functions with no need for special software or hardware upgrades.
ALCC
POWER
PRIMARY SELECTED
SECNDRY SELECTED
SECONDARY CHANNEL
ACTIVE
FAULT
FAULTTEST
+
GAIN
_
PRIMARY CHANNEL
ACTIVE
FAULT
FAULTTEST
+
GAIN
_
Figure 1 ALCC Speaker Line Output Card
Features
P/N 315-050263-3
Two isolated audio channels, 70VRMS input from ZAC-30 (MXL) or ZAC-40 (XLS/Desigo Fire Safety Modular/Cerberus PRO Modular) amplifiers.
Single channel output to the AIC, 0.775VRMS.
±6dBu output adjustment capability, independent for each channel.
Up to 63 ALCCs on a single audio riser.
Building
Siemens Siemens
Siemens
Siemens Siemens
TT
ecec
hnologies Dihnologies Di
T
ec
hnologies Di
TT
ecec
hnologies Dihnologies Di
IndustryIndustry
Industry
IndustryIndustry
visionvision
vision
visionvision
,,
Inc. Inc.
,
Inc.
,,
Inc. Inc.
Page 2
Visually indicated input channel prioritization control logic based on audio activity and fault detection.
Audio path supervision for both channels, reported visually by LEDs and to the system by the AIC audio input supervision circuitry.
All-analog circuitry makes the ALCC completely transparent to the overlying system structure.
OPERATION The ALCC provides the capability of conducting a global emergency page across
multiple remote XLS/Desigo Fire Safety Modular/Cerberus PRO Modular nodes, up to 63 nodes per audio riser. The emergency page originates at an XLS/Desigo Fire Safety Modular/Cerberus PRO Modular or MXL global paging station, where it is broadcast at 70VRMS over an audio riser by a ZAC-40 (XLS/Desigo Fire Safety Modular/Cerberus PRO Modular) or ZAC-30 (MXL) amplifier. A single remote XLS/ Desigo Fire Safety Modular/Cerberus PRO Modular node contains one ALCC, which steps the incoming speaker-level audio down to line-level audio that is compatible with the AIC audio input (0.775VMRS, independently adjustable to ±6dBu). The AIC digitizes the audio, which is subsequently transmitted by a DAC-NET to local amplifier(s) for broadcast over the local speaker zones. The ALCC incorporates two independent audio channels and is therefore capable of supporting two global paging stations. In case of a simultaneous page, the ALCC control logic prioritizes the primary channel over the secondary channel. On-board audio detection circuitry monitors the audio risers for incoming audio, while supervision circuitry reports any issues with the audio path via front-accessible LEDs, and, if necessary, disconnects its output from the AIC input, causing a trouble to be reported to the system. The ALCC relies on the originating amplifier for supervision of the audio risers, and on the AIC for supervision of the connection to the ALCC. Since the AIC monitors the presence of signal on its audio input, it is responsible for reporting audio path faults to the XLS/Desigo Fire Safety Modular/Cerberus PRO Modular system.
The ALCC contains no digital circuitry and integrates seamlessly into the existing XLS/Desigo Fire Safety Modular/Cerberus PRO Modular framework, as it is com­pletely transparent to the overlying system structure.
Refer to the ALCC Usage Restrictions on page 8.
Controls and Indicators The following table contains a description of LED indicators visible through the front
bezel of the ALCC:
DELROLOCETATS"NO"ROFSETON
REWOPneerG.derewopsiCCLAehTekaM.derewoptonsiCCLAehT
YRAMIRP
EVITCA
EVITC
A
YRAMIRP
DETCELES
DETCELES
YRAMIRP
TLUAF
TLUAF
neerGehtnooiduafoecneserpsetacidnI
YRADNOCES
neerGehtnooiduafoecneserpsetacidnI
neerGdecruossiCCLAehtfotuptuoehT
YRADNOCES
neerGdecruossiCCLAehtfotuptuoehT
wolleYyramirpehtnotneserpsitluafA
YRADNOCES
wolleYyra
.
