Siemens Acvatix SAS31.03, Acvatix SAS61.53, Acvatix SAS61.33 User Manual

Page 1
SAS31.03 SAS61.53 SAS61.33
Acvatix™ Actuators SAS.., SAT.. for valves
Basic Documentation
CE1P4041en 2015-05-19 Building Technologies
Page 2
Building Technologies 2015-05-19
Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzer l and Phone +41 41-724 24 24
www.sie
mens.com/buildingtech nologies
© Siemens Switzerland Ltd, 2015
Technical specif ications and avail ability subject to change with out notice.
Page 3
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Contents 2015-05-19
Contents
1 About this document ation ................................................................... 5
1.1 Navigation ............................................................................................. 5
1.2 Revision history ..................................................................................... 5
1.3 Reference documents ............................................................................ 5
1.4 Before you start ..................................................................................... 5
1.4.1 Trad emarks ........................................................................................... 5
1.4.2 Copyright ............................................................................................... 5
1.4.3 Quality assurance .................................................................................. 6
1.4.4 Documen t use / reque st to the reader .................................................... 6
1.5 Scope of this documen tation .................................................................. 6
2 Engineering .......................................................................................... 7
2.1 Product description ................................................................................ 7
2.2 Use ........................................................................................................ 7
2.3 Typ e summa ry ....................................................................................... 8
2.3.1 Stroke actuators ..................................................................................... 8
2.4 Ordering ................................................................................................ 8
2.5 Equipment comb inations ........................................................................ 9
2.5.1 2-port / 3-por t threa d ed va l ves w ith s tro ke actu ato r SA S.. ...................... 9
2.5.2 2-port / 3-por t thread ed va l ves w ith stroke actu a tor SAT.. ....................... 9
2.6 Accessories ......................................................................................... 10
2.6.1 Electrica l acces sories .......................................................................... 1 0
2.6.2 Mechan ical accessories ....................................................................... 10
2.7 Product replacement s .......................................................................... 10
2.7.1 Stro ke actuators SAS../S A T.. to SQS.. .................................................. 10
2.7.2 Electrica l access ories .......................................................................... 1 1
2.8 Sp are parts .......................................................................................... 1 1
2.9 Sizing .................................................................................................. 12
2.9.1 Paralle l operation of actuators .............................................................. 12
2.9.2 Permiss ible cab le length and wire cros s -sectio nal area ........................ 12
2.10 Warranty .............................................................................................. 13
3 Handling ............................................................................................. 14
3.1 Mounting and inst allation ..................................................................... 14
3.1.1 Mounting positions ............................................................................... 14
3.1.2 Fitting stro ke actu ato rs SAS.. to thread e d valves ................................. 14
3.1.3 Accessories ......................................................................................... 15
3.1.4 Wiring (installat ion) .............................................................................. 18
3.2 Commiss ioning and operation .............................................................. 20
3.2.1 Function check and Calibra tion ............................................................ 20
3.2.2 Maintenance ........................................................................................ 22
3.2.3 Disposa l .............................................................................................. 22
4 Functi ons and control ....................................................................... 23
4.1 3-pos ition contro l ................................................................................. 23
4.2 Modulat ing control ............................................................................... 25
4.2.1 Position ing signal and flow character istic selec tion ............................... 26
4.2.2 Position feedback U ............................................................................. 27
4.2.3 Calibration ........................................................................................... 27
4.2.4 Signal priorities .................................................................................... 2 8
Page 4
Building Technologies Contents 2015-05-19
4.2.5 Detection of val ve seat ......................................................................... 29
4.2.6 Detection of foreign bod ies .................................................................. 30
4.2.7 Forced contro l Z .................................................................................. 30
4.3 T ech nical and mechan ical design ......................................................... 31
4.3.1 Tran smission of powe r ......................................................................... 31
4.3.2 Coupling .............................................................................................. 31
4.3.3 Fail safe function ................................................................................. 32
4.3.4 Manua l adjus ter ................................................................................... 33
4.3.5 Indicators ............................................................................................. 34
4.3.6 Electrica l acces sories .......................................................................... 3 5
4.3.7 Mechan ical accessories ....................................................................... 35
5 Tec hnical data .................................................................................... 36
6 Connec tion diagrams and dimens ions ............................................. 38
6.1 Interna l diagra ms ................................................................................. 38
6.2 Conne ction terminals ........................................................................... 39
6.2.1 Actuators ............................................................................................. 39
6.2.2 Electrica l acces sories .......................................................................... 4 0
6.2.3 Cable labeling ...................................................................................... 40
6.3 Conne ction diagrams ........................................................................... 41
6.4 Dimensions.......................................................................................... 42
6.4.1 Stroke actuators ................................................................................... 42
Revision numbers ............................................................................................. 44
7 Glossary ............................................................................................. 45
7.1 Symbols .............................................................................................. 45
7.2 T erms .................................................................................................. 45
Index 47
Page 5
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies About this documentation 2015-05-19
1 About this documentation
1.1 Navigation
Information about a specific actuator is provided throughout the document . The structure of chapters 2 to 4 is as follows:
Glossary and Index are arranged at the end of the document.
