Siemens AEROGYR RWI65.01 User Manual

Page 1
205
3
AEROGYR™
Controller RWI65.01
for cental air handling SW version 3.3
. . . .
Use
Plants
Regulating units and actuators
Operating voltage AC 24 V, signal voltage DC 0-10 V; all control and monitoring functions in one unit; major control tasks: temperature control, compensation, cascade control with minimum/maximum limitation of supply air temperature, control of d.h.w. circuit; Connection to Landis & Staefa building automation systems by means of communication cards
Ventilating and air conditioning plants with:
Hot water or electric air heater batteries
Direct expansion cooler batteries or chilled water cooling
Valve and air damper actuators
Control units for thermal wheel type heat exchangers
Step switches for chillers and electric air heater batteries
Current valves for electric air heater batteries
Regulating units for heating, cooling or heat recovery
Auxiliary units for chillers or circulating pumps and fans
Signal converters for pneumatic/electric two- or three-position signals
Signal doublers and signal inverters
POLYGYR
UNIGYR
®
(DC 0...10 V compatible)
®
(DC 0...10 V compatible)

Accessories

Siemens Building Technol ogi es CM2N3205E / 05.2001 Landis & Staefa Divisi on 1/18
Name Type reference Remarks FLN Communication card AZI65.1
LON/BACnet Communication card AZI65.2 LPB Communication card AZI65.3 Instructions set (de, fr, it) ARG65.40 Instructions set (en, sv, fi, no) ARG65.41 Instructions set (nl, es, da) ARG65.42 Instructions set (cs, sk, hu, pl, ru) ARG65.46
1) Optional
2) Consists of operating c ard 2, operating instructions, and m ounting instructions
1)
1)
1)
2)
2)
2)
2)
see data sheet 3206 see data sheet 3207 see data sheet 3208 included, if ordered included, if ordered included, if ordered included, if ordered
Page 2

Ordering and delivery

When ordering the controller, please indicate the type reference RWI65.01. To ensure
the unit is supplied with the correct language version of the instructions, indicate the type reference of the instructions required, e.g., ARG65.41 (for English, Swedish, Finnish).
Communication cards must be ordered separately, e.g., AZI65.1.
Controllers and poss. communication cards are packed and supplied separately.

Equipment combinations

Functions

Control and monitoring
Name Type reference Data sheet Temperature sensor QAA24, QAA26 1721
QAM22..., QAE21.9..., 1771, 1792 QAE22… 1771, 1792, 1791 QAD22..., QAC22, 1801, 1811 QAA64 1722 QAF63.2, QAF63.6 1821
Remote setpoint transmitter QAA26 1721
FZA21.21, FZA61.11 3470, 3471
Signal source RVL55, 2602
PTM1.2Y10 8161
Temperature control
Compensation
Room/supply air temperature cascade control with minimum and maximum limitation
of the supply air temperature
Control of air heater battery's hot water circuit (active frost protection unit, maintained
temperature)
Control of up to three regulating units in sequence (plants with air dampers or heat
recovery)
Control functions for optimum use of energy (maximum economy changeover) can be
provided
Suitable for plants with the following operating actions:
2 x heating/heat recovery 1 x cooling
Switching on/off of plant through:
Direct control of units or enabling of switching commands via potential-free relay contacts
Enabling of circulating pump or electric air heater battery
Enabling of chiller (dx-cooling) or circulating pump
Monitoring of operational sequences and indication of operational statuses of factory
defined plant elements
Control of plant in the event of risk of frost
Indication and fault status signal from up to six predefined and two freely selectable
plant elements
Communication card
In large plants, the AZI65.1 communication card is used to facilitate the dialog between a central station and the plant. The dialog can be carried out either locally or via the network and comprises:
Registration of messages and alarms
Selection of operating modes and set values
Registration and graphic representation of actual values and statuses
Acquisition and evaluation of plant data
CM2N3205E / 05.2001 Siemens Building Technologies 2/18 Landis & Staefa Division
Page 3

