Siemens ACVATIX SQV..P, ACVATIX SQV91P30, ACVATIX SQV91P40 Series Manual

Page 1
s
4
ACVATIX™
Use
Electromotive actuators for
SQV..P..
combi valves
For combi valves VPF43.. and VPF53..
SQV91.. Operating voltage AC/DC 24 V,
Positioning signal 3-position, DC 0-10 V, DC 4-20 mA
Position feedback and selection of flow characteristicManual adjuster, position and status indi cation (LED)Selectable positioning times 40-240 secondsFail-safe function (combi valve open/cl osed)Selection of acting directionOptional functio nal extension: Auxiliary switch, potentiometer, and
AC 230 V module
Direct mounting on combi valvesUL approved
Electromotive actuators to operate Siemens combi valves for type series VPF43.. and VPF53.. with 20/40/43 mm stroke, as control valves for ventilation, air conditioning, district heating and refrigeration plants.
CE1N4833en 2017-11-15
Building Technologies
Page 2
Type summary
2)
Type Stock No. Stroke
SQV91P30
SQV91P40
S55150-A130
S55150-A131
Electrical accessories
Spare parts, rev. number
Ordering
Pos.
force
20/40/43 mm 1100 N
1)
AC 230 V requires accessory ASP1.1.
2)
The positioning time can be selected using the DIL switch, see page 7.
Operat i ng
voltage
AC/DC 24 V AC 230 V
Positi oni ng
3-position DC 0…10 V
1)
DC 4…20 mA
signal
Auxiliary switch
Type
pair
ASC10.42
Spring
return
time
30 sec
Potentiometer
ASZ7.6/1000
Pos. time
20mm 40mm
40 sec 60 sec 90 sec
120 sec
80 s 120 s 180 s 240 s
AC 230 V module
ASP1.1
Stock number S55845-Z137 S55845-Z136 S55845-Z138
Max. 2
SQV91P30 SQV91P40
Max. 1 Max. 1 Max. 1 Max. 1
No spare parts available. Revision numbers, see page 13.
Fail-safe function
Stem retracts
Stem extends
Example
Delivery
Equipment combination
Type Stock number Designation Quantity
SQV91P40 S55150-A131 Actuator 1 ASZ7.6/1000 S55845-Z136 Potentiometer 1
Actuator, combi valve, and accessories are individually packed for delivery.
Valve type DN PN class
Flow V
[m3/h]
100
Data sheet
Combi valves
50
2,3…25
65 4,4…35
VPF43..
Flange
80 5,3…43
100 12,1…90
16
N4315
125 18,5…135 150 25,6…195
50
2,3…25
65 4,4…35
VPF53..
Flange
80 5,3…43
100 12,1…90
25
N4316
125 18,5…135 150 25,6…195
2 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
Page 3
Technology/Mechanical design
1
4833Z01
1235764
The actuator can be operated as a 3-position or modulating actuator in two acting directions depending on the type of connection. It is suitable for both combi valves VPF.. with 20 mm stroke as well as for valves with a 40 mm and 43 mm stroke. The stroke is calibrated automatically during initialization. The actuator includes a position feedback. The actuator travels to the end position in the event of power loss, see "Fail-safe
function", page 5. Up to 45 seconds pass until the actuator is available again following
a restart or start after the fail-safe function is triggered. The positioning time (40 to 240 seconds) and the flow characteristic (lin/log) can be set via the DIL switches.
1 Status and acting direction
indication (LED) 2 Housing cover 3 Entry points for cable glands 4 Manual adjuster 5 Indication of upper end
position 6 Valve stem coupling 7 Indication of lower end
position 8 Valve neck coupling
Auto mode
Manual mode
Initialization, automatic coupling, calibration
3-position control signal
The manual adjuster is disengaged.
The manual adjuster allows for manually setting the position. The motor is switched off when the manual adjuster is engaged. The fail-safe function (spring return) is reactivated after the manual adjuster is disengaged, and the actuator travels again to the set position without calibration. The actuator remains in this position without active operating voltage for as long as the manual adjustor is engaged.
The actuator independently calibrates itself for each type of connection. Initialization occurs as soon as operating voltage is supplied for the first time and the waiting period ends. The actuator travels to the lower stop of the combi valve, thus enabling automatic coupling with the valve stem. It then travels to the upper stop, records and stores it. Recalibration can be manually triggered any time, see "Recalibration", page 5.
