Operating voltage AC 24 V, signal voltage DC 0-10 V;
all control and monitoring functions in one unit;
major control tasks: temperature control, compensation, cascade control with
minimum/maximum limitation of supply air temperature, control of d.h.w. circuit;
Connection to Landis & Staefa building automation systems by means of
communication cards
Ventilating and air conditioning plants with:
• Hot water or electric air heater batteries
• Direct expansion cooler batteries or chilled water cooling
• Valve and air damper actuators
• Control units for thermal wheel type heat exchangers
• Step switches for chillers and electric air heater batteries
• Current valves for electric air heater batteries
• Regulating units for heating, cooling or heat recovery
• Auxiliary units for chillers or circulating pumps and fans
• Signal converters for pneumatic/electric two- or three-position signals
NameType referenceRemarks
FLN Communication cardAZI65.1
LON/BACnet Communication cardAZI65.2
LPB Communication cardAZI65.3
Instructions set (de, fr, it)ARG65.40
Instructions set (en, sv, fi, no)ARG65.41
Instructions set (nl, es, da)ARG65.42
Instructions set (cs, sk, hu, pl, ru)ARG65.46
1) Optional
2) Consists of operating c ard 2, operating instructions, and m ounting instructions
1)
1)
1)
2)
2)
2)
2)
see data sheet 3206
see data sheet 3207
see data sheet 3208
included, if ordered
included, if ordered
included, if ordered
included, if ordered
Page 2
Ordering and
delivery
•When ordering the controller, please indicate the type reference RWI65.01. To ensure
the unit is supplied with the correct language version of the instructions, indicate the
type reference of the instructions required, e.g., ARG65.41 (for English, Swedish,
Finnish).
• Communication cards must be ordered separately, e.g., AZI65.1.
• Controllers and poss. communication cards are packed and supplied separately.
Equipment
combinations
Functions
Control and monitoring
NameType referenceData sheet
Temperature sensorQAA24, QAA261721
• Room/supply air temperature cascade control with minimum and maximum limitation
of the supply air temperature
•Control of air heater battery's hot water circuit (active frost protection unit, maintained
temperature)
•Control of up to three regulating units in sequence (plants with air dampers or heat
recovery)
•Control functions for optimum use of energy (maximum economy changeover) can be
provided
•Suitable for plants with the following operating actions:
2 x heating/heat recovery
1 x cooling
•Switching on/off of plant through:
Direct control of units or enabling of switching commands via potential-free relay
contacts
• Enabling of circulating pump or electric air heater battery
• Enabling of chiller (dx-cooling) or circulating pump
• Monitoring of operational sequences and indication of operational statuses of factory
defined plant elements
• Control of plant in the event of risk of frost
• Indication and fault status signal from up to six predefined and two freely selectable
plant elements
Communication card
In large plants, the AZI65.1 communication card is used to facilitate the dialog between
a central station and the plant. The dialog can be carried out either locally or via the
network and comprises:
• Registration of messages and alarms
• Selection of operating modes and set values
• Registration and graphic representation of actual values and statuses
• Acquisition and evaluation of plant data
CM2N3205E / 05.2001Siemens Building Technologies
2/18Landis & Staefa Division
Page 3
Technical design
Control
Compensation
Automatic sensor identification (ASD logic), including type of sensor (active or pas-sive).
Automatic activation of incorporated control functions owing to ACC logic which, through
ASD, identifies the intended purpose of the control function. This means that the control
will be optimally adapted to the plant.
P-band and integral action time (TN) are separately adjustable, so that P-control (with
integral action time = 0) or PI control can be selected.
The controller is supplied as a PI controller. The set values of heating and cooling can
be adjusted separately. Overlapping of heating/ cooling sequences is not possible.
For the control of mixed air dampers or heat recovery equipment, both operating action
and operating mode can be selected.
The actual values of the various outputs are permanently displayed.
The following compensation functions can be implemented:
•Outside temperature compensated controller set value. This function is integrated in
the controller. The parameters of compensation can be set
∆∆∆∆
[K]
w
6
5
4
3
2
1
Winter
compensation
Sw
Ew
Fw
Summer
compensation
Fs
Ss
Es
3205D12E
Temperature control
[°C]
TA
−
−20−15−10−5±
30
0510 15 20 2530 35
40
•Compensation by means of an active or passive potentiometer, as an absolute set
value or as a set value shift
[K]
∆∆∆∆
w
Data point 45
Data point 44
+ 5
0
El
− 5
0
100011171235
510
Eh
Z3
Z3
3205D13E
[V]
[Ω]
•Compensation across the entire setpoint range from an L&S building automation
system via a data bus (FLN bus or LON/BACnet bus) and communication card
(AZI65.1 respectively AZI65.2)
•Connection of a supply air temperature sensor (B2) automatically activates supply air
temperature control
• Room/supply air temperature cascade control
• Connection of room or extract air (B1) and supply air temperature sensors (B2)
automatically activates cascade control
The output signal of the room/extract air temperature controller acts on the set value
of the supply air temperature controller. This effect (standard value is preset) can be
changed. Cascade control acquires disturbances in the supply air and offsets them
before they have an impact on the room or extract air temperature. The limitation
functions are not affected by the cascade.