Technical design

Control
Compensation
Automatic sensor identification (ASD logic), including type of sensor (active or pas-sive). Automatic activation of incorporated control functions owing to ACC logic which, through ASD, identifies the intended purpose of the control function. This means that the control will be optimally adapted to the plant. P-band and integral action time (TN) are separately adjustable, so that P-control (with integral action time = 0) or PI control can be selected.
The controller is supplied as a PI controller. The set values of heating and cooling can be adjusted separately. Overlapping of heating/ cooling sequences is not possible.
For the control of mixed air dampers or heat recovery equipment, both operating action and operating mode can be selected. The actual values of the various outputs are permanently displayed.
The following compensation functions can be implemented:
Outside temperature compensated controller set value. This function is integrated in
the controller. The parameters of compensation can be set
∆∆∆∆
[K]
w
6 5 4 3 2 1
Winter compensation
Sw
Ew
Fw
Summer compensation
Fs
Ss
Es
3205D12E
Temperature control
[°C]
TA
−20−15−10−5±
30
0 5 10 15 20 25 30 35
40
Compensation by means of an active or passive potentiometer, as an absolute set
value or as a set value shift
[K]
∆∆∆∆
w
Data point 45
Data point 44
+ 5
0
El
5 0
1000 1117 1235
510
Eh
Z3
Z3
3205D13E
[V]
[Ω]
Compensation across the entire setpoint range from an L&S building automation
system via a data bus (FLN bus or LON/BACnet bus) and communication card (AZI65.1 respectively AZI65.2)
Connection of a supply air temperature sensor (B2) automatically activates supply air
temperature control
Room/supply air temperature cascade control
Connection of room or extract air (B1) and supply air temperature sensors (B2)
automatically activates cascade control The output signal of the room/extract air temperature controller acts on the set value of the supply air temperature controller. This effect (standard value is preset) can be changed. Cascade control acquires disturbances in the supply air and offsets them before they have an impact on the room or extract air temperature. The limitation functions are not affected by the cascade.
Siemens Building Technol ogi es CM2N3205E / 05.2001 Landis & Staefa Divisi on 3/18
Page 4
Minimum and maximum limitation of the supply air temperature are automatically
activated
x
Z wZ
Heating mode
x
w
Z
Cooling mode
Z
3205D03E
Economizer operation
Y20
Y10 Y30
w
LH
w
Z
Z
w
H
w
LL
KE =
R
wHx
R
Z /
R KE = Z / R
x
R
Y20
Y10 Y30
w
LH
w
C
Z
w
Z
w
LL
w
x
C
R
Based on the measured difference of outside and extract air temperature, the plant is operated with reduced fresh air supply or heat recovery. Prerequisites for activation:
DIL switch 4 (economizer) set to OFF (=YES)
Outside and extract air temperature sensors connected
HR system
Y30
10
0
T
[V]
B4 < B1
2 K2 K
B4 > B1
T
Y30
10
min
Y30
0
[V]
Mixing dampers
[V]
Y30
10
B4 < B1
Y30
min
0
T
[V]
Y30
10
B4 > B1
0
T
00
x
R
3205D07E
Control sequences
Function diagram 1
The RWI65.01 allows control sequences with both operating actions for air dampers/heat recovery. The operating action is selected with DIL switches 5-7.
Application with mixing air dampers
[%]
Y
100
Y30
(DtPnt 6)
min
Y10 Y30
X T
n1
P1
X T
n3
P3
Y20
(DtPnt. 20)
SA
SD
(DtPnt 21)
X
P2
T
w
w
c
h
n2
T
3204D04E
CM2N3205E / 05.2001 Siemens Building Technologies 4/18 Landis & Staefa Division
Page 5
Function diagramm 2
Application with HR system
[%]
Y
Frost protection
100
Y10 Y30
X
P1
T
n1
X
T
n3
Y20
(DtPnt 20)
SA
SD
(DtPnt 21)
P3
w
w
c
h
X T
n2
P2
T
3205D05E
SA: Data point 20 "Switching interval" SD: Data point 21 "Switching differential"
For ventilating and air conditioning plants with hot water air heater batteries. Frost protection operation is selected with DIL switch 8 (water). Frost protection is used to
protect the air heater battery against freezing
facilitate plant startup at low outside temperatures
All parameters for frost protection are factory-set and can be changed: Response temperatures, set values, P-bands and integral action times. The frost protection concept functions with both kinds of temperature acquisi tion (in the water circuit or at the air heater battery's outlet). The protective actions are the following:
Continuous opening of heating valve, activation of circulating pump
Switching off the fan or closing the air damper
Maintaining the temperature when the fan is switched off (on the water side only)
Fault status signal in the event of risk of frost
To ensure frost protection, the use of the following sensors is required:
QAD22.../QAE21.9 for temperature acquisition in the water circuit
QAF63... for temperature acquisition at the battery's outlet
Plant ON
Air-/water side
[ % ]
Y
100 100
00
w
w
½ X
2 K
Q23/Q24 Q13/Q14
T Temperature in air heater battery circuit or air temperature directly aft er t he air heat er bat t ery Q Load Y Manipulated variable Y10 Control command at heating valv e Q13/Q14 Relay output "Pump" Q23/Q24 Relay output "Fan/air damper" X
pd
X
pn
w
w
w
wn
Zt Min. running time of circulating pump (dat a point 52)
P-band "Frost protection controller" (data point 9) P-band "Standby controller" (data point 10) Frost alarm value (data point 7) Set value "Standby controller" (data point 8)
I
Y10(P) Y10(PI)
pd
X
pd
Zt
Water side Air side
[ % ]
Y
TQ
Plant OFF
w
wn
Zt
Q13/Q14
100
[ % ]
Y
Y10(P)
0
w
w
2K
Xpn
T
Zt
Q13/Q14
3205D14E
Siemens Building Technol ogi es CM2N3205E / 05.2001 Landis & Staefa Divisi on 5/18
Page 6
Control and monitoring
The RWI65.01 provides all control and monitoring functions mentioned above. Prerequisite: Correct configuration of the heat source (water or electric) with DIL switch 8.
Switching on of plant, provided:
Monitoring operation of plants that use hot water air heater batteries
Monitoring operation of plants that use electric air heater batteries
Operating mode is set to "Automatic" ( ) and timeswitch program of timeswitch is
set to "ON", or
Operating mode "Manual ON" ( I )
Continuous checkback signal of plant's and circulating pump's operational status,