resiryramirp
.resiryradnoces
.resiryramirpehtmorf
.dracehtotrewop
.dracehtotrewop
2-CC/5-CC
.detcepxesioidua
.detcepxesioidua
.resiryradnocesehtmorf
eh
tgnilcycyrT.lennahcoidua
dnocesehtnotneserpsitluafA
ehtgnilcycyrT.lennahcoidua
.lanoitcnuf
.la
noitcnuf
ETATS"FFO"ROFSETON
ideggulpsidracerus
CLAehtfotuptuoehT
.resiryramirpehtmorf
fI.ylreporpn
,21-CSPnoeruliafrofkcehc,os
ehtnooiduafoecnesbasetacidnI
figniriwresirkcehC.resiryramirp
ehtnooiduafoecnesbasetacidnI
figniriwresirkcehC.resiryradnoces
decruossiC
.resiryradnocesehtmorf
decruossiCCLAehtfotuptuoehT
yllufsilennahcoiduayramirpehT
yllufsilennahcoiduayradnocesehT
Siemens Industry, Inc. Building Technologies Division
P/N 315-050263-32
Page 3
The following table contains a description of controls accessible through the front bezel of the ALCC:
EMANEPYTNOITPIRCSED
NIAG1LENNAHC
TNEMTSUJDA
NIAG2LENNAHC
TNEMTSUJDA
1LENNAHC
TSETTLUAF
2LENNAHC
TSETTLUAF
retemoitnetoP
retemoitnetoP
hctiwSyratnemoM
hc
tiwSyratnemoM
wteblennahc
lennahc
.ylnoesuyrotcaF
.ylnoesuyrotcaF
yramirpCCLAehtfotuptuoehtstsujdA
.uBd6+dnauBd6-nee
yradnocesCCLAehtfotuptuoehtstsujdA
.uBd6+dnauBd6-neewteb
.tsettluaflennahcyramirpCCLA
.tsettluaflennahcyradnocesCCLA
INSTALLATION The ALCC plugs perpendicularly into a CC-2 or CC-5 slot via two 96-pin DIN connec-
tors and can occupy any slot in the card cage.
Slide the ALCC card into the card guides front bezel up, until the card edge connec­tors contact the motherboard receptacles. The LEDs, test buttons, adjustment potentiometers, and the legend should be visible and accessible.
Verify that the card edge connectors align properly with the motherboard receptacles. There is only one correct way to plug in the card. If it does not align, DO NOT FORCE the card.
Figure 2 Installing The ALCC
WIRING
Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the card until the connectors plug firmly into the motherboard receptacles. Secure the ALCC to the card cage with captive screws.
Power up the system and verify that the ALCC power LED turns ON.
For all versions of Zeus earlier than 7.0, the ALCC is not an option under CC-5 or CC-2. As a result, such proper­ties as card cage slot availability and battery / power supply current draw must be accounted for manually in those Zeus versions prior to 7.0.
It is recommended to install the ALCC in a slot adjacent to the AIC.
Remove all system power before installation, first battery then AC. (To power up, connect the AC first, then the battery.)
All field wiring of the ALCC is connected to the CC-2/CC-5 terminal blocks located above and below the card cage slot, in which it is installed.
To connect external wiring:
1. Loosen the screw of the terminal by turning it counterclockwise.
2. Insert the wire into the side of the terminal block.
3. Tighten the screw of the terminal block by turning it clockwise.
Siemens Industry, Inc. Building Technologies Division
P/N 315-050263-33
Page 4
Figure 3 is an example system diagram of an XLSV/Desigo Fire Safety Modular/
e
Cerberus PRO Modular network with both MXL (primary) and XLSV/Desigo Fire Safety Modular/Cerberus PRO Modular (secondary) global paging stations.