1.2 Revision history
Revision Date Changes Chapter
First edition 2015- 05-19 - -
1.3 Reference documents
Type of document SAS.. SAT..
Data Sheet N4581 N4584 Mounting Ins tructions lasered on cover
CE Declaration of Conformit y
AC 230 V T4581X1 T4584X1 AC/DC 24 V T4581X2 T4584X2
Environmental Declaration E4581 E4584
1.4 Before you start
1.4.1 Trademarks
The table below lists the third-party trademarks used in this document and their legal owners. The use of trademarks is subject to international and domestic provisions of the law.
Trademarks Legal owner
Acvatix
TM
Siemens Switzerland Ltd
All product names listed in the table are registered (®) or not registered (™) trademark s of the owner listed in the table. We forgo the labeling (e.g. using the symbols ® and ™) of t rademarks for the purposes of legibility based on the reference in this section.
1.4.2 Copyright
This document m ay be duplicated and distributed only with the express permission of Siemens, and may be passed on only to authorized persons or companies with the required technical knowledge.
Note
Page 6
Building Technologies About this documentation 2015-05-19
1.4.3 Quality assurance
These documents were prepared with great car e.
· The contents of all documents are checked at regular intervals
· All necessary corrections are included in subsequent versions
· Anpassungen bzw. Documents are automaticall y amended as a consequence of
modificati ons and corrections to the products described Please make sure that you ar e aware of the latest document revision date. If you find lack of clarity while using this document, or if you have any criticisms or suggestions, please contact the product manager in your nearest branch office. The addresses of the Siemens regional companies are available at
www.siem ens.com/acvatix
.
1.4.4 Document use / request to the reader
Before using our products, it is important that you read the documents supplied with or ordered at the same time as the products (equipm ent, applications, tools etc.) carefully and in full. We assume that persons using our products and documents are authorized and trained appropriately and have the technical knowledge required to use our products as intended. More information on the products and applications is available:
· On the intranet (Siemens employees only) at
https://workspace. sbt.siem ens.com/cont ent/00001123/def ault.aspx.
· From the Siemens branch office near you www.siemens.com/acv atix or from
your system suppli er.
· From the support team at headquarters f ieldsupport-z ug.ch.sbt@si emens.com
if
there is no local point of contact.
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
1.5 Scope of this documentation
This document shall serve as a source of knowledge. In addition t o basi c information, it provides general technical information about the actuators used in HVAC plants. It is also targeted at engineering staff, HVAC electrical planners, system integrators and service engineers and provi des all information required for planning work, correct installation, commissioning and service.
Page 7
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Engineering 2015-05-19
2 Engineering
2.1 Product description
The line of small actuators is comprised of stroke actuators SAS.. and SAT..
1
User interface Electrical connections
2
Power tr ansmission and preparation Print Motor
3
Yoke (for assemb ly of actuat or and seat, slipper valve)
SAS.., SAT..