based on the signals delivered by the monitoring elements such as flow switch and overcurrent protection
Switching off actions, depending on the selected alarm priority (A or b), and operating
mode as well as delays aimed at avoiding incorrect signals are adjustable
Permanent monitoring of frost protection
To save pump energy and to avoid damage to the pump:
Parallel output of heating and pump on command when there is a demand for heat
Pump kick, interval and minimum running time are adjustable
Activation of electric air heater battery only when there is a demand for heat and
when the monitoring elements are enabled
Continuous checkback signal of plant's operational status, especially that of the
electric air heater battery, based on the signals delivered by the monitoring elements such as flow switch or filter switch, thermal cutout or overcurrent protection
Switching off of plant elements, depending on the selected alarm priority (A or b)
Adjustable alarm delays for disturbances of filter or flow
Adjustable fan overrun times
Monitoring operation in refrigeration plants
Efficiency supervision of the heat recovery system
Time switch
Two possibilities of controlWith integrated ON/OFF command (Q20)With DC 0...10 V control signal via digital or binary step switches
Adaptation to compressor or heat pump operation by setting a switching interval and
a switching differential
Selectable pump kick for heat pump operation
Switching off of plant elements, depending on the selected alarm priority (A or b)
An additional sensor must be installed if this function is used. Three temperature values (temperature behind heat recovery, equipment, outdoor air and extract air temperature) are required to calculate efficiency. The calculated value is shown on the controller and it generates an alarm if it falls below an adjustable threshold value. To display data points 110 to 118, set DIL switch No. 2 to the left. The efficiency value acts as a fault indicator, for example, for defective, polluted or incorrectly connected heat recovery equipment. This function (display/alarming) is supported by the FLN integration solutions (AZI65.1 / UNIGYR, VISIONIK) and LON/BACnet (AZI65.2 / DESIGO 30). When this function is used, the Z-input is not available for other functions.
The timeswitch is a weekly time switch with programmable switching on/off times for every weekday. The switching on/off times can be reprogrammed at any time without having to readjust the time of day. The switching statuses are immediately adapted to the new switching on/off times. Summer/wintertime changeover: Depending on the season, one hour is either added to the actual time (display with a solid square = summertime) or subtracted from it. The time program is stored should a power failure occur - like all other settings.
. . . . . . . . . .
CM2N3205E / 05.2001 Siemens Building Technologies 6/18 Landis & Staefa Division
Page 7
Fault status signals
A
and indication
Legend
cknowledging the fault
status signal
The RW165.01 can acquire and process nine fault status signals from plant elements and plant statuses. When the front door is closed, the signals are shown in lines 9 and 10 of the display as follows:
1234
p
B9
E3
E2
I
E5
657
1 Frost danger supervision (signal input B9),
Display: 0 = normal, A or b = frost alarm.
2 Flow supervision (signal input B9)
Display: 0 = normal, 1 = start phase, A or b = flow fault.
3 Overload of refrigeration machine or chilled water circuit pump (signal input E4)
Display: 0 = Q20 cooling switched off, 1 = Q20 cooling switched on, A or b = cooling fault.
4 Open usage e.g. for filter supervis ion (s ignal input E7)
Display: 0 = normal, 1 = start phase, A or b = fault at E7.
5 Overload/overheating of circ ulat ing pum p or air heat er bat t ery (signal input E3),
Display: 0 = Q13/Q14 heater switched off, 1 = Q13/Q14 heater switched on, A or b = pump or air heater battery fault.
6 Overload fan (signal input E5),
Display: 0 = Q23 fan switched off, 1 = Q23 fan switched on, A or b = fan fault.
7 Fire/smoke supervision (signal input E1),
Display: 0 = normal, A or b = fire / smoke alarm.
8 Open usage (signal input E8),
Display: 0 = normal, 1 = start phase, A or b = fault at E8.
9 Heat recovery equipment efficiency supervision (signal input Z3)
Display: no pointer = normal, visible pointer = effic ienc y is below the set alarm thres hold
E4
E1
8 9
9
10
A 0 b 0
1 1 0
3205Z07
E7
E8
Depending on priority, fault status signals are indicated by a flashing "A" or "b" in the display (with efficiency supervision using pointer) and by a flashing red LED located on the acknowledge button on the unit front. At the same time, it is available as a centralized alarm at centralized alarm output F91 (priority A) or F 92 (priority b).
Fault status signal priorities (A or b) can be selected for inputs E1 to E5, E7, E8, B9 and Z3.
Status signal inputs E1 to E8 can be individually adapted to the contact state of the corresponding status signal element (normally closed or normally open).
Alarm delays to avoid false alarms can be selected for status signal inputs E2 and E7.
Any fault displayed can be acknowledged from the acknowledgment button on the unit front. When a fault is acknowledged, the priority display changes from flashing to steady and the centralized fault status signal at centralized alarm output F … is cancelled.
The display of a priority "b" fault status signal goes out when the signal is no longer present at the fault status signal input. When no other fault status signal is present at the fault status signal inputs, the display in the acknowledgment button changes from red to green.
The fault status signal indications (display and acknowledgment button) for a priority "A" fault can be cancelled by pushing the acknowledgment button again, as long as no other fault status signals with priority "A" are present.
The function flow diagrams at the end of this data sheet show how the fault status signals affect the RWI65 outputs.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Siemens Building Technol ogi es CM2N3205E / 05.2001 Landis & Staefa Divisi on 7/18
Page 8