– Minimum and maximum limitation of the supply air temperature are automatically
activated
x
ZwZ
Heating mode
x
w
Z
Cooling mode
Z
3205D03E
Economizer operation
Y20
Y10
Y30
w
LH
∆
w
Z
Z
∆
w
H
w
LL
KE =
∆
R
wHx
R
∆
Z /
R KE = ∆ Z / ∆ R
x
R
Y20
Y10
Y30
w
LH
w
C
Z
∆
w
Z
w
LL
w
x
C
R
Based on the measured difference of outside and extract air temperature, the plant is
operated with reduced fresh air supply or heat recovery. Prerequisites for activation:
• DIL switch 4 (economizer) set to OFF (=YES)
• Outside and extract air temperature sensors connected
HR system
Y30
10
0
T
[V]
B4 < B1
2 K2 K
B4 > B1
T
∆
Y30
10
min
Y30
0
[V]
Mixing dampers
[V]
Y30
10
B4 < B1
Y30
min
0
T
[V]
Y30
10
B4 > B1
0
T
∆
00
x
R
3205D07E
Control sequences
Function diagram 1
The RWI65.01 allows control sequences with both operating actions for air
dampers/heat recovery. The operating action is selected with DIL switches 5-7.
Application with mixing air dampers
[%]
Y
100
Y30
(DtPnt 6)
min
Y10Y30
X
T
n1
P1
X
T
n3
P3
Y20
(DtPnt. 20)
SA
SD
(DtPnt 21)
X
P2
T
w
w
c
h
n2
T
3204D04E
CM2N3205E / 05.2001Siemens Building Technologies
4/18Landis & Staefa Division
Page 5
Function diagramm 2
Application with HR system
[%]
Y
Frost protection
100
Y10Y30
X
P1
T
n1
X
T
n3
Y20
(DtPnt 20)
SA
SD
(DtPnt 21)
P3
w
w
c
h
X
T
n2
P2
T
3205D05E
SA:Data point 20 "Switching interval"
SD:Data point 21 "Switching differential"
For ventilating and air conditioning plants with hot water air heater batteries. Frost
protection operation is selected with DIL switch 8 (water). Frost protection is used to
• protect the air heater battery against freezing
• facilitate plant startup at low outside temperatures
All parameters for frost protection are factory-set and can be changed: Response
temperatures, set values, P-bands and integral action times. The frost protection
concept functions with both kinds of temperature acquisi tion (in the water circuit or at
the air heater battery's outlet). The protective actions are the following:
• Continuous opening of heating valve, activation of circulating pump
• Switching off the fan or closing the air damper
• Maintaining the temperature when the fan is switched off (on the water side only)
• Fault status signal in the event of risk of frost
To ensure frost protection, the use of the following sensors is required:
• QAD22.../QAE21.9 for temperature acquisition in the water circuit
• QAF63... for temperature acquisition at the battery's outlet
Plant ON
Air-/water side
[ % ]
Y
100100
00
w
w
½ X
2 K
Q23/Q24Q13/Q14
TTemperature in air heater battery circuit or air temperature directly aft er t he air heat er bat t ery
QLoad
YManipulated variable
Y10Control command at heating valv e
Q13/Q14 Relay output "Pump"
Q23/Q24 Relay output "Fan/air damper"
X
pd
X
pn
w
w
w
wn
ZtMin. running time of circulating pump (dat a point 52)
P-band "Frost protection controller" (data point 9)
P-band "Standby controller" (data point 10)
Frost alarm value (data point 7)
Set value "Standby controller" (data point 8)
The RWI65.01 provides all control and monitoring functions mentioned above.
Prerequisite:
Correct configuration of the heat source (water or electric) with DIL switch 8.