PRIMARY GLOBAL PAGING STATION SECONDARY GLOBAL PAGING STATION
PRIMARY AUDIO RISER
LED LED switch
ZAC-30 or EL-410D
VSM-1
ZAC-30
EOLR
NIM-1W
XNET
(not required for
global paging from
an MXLV head end )
OCC-1
ACM-1
PRIMARY AUDIO RISER
MXLV
ZAC-40
NIC-C
DAC-NET
AIC
ALCC
XNET
SECONDARY AUDIO RISER
XNET
ZAC-40 or ZAM-180
LVMMMM-1
AUDIO AUDIO PRESENT
CONTACT
SCM-8
LED LED switch
LED LED switch
EOLR
XLSV/Desigo Fir Safety Modular/ Cerberus PRO Modular
PRIMARY AUDIO RISER
PRIMARY AUDIO RISER
SECONDARY AUDIO RISER
SECONDARY AUDIO RISER
ALCC
ALCC
AIC
AIC
REMOTE PAGING STATION WITH EXTERNAL CABINET
HNET HNET
EOLR EOLR
XLSV/Desigo Fire Safety Modular Cerberus PRO Modular
DAC-NET
EOLR
switch
XLSV/Desigo Fire Safety Modular/ Cerberus PRO Modular
DNET
NIC-C
XNET
NIC-C
switch
LED LED
NIC-C
ZAC-40 or ZAM-180
LVM
(local page only)
AUDIO AUDIO PRESENT CONTACT
REMOTE PAGING STATION
LED LED
DAC-NET
ZAC-40 or ZAM-180
LVM
AUDIO AUDIO PRESENT CONTACT
(local page only)
DAC-NET
switch
LED LED
NIC-C
ZAC-40 or ZAM-180
XLSVR/Desigo Fire Safety Modular/ Cerberus PRO Modular
LVM
(local page only)
Figure 3 ALCC Example System Wiring
Siemens Industry, Inc. Building Technologies Division
P/N 315-050263-34
Page 5
Figure 4 illustrates redundant audio riser wiring for global paging applications that use
T
the ALCC.
XLSV/Desigo
Fire Safety
Modular/
Cerberus
PRO
Modular
PRIMARY GLOBAL
PAGIN G STATION
ZAC-40
ZAC-40
PRIMARY AUDIO RISER #1
PRIMARY AUDIO RISER #2
SECONDARY AUDIO RISER #1
SECONDARY AUDIO RISER #2
SECONDARY GLOBAL
XLSV/Desigo
Fire Safety
Modular/
Cerberus
PRO
Modular
PAGIN G STATION
ZAC-40
ZAC-40
Siemens Industry, Inc. Building Technologies Division
ALCC
AIC
ALCC
REMOTE PAGING STATION
Figure 4 ALCC Redundant Audio Riser Diagram
XLSV/Desigo
Fire Safety
Modular/
Cerberus
PRO
Modular
SECONDARY RISER AUDIO SECONDARY PRESENT CONTAC
PRIMARY RISER AUDIO PRIMARY PRESENT CONTACT
P/N 315-050263-35
Page 6
NOTES ALCC terminals 1, 2, 4, and 5:
1. Install the ALCC and the AIC in adjacent slots of a CC-5 / CC-2.
2. Audio connection on terminals 1 and 2 is supervised; the dry contact connection on terminals 4 and 5 is not supervised.
3. 18AWG min., 12AWG max. unshielded twisted pair (UTP).
4. Audio connection on terminals 1 and 2 is rated for maximum (+15dBu (4.34VRMS) into 600 Ohms).
ALCC terminals 17 – 24:
1. Supervised and power limited.
2. 18AWG min., 12AWG max. Use shielded or unshielded twisted pair (STP or UTP).
3. If using shielded cabling, terminate shields at one end only.
4. 80 ohms max. per riser, 70VRMS, 40W max., supervised, power limited.
5. Line capacitance is 0.33 μF Line to Line, 0.66 μF Line to Ground max. for each audio riser.
6. Parallel wiring (T-tapping) is not allowed.
7. All ALCC audio riser wiring is rated power limited and should be wired in accordance with applicable codes.
8. The ALCC supports both Class A and Class B audio riser wiring. Refer to Figure 6 for details.
Figure 5 outlines the input and output connections of the ALCC and the relevant input connections of a nearby AIC. Please refer to AIC Installation Instructions, P/N 315-035300, for details on AIC wiring.