Mechanical design

The controller consists of controller insert and base. The controller insert accommodates all operating elements and the electronic circuits. It is secured to the base by two screws which are designed such that they push the insert away from the base when they are loosened. The microprocessor with the memory, the associated electronic components, and the display are carried by one printed circuit board, the relays by another. Another board serves for communication and carries a specific microprocessor with the ass ociated interface. An EEPROM stores all setting values. In the event of a power failure, the setting values are thus retained for an almost unlimited period of time. The reserve for the weekly time switch (48 hours typically) is contained in the controller insert. For this reason, the insert can be removed without having an effect on the actual time setting. The base is made of plastic and is designed for both wall and flush panel mounting. In the case of flush panel mounting, the controller is secured by a clamp. The base carries four terminal blocks and a terminal strip for establishing the electrical connections with the controller insert.
Display, setting and operating elements
Legend
1 9 10 11
Set point heating Set point cooling Actual set point Min. supply air temp. Max supply air temp. Day Start time Stop time
Data point number
Data point value
1 2 3 4 5 6 7 8 9
10
3205Z04E
32 4 567 8
1 Front cover 2 Operating card 1 (for operating level 1) and operating ins t ruc t ions 3 Opening for acknowledgement of fault when front cover is closed 4 Connection facility for local network 5 Indicator lamp for plant status (ON/OFF) 6 Indicator lamp and acknowledge button for fault stat us s ignals 7 Setting buttons 8 Keyhole for opening the front cover (key enclos ed) 9 Covering plate with operating card 2 (for operating levels 2 and 3) 10 Display with 10 lines 11 Function buttons
Operation with front cover closed (operating level 1)
When the front cover is closed, the display shows (from top to bottom): Selection of operating mode (solid square), manipulated variables, temperatures, weekday, time of day, and status information. The following setting choices exist (if enabled): Selection of operating mode (automatic, on, standby), weekday, and summer- or wintertime.
Y 10
1
I
Landis & Staefa RWI65.01
B9E3E2E5E4E1E7
CM2N3205E / 05.2001 Siemens Building Technologies 8/18 Landis & Staefa Division
Y 20
2
Y 30
3
I
T
4 5
I
T
T
6
1...7
2
∆∆∆∆
P
I
7
+1h
8 9
10
E8
RWI65.01 with front co ver closed
3205Z16
Page 9
Operation with front cover open (operating levels 2 and 3)
After opening the front cover, operating card 2 can be accessed: The 10 lines on the front (operating level 2) show the setting and measuring choices available for operation. The values can be readjusted when operating level 2 is active. By simultaneously pressing the two function buttons at the bottom (lines 9 and 10), the third operating level can be activated, which is used for service purposes. This operating level facilitates access to switching data and manipulated variables (service settings). The reverse side of operating card 2 contains appropriate information. By closing the front cover, operating level 1 is automatically reactivated.
Configuration of controller with DIL switches
The DIL switches used for the configuration of the controller are located underneath the covering plate. To check or change settings, the front cover must be opened and the covering plate removed.
8
7
6
5
8 7 6 5 4 3 2 1
4
3
2
1
Y30
Y30 Y1 0
Y30 Y30
Test Run
Y30
Y10 Y30
1 2 3 4 5 6 7 8 9
10
Front cover and covering plateremoved
3205Z11
Positions of DIL switches as supplied
(all switches in OFF position, meaning given in bold letters): 8 Type of heating ELECTRIC / WATER 7 Sequence Y30 active NO / YES 6 Order Y30 COMFORT / ECONOMY 5 Operating action Y30 INVERTED / NORMAL 4 Economizer Y30, NO / YES
Max. ECO changeover, heat recovery
3 Not used
2 Display "Heat recovery equip-
ment efficiency supervision" YES / NO
1 Test mode YES1) / NO
. . .
1) For factory settings only
Communication cards AZI65...
The RWI65.01 can communicate with an active bus device (master) with the aid of – the FLN (Floor Level Network) communication card AZI65.01 or – the LON/BACnet (Local Operating Network with BACnet protocol) communication
card AZI65.02 or
– the LPB (Local Process Bus) communication card AZI65.03 Each card contains the electronic circuits required for communication.
The compartment be-comes accessible after opening the front door and removing the cover. The communication card slides into its compartment in grooves.
Fitting the FLN communication card in the RWI65.01 requires no re-commissioning, but only bus registration for data exchange on the network.
Siemens Building Technol ogi es CM2N3205E / 05.2001 Landis & Staefa Divisi on 9/18
Page 10
7
6
5
4
3
2
1
8 7 6 5 4 3 2 1
Y30
Y30 Y10
Y30 Y30
Test Run
Y30
Y10 Y30
18
2 3 4 5 6 7 8 9
10
3205Z17
Recyclability, environ­mental protection, operating safety

Engineering notes

Installation notes

80 % of the plastics used can be recycled. The unit uses a supercapacitor in place of NiCd batteries which need to be replaced every two years - also for the benefit of operating safety and environmental protection.
The operating voltage required to power the controller is AC 24 V. The transformer used must be suitable for safety extra low voltage, 100 % duty, and must have separate windings.
Terminals Q13/Q14 and Q23/Q24 must not be used with different nominal voltages Fuses, switches, wiring and earthing must be in compliance with local regulations.
The limitations cannot be used as safety functions. These always require separate safety devices. All important variables that are required for commissioning are to be shown on the plant documentation (wiring diagram, etc.), if known at the time of planning.
The controller is designed for wall mounting (in an open space or a control panel) or flush panel mounting (control panel front, console, etc.). The permissible ambient conditions must be observed. First, the base is to be mounted and wired up. The cables inside the base are to be accommodated such that the insert can be easily fitted. Secure fixing screws only after commissioning.