Switching on of plant,
provided:
Monitoring operation of
plants that use hot water
air heater batteries
Monitoring operation of
plants that use electric
air heater batteries
•Operating mode is set to "Automatic" ( ) and timeswitch program of timeswitch is
set to "ON", or
• Operating mode "Manual ON" ( I )
• Continuous checkback signal of plant's and circulating pump's operational status,
based on the signals delivered by the monitoring elements such as flow switch and
overcurrent protection
•Switching off actions, depending on the selected alarm priority (A or b), and operating
mode as well as delays aimed at avoiding incorrect signals are adjustable
•Permanent monitoring of frost protection
To save pump energy and to avoid damage to the pump:
• Parallel output of heating and pump on command when there is a demand for heat
• Pump kick, interval and minimum running time are adjustable
• Activation of electric air heater battery only when there is a demand for heat and
when the monitoring elements are enabled
•Continuous checkback signal of plant's operational status, especially that of the
electric air heater battery, based on the signals delivered by the monitoring elements
such as flow switch or filter switch, thermal cutout or overcurrent protection
• Switching off of plant elements, depending on the selected alarm priority (A or b)
• Adjustable alarm delays for disturbances of filter or flow
• Adjustable fan overrun times
Monitoring operation in
refrigeration plants
Efficiency supervision
of the heat recovery
system
Time switch
•Two possibilities of control
– With integrated ON/OFF command (Q20)
– With DC 0...10 V control signal via digital or binary step switches
•Adaptation to compressor or heat pump operation by setting a switching interval and
a switching differential
• Selectable pump kick for heat pump operation
• Switching off of plant elements, depending on the selected alarm priority (A or b)
An additional sensor must be installed if this function is used. Three temperature values
(temperature behind heat recovery, equipment, outdoor air and extract air temperature)
are required to calculate efficiency. The calculated value is shown on the controller and
it generates an alarm if it falls below an adjustable threshold value.
To display data points 110 to 118, set DIL switch No. 2 to the left.
The efficiency value acts as a fault indicator, for example, for defective, polluted or
incorrectly connected heat recovery equipment.
This function (display/alarming) is supported by the FLN integration solutions (AZI65.1 /
UNIGYR, VISIONIK) and LON/BACnet (AZI65.2 / DESIGO 30).
When this function is used, the Z-input is not available for other functions.
The timeswitch is a weekly time switch with programmable switching on/off times for
every weekday.
The switching on/off times can be reprogrammed at any time without having to readjust
the time of day. The switching statuses are immediately adapted to the new switching
on/off times.
Summer/wintertime changeover: Depending on the season, one hour is either added to
the actual time (display with a solid square = summertime) or subtracted from it.
The time program is stored should a power failure occur - like all other settings.
.
.
.
.
.
.
.
.
.
.
CM2N3205E / 05.2001Siemens Building Technologies
6/18Landis & Staefa Division
Page 7
Fault status signals
A
and indication
Legend
cknowledging the fault
status signal
The RW165.01 can acquire and process nine fault status signals from plant elements
and plant statuses. When the front door is closed, the signals are shown in lines 9 and
10 of the display as follows:
1234
∆
p
B9
E3
E2
I
E5
657
1Frost danger supervision (signal input B9),
Display: 0 = normal, A or b = frost alarm.
2Flow supervision (signal input B9)
Display: 0 = normal, 1 = start phase, A or b = flow fault.
3Overload of refrigeration machine or chilled water circuit pump (signal input E4)
Display: 0 = Q20 cooling switched off, 1 = Q20 cooling switched on,
A or b = cooling fault.
4Open usage e.g. for filter supervis ion (s ignal input E7)
Display: 0 = normal, 1 = start phase, A or b = fault at E7.
5Overload/overheating of circ ulat ing pum p or air heat er bat t ery (signal input E3),
Display: 0 = Q13/Q14 heater switched off, 1 = Q13/Q14 heater switched on,
A or b = pump or air heater battery fault.
6Overload fan (signal input E5),
Display: 0 = Q23 fan switched off, 1 = Q23 fan switched on,
A or b = fan fault.
7Fire/smoke supervision (signal input E1),
Display: 0 = normal, A or b = fire / smoke alarm.
8Open usage (signal input E8),
Display: 0 = normal, 1 = start phase, A or b = fault at E8.
Display: no pointer = normal, visible pointer = effic ienc y is below the set alarm thres hold
E4
E1
89
9
10
A 0 b 0
1 1 0
3205Z07
E7
E8
Depending on priority, fault status signals are indicated by a flashing "A" or "b" in the
display (with efficiency supervision using pointer) and by a flashing red LED located on
the acknowledge button on the unit front. At the same time, it is available as a
centralized alarm at centralized alarm output F91 (priority A) or F 92 (priority b).
Fault status signal priorities (A or b) can be selected for inputs E1 to E5, E7, E8, B9 and
Z3.
