Positioning signal 3-position, DC 0-10 V, DC 4-20 mA
∂ Position feedback and selection of flow characteristic
∂ Manual adjuster, position and status indi cation (LED)
∂ Selectable positioning times 40-240 seconds
∂ Fail-safe function (combi valve open/cl osed)
∂ Selection of acting direction
∂ Optional functio nal extension: Auxiliary switch, potentiometer, and
AC 230 V module
∂ Direct mounting on combi valves
∂ UL approved
Electromotive actuators to operate Siemens combi valves for type series VPF43..
and VPF53.. with 20/40/43 mm stroke, as control valves for ventilation, air
conditioning, district heating and refrigeration plants.
CE1N4833en
2017-11-15
Building Technologies
Page 2
Type summary
2)
TypeStock No.Stroke
SQV91P30
SQV91P40
S55150-A130
S55150-A131
Electrical accessories
Spare parts, rev.
number
Ordering
Pos.
force
20/40/43 mm 1100 N
1)
AC 230 V requires accessory ASP1.1.
2)
The positioning time can be selected using the DIL switch, see page 7.
Operat i ng
voltage
AC/DC 24 V
AC 230 V
Positi oni ng
3-position
DC 0…10 V
1)
DC 4…20 mA
signal
Auxiliary switch
Type
pair
ASC10.42
Spring
return
time
30 sec
Potentiometer
ASZ7.6/1000
Pos. time
20mm 40mm
40 sec
60 sec
90 sec
120 sec
80 s
120 s
180 s
240 s
AC 230 V module
ASP1.1
Stock numberS55845-Z137S55845-Z136S55845-Z138
Max. 2
SQV91P30
SQV91P40
Max. 1Max. 1
Max. 1Max. 1
No spare parts available.
Revision numbers, see page 13.
Actuator, combi valve, and accessories are individually packed for delivery.
Valve typeDNPN class
Flow V
[m3/h]
100
Data sheet
Combi valves
50
2,3…25
654,4…35
VPF43..
Flange
805,3…43
10012,1…90
16
N4315
12518,5…135
15025,6…195
50
2,3…25
654,4…35
VPF53..
Flange
805,3…43
10012,1…90
25
N4316
12518,5…135
15025,6…195
2 / 14
SiemensElectromotive actuators for combi valvesCE1N4833en
Building Technologies2017-11-15
Page 3
Technology/Mechanical design
1
4833Z01
1235764
The actuator can be operated as a 3-position or modulating actuator in two acting
directions depending on the type of connection. It is suitable for both combi valves
VPF.. with 20 mm stroke as well as for valves with a 40 mm and 43 mm stroke. The
stroke is calibrated automatically during initialization.
The actuator includes a position feedback.
The actuator travels to the end position in the event of power loss, see "Fail-safe
function", page 5. Up to 45 seconds pass until the actuator is available again following
a restart or start after the fail-safe function is triggered.
The positioning time (40 to 240 seconds) and the flow characteristic (lin/log) can be set
via the DIL switches.
1 Status and acting direction
indication (LED)
2 Housing cover
3 Entry points for cable glands
4 Manual adjuster
5 Indication of upper end
position
6 Valve stem coupling
7 Indication of lower end
position
8 Valve neck coupling
Auto mode
Manual mode
Initialization, automatic
coupling, calibration
3-position control signal
The manual adjuster is disengaged.
The manual adjuster allows for manually setting the position. The motor is switched off
when the manual adjuster is engaged. The fail-safe function (spring return) is
reactivated after the manual adjuster is disengaged, and the actuator travels again to
the set position without calibration.
The actuator remains in this position without active operating voltage for as long as the
manual adjustor is engaged.
The actuator independently calibrates itself for each type of connection. Initialization
occurs as soon as operating voltage is supplied for the first time and the waiting period
ends. The actuator travels to the lower stop of the combi valve, thus enabling automatic
coupling with the valve stem. It then travels to the upper stop, records and stores it.
Recalibration can be manually triggered any time, see "Recalibration", page 5.
The combi valve can travel to any position by supplying voltage to terminal G1 or G2 as
well as L11) or L21).
∂ Voltage on G2, L2:Actuator stem retracts, combi valve opens.
∂ Voltage on G1, L1:Actuator stem extends, combi valve closes.
∂ No voltage on G1 and G2:Actuator stem stays at the applicable
or L1 and L2:position.
1)
When using the AC 230 V m odule ASP1.1.
3 / 14
SiemensElectromotive actuators for combi valvesCE1N4833en
Building Technologies2017-11-15
Page 4
Changeover of acting
direction
Direct acting
Reverse acting
The acting direction of the stroke direction can be reversed by exchanging
connections G1 and G2 or L1 and L2.