Commissioning notes

Aids
Settings
Recommendation
CM2N3205E / 05.2001 Siemens Building Technologies 10/18 Landis & Staefa Divisi on
For commissioning and operation, refer to the operating instructions supplied with the controller. When commissioning the plant, all functions of the controller and the communications card (if fitted) are to be checked. Separate preselection of all switching and position outputs can be made at the service level (provided operating level 3 is active). All actual values and remote operation signals can be called up.
The controller is supplied with all control functions and parameters factory-set. Where required, it needs to be configured for various logic functions, e.g. with electric heating, where certain safety measures must be observed. Changing the configuration or data settings: By means of inbuilt DIL switches. Changing the values: With function buttons at the operating level. Any change is immediately saved when acknowledgement is made (when the display stops flashing).
Note changed values on the reverse side of the operating instructions (folded sheet).
Page 11
Operating and
A
A
maintenance notes
Selection of the operating mode and time and weekday settings can be blocked when the front cover is closed. Various operational faults are identified and indicated by the controller.
Setting aid

Technical data

Power supply
Inputs
Digital inputs E1.. .E8
nalog inputs
B1, B2, B4, B9, Z
Outputs
nalog outputs
Y10, Y20, Y30
Relay outputs Q13/Q14, Q23/Q24
Relay output F91, F92
Degree of protection
Environmental conditions
Standards
Product standards
Electromagnetic compatibility
conformity as per
Miscellaneous
Note changed values on the reverse side of the operating instructions (folded sheet).
Operating voltage AC 24 V ±20 %
Safety extra-low voltage (SELV) as per EN 60 730
External transformer (100 % duty) as per EN 60 742 Fusing of supply line (external) 10 A max. Frequency 50 Hz or 60 Hz Power consumption 10 VA
Voltage at open input DC 20...23 V
Logic 0
Logic 1 Current at "Logic 0" 9 mA Perm. line lengths with copper 1.5 mm
Sensors
Passive LG-Ni1000
Active DC 0...10 V
Measuring range 50...+150 °C
Perm. line lengths with copper 1.5 mm Setpoint transmitter
Passive 1000...1235
Active DC 0...10 V
Setting range 50...+150 °C
Perm. line lengths dep. on transmitter t ype
Output voltage DC 0...10 V Output current Max. load sustained short-circ ui t
Switching capacity, vol t age AC 19 V min., 265 V max. Switching capacity, c urrent at AC 19 V 20 mA min., 4 A / 3 A Switching capacity, c urrent at AC 265 V 5 mA min., 4 A / 3 A
Switching capacity, vol tage DC 5 V min., AC 42 V Switching capacity, c u rrent 100 mA min., 1 mA max.
Protection class III as per EN 60 730 Housing protection
when mounted on a flat wall IP 40 as per EN 60 529
when mounted in a control panel front
Casing IP 40 as per EN 60 529 Base IP 20 as per EN 60 529
Operation as per IEC 721-3-3
Climatic condit i ons clas s 3K5
Temperature 5...+50 °C Humidity (non-condensing)
Transport as per IEC 721-3-2
Climatic condit i ons clas s 2K3
Temperature Humidity
Mechanical conditions class 2M2
Automatic elec t ri c controls
for household and similar use EN 60 730 Emissions as per EN 50 081-1
Immunity as per EN 50 082-2 EMC directives 89/336/EEC
Low voltage directive 73/23/EEC Reserve in the event of a power failure 48 h (typical)
Connection terminals f or wires 2 x 1.5 mm Weight (incl . packaging) 1.17 k g
1) at cos ϕ = 0.6
2) SELV as per EN 60 730
2
2
<DC 1 V >DC 5 V
300 m max.
200 m max.
±1 mA max.
<95 % r.h.
25...+70 °C <95 % r.h.
1)
1)
max.
2)
2
or 1 x 2.5 mm
max.
max.
2
Siemens Building Technol ogi es CM2N3205E / 05.2001 Landis & Staefa Divisi on 11/18
Page 12

Internal diagram

GM
B4 B9 Z3 GE E1 E2 E3 E4 E5 E6 E7 E8
B1 B2
Q13
Q23
AZI65...
G0
G AC 24 V operating voltage (system potential) G0 AC 24 V operating voltage (system neutral)
M Measuring neut ral B1 Measuring signal from room or extract air temperat ure s ensor (LG-Ni1000 Ω / DC 0...10 V) B2 Measuring signal from supply air temperature sensor (LG-Ni1000 Ω / DC 0...10 V) B4 Measuring signal from outside sensor (LG-Ni1000 Ω / DC 0...10 V) B9 Measuring signal from frost protect ion unit (LG-Ni1000 Ω / DC 0...10 V) Z3 Compensating signal from peripheral equipment (1000...1225 Ω / DC 0...10 V)
Y10 DC 0...10 V control signal for heating Y20 DC 0...10 V control signal for cooling Y30 DC 0...10 V control signal for heat recovery/m ixed air dam pers Q20 AC 24 V control signal for compressor, dx-cooling or circulat ing pum p
Q13, Q14 Potential-free relay contact t o s witch circulating pum ps or an elec t ric air heat er bat t ery Q23, Q24 Potential-free relay contacts to switch fans
GE Signal voltage neutral for digitals stat us input s E1 Digital signal input "Fire/smoke" E2 Digital signal input "Disturbed flow" E3 Digital signal input "Circulating pump/electric air heater batt ery" E4 Digital signal input "Common falut signal form chiller" E5 Digital signal input "Fan, overcurrent" E6 Digital signal input "Extended operation" (with automatic operation only E7 Digital signal input, freely available E8 Digital signal input, freely available
GF Signal voltage neutral for common fault status signals (AC/DC 5...42 V) F91 Common fault signal according to alarm priority A (AC/DC 5...42 V) F92 Common fault signal according to alarm priority b (AC/DC 5...42 V)
UN, UP Terminals (2...3) for communication Note: LG-Ni1000 sensors = Landis & Staefa standard
Q20
GFY10 G GY20 GY30
UP UN
F91
F92
Q14
Q24
3205G01