Status signal inputs E1 to E8 can be individually adapted to the contact state of the
corresponding status signal element (normally closed or normally open).
Alarm delays to avoid false alarms can be selected for status signal inputs E2 and E7.
Any fault displayed can be acknowledged from the acknowledgment button on the unit
front. When a fault is acknowledged, the priority display changes from flashing to steady
and the centralized fault status signal at centralized alarm output F … is cancelled.
The display of a priority "b" fault status signal goes out when the signal is no longer
present at the fault status signal input. When no other fault status signal is present at
the fault status signal inputs, the display in the acknowledgment button changes from
red to green.
The fault status signal indications (display and acknowledgment button) for a priority "A"
fault can be cancelled by pushing the acknowledgment button again, as long as no
other fault status signals with priority "A" are present.
The function flow diagrams at the end of this data sheet show how the fault status
signals affect the RWI65 outputs.
The controller consists of controller insert and base.
The controller insert accommodates all operating elements and the electronic circuits. It
is secured to the base by two screws which are designed such that they push the insert
away from the base when they are loosened.
The microprocessor with the memory, the associated electronic components, and the
display are carried by one printed circuit board, the relays by another. Another board
serves for communication and carries a specific microprocessor with the ass ociated
interface. An EEPROM stores all setting values. In the event of a power failure, the
setting values are thus retained for an almost unlimited period of time. The reserve for
the weekly time switch (48 hours typically) is contained in the controller insert. For this
reason, the insert can be removed without having an effect on the actual time setting.
The base is made of plastic and is designed for both wall and flush panel mounting. In
the case of flush panel mounting, the controller is secured by a clamp. The base carries
four terminal blocks and a terminal strip for establishing the electrical connections with
the controller insert.
Display, setting and
operating elements
Legend
191011
Set point heating
Set point cooling
Actual set point
Min. supply air temp.
Max supply air temp.
Day
Start time
Stop time
Data point number
Data point value
1
2
3
4
5
6
7
8
9
10
3205Z04E
324567 8
1Front cover
2Operating card 1 (for operating level 1) and operating ins t ruc t ions
3Opening for acknowledgement of fault when front cover is closed
4Connection facility for local network
5Indicator lamp for plant status (ON/OFF)
6Indicator lamp and acknowledge button for fault stat us s ignals
7Setting buttons
8Keyhole for opening the front cover (key enclos ed)
9Covering plate with operating card 2 (for operating levels 2 and 3)
10Display with 10 lines
11Function buttons
Operation with front cover
closed
(operating level 1)
When the front cover is closed, the display shows (from top to bottom): Selection of
operating mode (solid square), manipulated variables, temperatures, weekday, time of
day, and status information.
The following setting choices exist (if enabled): Selection of operating mode (automatic,
on, standby), weekday, and summer- or wintertime.
Y 10
1
I
Landis & Staefa
RWI65.01
B9E3E2E5E4E1E7
CM2N3205E / 05.2001Siemens Building Technologies
8/18Landis & Staefa Division
Y 20
2
Y 30
3
I
T
4
5
I
T
T
6
1...7
2
∆∆∆∆
P
I
7
+1h
8
9
10
E8
RWI65.01 with front co ver closed
3205Z16
Page 9
Operation with front cover
open
(operating levels 2 and 3)
After opening the front cover, operating card 2 can be accessed: The 10 lines on the
front (operating level 2) show the setting and measuring choices available for operation.
The values can be readjusted when operating level 2 is active.
By simultaneously pressing the two function buttons at the bottom (lines 9 and 10), the
third operating level can be activated, which is used for service purposes. This operating
level facilitates access to switching data and manipulated variables (service settings).
The reverse side of operating card 2 contains appropriate information. By closing the
front cover, operating level 1 is automatically reactivated.
Configuration of controller
with DIL switches
The DIL switches used for the configuration of the controller are located underneath the
covering plate. To check or change settings, the front cover must be opened and the
covering plate removed.
8
7
6
5
8
7
6
5
4
3
2
1
4
3
2
1
Y30
Y30 Y1 0
Y30Y30
TestRun
Y30
Y10 Y30
1
2
3
4
5
6
7
8
9
10
Front cover and covering
plateremoved
3205Z11
Positions of DIL switches as supplied
(all switches in OFF position, meaning given in bold letters):
8Type of heatingELECTRIC / WATER
7Sequence Y30 activeNO / YES
6Order Y30COMFORT / ECONOMY
5Operating action Y30INVERTED / NORMAL
4Economizer Y30,NO / YES
Max. ECO changeover,
heat recovery
3Not used
2Display "Heat recovery equip-
ment efficiency supervision"YES / NO
1Test modeYES1) / NO
.