SAS.. / SAT.. SAS..5.. / SAT ..5.. SAS..33..
A1 Manual adjuster (with slide switch) A2 Dummy cover ( wi thout manual adjuster) A3 Manual adjuster (without slide swi tch) B Cable glands (M16 / M20) C Position indication D Status indication (SA..61.., 0…10 V) E Housing cover F Housing G Valve stem coupling H Housing of spring return
2.2 Use
For use in connection with Siemens 2-port or 3-port valves, as control or shutoff valves for HVAC plants.
Mechanical design
Components
SAS.. / SAT..
Page 8
Building Technologies Engineering 2015-05-19
2.3 Type summary
2.3.1 Stroke actuators
All types: · Stroke 5.5 mm
· Positioning force SAS.. 400 N SAT.. 300 N
Product
no.
Stock no.
Operating
voltage
Positioning
signal
Power
consumption
Positioning
time
Fail safe
function /
Spring return
time
Manual
adjuster
Position
feedback
Remark
SAS31.00
S55158-A106
AC 230 V 3-position
2.8 / 2.4 VA
5)
120 s
no / yes
-
1) 3)
SAS31.03
S55158-A107
3.5 / 2.9 VA
5)
30 s
SAS31.50
S55158-A108 3.5 / 2.9 VA
5)
120 s yes / <28 s
6)
no
SAS31.53
S55158-A109
5.5 / 3.8 VA
5)
30 s yes / <14 s
6)
SAS61.03
S55158-A100
AC/DC 24 V
DC 0…10 V
DC 4…20 mA
0…1000 Ω
5.3 / 4.5 VA
5)
30 s
no /
yes
DC 0…10 V
1)
4)
SAS61.03U
S55158-A100-A100
5.3 / 4.5 VA
5)
2)
SAS61.33
S55158-A101 5.9 / 4.8 VA
5)
yes / <14 s
6)
1)
SAS61.33U
S55158-A101-A100
5.9 / 4.8 VA
5)
2)
SAS61.53
S55158-A102 5.8 / 5.0 VA
5)
no
1)
SAS81.00
S55158-A103
AC/DC 24 V
3-position
2.2 / 2.0 VA
5)
120 s
no /
yes -
1)
SAS81.00U
S55158-A103-A100 2.2 / 2.0 VA
5)
2)
SAS81.03
S55158-A104
2.5 / 2.1 VA
5)
30 s
1)
SAS81.03U
S55158-A104-A100 2.5 / 2.1 VA
5) 2)
SAS81.33
S55158-A105
3.4 / 2.4 VA
5)
yes / <14 s
6)
1)
SAS81.33U
S55158-A105-A100 3.4 / 2.4 VA
5)
2)
SAT31.008
S55158-A119
AC 230 V 3-position
5.0 / 2.5 VA
5)
8 s n o / yes
-
1)
3)
SAT31.51
S55158-A120 5.5 / 3.2 VA
5)
15 s yes / <8 s
6)
no
SAT61.008
S55158-A117
AC/DC 24 V
DC 0…10 V
DC 4…20 mA
0…1000 Ω
7.1 / 4.6 VA
5)
8 s n o / yes
DC 0…10 V
4)
SAT61.51
S55158-A118
6.4 / 4.8 VA
5)
15 s yes / <8 s
6)
no
1)
Cable gland: M16 and M20 (ISO50 262)
2)
Cable gland: ½“ (UL514C)
3)
Approbation: CE
4)
Approb ation: CE and UL (only 24 V)
5)
Sec ond val ue: Power cons umption in neu tral positi on
6)
Spring return time inc reased slightly at low temper atures
2.4 Ordering
Product no. Stock no. Description Quantity
SAS31.00 S55158-A106 Actuator 1 + auxiliary components (connections, auxiliary switches…)
Actuators, valves and accessories are supplied in individual packs.
Example
Delivery
Page 9
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Engineering 2015-05-19
2.5 Equipment combinations
2.5.1 2-port / 3-port threaded valves with stroke actuator SAS..