The combi valve can travel to any position by supplying voltage to terminal G1 or G2 as well as L11) or L21).
Voltage on G2, L2: Actuator stem retracts, combi valve opens. Voltage on G1, L1: Actuator stem extends, combi valve closes. No voltage on G1 and G2: Actuator stem stays at the applicable
or L1 and L2: position.
1)
When using the AC 230 V m odule ASP1.1.
3 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
Page 4
Changeover of acting direction
Direct acting
Reverse acting
The acting direction of the stroke direction can be reversed by exchanging connections G1 and G2 or L1 and L2.
Positioning signal OPEN on G2, L2. Positioning signal CLOSED on G1, L1.
Positioning signal OPEN on G1, L1. Positioning signal CLOSED on G2, L2.
Notes
Positioning signals Yu and Yi DC 0-10 V (Yu) DC4-20 mA (Yi)
Direct acting
Reverse acting
Do not use connection Yu (DC 0-10 V) and Yi (DC 4-20 mA). Positioning times can be selected, see "Positioning times“, page 7". Valve characteristic curves "lin" or "log" cannot be selected. Position feedback U is activated after initialization/calibration.
Electronic motor shutdown is triggered in the end positions (valve stop or upon reaching maximum stroke) or by overload (no end switch).
The combi valve can be driven to any position by connecting a continuous positioning signal Yu or Yi. The acting direction can be reserved (direct/reverse acting) by connecting operating voltage to G1 or G2:
Operating voltage AC/DC 24 V on G1 or AC 230 V on L1
Pos. signal to Yu, Yi increasing: Actuator stem retracts, combi valve opens. Pos. signal to Yu, Yi decreasing: Actuator stem extends, v alve closes. Pos. signal to Yu, Yi continuous: Actuator stem remains in the respective pos.
Operating voltage AC/DC 24 V on G2 or AC 230 V on L2
Pos. signal to Yu, Yi increasing: Actuator stem extends, combi valve closes. Pos. signal to Yu, Yi decreasing: Actuator stem retracts, combi valve opens. Pos. signal to Yu, Yi continuous: Actuator stem remains in the respective pos.
Acting direction
Direct acting Reverse acting
Notes
Position signal Operating voltage Actuator stem Combi valve
Yu, Yi increasing G1 to AC/DC 24 V
Retracts Opens
L1 to AC 230 V
Yu, Yi increasing G2 to AC/DC 24 V
Extends Closes
L2 to AC 230 V
The input with the higher value has priority when a positioning signal is available
at both Yu and Yi.
When using the AC 230 V module ASP1.1, the SQV..P can also be
operated with a DC 0…10 V or DC 4…20 mA positioning signal.
The actuator travels to the applicable end position depending on the selected
acting direction if Yu or Yi are interrupted:
Operating voltage to G1 or L1 Actuator stem extends. Operating voltage to G2 or L2 Actuator stem retracts.
Positioning times can be selected, see "Positioning times“, page 7". Valve characteristic curves "lin" or "log" can be selected. Position feedback U is activated after initialization/calibration. Parallel operation with up to 5 actuators possible, see "Technical data", page 10.
4 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
Page 5
Position feedback U
Position feedback U (DC 0…10 V) is always proportional to stroke H for the actuator. It is also active when using the AC 230 V module ASP1.1.
DIL switch Flow characteristics Position feedback U
Fail-safe function
lin = linear
1)
log = equal percentage, ngl = 3
(logarithmic normal)
log = equal percentage, ngl = 3
(exponential normal)
1)
Factory setting
The actuator travels to the applicable end position (the stem retracts or extends depending on the model) using the preloaded spring if operating voltage to terminal G or L is lost or shut down. In this case, the actuator's control function is locked for 45 seconds (both LEDs are green) to reach the end position at any rate. There is no recalibration. The reset positioning speed ensures that no pressure surges occur in the piping.
End position
SQV91P30 Actuator stem retracted Combi valve opened (V = 100%). SQV91P40 Actuator stem extended Combi valve closed (V = 0%).
Recalibration
Recalibration can be manually triggered any time.
1. Operating voltage is supplied.
2. Engage and disengage the manual adjuster twice within 4 seconds.
3. Both LEDs flash green.
4. Recalibration is successful when both LEDs are lit green.
5. Return to normal control function.
Notes
Position feedback U is inactive or corresponds to value "0". The shortest possible runtime is initialized. Recalibration is valid only after the entire process is completed. Additional engaging the manual adjuster interrupts the process.