.
.
1) For factory settings only
Communication cards
AZI65...
The RWI65.01 can communicate with an active bus device (master) with the aid of
– the FLN (Floor Level Network) communication card AZI65.01 or
– the LON/BACnet (Local Operating Network with BACnet protocol) communication
card AZI65.02 or
– the LPB (Local Process Bus) communication card AZI65.03
Each card contains the electronic circuits required for communication.
The compartment be-comes accessible after opening the front door and removing the
cover. The communication card slides into its compartment in grooves.
Fitting the FLN communication card in the RWI65.01 requires no re-commissioning, but
only bus registration for data exchange on the network.
80 % of the plastics used can be recycled.
The unit uses a supercapacitor in place of NiCd batteries which need to be replaced
every two years - also for the benefit of operating safety and environmental protection.
The operating voltage required to power the controller is AC 24 V. The transformer used
must be suitable for safety extra low voltage, 100 % duty, and must have separate
windings.
Terminals Q13/Q14 and Q23/Q24 must not be used with different nominal voltages
Fuses, switches, wiring and earthing must be in compliance with local regulations.
The limitations cannot be used as safety functions. These always require separate
safety devices. All important variables that are required for commissioning are to be
shown on the plant documentation (wiring diagram, etc.), if known at the time of
planning.
The controller is designed for wall mounting (in an open space or a control panel) or
flush panel mounting (control panel front, console, etc.). The permissible ambient
conditions must be observed. First, the base is to be mounted and wired up. The cables
inside the base are to be accommodated such that the insert can be easily fitted.
Secure fixing screws only after commissioning.
Commissioning
notes
Aids
Settings
Recommendation
CM2N3205E / 05.2001Siemens Building Technologies
10/18Landis & Staefa Divisi on
For commissioning and operation, refer to the operating instructions supplied with the
controller. When commissioning the plant, all functions of the controller and the
communications card (if fitted) are to be checked. Separate preselection of all switching
and position outputs can be made at the service level (provided operating level 3 is
active). All actual values and remote operation signals can be called up.
The controller is supplied with all control functions and parameters factory-set. Where
required, it needs to be configured for various logic functions, e.g. with electric heating,
where certain safety measures must be observed.
Changing the configuration or data settings: By means of inbuilt DIL switches.
Changing the values: With function buttons at the operating level. Any change is
immediately saved when acknowledgement is made (when the display stops flashing).
Note changed values on the reverse side of the operating instructions (folded sheet).
Page 11
Operating and
A
A
maintenance notes
Selection of the operating mode and time and weekday settings can be blocked when
the front cover is closed. Various operational faults are identified and indicated by the
controller.
Setting aid
Technical data
Power supply
Inputs
Digital inputs E1.. .E8
nalog inputs
B1, B2, B4, B9, Z
Outputs
nalog outputs
Y10, Y20, Y30
Relay outputs
Q13/Q14, Q23/Q24
Relay output
F91, F92
Degree of protection
Environmental conditions
Standards
Product standards
Electromagnetic
compatibility
conformity as per
Miscellaneous
Note changed values on the reverse side of the operating instructions (folded sheet).
Operating voltageAC 24 V ±20 %
Safety extra-low voltage (SELV) as perEN 60 730
External transformer (100 % duty) as perEN 60 742
Fusing of supply line (external)10 A max.
Frequency50 Hz or 60 Hz
Power consumption10 VA
Voltage at open inputDC 20...23 V
Logic 0
Logic 1
Current at "Logic 0"9 mA
Perm. line lengths with copper 1.5 mm
Sensors
PassiveLG-Ni1000 Ω
ActiveDC 0...10 V
Measuring range−50...+150 °C
Perm. line lengths with copper 1.5 mm
Setpoint transmitter
Passive1000...1235 Ω
ActiveDC 0...10 V
Setting range−50...+150 °C
Perm. line lengthsdep. on transmitter t ype
Output voltageDC 0...10 V
Output current
Max. loadsustained short-circ ui t
Switching capacity, vol t ageAC 19 V min., 265 V max.
Switching capacity, c urrent at AC 19 V20 mA min., 4 A / 3 A
Switching capacity, c urrent at AC 265 V5 mA min., 4 A / 3 A
Switching capacity, vol tageDC 5 V min., AC 42 V
Switching capacity, c u rrent100 mA min., 1 mA max.