Typical applications:
· Heating plants
· District heating plants
· Ventilation and air conditi oning pl ants
Actuators
Stroke Positioning force Data sheet
SAS..
5.5 mm 400 N N4581
PN 16 VVG44..
PN 16
VXG44.. SAS..
Medium 1…120 °C Medium 1…120 °C DN G k
vs∆ps∆pmax
Data sheet N4364 Data sheet N4464 [Inch] [m3/h] [kPa] [kPa]
VVG44.15-..
1)
VXG44.15-..
1)
15 G 1 B 0.25 / 0.4 / 0.63 1600 400
VVG44.15-..
1)
VXG44.15-..
1)
15 G 1 B 1 / 1.6 725 400
VVG44.15-..
1)
VXG44.15-..
1)
15 G 1 B 2.5 / 4 400 400 VVG44.20-6.3 VXG44.20-6.3 20 G 1 1/4 B 6.3 750 400 VVG44.25-10 VXG44.25-10 25 G 1 1/2 B 10 400 400 VVG44.32-16 VXG44.32-16 32 G 2 B 16 250 250 VVG44.40-25 VXG44.40-25 40 G 2 1/4 B 25 125 125
PN 25 VVG55.. SAS..
Medium 1…130 °C DN G k
vs∆ps∆pmax
Data sheet N4379 [Inch] [m3/h] [kPa] [kPa]
VVG55.15-..
1)
15 G 3/4 B 0.25 / 0.4 / 0.63 2500 1200
VVG55.15-..
1)
15 G 3/4 B 1 / 1.6 / 2.5 2000 1200
VVG55.20-4 20 G 1 B 4 1000 1000 VVG55.25-6.3 25 G 1 1/4 B 6.3 800 800
1)
.. = insert kvs value
2.5.2 2-port / 3-port threaded valves with stroke actuator SAT..
Typical applications:
· Heating plants
· Ventilation plants
Actuators
Stroke Positioning force Data sheet
SAT..
5.5 mm 300 N N4584
PN 25 VVG549.. SAT..
Medium 2...13 0 °C
1)
DN G k
vs∆ps∆pmax
Data sheet Q4380 [Inch] [m3/h] [kPa] [kPa]
VVG549.15-0.25
15 G 3/4 B
0.25
1200
2500
VVG549.15-0.4 0.4 VVG549.15-0.63 0.63 VVG549.15-1 1
1500
VVG549.15-1.6 1.6 VVG549.15-2.5 2.5 VVG549.20-4K
2)
20 G 1 B 4
1600
VVG549.25-6.3K
2)
25 G 1 1/4 B 6.3
1)
Briefly 150 °C, with ALG..B fittings up to 100 °C
2)
Pressure compensated
Page 10
10 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Engineering 2015-05-19
2.6 Accessories
2.6.1 Electrical accessories
Product no. Accessor y Description
SAS.. / SAT.. ASC10.51 Auxiliary switch
2.6.2 Mechanical accessories
Product no. Accessor y Description
SAS.. / SAT.. ASK39.2 Weather shield
2.7 Product replacements
Replacement of SQS../SSC.. actuators by SAS.. and SAT.. actuators.
· W hen replacing actuators consider positioning force and torque.
· Adjust in the controller the parameter "Running time" (corresponds to positioning
time + idle stroke) and "Positioning time" if changed, to ensure stable control.
· The replacement of accessory items needs t o be taken into consideration also. In that case, compatibility is not necessarily ensured.
2.7.1 Stroke actuators SAS../SAT.. to SQS..
SQS.. SAS.. / SAT..
VVG44.. VXG44.. VVG55.. VVG549..