Blockade detection
The valve actuator indicates detected blockage by setting the feedback signal to 0 V after ca. 90 seconds. The actuator, however, tries to overcome the blockage during this period. Normal control function is reactivated if the blockage is overcome and position feedback U is once again available.
5 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
Page 6
4
833Z0
8
483
3Z0
9
4
8
3
3Z1
0
4833Z11
4833Z12
4
8
33Z13
4
833Z1
4
Response at the end positions
Blockade detection is always operational. In other words, the actuator demonstrates the following response at end positions H
and H0 not only during
100
initialization and calibration, but also during normal control operation:
1. The actuator travels to the end position; the LED is lit in the direction of travel.
2. It detects the end position; both LEDs are lit green.
3. It then briefly travels in the opposite direction; the LED is lit in the direction of travel.
4. It then returns to the end position; LED is lit in the direction of travel
5. It detects the end position; both LEDs are lit green.
This response is repeated with time intervals between travels increasing exponentially. The intervals are:
25 seconds 1 min 40 seconds 6 min 40 seconds 26 min
1 h 46 min 40 seconds 7 h 6 min 40 seconds
1 day 4 h 26 min 40 seconds
for the previous interval.
Status and acting direction indication (LED)
The status and acting direction indication consists of two green, lit LEDs.
Indication Function
ƒ LED flashes
green
ƒ LED flashes
green
ƒ Steady green
ƒ Initialization. ƒ Manual mode.
ƒ Delay after operating voltage is supplied, or the
fail-safe function is triggered.
Actuator stem retracts.
ƒ --
ƒ --
Actuator stem extends.
ƒ Steady green
ƒ Steady green
End position reached.
ƒ Steady green
ƒ LED flashes
Blockage or foreign object detected during retraction.
green
ƒ --
ƒ --
Blockage or foreign object detected during extension.
ƒ LED flashes
green
ƒ --
No operating voltage
ƒ --
Frost protection thermostat.
6 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
The actuators can be operated using a frost protection thermostat or temperature detector, see "Connection diagrams", page 11.
Page 7
4833Z15
123
1
1)
4833Z02
a
483
3Z02b
4833Z
02c
4833Z02
d
483
3Z0
3
a
4833Z03
b
4833Z03
c
4833Z03
d
1 Status and acting
direction indication
(LED) 2 DIL switch 3 Connection
terminals
DIL switch
Positioning times
DIL switch
Flow characteristics
Positioning time
DIL switch Speed
ON
1234
ON
1234
ON
1234
ON
2 sec/mm 40 sec2) 80 sec
3 sec/mm 60 sec 120 sec
4,5 sec/mm 90 sec 180 sec
20 mm 40 mm
2)
6 sec/mm 120 sec 240 sec
1234
1)
Toleranc e: ± 1 sec
2)
Factory setting
The flow characteristics can be used only for connections with constant positioning signals DC 0…10 V and DC 4…20 mA.
DIL switch Flow characteristics
ON
lin = linear
1234
1)
ON
ON
log = equal percentage, ngl =
3
1234
ON
1234
(logarithmic normal)
log = equal percentage, ngl =
3
1234
1)
Factory setting
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
(exponential normal)
7 / 14
Page 8
Accessories
4833Z18
4833Z17
4833Z16
Type
Stock no.
ASC10.42
S55845-Z137
ASZ7.6/1000
S55845-Z136
ASP1.1
S55845-Z138
Auxiliary switch pair Potentiometer AC 230 V module
Notes
Engineering
Switching points can be continuously adjusted
0…1000 Ω AC 230 V to AC 24 V
converter
between 0 and 100%
Installatio
Max. 1 Max. 1
n
Max. 2
See section "Technical data" (page 10) for more information.
Install electrical connections in accordance with local regulations on electric installations as well as internal or connecting diagrams as of page 10.
Observe safety regulations and restrictions designed to ensure the safety of people and property at all times!
An internal controller controls the actuator for 3-position or DC 4…20 mA
positioning signal connection types, see "Connection diagrams", page 11.
For DC 0…10 V connections (input impedance Ri = 100 k), up to 5 actuators
can be controlled in parallel by a controller with a rating of 1 mA.