Protection classIII as per EN 60 730
Housing protection
when mounted on a flat wallIP 40 as per EN 60 529
when mounted in a control panel front
CasingIP 40 as per EN 60 529
BaseIP 20 as per EN 60 529
Operation as per IEC 721-3-3
Climatic condit i onsclas s 3K5
Temperature−5...+50 °C
Humidity (non-condensing)
Transport as per IEC 721-3-2
Climatic condit i onsclas s 2K3
Temperature
Humidity
Mechanical conditionsclass 2M2
Automatic elec t ri c controls
for household and similar useEN 60 730
Emissions as per EN 50 081-1
Immunity as per EN 50 082-2
EMC directives89/336/EEC
Low voltage directive73/23/EEC
Reserve in the event of a power failure48 h (typical)
Connection terminals f or wires2 x 1.5 mm
Weight (incl . packaging) 1.17 k g
GAC 24 V operating voltage (system potential)
G0AC 24 V operating voltage (system neutral)
MMeasuring neut ral
B1Measuring signal from room or extract air temperat ure s ensor (LG-Ni1000 Ω / DC 0...10 V)
B2Measuring signal from supply air temperature sensor (LG-Ni1000 Ω / DC 0...10 V)
B4Measuring signal from outside sensor (LG-Ni1000 Ω / DC 0...10 V)
B9Measuring signal from frost protect ion unit (LG-Ni1000 Ω / DC 0...10 V)
Z3Compensating signal from peripheral equipment (1000...1225 Ω / DC 0...10 V)
Y10DC 0...10 V control signal for heating
Y20DC 0...10 V control signal for cooling
Y30DC 0...10 V control signal for heat recovery/m ixed air dam pers
Q20AC 24 V control signal for compressor, dx-cooling or circulat ing pum p
Q13, Q14 Potential-free relay contact t o s witch circulating pum ps or an elec t ric air heat er bat t ery
Q23, Q24 Potential-free relay contacts to switch fans
GESignal voltage neutral for digitals stat us input s
E1Digital signal input "Fire/smoke"
E2Digital signal input "Disturbed flow"
E3Digital signal input "Circulating pump/electric air heater batt ery"
E4Digital signal input "Common falut signal form chiller"
E5Digital signal input "Fan, overcurrent"
E6Digital signal input "Extended operation" (with automatic operation only
E7Digital signal input, freely available
E8Digital signal input, freely available
GFSignal voltage neutral for common fault status signals (AC/DC 5...42 V)
F91Common fault signal according to alarm priority A (AC/DC 5...42 V)
F92Common fault signal according to alarm priority b (AC/DC 5...42 V)
UN, UPTerminals (2...3) for communication
Note: LG-Ni1000 Ω sensors = Landis & Staefa standard
Q20
GFY10 GGY20GY30
UP UN
F91
F92
Q14
Q24
3205G01
Connection diagrams
Connections on the
measuring side
Connection diagramm 1:
Measuring part for temperature with passive main
and auxiliary sensors
Connection diagramm 2:
Connection of an active
remote setting unit
Legend to connection
diagrams 1 and 2
G
BM
G
B1
MB4B9
Y10Y20Y30G0
G0
G
G
G0
N1Controller RWI65.01
B1QAA23/QAM22 room or extract air temperature sensor
B2QAM22 supply air temperature sensor
B4QAM22/QAC22 outside sensor
B9QAD22.../QAE22...
R1FZA61.11 remote setting unit
MB2Z3
B1
Y10Y20Y30G0
MMMBBB
B1
B2B4B9
B2 MMM
B4B9
GG0
Y9
G0
R1
3205A02
N1
3205A04
N1
CM2N3205E / 05.2001Siemens Building Technologies
12/18Landis & Staefa Divisi on
Page 13
Connection diagram 3:
Connection of outside
temperature signal from a
signal source other than the
QAM22/QAC22 and an active
frost protection sensor
G
G0
G0
G
BM
B1
B1
MB2 B4 B9
Y10Y20
U4 M
B2
MMM
N2B9
Y30
G
BMBM
3205A03
N1
Connection diagram 4:
Connection of a passive
remote setting unit
Connections on the
control side
Connection diagram 5
Connections on the
control and monitoring
side
Connection diagram 6
G
G0
G
G0
L
G
AC 24 V
G
G0
R1
B2
B1
Y10Y20Y30G0
G
B1 M
GGGG0G0G0
GYRMG0GYRM
B4B9MRZ3 M
B2B4
Y10
UUU
Y20Y30
GY
G0G0
B9
RM
Y1Y2Y3
F1F2
∆
p
T
3205A05
N1
N1
3205A06
3205A07
DC/AC 5 ... 42 V
Note
Legend to connection
diagrams 3 to 6
E7
GEE1E2E3E4E5E6
Logic Center
AC 24 V
AC 230 V
AC 24 V
E8
Q20
GF
F91Q24
Q13 Q23
F92Q14
N1
F1F2
H1H2 H3
K1K2
G0
N
The RWI65.01 allows selection of N.C. or N.C. contacts, depending on the requirements
Terminals Q13/14 and Q23/24 must not be used with different nominal voltages!!