Pos. time
Pos.
force
Pos. time
Pos.
force
Product no. OEM [s] [N] Prod u ct no. [s] [N] DN15…40 DN15…25 DN15…25 SQS35.00 SQS359.00/189
150
400
SAS31.00 120
400
P P ­SQS35.000C P P ­SQS35.00SL P P -
SQS35.03 SQS359.03
35 SAS31.03 30
P P ­SQS359.03/189 P P -
SQS35.50 - 150 SAS31.50 120 P P ­SQS35.53 - 35 SAS31.53 30 P P
- SQS359.05 15 250 SAT31.008 8 300
- - P
- SQS359.54 20 400 SAT31.51 15 - - P
SQS65 - 150
400
SAS61.03
30 400
P P -
SQS65.2 -
35
- P P ­SQS65.5 - SAS61.53 P P ­SQS65.5U - SAS61.33U P P ­SQS65U - SAS61.03U P P ­SQS85.00 - 150
400
SAS81.00 120
400
P P -
SQS85.03 -
35
SAS81.03
30
P P -
SQS85.53U - SAS81.33U P P -
Note
Page 11
11 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Engineering 2015-05-19
2.7.2 Electrical accessories
· If auxiliary switches are used, their switching point s should be indicat ed on the plant schematic.
· Do not insulate the yoke and housing of the actuator and the valve stem, as air circulation must be ensured.
· Non-observance of the above may result in accidents and fires!
· Do not touch the hot parts without prior protective measures to avoid
burns!
Stroke actuators SQS.. SAS.. ASC9.6 Auxiliary switch ASC9.6 ASC10.51
2.8 Spare parts
The following spare parts are av ailable:
Stock number Description
8000069479 Housing cover with screws and
light conductor as an assembly, without laser marking
Notes
SAS.. SAT..
Page 12
12 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Engineering 2015-05-19
2.9 Sizing
2.9.1 Parallel operation of actuators
3-position actuators must have one specifi c controller each; refer to chapter
6.3 Connection diagram s (page 41).
Up to 10 actuators can drive in parallel on a controller output with a rating of 1 mA. Modulating actuators have an input impedance of 100 kΩ.
2.9.2 Permissible cable length and wire cross-sectional area
Cable lengths and wire cross-sectional areas depend on the following criteria of the actuators:
· Current draw
· Permissible voltage drop across the power supply lines
The control acc uracy of the modulating actuators can be improved by using 4-wire connections, t hus ensuring that voltage drops on G0 will not distort t he positioning signal.
When determini ng the cable length and the wire cross-sectional area, adherence to the permissible operating voltage tolerance at the actuator is of importance, in addition to the permissible voltage drop across the operating voltage and signal lines (see table below).
Product
no.
Operating voltage Terminal
Max. permissible voltage
drop
SA..31.. AC 230 V N, Y1, Y2 2% each (total of 4 %) SA..61..
AC/DC 24 V
G0, Y, U 1% each (at DC 0…10 V)
SA..81.. G, Y1, Y2 4% each (tot al of 8%)
The following criteria must be considered:
· With modulating control, the permissible positioning signal error must not exceed 1%, the reason being the voltage drop on the G0 wire.
· The voltage drop, caused by charging current peaks in the actuator’s DC circuit, must not exceed 2 Vpp.
· If the G0 line is not correctly sized, load changes of the actuator due to changes of the DC voltage drop might lead to self-oscillations.
· The operating voltage drop at AC/DC 24 V may be a max im um of 8% (4% across the G0 wire).
SAS31.. and SAS81..
SAS61..
Note
Basic diagram
vol tage
drop across the power supply cabl es
Page 13
13 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Engineering 2015-05-19
The following diagram can be used to determine the cable lengths and wire cross­sectional areas.
Cable leng t h L
Power P
Permissible cable length L as a function of powerP and cross-section al area of wire as a par ameter
P is the decisive power consumption of all actuators connected in parallel. When operating on AC 24 V, power consumption is in VA; when operating on DC 24 V, in W.