Connection diagrams

Connections on the measuring side
Connection diagramm 1: Measuring part for tem­perature with passive main and auxiliary sensors
Connection diagramm 2: Connection of an active remote setting unit
Legend to connection diagrams 1 and 2
G
BM
G
B1
MB4B9
Y10 Y20 Y30G0
G0
G
G
G0
N1 Controller RWI65.01 B1 QAA23/QAM22 room or extract air temperature sensor B2 QAM22 supply air temperature sensor B4 QAM22/QAC22 outside sensor B9 QAD22.../QAE22... R1 FZA61.11 remote setting unit
MB2 Z3
B1
Y10 Y20 Y30G0
MMMBBB
B1
B2 B4 B9
B2 M M M
B4 B9
GG0
Y9
G0
R1
3205A02
N1
3205A04
N1
CM2N3205E / 05.2001 Siemens Building Technologies 12/18 Landis & Staefa Divisi on
Page 13
Connection diagram 3: Connection of outside temperature signal from a signal source other than the QAM22/QAC22 and an active frost protection sensor
G
G0
G0
G
BM
B1
B1
MB2 B4 B9
Y10 Y20
U4 M
B2
MMM
N2 B9
Y30
G BMBM
3205A03
N1
Connection diagram 4: Connection of a passive remote setting unit
Connections on the control side
Connection diagram 5
Connections on the control and monitoring side
Connection diagram 6
G
G0
G
G0
L
G
AC 24 V
G
G0
R1
B2
B1
Y10 Y20 Y30G0
G
B1 M
GGGG0G0G0
GYRMG0GYRM
B4 B9MRZ3 M
B2 B4
Y10
U U U
Y20 Y30
GY
G0 G0
B9
RM
Y1 Y2 Y3
F1 F2
p
T
3205A05
N1
N1
3205A06
3205A07
DC/AC 5 ... 42 V
Note
Legend to connection diagrams 3 to 6
E7
GE E1 E2 E3 E4 E5 E6 Logic Center
AC 24 V
AC 230 V
AC 24 V
E8
Q20
GF
F91 Q24
Q13 Q23
F92 Q14
N1
F1 F2
H1 H2 H3
K1 K2
G0
N
The RWI65.01 allows selection of N.C. or N.C. contacts, depending on the requirements Terminals Q13/14 and Q23/24 must not be used with different nominal voltages!!
N1 RWI65.01 controller N2 RVL55 with AZY55.60 plug-in module (outside temperature signal) B9 QAF63... frost protection sensor F1, F2 Overload relay contacts H1 Auxiliary unit for circulating pump or signal for chiller H2 Auxiliary unit for common fault status priority A H3 Auxiliara unit for common fault status prorit y b K1 Contacts for circulating pump or electric air heater battery K2 Motor contactor for fan R1 FZA21.21 or QAA26 remote setting unit Y1 Regulating unit for heating Y2 Regulating unit for cooling Y3 Regulating unit for heat recovery / mixed air dampers
Siemens Building Technol ogi es CM2N3205E / 05.2001 Landis & Staefa Divisi on 13/18
Page 14

List of data points

Data point values and measured values can be called up as data under certain data point numbers. The factory setting of all values is such that the controller will meet the requirements of most plants. If necessary, they can be readjusted on an individual basis.