Positioning signal OPEN on G2, L2. Positioning signal CLOSED on G1, L1.
Positioning signal OPEN on G1, L1. Positioning signal CLOSED on G2, L2.
Notes
Positioning signals Yu
and Yi
DC 0-10 V (Yu)
DC4-20 mA (Yi)
Direct acting
Reverse acting
∂ Do not use connection Yu (DC 0-10 V) and Yi (DC 4-20 mA).
∂ Positioning times can be selected, see "Positioning times“, page 7".
∂ Valve characteristic curves "lin" or "log" cannot be selected.
∂ Position feedback U is activated after initialization/calibration.
Electronic motor shutdown is triggered in the end positions (valve stop or upon
reaching maximum stroke) or by overload (no end switch).
The combi valve can be driven to any position by connecting a continuous positioning
signal Yu or Yi. The acting direction can be reserved (direct/reverse acting) by
connecting operating voltage to G1 or G2:
Operating voltage AC/DC 24 V on G1 or AC 230 V on L1
∂ Pos. signal to Yu, Yi increasing: Actuator stem retracts, combi valve opens.
∂ Pos. signal to Yu, Yi decreasing: Actuator stem extends, v alve closes.
∂ Pos. signal to Yu, Yi continuous: Actuator stem remains in the respective pos.
Operating voltage AC/DC 24 V on G2 or AC 230 V on L2
∂ Pos. signal to Yu, Yi increasing: Actuator stem extends, combi valve closes.
∂ Pos. signal to Yu, Yi decreasing: Actuator stem retracts, combi valve opens.
∂ Pos. signal to Yu, Yi continuous: Actuator stem remains in the respective pos.
Acting direction
Direct acting
Reverse acting
Notes
Position signalOperating voltageActuator stemCombi valve
Yu, Yi increasingG1 to AC/DC 24 V
RetractsOpens
L1 to AC 230 V
Yu, Yi increasingG2 to AC/DC 24 V
ExtendsCloses
L2 to AC 230 V
∂ The input with the higher value has priority when a positioning signal is available
at both Yu and Yi.
∂ When using the AC 230 V module ASP1.1, the SQV..P can also be
operated with a DC 0…10 V or DC 4…20 mA positioning signal.
∂ The actuator travels to the applicable end position depending on the selected
acting direction if Yu or Yi are interrupted:
Operating voltage to G1 or L1Actuator stem extends.
Operating voltage to G2 or L2Actuator stem retracts.
∂ Positioning times can be selected, see "Positioning times“, page 7".
∂ Valve characteristic curves "lin" or "log" can be selected.
∂ Position feedback U is activated after initialization/calibration.
∂ Parallel operation with up to 5 actuators possible, see "Technical data", page 10.
4 / 14
SiemensElectromotive actuators for combi valvesCE1N4833en
Building Technologies2017-11-15
Page 5
Position feedback U
Position feedback U (DC 0…10 V) is always proportional to stroke H for the actuator. It
is also active when using the AC 230 V module ASP1.1.
DIL switchFlow characteristicsPosition feedback U
Fail-safe function
lin = linear
1)
log = equal percentage, ngl = 3
(logarithmic normal)
log = equal percentage, ngl = 3
(exponential normal)
1)
Factory setting
The actuator travels to the applicable end position (the stem retracts or extends
depending on the model) using the preloaded spring if operating voltage to terminal G
or L is lost or shut down. In this case, the actuator's control function is locked for 45
seconds (both LEDs are green) to reach the end position at any rate. There is no
recalibration. The reset positioning speed ensures that no pressure surges occur in the
piping.
End position
SQV91P30 Actuator stem retractedCombi valve opened (V = 100%).
SQV91P40 Actuator stem extendedCombi valve closed (V = 0%).
Recalibration
Recalibration can be manually triggered any time.
1. Operating voltage is supplied.
2. Engage and disengage the manual adjuster twice within 4 seconds.
3. Both LEDs flash green.
4. Recalibration is successful when both LEDs are lit green.
5. Return to normal control function.
Notes
∂ Position feedback U is inactive or corresponds to value "0".
∂ The shortest possible runtime is initialized.
∂ Recalibration is valid only after the entire process is completed.
∂ Additional engaging the manual adjuster interrupts the process.
Blockade detection
The valve actuator indicates detected blockage by setting the feedback signal to 0 V
after ca. 90 seconds. The actuator, however, tries to overcome the blockage during this
period. Normal control function is reactivated if the blockage is overcome and position
feedback U is once again available.