The switching points must be entered on the plant diagram when using the
double auxiliary switch ASC10.42.
Do not insulate the actuator console and valve stem, as air circulation must be
ensured.
Non-observance of the above may result in accidents and fires!Do not touch the hot parts without prior protecti ve measures to avoid
burns!
For permitted temperatures, see "Technical data", page 10.
Mounting
Mounting instructions 74 319 0821 0 on mounting combi valves are included in the actuator's packaging. Mounting instructions for accessories are located in the respective packaging.
Accessories Mounting instructions ASC10.42 ASZ7.6/1000 ASP1.1
8 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
S55845-Z137 M4833.1 74 319 0860 0 S55845-Z136 M4833.2 74 319 0861 0 S55845-Z138 M4833.3 74 319 0862 0
Page 9
90°
Mounting positions
90°
Commissioning
Maintenance
Recommendation
Recommendation
Disposal
Repair
Check the wiring and carry out a functional check as part of commissioning. Make or check the settings as per the plant diagram for auxiliary switches and
potentiometers.
The actuators are maintenance-free.
Regularly check functioning (trial) of actuators with safety functions.
When servicing the actuating device:
Switch off both pump and operating voltage. Close the main shutoff valve in the piping. Release pressure in the pipes and allow them to cool down completely. Disconnect electrical connections from the terminals as needed. The actuator must be properly installed prior to recommissioning the valve.
Trigger stroke calibration after servicing.
There are no spare parts available; the entire actuator must be replaced.
Removing the s pring on the ac tuator is prohibited due to the high risk of
injury.
Warranty
Note
The device is considered an electronics device for disposal in terms of European Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this
purpose.
Comply with all local and currently applicable laws and
regulations.
The engineering data specified in section "Equipment combination" (page 2) are only guaranteed in connection with the Siemens valves listed.
When using the actuators together with third-party valves, correct functioning must be ensured by the user, and Siemens will assume no responsibility.
9 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
Page 10
Technical data
2)
3)
3)
5)
SQV..P..
Power supply Operating voltage AC 24 V ± 20%
With ASP1.1 AC 230 V module AC 230 V ± 15%
Frequenc y 50…60 Hz Fusing ac. DIN 57100 part 430 (supply lines) 6 A…10 A slow Power c onsumption 20 VA / 7,5 W
With ASP1.1 AC 230 V module 22 VA
Function data Positioning times 20 mm
40 mm
Positioning force 1100 N Nominal stroke 20 mm / 40 mm / 43 mm Permissible medium temperature (valve fitted) 1…120 °C
Signal inputs Position signal Terminal G1, G2 3-position
Voltage AC 24 V ± 20%
Terminal Yu Voltage DC 0…10 V
Input impedance ≥100 kΩ
Terminal Yi Power DC 4…20 mA
Input impedance 50 Ω
Fail-safe function
Terminal G SQV91P30 Loss of operating voltage
SQV91P40 Loss of operating voltage
Spring r eturn time 20 mm 15 s ec
40 mm 30 sec
Position feedback Position f eedback U DC 0...10 V
Load impedance >2.5 kΩ res.
Connecting cable Wire cross-sectional areas
Cable entry 2 entry points M20 x 1.
Degree of protection Housing from v ertical to horizontal IP 66 as per EN 60529
Insulation class As per EN 60730
AC / DC 24 V III
With ASP1.1 AC 230 V module II
Environme ntal
Operation IEC 60721-3-3
conditions
Climatic conditi ons Class 3K5 Mounting location Indoors (weather-protected) Temperature General 0…55 °C Humidity (non-c ondensing) <95% r.h. Transport IEC 60721-3-2 Climatic conditi ons Class 2K3 Temperature -30…70 °C Humidity <95% r.h. Storage IEC 60721-3-1 Climatic conditi ons Class 1K3 Temperature -30…65 °C Humidity 5…95% r.h. Max. media temperature when mounted on combi valve
Norms and directives
Electromagnetic c ompatibility (Application) For residential, c ommercial and in dustrial environments
Product standard
EU Conformity (CE)
RCM Conf ormity UL conformity AC / DC 24 V UL 873
AC 230 V -
Environme ntal compatibility
DC 24 V ± 15%
40 1) / 60 / 90 / 180 sec 80 1) / 120 / 180 / 240 sec The positioning time depends on the DIL switch setting,
"Positioning times (page 7)
DC 24 V ± 15% AC 230 V ± 15%
Actuator stem retracted, combi valve fully open (100%).
