∂ SAY31P03 Operating voltage AC 230 V, 3-position control signal
∂ SAY61P03 Operating voltage AC/DC 24 V, control signal DC 0…10 V,
4…20 mA
∂ SAY81P03 Operating voltage AC/DC 24 V, 3-position control signal
∂ SAY61P03 Position feedback, override control,
choice of flow characteristic
∂ For direct mount ing on valves; no adjustments required
∂ Manual adjuster, position indicator and status indication per LED
∂ Optional functions with auxiliary switches,
function module
Electromotoric actuators for the operation of Siemens combi valves of type
VPI46.40F9.5Q and VPI46.50F12Q with 15 mm stroke as control valves in ventilation, air conditioning, and district heating systems.
Optional accessories: Auxiliary switch ASC10.51, s equence control, control action changeover
AZX61.1
Product no.
Stock no.S55845-Z103S55845-Z107
SAY31P..
SAY61P..
SAY81P..
Operating
voltage
AC 230 V 3-position
AC/DC 24 V
Auxiliary switch
ASC10.51
Max. 2Max. 1 AZX61.1
Positioning
signal
DC 0…10 V
DC 4…20 mA
0…1000 Ω
3-position
Function module
Spr. ret.
time
-30 s
AZX61. 1
Pos.
time
LED
-
Ο
-
Manual
adjuster
Push and fix
Weather shield ASK39.1
Extra
functions
1)
2), 3)
1)
Example
Delivery
Spare parts
Product no.Stock no.DescriptionQuantity
SAY81P03S55150-A 134Actuator1
ASC10.51S55845-Z103
Auxiliary switch
Actuators, valves and accessories are supplied in individual packs.
Housing coverScrew (valve stem c oupling)
Product nu mber /
Stock number
8000060843
U-brac ket
1
2 / 10
SiemensElectromotoric actuators for valvesA6V10628469_de--_c
Building Technologies2018-03-12
Page 3
Combinations
100
min
1)
TypeStock no.DN[mm][l/h][l/h][kPa]Data shee t
VPI46. 40F 9.5QS55264-V12940
VPI46.50F12QS55264-V130501400 11500 36
Product docume nta tion
Notes
Engineering
SAY31P03 and
SAY81P03
SAY61P03
Mounting
Mounting positions
%
V
H
1370 950025
15
%
V
min
100
∆p
N4855
Detailed Informations about the New Generation actuators can be found in the Basic
documentation for actuators (P4040).
3-position actuators must have their own specific controller, refer to "Connection
Diagrams" (page 8).
Up to 10 actuators can drive in parallel on a controller output with a rating of 1 mA.
Modulating actuators have an input impedance of 100 kΩ.
Indoor useOutdoor use
Acting direction
Maintenance
1)
Only in connection wit h weather shield ASK39.1
With valves whose stem is retracted in the fully closed position, "direct acting" means
that the valve is fully closed (100 %) when positioning signal Y = 0 V and Z = 0 Ω respectively.
Direct acting
Pos. signal Y DC 0…10 V
Pos. signal Z 0...1000 Ω
Y, ZP ositioning signal
VVolumetric flow
Acting dir ection: direct
4...20 mA
The actuators are maintenance-free.
3 / 10
SiemensElectromotoric actuators for valvesA6V10628469_de-- _c
Building Technologies2018-03-12
Page 4
Warranty
The engineering data specified in chapter "Combinations" (page 3) are only
guaranteed in connection with the Siemens valves listed.
Note
Disposal
When using the actuators in connection with valves of other manufacture,
correct functioning must be ensured by the user, and Siemens will assume
no responsibility.
The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be
disposed of as domestic garbage.
∂ Dispose of the device through channels provided for this
purpose.
∂ Comply with all local and currently applicable laws and regu-
lations.
4 / 10
SiemensElectromotoric actuators for valvesA6V10628469_de--_c
Building Technologies2018-03-12
Page 5
Technical Data
1)
1)
2)
SAY..P
Power supplyOperating voltage
Frequenc y45…65Hz
External supply line protection (EU)
Power consumption at 50 Hz
SAY31P03Stem retracts / extends6 VA / 3.5 W
SAY61P03Stem retracts / extends8 VA / 3.75 W
SAY81P03Stem retracts / extends5 VA / 3.75 W
Function dataPositioning times (with the specified nominal stroke)
The positioning time can vary, depending on the type
of valve -> refer chapter "Type summary" (page 2)
Positioning force200 N
Nominal stroke15 mm
Permissible medium temperature (valve fitted)1…120 °C
Signal inputsPositioning signal ”Y”SAY31P03, SAY81P033-position
SAY61P03 (DC 0...10 V) Current draw ≤ 0.1 mA
SAY61P03 (DC 4...20 mA) Current draw DC 4...20 mA ± 1%
Parallel operationSAY61P03≤ 10 (depending on c ontroler output)
Forced controlPositioning signal ”Z”SAY61P03 R = 0…1000 Ω, G, G0
Position feedbackPosition f eedback USAY61P03 DC 0...10 V
Connecting cableWire cross-sectional areas
Cab le entriesSAY..P..
SAY31P03AC 230 V ±15%
SAY61P03AC 24 V ± 20% / DC 24 V + 20% / -15%(SE LV)
SAY81P03AC 24 V ±20% / DC 24 V + 20 % / -15%(SELV)
∂ Fuse slow 6…10 A
∂ Circuit breaker max. 13 A, Characteristic B, C,
D according to EN 60898
∂ Power s ource with curr ent limitation of
max. 10 A
SAY31P03, SAY61P03, SAY81P0330 s
SAY31P..Voltage AC 230 V ±15%
SAY81P..Voltage AC 24 V ± 20 % / DC 24 V + 20 % / -15%
Input impedance ≥ 100 kΩ
Input impedance ≤ 500 Ω
R = 0…1000 Ω Stroke proportional to R
Z connected to G Max. stroke 100%
Z connected to G0 Min. stroke 0%
Voltage Max. AC 24 V ± 20%
Max. DC 24 V + 20% / -15%
Current draw ≤ 0.1 mA
Load impedance > 10 kΩ res.
Load Max. 1 mA
0.75…1.5 mm2, AWG 20…16
EU:2 entries ⊕ 20.5 mm (f or M20)
1 entry ⊕ 25.5 mm (for M25)
1)
Observe acting direction of DIL switches
2)
AWG = Americ an wire gauge
5 / 10
SiemensElectromotoric actuators for valvesA6V10628469_de-- _c
Building Technologies2018-03-12
Page 6
Degree of protectionProtection degree of housing from vertic al to
1)
2)
2)
3)
IP54 as per EN 60529
horizontal
Protection classAs per EN 60730-1
Actuators SAY31P03YAC 230 V II
Actuators SAY61P03YAC / DC 24 V III
Actuators SAY81P03YAC / DC 24 V III
Environmental conditionsOperationIEC 60721-3-3
Climatic conditionsClass 3K5
Mounting locationIndoors (weather-protected)
Temperature General5…55 °C
1 – 2 frost hazard / sensor is interrupted (thermostat closes with frost)
1 – 3 normal operation
F3Temperature detector
F4Frost protection monitor with 0…1000 Ω signal output, does NOT support QAF21.. or QAF61..
MMeasuring neutral
N1C ontrol ler
SNS ystem neutral
SPSystem potential AC/DC 24 V
UPosition f eedback
YPosition signal
ZPositioning signal forc ed control