5 / 14
SiemensElectromotive actuators for combi valvesCE1N4833en
Building Technologies2017-11-15
Page 6
4
833Z0
8
483
3Z0
9
4
8
3
3Z1
0
4833Z11
4833Z12
4
8
33Z13
4
833Z1
4
Response at the end
positions
Blockade detection is always operational. In other words, the actuator
demonstrates the following response at end positions H
and H0 not only during
100
initialization and calibration, but also during normal control operation:
1. The actuator travels to the end position; the LED is lit in the direction of travel.
2. It detects the end position; both LEDs are lit green.
3. It then briefly travels in the opposite direction; the LED is lit in the direction of travel.
4. It then returns to the end position; LED is lit in the direction of travel
5. It detects the end position; both LEDs are lit green.
This response is repeated with time intervals between travels increasing
exponentially. The intervals are:
25 seconds
1 min 40 seconds
6 min 40 seconds
26 min
1 h 46 min 40 seconds
7 h 6 min 40 seconds
1 day 4 h 26 min 40 seconds
for the previous interval.
Status and acting
direction indication (LED)
The status and acting direction indication consists of two green, lit LEDs.
IndicationFunction
ƒ LED flashes
green
ƒ LED flashes
green
ƒ Steady green
ƒ Initialization.
ƒ Manual mode.
ƒ Delay after operating voltage is supplied, or the
fail-safe function is triggered.
Actuator stem retracts.
ƒ --
ƒ --
Actuator stem extends.
ƒ Steady green
ƒ Steady green
End position reached.
ƒ Steady green
ƒ LED flashes
Blockage or foreign object detected during retraction.
green
ƒ --
ƒ --
Blockage or foreign object detected during extension.
ƒ LED flashes
green
ƒ --
No operating voltage
ƒ --
Frost protection
thermostat.
6 / 14
SiemensElectromotive actuators for combi valvesCE1N4833en
Building Technologies2017-11-15
The actuators can be operated using a frost protection thermostat or temperature
detector, see "Connection diagrams", page 11.
Page 7
4833Z15
123
1
1)
4833Z02
a
483
3Z02b
4833Z
02c
4833Z02
d
483
3Z0
3
a
4833Z03
b
4833Z03
c
4833Z03
d
1 Status and acting
direction indication
(LED)
2 DIL switch
3 Connection
terminals
DIL switch
Positioning times
DIL switch
Flow characteristics
Positioning time
DIL switchSpeed
ON
1234
ON
1234
ON
1234
ON
2 sec/mm40 sec2) 80 sec
3 sec/mm60 sec120 sec
4,5 sec/mm90 sec180 sec
20 mm40 mm
2)
6 sec/mm120 sec240 sec
1234
1)
Toleranc e: ± 1 sec
2)
Factory setting
The flow characteristics can be used only for connections with constant positioning
signals DC 0…10 V and DC 4…20 mA.
DIL switchFlow characteristics
ON
lin = linear
1234
1)
ON
ON
log = equal percentage, ngl =
3
1234
ON
1234
(logarithmic normal)
log = equal percentage, ngl =
3
1234
1)
Factory setting
SiemensElectromotive actuators for combi valvesCE1N4833en
Building Technologies2017-11-15
(exponential normal)
7 / 14
Page 8
Accessories
4833Z18
4833Z17
4833Z16
Type
Stock no.
ASC10.42
S55845-Z137
ASZ7.6/1000
S55845-Z136
ASP1.1
S55845-Z138
Auxiliary switch pairPotentiometerAC 230 V module
Notes
Engineering
Switching points can be
continuously adjusted
0…1000 ΩAC 230 V to AC 24 V
converter
between 0 and 100%
Installatio
Max. 1Max. 1
n
Max. 2
See section "Technical data" (page 10) for more information.
Install electrical connections in accordance with local regulations on electric
installations as well as internal or connecting diagrams as of page 10.
Observe safety regulations and restrictions designed to ensure the safety of people
and property at all times!
∂ An internal controller controls the actuator for 3-position or DC 4…20 mA
positioning signal connection types, see "Connection diagrams", page 11.
∂ For DC 0…10 V connections (input impedance Ri = 100 kΩ), up to 5 actuators
can be controlled in parallel by a controller with a rating of 1 mA.
∂ The switching points must be entered on the plant diagram when using the
double auxiliary switch ASC10.42.
∂ Do not insulate the actuator console and valve stem, as air circulation must be
ensured.
∂ Non-observance of the above may result in accidents and fires!
∂ Do not touch the hot parts without prior protecti ve measures to avoid
burns!
∂ For permitted temperatures, see "Technical data", page 10.