In order to ensure correct wiring of the audio riser, please follow the installation instructions for the respective originating amplifiers being used in the global paging stations. All amplifier specifications, such as the style and class of wiring or the values of EOL resistors, remain in effect. Please note that the ALCC has been designed exclusively for use with one of the following amplifiers: ZAC-40 (XLS/ Desigo Fire Safety Modular/Cerberus PRO Modular) or ZAC-30 (MXL).
Make sure the amplifiers’ outputs are set to 70VRMS. Please refer to the ZAC-40 Installation Instructions, P/N 315-035400, or the ZAC-30 Installation Instructions, P/N 315-092960, as appropriate.
Do not adjust the volume on the AIC. Use the ALCC volume adjustment potentiom­eter to adjust volume for each channel independently.
AUDIO ACTIVE DRY CONTACT -
AUDIO ACTIVE DRY CONTACT +
AUDIO OUT -
AUDIO OUT +
DO NOT USEDO NOT USE
12345678
910111213141516
DO NOT USE
AIC
ONE SLOT OF CC-2 / CC-5
17 18 19 20 21 22 23 24
DO NOT USE
PRIMARY AUDIO RISER
SECONDARY AUDIO RISER
POWER LIMITED
POWER LIMITED
AUDIO IN
+IN
+OUT
-IN
-OUT
+IN
+OUT
-IN
-OUT
12345678
910111213141516
DO NOT USE
ALCC
ONE SLOT OF CC-2 / CC-5
17 18 19 20 21 22 23 24
Figure 5 ALCC Wiring
Siemens Industry, Inc. Building Technologies Division
P/N 315-050263-36
Page 7
GLOBAL PAGING
STA TION
ZAC-40
(XLS/Desigo
Fire Safety
Modular/
Cerberus PRO
Modular)
or
ZAC-30
(MXL)
CLASS A
EOLR
68k OHMS
CLASS A ONLY
AUDIO RISER (CLASS A and CLASS B)
CLASS B
EOLR
68k OHMS
LAST
ALCC
FIRST
ALCC
Figure 6 ALCC Class A and Class B Wiring Diagram
Siemens Industry, Inc. Building Technologies Division
P/N 315-050263-37
Page 8
ELECTRICAL RATINGS
REWOPTUPNI
tnerruCenalPkcaBV42Am531
tnerruCV42lanimreTwercS0
tnerruCenalPkcaBV2.6Am01
tnerruCybdnatSV42Am59
The back plane and screw terminal currents represent the absolute maximum currents that are consumed by the ALCC in the worst case operating condition. These currents are used only for power supply loading calculations. The standby current represents the current consumed from the 24V battery by the ALCC in the quiescent standby mode. This current is used in the battery size calculation.
USAGE RESTRICTIONS For UL and ULC approved product the following usage restrictions apply:
a. The ALCC cannot be used with the Fireman’s Master Telephone (FMT) or
the Telephone Zone Card (TZC-8B) as the source of paging audio.
For UL approved product the following usage restrictions apply:
a. The maximum power of the ZAM-180 amplifier using the ZAC-40 (XLS/
Desigo Fire Safety Modular/Cerberus PRO Modular) as the ALCC paging source is limited at 170W.
b. The maximum power of the ZAM-180 amplifier using the ZAC-30 (MXL) as
the ALCC paging source is limited at 160W.
For ULC approved product the following usage restrictions apply:
a. The maximum power of the ZAM-180 amplifier using the ZAC-40 (XLS/
Desigo Fire Safety Modular/Cerberus PRO Modular) as the ALCC paging source is limited at 165W.
b. The ZAC-30 (MXL) is not allowed as the ALCC paging source.
Cyber security disclaimer
Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept.
It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is customized to individual security needs. Such a security concept may result in additional site-specific preventive action to ensure that the building comfort, fire safety , security management or physical security system for your site are operated in a secure manner. These measures may include, but are not limited to, separating networks, physically protecting system components, user awareness programs, defense in depth, etc.
For additional information on building technology security and our offerings, contact your Siemens sales or project department. We strongly recommend customers to follow our security advisories, which provide infor­mation on the latest security threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security-advisories.htm
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
Siemens Canada, Ltd. 1577 North Service Road East Oakville, Ontario L6H 0H6 Canada
Document ID A6V10248630
P/N 315-050263-3