Operating voltage Permissible voltage drop / wire Formula for wire le ngth
AC 230 V 2 % of AC 230 V
L = 46 ·
P
A1313 ·
[m]
AC 24 V
4 % of AC 24 V
L =
P
A1313 ·
[m]
1 % of DC 10 V
L =
(DC)I
A5.47 ·
[m]
A Cross-sectional area of wire in mm
2
L Permiss ible wire l ength in m P Power consumption in VA (AC) or W (DC) (see actuator’s rating plate) I(DC) DC current part (in A) on G0 wire
2.10 Warranty
The engineeri ng data specif ied in chapter 2.5 Equipment combinations (page 9) are only guaranteed in connection with the Siemens valves listed.
When using the actuators in connection with valves of other manufacture, correct functioning m ust be ensured by the user, and Siemens will assume no responsibili ty.
L/P-diagram for AC/DC 24 V
Note
Formulas for wire lengths
Note
Page 14
14 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Handling 2015-05-19
3 Handling
3.1 Mounting and installation
3.1.1 Mounting positions
Indoor use Outdoor use
1)
1)
Only in connection with weather shield ASK39.2, housing protection IP54 remains unchanged
3.1.2 Fitting stroke actuators SAS.. to threaded valves
First, observe chapter 3.1.1 Mounting positions.
123
tighten firmly by hand
123
-
tighten firmly by hand
SAS..0.. SAT..0..
SAS..5..
Page 15
15 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Handling 2015-05-19
3.1.3 Accessories
Before fitting the accessory items shown below, the following steps must be performed:
1. Actuat or is mechanically connected to a Siemens valve.
2. Observe compati bility and choice of combinations. Refer to 2.6 (page 10).
3. Disconnect actuator, auxiliary switch from power.
Attention if AC 230 V connected danger of life!
4. Onl y required with actuators without fail safe function: Using the manual adjuster, drive the actuator’s stem to the fully retracted position and fix the coupling. See “M anual operation” and “Fixing the position” ( page 33).
5. To fit an auxiliary switch the housing cover must be removed and the M16 knock-out broken out .
1
PZ 2
2
3
No. 3
A Plug-in space for accessory B
Connection terminal
Special notes on mounting
Interior view
Page 16
16 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Handling 2015-05-19
Scope of delivery
· 1 auxiliary switch
· 1 sc rew
First, observe "Special notes on mounting" (page 15).
123
No.: 1
4
Adjust switch position (refer also to "Manual adjust er" page 33)
Without
fail safe function
(SA..1.0..)
With fail safe function (SA..1.3.. / SA..1.5..)
5
No.: 1
When initial situation: 0 Ω
When initial situation: Ω
Auxiliary switch ASC10.51
Plug-in space for accessory
Page 17
17 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Handling 2015-05-19
6
Observe "Wiring ( installation)" (page 18)
7
Observe "Connection terminals" (page 39)
8 9
max. 1.2 Nm
Before commissioning with the control, check the exact position again; see "Auxiliary switch", page 21.
First, observe "Special notes on mounting” (page 15).
Scope of delivery
Weather shield ASK39.2 2 UV-proof cable ties
· To protect the actuator from weather effects when used outdoors, the weather
shield must always be fitted. The housing protection IP54 remains unchanged.
· If fitted several times, 2 UV-proof cable ties (700 x 7 mm) must be used when
fitted again.
· The manual adjuster cannot be used when the weather shield is mounted.
1
2
Note
Weather shield ASK39.2
Notes
Page 18
18 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Handling 2015-05-19
3.1.4 Wiring (installation)
Conduct the electrical connections in accordance with local regulati ons on electrical installations as well as chapter 6.2 "Connection terminals" on page 39.
The cable endings m ust be prepared before as follows:
A
EU: M20 US: ½“
Connection actuator
B
EU: M16 US: ½“
Connection accessories
Cable glands (not contained in scope of delivery)
Metric Metric Inch thread
M16 M20 ½“
· W ithout cable gland IP protection is not guaranteed!
· Guide the cable in a loop to the cable gland, so water can drop off.
Prior to installation, the following preconditions must be satisfied:
· Actuator is mechanically connected to a Siemens valve.
· Housing cover is removed.