Nr. Descri ption Range Factory setting

Current measured values
Limitation of m a nipulated variables
Set values of frost protection/st a ndby cont roller
Parameters of frost protection / st a ndby controller
Control paramet e rs of room temperature controller
Control paramet e rs of supply air temperature controller
Switching points of compressor
Summer compensation
Winter compensation
Alarm priorities
Measuring ranges of active sensors
Measured value correction, sensor inputs
Time elements
Active level I/Os
Preselection sensor identification
1 B9 Frost temperature –50.0...+150.0 °C ----­2 Z3 Compensating variable –50.0...+150.0 °C ----­3 F91 Common fault relay A OFF / On ----­4 F92 Common fault relay b OFF / On ----­5 E6 Time channel
1)
OFF / On -----
6 Min. limitation Y30 0...100 % 0 %
7 Frost alarm value 2.. . 15 °C 5 °C 8 Set value "standby controller" 2...50 °C 25 °C
9 P-band "frost prot. controller" 1...30 K 5 K 10 P-band "Standby controller" 1...200 K 10 K 11 Integral action time "standby controller" 0.00...10.00 min 3.00 min
12 KE room (cascade effect) 0.1...20 2.0 13 Integral action time "room" 0.00...40.00 min 8.00 min
14 P-band "heating" 1...200 K 20 K 15 Integral act.time "heating" 16 P-band "HR" 1...200 K 15 K 17 Integral action time "HR" 18 P-band "cooling" 1...200 K 15 K 19 Integral act.time "cooling"
2)
2)
2)
0.00...10.00 min 2.30 min
0.00...10.00 min 2.00 min
0.00...10.00 min 2.00 min
20 Switching interval SA 1...100 % 20 % 21 Switching differential 1...100 % 10 %
22 Starting point 20...40 °C 25 °C 23 End point 20...40 °C 30 °C 24 Delta 0...10 K 2 K
25 Starting point –30...+20 °C 5 °C 26 End point –30...+20 °C –20 °C 27 Delta 0...10 K 2 K
28 E1 Fire / smoke A / b A 29 E2 Fan, filter monitor A / b A 30 E3 Overload "pump/electric " A / b A 31 E4 Overload "chiller" A / b A 32 E5 Overcurrent "fan" A / b A 33 Frost alarm A / b A 34 E7 AUX 1 A / b A 35 E8 AUX 2 A / b A
36 Room sensor, min. –50.0...+150.0 °C 0 °C 37 Room sensor, max. –50.0...+150.0 °C 50 °C 38 Supply air sensor, min. –50.0...+150.0 °C 0 °C 39 Supply air sensor, max. –50.0...+150.0 °C 50 °C 40 Outside sensor, min. –50.0...+150.0 °C –35 °C 41 Outside sensor, max. –50.0...+150.0 °C 35 °C 42 Frost sensor, min. –50.0...+150.0 °C 0 °C 43 Frost sensor, max. –50.0...+150.0 °C 15 °C
15)
15)
44 Compensation, min. –50.0...+150.0 °C –5 °C 45 Compensation, max. –50.0...+150.0 °C 5 °C
46 B1 Room temperature –5.00...+5.0 K 0. 0 K 47 B2 Supply air temperature –5.00...+5.0 K 0.0 K 48 B4 Outside temperature –5.00...+5.0 K 0. 0 K 49 B9 Frost temperature –5.00...+5.0 K 0.0 K 50 Z3 Compensation –5.00...+5.0 K 0.0 K
51 Integral action time "fan"
3)
00.00...30.00 min 5.00 min 52 Min. HC pump running time 00.00...30.00 min 5.00 min 53 HC pump kick interval 00.00...24.00 h 24.00 h 54 Alarm delay "filter" 00.00... 05. 00 m in 0.20 min 55 Alarm delay "AUX" 00.00...05.00 min 0.00 min 56 Time channel switch on time 57 Startup logic (air damper)
4)
5)
00.00...12.00 h 00.00 h
00.00...60.00 min 00.00 min 58 Power up start delay 00.00...30.00 min 00.00 min
59 E1 Fire/smoke CLSd/OPEn OPEn 60 E2 Fan, filter monitor CLSd/OPEn OPEn 61 E3 Overload "pump" CLSd/OPEn OPEn 62 E4 Overload "chiller" CLSd/OPEn OPEn 63 E5 Overcurrent "fan" CLSd/OPEn OPEn 64 E6 Time channel CLSd / OPEn OPEn 65 E7 AUX1 CLSd/OPEn OPEn 66 E8 AUX2 CLSd/OPEn OPEn
67 B1 Room temperature Auto/Pass/Act Auto 68 B2 Supply air temperature Auto / Pass/Act Auto 69 B4 Outside temperature Aut o / Pass/Act Auto 70 B9 Frost temperature Auto/Pass /Act Auto 71 Z3 Compensation Auto/Pass/ Act Auto
CM2N3205E / 05.2001 Siemens Building Technologies 14/18 Landis & Staefa Divisi on
Page 15
Miscellaneous
For LPB
Heating curve for heating demand
Efficiency supervision (Heat recovery system)
72 Hours run counter 0...9999 x 10 h -----12) 73 Operation lock "front" 74 Enable "pumpt kick" 75 Cycle time "test mode" 76 Actual value filter 77 RWI soft ware version 78 Communication address
6)
7)
8)
9)
10)
11)
OFF/On OFF OFF/On OFF
00.00...05.00 min 00.00 min OFF/On On “00.00” -----
----, 0...126 - - - -
79 Segment number 0...14 0 80 Device no. for supplier holiday program 0...16 0 81 Segment no. for supplier holiday program 0...14 0 82 Supplier clock time 0...2 0 83 Bus supply 0/1 1
84 Outside temp. on min. heat ing dem and
35...+35 °C 20 °C
85 Minimum heating demand 0...100 °C 40 °C 86 Outside temp. on max. heat ing dem and
35...+35 °C −−−−15 °C
87 Maximum heating demand 0...100 °C 60 °C 88 Current heating demand 0...100 °C (Read value) 89 Release cooling
16)
50...+150 °C 14 °C
110 Efficiency meas urem ent enabled OFF/On OFF 111 Selection of the m eas urem ent s et up 1/2 1 112 Alarm delay 00.00...10.00 hh.mm 00.10 hh.mm 113 Alarm priority A/b b 114 Disable above outs ide air t em perat ure
35...+35 °C 15 °C
115 Correction of fan influence 0,0...5 K 0,5 K 116 Alarm threshold 0...100 % 50 % 117 Measured v alue
50...+150 °C (Read value)
118 Efficiency 0...100 % (Read value)
. . . . . . .
Legend
1) Indicates whether input E6 is high or low (time signal "yes" or "no")
2) Integral action time (TN) = 0 seconds means P-cont rol f or t he res pec t ive control sequence Integral action time (TN) < 0 seconds means PI-c ont rol f or t he res pec t ive control sequence
3) Only if RWI65.01 has been configured for elec t ric air heat er bat t ery On completion of the set overrun t im e, t he f ans will be switched off and the outside air dampers s hut .
4) Period of time during which the plant - after receipt of pulse at E6 - should be in operation. When set to 0 seconds , t he plant will be switched on and off when signal is received at E6 (external time switch) (in "Automatic" operation only and when the internal time switch has switched off or in set to permanently OFF)
5) Period of time during which the plant may operate with 100 % recirculated air (after plant startup)
6) If operating level 1 is deactivated (data point value = 0), readjustment of values is not possible two minutes after closing the front c over (with the exception of summer/wintertime changeover)
7) Every day at 15.00 hrs, a switch on signal of 30 seconds is f ed t o out put Q20 (periodic pum p run)
8) Only internally
9) Only internally; can be used with demonstrations when - without using an actual value filter - the control system responds quickly to deviat ions
10) The display shows the current program number, which may vary, depending on the OEM version
11) To be set if controller is equipped with a communications card. If no comm unic at ions c ard is us ed, t he value set has no effect on t he RWI65.01. If the RWI65.01 is equipped with the AZI65.3 LPB communication card, the com m unic at ion addres s becomes the LPB device number with a range of 0 to 16 and a factory setting of 0. If the RWI65.01 is equipped with the AZI65.1 FLN communication card, the dann the valid address range is 33 to 126.
12) Connted are the number of fan operating hours. The readable value can be reset to zero or the former reading. To do this, proceed as f ollows:
1. Press function but t on 10 .
2. Press setting but t on "" if c ount er s hall be reset to zero.
Press setting button "+" if counter shall be res et t o t he f orm er reading.
3. To confirm resetting: Pres s f unc t ion but t on 10 again.
13) Active only if coded for hot water heating coil!
00.00 Pump kick interval in deactivated
00.05 - 24.00 Pump kick int erval for 30 seconds at the set interval Auto Pump will be activated f or 30 s ec onds at 24-hour int ervals, or pump runs
continuensly when the outside temperature falls befor 5 °C
Cont Pump continuensly activated
14) The value of 0 means: Automatic activation of c as c ade aut horit y in lock ed. Maximum Economy Changeover (MECH) with pure supply air temperature control in possible. In that case, the connected room t em perat ure s ens or, together with the outside sensor, in only used for MECH.
15) When using the QAF63... frost sensor, the factory-setting may not be changed!
16) The cooling signal is released above the set outside air temperature v alue. I n order t o avoid sliding on changing outside temperatures, a hysteresis of 1 K has been integrated.
Siemens Building Technol ogi es CM2N3205E / 05.2001 Landis & Staefa Divisi on 15/18
Page 16