Actuator stem extended, c ombi valve fully closed (0%).
Load Max. 4 mA
0.75…1.5 mm2, AWG 20…16
1 entry points M16 x 1.5
130 °C
EN60730- x
CE1T4833xx01
CE1T4833xx02
5)
5)
The product envir onmental declaration CE1E4833en contains data on environmentally compatible product design and assessments (RoHS complianc e, materials composition, packaging, environmental benefit, disposal).
4)
10 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
Page 11
SQV..P.. Dimensions See "Dimensions" (page 13) Accessories Potentiometer ASZ7.6/1000 0…1000 Ω ± 20%
Voltage AC / DC 24 V
Load < 1 W
Double auxiliary switch ASC10.42 Switching
AC/DC 12…AC 230 V, 6 A resistive, 2 A inductive capacity AC 230 V module ASP1.1
Voltage AC 230 V ± 5%
Power c onsumption 22 VA
1)
Factory setting
2)
Control function is locked for 45 seconds.
3)
At +23 °C ambient temperature and 1100 N nominal load
4)
AWG = American wire gauge.
5)
The documents can be downloaded from http://siemens.c om/bt/download
Connec tion diagr a m s
Connec tion diagr a m s
AC / DC 24 V
DC 0…10 V, DC 4…20 mA 3-position
AC 230 V
Y1 act uator N1 controller F1 frost pr otection thermostat
DC 0…10 V, DC 4…20 mA 3-position
Y1 act uator N1 controller F1 frost pr otection thermostat
11 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
Page 12
1)
1)
Connection terminals DC 0…10 V
AC / DC 24 V
DC 4…20 mA
with AC 230 V module ASP1.1
AC 230 V
Fail-safe function (system potential)
System neutral
AC/DC 24 V, acting direction: Actuator stem extends as the positioning signal increases
AC/DC 24 V, acting dir ection: Actuator stem r etracts as the positioning signal increas es
Positioning signal DC 0…10 V
Positioning signal DC 4…20 mA
Position f eedback DC 0...10 V
AC 230 V, acting direction: Actuator stem retracts as the positioning signal increases
AC 230 V, acting direction: Actuator extends as the positioning signal increases
1)
Neutral
Fail-safe function (phase)
Position f eedback DC 0…10 V
Positioning signal DC 4…20 mA
Positioning signal DC 0…10 V
1)
1)
3-position
1)
Connect either G1 or G; or L1 or L2. Refer to the description at "Positioning signals Yu and Yi", page 4 for additional details.
AC / DC 24 V
With AC 230 V module ASP1.1
AC 230 V
Fail-safe function (system potential)
System neutral
AC/DC 24 V, acting direction: Actuator stem retracts, combi valves fully open (100%)
AC/DC 24 V, acting direction: Actuator stem extends, combi valves fully closed (0%)
Positioning signal DC 0…10 V (not used for the 3-position operation)
Positioning signal DC 4…20 mA (not used for 3-position operation)
Position f eedback DC 0…10 V
AC 230 V, acting direction: Actuator stem extends, combi valves fully closed (0%)
AC 230 V, acting direction, Actuator stem retracts, combi valve fully open (100%)
1)
Neutral
Fail-safe function (phase)
1)
1)
Position f eedback DC 0…10 V
Positioning signal DC 4…20 mA (not used for the 3-position oper ation)
Positioning signal DC 0…10 V (not used for 3-position operation)
1)
Refer to the description at "3-position control sig nal", page 3 for additional details.
12 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
Page 13
Dimensions
All dimensions in mm
289
44
Revision numbers
64
4833Z19
> 100 mm Minimum mounting distance to wall or ceiling, for mounting, ►► >200 mm
Type Revisi on number Type Revision n u mber
SQV91P30 A SQV91P40 A
connection, operation, maintenance etc.
13 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
Page 14
Issued by
www.siemens.c om/buildingtechnologies
Siemens Switzerland Ltd Building Technologies Division International H eadquarters Gubelstrasse 22 6301 Zug Switzerland Tel. +41 58-724 24 24
14 / 14
Siemens Electromotive actuators for combi valves CE1N4833en Building Technologies 2017-11-15
© Siemens Switzerland Ltd, 2011
Technical specifications and availability subject to change without notice.
Loading...