Preparation of wire endings
Cable entries
Cable glands
Notes
Preconditions
Page 19
19 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Handling 2015-05-19
1
No: 4
2
PZ 2
3 4
5 6
Observe "Connection terminals" (page 39)
1
No: 3
2
3 4
Observe "Connection terminals" (page 39)
Actuator
Auxiliary switch ASC10.51
Page 20
20 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Handling 2015-05-19
3.2 Commissioning and operation
3.2.1 Function check and Calibration
Before making the function check, the following preconditions must be satisfied:
· "Environment al conditions" specified in chapter "Technical data" (page 36)
· Actuator is mechanically connected to a Siemens valve.
· Actuator is in "Manual operation" mode (page 33).
If available, the actuator can be operated with the help of t he “Manual adjuster” (see page 33).
Manual adj uster
Stroke
actuator
Rotary actuator
Control path valve Aà AB
Bypass valve
B à AB
Turning in clockw ise direction
Actuator’s stem exten ds
Actuator’s spindle turns in clock w ise direction
Opening Closing
Turning in counter­clockw ise direction
Actuator’s stem retracts
Actuator’s spindle turns in counterclockwise direction
Closing Opening
· If the actuator is forced to travel beyond its end positi ons, overload protection responds.
· Observe informati on given in chapter 4.2.1 Positioning signal and flow characteri stic selection, page 26.
Before making the function check, the following preconditions must be satisfied:
· "Environment al conditions" specified in chapter "Technical data" (page 36).
· Actuator is mechanically connected to a Siemens valve.
· Actuator is in “Automatic” mode (page 33).
· Actuator and, if required, accessories are correctl y fitted and connected. Also
refer to chapter 6.2 Connection terminals (page 39).
· Power i s applied.
Calibration is required with modulating actuators and SA..61.. before the function check.
Before making the calibration, the following preconditions must be satisfied:
· A description of the calibration function is given in chapter 4.2.3 Calibration (page 27).
· Housing cover is removed (see “Special notes on mounting”, page 15).
1
Bridge contact
2
Check LED (pag e 34)
If required, calibration can be repeated any number of times.
Make the function check for modulating actuators after the calibration with a point test according to the following table:
Manually
Notes
Electrically
SA..61..
General notes on calibration
Page 21
21 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Handling 2015-05-19
Connection terminals Stroke actuator Rotary actuator
Control path valve Aà AB
Bypass valve
B à AB
Position
feedback U
Y
6 V
13.6 mA
Actuator’s stem extends (60%)
Actuator’s spindle turns in clockwise direction (60 %)
Opening Closing 6 V
Y
5 V 12 mA
Actuator’s stem retracts (50%)
Actuator’s spindle turns in counterclockwise direction (50 %)
Closing Opening 5 V
Z connected to G
Actuator’s stem extends
Actuator’s spindle turns in clockw ise direction
Opening Closing 10 V
Z connected to G0
Actuator’s stem retracts
Actuator’s spindle turns in counterclockwise direction
Closing Opening 0 V
Only SAS61.33, SAS61.33U , SAS61.53, SAT61.51 No voltage at G and G0 (fail safe function)
1)
Actuator’s stem retracts (until end position is reached)
- Closing Opening -
1)
Closing action is al ways completed firs t, also when power returns.
Make the function check for 3-position actuators according to the f ollowing table:
Connection terminals Stroke actuator Rotary actuator
Control path valve Aà AB
Bypass valve
B à AB
Voltage at Y1 Actuator’s stem extends
Actuator’s spindle turns in clockw ise direction
Opening Closing
Voltage at Y2 Actua tor’s stem retra cts
Actuator’s spindle turns in counter c l ock wise directi on
Closing Opening
No voltage at Y1 and Y2
Actuator’s stem maintains the position
Actuator’s spin dle maintains the position
Maintai ns t he position
Only SAS31.50, SAS31.53, SAS81. 33, SAS81.33U, SAT31.51 No voltage at G and G0 (fail safe function)
1)
Actuator’s stem retracts (until end position is reached)
- Closing Opening
1)
Closing action is al ways completed firs t, also when power returns.