N1RWI65.01 controller
N2RVL55 with AZY55.60 plug-in module (outside temperature signal)
B9QAF63... frost protection sensor
F1, F2 Overload relay contacts
H1Auxiliary unit for circulating pump or signal for chiller
H2Auxiliary unit for common fault status priority A
H3Auxiliara unit for common fault status prorit y b
K1Contacts for circulating pump or electric air heater battery
K2Motor contactor for fan
R1FZA21.21 or QAA26 remote setting unit
Y1Regulating unit for heating
Y2Regulating unit for cooling
Y3Regulating unit for heat recovery / mixed air dampers
Data point values and measured values can be called up as data under certain data
point numbers. The factory setting of all values is such that the controller will meet the
requirements of most plants. If necessary, they can be readjusted on an individual
basis.
Nr.Descri ptionRangeFactory setting
Current measured values
Limitation of m a nipulated
variables
Set values of frost
protection/st a ndby cont roller
Parameters of frost
protection / st a ndby
controller
Control paramet e rs of room
temperature controller
Control paramet e rs of supply
air temperature controller
Switching points of
compressor
Summer compensation
Winter compensation
Alarm priorities
Measuring ranges of active
sensors
Measured value correction,
sensor inputs
Time elements
Active level I/Os
Preselection sensor
identification
1B9 Frost temperature–50.0...+150.0 °C----2Z3 Compensating variable–50.0...+150.0 °C----3F91 Common fault relay AOFF / On----4F92 Common fault relay bOFF / On----5E6 Time channel
1)
OFF / On-----
6Min. limitation Y300...100 %0 %
7Frost alarm value2.. . 15 °C5 °C
8Set value "standby controller"2...50 °C25 °C
9P-band "frost prot. controller"1...30 K5 K
10P-band "Standby controller"1...200 K10 K
11Integral action time "standby controller"0.00...10.00 min3.00 min
12KE room (cascade effect)0.1...202.0
13Integral action time "room"0.00...40.00 min8.00 min
14P-band "heating"1...200 K20 K
15Integral act.time "heating"
16P-band "HR"1...200 K15 K
17Integral action time "HR"
18P-band "cooling"1...200 K15 K
19Integral act.time "cooling"
22Starting point20...40 °C25 °C
23End point20...40 °C30 °C
24Delta0...10 K2 K
25Starting point–30...+20 °C5 °C
26End point–30...+20 °C–20 °C
27Delta0...10 K2 K
28E1 Fire / smokeA / bA
29E2 Fan, filter monitorA / bA
30E3 Overload "pump/electric "A / bA
31E4 Overload "chiller"A / bA
32E5 Overcurrent "fan"A / bA
33Frost alarmA / bA
34E7 AUX 1A / bA
35E8 AUX 2A / bA
36Room sensor, min.–50.0...+150.0 °C0 °C
37Room sensor, max.–50.0...+150.0 °C50 °C
38Supply air sensor, min.–50.0...+150.0 °C0 °C
39Supply air sensor, max.–50.0...+150.0 °C50 °C
40Outside sensor, min.–50.0...+150.0 °C–35 °C
41Outside sensor, max.–50.0...+150.0 °C35 °C
42Frost sensor, min.–50.0...+150.0 °C0 °C
43Frost sensor, max.–50.0...+150.0 °C15 °C
15)
15)
44Compensation, min.–50.0...+150.0 °C–5 °C
45Compensation, max.–50.0...+150.0 °C5 °C
46B1 Room temperature–5.00...+5.0 K0. 0 K
47B2 Supply air temperature–5.00...+5.0 K0.0 K
48B4 Outside temperature–5.00...+5.0 K0. 0 K
49B9 Frost temperature–5.00...+5.0 K0.0 K
50Z3 Compensation–5.00...+5.0 K0.0 K
51Integral action time "fan"
3)
00.00...30.00 min5.00 min
52Min. HC pump running time00.00...30.00 min5.00 min
53HC pump kick interval00.00...24.00 h24.00 h
54Alarm delay "filter"00.00... 05. 00 m in0.20 min
55Alarm delay "AUX"00.00...05.00 min0.00 min
56Time channel switch on time
57Startup logic (air damper)
4)
5)
00.00...12.00 h00.00 h
00.00...60.00 min00.00 min
58Power up start delay00.00...30.00 min00.00 min
CM2N3205E / 05.2001Siemens Building Technologies
14/18Landis & Staefa Divisi on
Page 15
Miscellaneous
For LPB
Heating curve for heating
demand
Efficiency supervision
(Heat recovery system)
72Hours run counter0...9999 x 10 h-----12)
73Operation lock "front"
74Enable "pumpt kick"
75Cycle time "test mode"
76Actual value filter
77RWI soft ware version
78Communication address
6)
7)
8)
9)
10)
11)
OFF/OnOFF