Mounting
Mounting instructions 74 319 0821 0 on mounting combi valves are included in the
actuator's packaging. Mounting instructions for accessories are located in the
respective packaging.
∂ Check the wiring and carry out a functional check as part of commissioning.
∂ Make or check the settings as per the plant diagram for auxiliary switches and
potentiometers.
The actuators are maintenance-free.
∂ Regularly check functioning (trial) of actuators with safety functions.
When servicing the actuating device:
∂ Switch off both pump and operating voltage.
∂ Close the main shutoff valve in the piping.
∂ Release pressure in the pipes and allow them to cool down completely.
∂ Disconnect electrical connections from the terminals as needed.
∂ The actuator must be properly installed prior to recommissioning the valve.
Trigger stroke calibration after servicing.
∂ There are no spare parts available; the entire actuator must be replaced.
∂ Removing the s pring on the ac tuator is prohibited due to the high risk of
injury.
Warranty
Note
The device is considered an electronics device for disposal in terms of
European Directive 2012/19/EU and may not be disposed of as
domestic garbage.
●Dispose of the device through channels provided for this
purpose.
●Comply with all local and currently applicable laws and
regulations.
The engineering data specified in section "Equipment combination" (page 2) are
only guaranteed in connection with the Siemens valves listed.
When using the actuators together with third-party valves, correct
functioning must be ensured by the user, and Siemens will assume no
responsibility.
9 / 14
SiemensElectromotive actuators for combi valvesCE1N4833en
Building Technologies2017-11-15
Page 10
Technical data
2)
3)
3)
5)
SQV..P..
Power supplyOperating voltageAC 24 V ± 20%
With ASP1.1 AC 230 V module AC 230 V ± 15%
Frequenc y50…60 Hz
Fusing ac. DIN 57100 part 430 (supply lines)6 A…10 A slow
Power c onsumption20 VA / 7,5 W
With ASP1.1 AC 230 V module 22 VA
Function dataPositioning times20 mm
40 mm
Positioning force1100 N
Nominal stroke20 mm / 40 mm / 43 mm
Permissible medium temperature (valve fitted)1…120 °C
Signal inputsPosition signalTerminal G1, G23-position
Voltage AC 24 V ± 20%
Terminal YuVoltage DC 0…10 V
Input impedance≥100 kΩ
Terminal YiPowerDC 4…20 mA
Input impedance50 Ω
Fail-safe function
Terminal GSQV91P30 Loss of operating voltage
SQV91P40Loss of operating voltage
Spring r eturn time20 mm 15 s ec
40 mm30 sec
Position feedbackPosition f eedback UDC 0...10 V
Load impedance>2.5 kΩ res.
Connecting cableWire cross-sectional areas
Cable entry2 entry pointsM20 x 1.
Degree of protectionHousing from v ertical to horizontalIP 66 as per EN 60529
Insulation classAs per EN 60730
AC / DC 24 VIII
With ASP1.1 AC 230 V moduleII
Environme ntal
OperationIEC 60721-3-3
conditions
Climatic conditi onsClass 3K5
Mounting locationIndoors (weather-protected)
Temperature General0…55 °C
Humidity (non-c ondensing)<95% r.h.
TransportIEC 60721-3-2
Climatic conditi onsClass 2K3
Temperature-30…70 °C
Humidity<95% r.h.
StorageIEC 60721-3-1
Climatic conditi onsClass 1K3
Temperature-30…65 °C
Humidity5…95% r.h.
Max. media temperature when mounted on
combi valve
Norms and directives
Electromagnetic c ompatibility (Application)For residential, c ommercial and in dustrial environments
Product standard
EU Conformity (CE)
RCM Conf ormity
UL conformityAC / DC 24 VUL 873
AC 230 V-
Environme ntal
compatibility
DC 24 V ± 15%
40 1) / 60 / 90 / 180 sec
80 1) / 120 / 180 / 240 sec
The positioning time depends on the DIL switch setting,
"Positioning times“ (page 7)
DC 24 V ± 15%
AC 230 V ± 15%
Actuator stem retracted, combi valve fully open (100%).
Actuator stem extended, c ombi valve fully closed (0%).
LoadMax. 4 mA
0.75…1.5 mm2, AWG 20…16
1 entry pointsM16 x 1.5
130 °C
EN60730- x
CE1T4833xx01
CE1T4833xx02
5)
5)
The product envir onmental declaration CE1E4833en
contains data on environmentally compatible product
design and assessments (RoHS complianc e,
materials composition, packaging, environmental benefit,
disposal).
4)
10 / 14
SiemensElectromotive actuators for combi valvesCE1N4833en
Building Technologies2017-11-15