Function flow diagrams for fault status signals

Incoming fault status signals
I/O Explanation
Fire/
E1
smoke
Flow/
E2
faults
Overloaded circulation pump
E3
Overloaded air heater
Chiller
E4
Overloaded
E5
fan
AUX 1
E7
AUX 2
E8
Frost protection
B9
unit
Heating source
Water Water Electr.
Electr. Water Water Electr.
Eletrc. Water
Water Electr. Electr.
Water Water
Electr. Electr. Water Water Electr. Electr.
Water Water Electr.
Electr.
Water Water Electr.
Electr. Water Water
Fault reaction
A B A
B A
B A B A B
A B
A B A B
A B
A B
A B A B A B A B A B
Q13 Q14
Q23
Y10 Y20 Y30 Q20 F91 F92
Q24
Green LED
Red LED
Dark Lit
Off/interlocked On/delocked
On/delo ck e d when Y1 0 ≥ 0 % Off/interlocked when Y10 ≥ 0 %
Flashing Off/interlocked (switch-off delayed) Dark (Y10 ≥ 0 %)
3205Z18E
CM2N3205E / 05.2001 Siemens Building Technologies 16/18 Landis & Staefa Divisi on
Page 17
Acknowledged present fault status signals
I/O Explanation
Fire/
E1
smoke
Flow/
E2
faults
Overloaded circulation pump
E3
Overloaded ventilator
Chiller
E4
Overloaded
E5
fan
AUX 1
E7
E8 AUX 2
Frost protection
B9
unit
Heating source
Water Water
Electr. Electr. Water Water Electr. Electr. Water Water Electr. Electr.
Water Water Electr. Electr. Water Water Electr. Electr. Water Water Electr. Electr. Water Water Electr. Electr. Water Water
Fault reaction
A B A B A B A B A B A B
A B A B A B A B A B A B A B A B A B
Q13 Q14
Q23
Y10 Y20 Y30 Q20 F91 F92
Q24
LED Green
LED Red
Dark Off/interlocked Lit
On/delocked
On/delocked when Y10 ≥ 0 % Off/interlocked when Y10 ≥ 0 %
Flashing Off/interlocked (switch-off delayed) Dark (Y10 ≥ 0 %)
3205Z19E
Siemens Building Technol ogi es CM2N3205E / 05.2001 Landis & Staefa Divisi on 17/18
Page 18

Dimensions

R
1
2
4.
3
106,5
58
2619
272,5
26 2613,5
137
145
Panel cutout
152,6
63
3426
5,5
5
,
1919
+ 1
0
133
138
5
Pg 11
2,5 106,5 24 30,3
5353
144
66
17,5 10
30 30
Dimensions in mm
CM2N3205E / 05.2001 Siemens Building Technologies 18/18 Landis & Staefa Divisi on
1999 Siemens Building Technologies Ltd.
max. R2
138
+ 1 0
3205M01
Loading...