OFF/OnOFF
00.00...05.00 min00.00 min
OFF/OnOn
“00.00”-----
----, 0...126- - - -
79Segment number0...140
80Device no. for supplier holiday program0...160
81Segment no. for supplier holiday program0...140
82Supplier clock time0...20
83Bus supply0/11
84Outside temp. on min. heat ing dem and
−35...+35 °C20 °C
85Minimum heating demand0...100 °C40 °C
86Outside temp. on max. heat ing dem and
110Efficiency meas urem ent enabledOFF/OnOFF
111Selection of the m eas urem ent s et up1/21
112Alarm delay00.00...10.00 hh.mm00.10 hh.mm
113Alarm priorityA/bb
114Disable above outs ide air t em perat ure
−35...+35 °C15 °C
115Correction of fan influence0,0...5 K0,5 K
116Alarm threshold0...100 %50 %
117Measured v alue
−50...+150 °C(Read value)
118Efficiency0...100 %(Read value)
.
.
.
.
.
.
.
Legend
1)Indicates whether input E6 is high or low (time signal "yes" or "no")
2)Integral action time (TN) = 0 seconds means P-cont rol f or t he res pec t ive control sequence
Integral action time (TN) < 0 seconds means PI-c ont rol f or t he res pec t ive control sequence
3)Only if RWI65.01 has been configured for elec t ric air heat er bat t ery
On completion of the set overrun t im e, t he f ans will be switched off and the outside air dampers s hut .
4)Period of time during which the plant - after receipt of pulse at E6 - should be in operation.
When set to 0 seconds , t he plant will be switched on and off when signal is received at E6 (external
time switch) (in "Automatic" operation only and when the internal time switch has switched off or in set to
permanently OFF)
5)Period of time during which the plant may operate with 100 % recirculated air (after plant startup)
6)If operating level 1 is deactivated (data point value = 0), readjustment of values is not possible two
minutes after closing the front c over (with the exception of summer/wintertime changeover)
7)Every day at 15.00 hrs, a switch on signal of 30 seconds is f ed t o out put Q20 (periodic pum p run)
8)Only internally
9)Only internally; can be used with demonstrations when - without using an actual value filter - the control
system responds quickly to deviat ions
10)The display shows the current program number, which may vary, depending on the OEM version
11)To be set if controller is equipped with a communications card. If no comm unic at ions c ard is us ed, t he
value set has no effect on t he RWI65.01.
If the RWI65.01 is equipped with the AZI65.3 LPB communication card, the com m unic at ion addres s
becomes the LPB device number with a range of 0 to 16 and a factory setting of 0.
If the RWI65.01 is equipped with the AZI65.1 FLN communication card, the dann the valid address
range is 33 to 126.
12)Connted are the number of fan operating hours.
The readable value can be reset to zero or the former reading. To do this, proceed as f ollows:
1.Press function but t on 10 .
2.Press setting but t on "−" if c ount er s hall be reset to zero.
Press setting button "+" if counter shall be res et t o t he f orm er reading.
3.To confirm resetting: Pres s f unc t ion but t on 10 again.
13)Active only if coded for hot water heating coil!
00.00Pump kick interval in deactivated
00.05 - 24.00Pump kick int erval for 30 seconds at the set interval
AutoPump will be activated f or 30 s ec onds at 24-hour int ervals, or pump runs
continuensly when the outside temperature falls befor 5 °C
ContPump continuensly activated
14)The value of 0 means:
Automatic activation of c as c ade aut horit y in lock ed. Maximum Economy Changeover (MECH) with pure
supply air temperature control in possible.
In that case, the connected room t em perat ure s ens or, together with the outside sensor, in only used for
MECH.
15)When using the QAF63... frost sensor, the factory-setting may not be changed!
16)The cooling signal is released above the set outside air temperature v alue. I n order t o avoid sliding on
changing outside temperatures, a hysteresis of 1 K has been integrated.