· Observe informati on given in chapter 4.2.1 Positioning signal and flow characteri stic selection, page 26.
Make the function check of the mounted auxiliary switch wit h a point test according to the following table – example switching point at 25% position:
Connection terminals
Stroke
actuator
Rotary
actuator
Terminal
S1 – S3
Terminal
S1 – S2
Voltage at Y2
Y = 0 V
Actuator’s stem retracts (until end position is reached)
Actuator’s spindle turns in counter­clockwise direction (until end position is reached)
- -
No voltage at Y1 und Y2
Y = 0 V
Actuator’s stem maintains the position
Actuator’s spindle maintains the
position Voltage at Y1 for desired valve position % + 2% x positioning time
Example:
SAS31. 00 = 27 % x 120 sec = 32.5 sec
Valve position % + 2% Y = 2.7 V
Actuator’s stem exten ds to desi red position (27%)
Actuator’s
spindle turns in
clockwise
direction to
desired
position (27%)
Check switching point with voltmeter
Actuator’s stem maintains the position
Actuator’s
spindle
maintains the
position
- -
SA..31.. and SA.. 81..
Note
Auxiliary switch ASC10.51
Page 22
22 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Handling 2015-05-19
3.2.2 Maintenance
The actuators are maintenance-free. Mounting:
· Do not touch the valve coupling if the components (valve/pipes) are hot
· If necessary, disconnect electrical connections from the terminals
The actuator must be correctly fitted to the valve before recommissioning.
3.2.3 Disposal
The products contain electric al and electronic components and must not be disposed of together with domestic waste. This applies in particular to the printed circuit board. Legislation may demand special handling of certain components, respectively it may be sensible from an ecological point of view.
Observe all local and currently valid legislation.
Page 23
23 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Functions and control 2015-05-19
4 Functions and control
4.1 3-position control
Example: brushless DC motor with fail saf e function
A 3-position signal drives the actuator via connection terminals Y1 or Y2. The required position is transferred to the valve.
1A/D conversion
2
Control functions
Identification of seat Control of direction Motor control Manual adj us tment
3Brushless DC motor 4Gear t rain
Fail safe function Manual adj us ter
Positioning
signal
Stroke actuator Rotary actuator
Control path valve Aà AB
Bypass valve
B à AB
Voltage at Y1
Actuator’s stem extends
Actuator’s spindle turns in clockwise direction
Opening Closing
Voltage at Y2
Actuator’s stem retracts
Actuator’s spindle turns in counter­clockw ise direction
Closing Opening
No voltage at Y1 and Y2
Actuator’s stem maintains the position
Actuator’s spindle maintai ns t he position
Maintai ns t he position
No voltage at Y1 and Y2; with fail safe function
Actuator’s stem retracts
Actuator’s spindle turns in counter­clockw ise direction
Closing Opening
Observe information given in chapter 4.2.1 Positioning signal and flow characteri stic selection on page 26.
Internal control ensures very constant positioning times and determination of the actuator’s position.
Note
Page 24
24 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Functions and control 2015-05-19
The specified positioning times refer to the respective nominal stroke / nomi nal angular rotati on. Since the end positions of rotary actuators are inside the actuator, the following remarks refer to stroke actuators. The resulting effective strokes vary, depending on the type of valve, resulting in shorter or longer actuator positioning times.
Stroke of valv e- actuator combinati o n [mm]
Positioning time [sec]
Legend diagram
A Mechanical end positi on i n actuator B Valves with 5.5 mm nominal stroke X Time to override idle stroke (delay time), see glossary
Deviations occur
· aft er several positi oni ng signals Y1 and Y2 in the same direction since the stroke movement starts with a delay of 50 ms.
· when positioning signals Y1 and Y2 are active for less than 50 ms since the stroke movement cannot be made in that case.
A B C Y1 Y2 0
Calculated position Actual position
Positioning time [m s]
Positioning signals
(power ap pl i ed)
No power applied
Positioning tim es strok e model
Notes
Page 25
25 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Functions and control 2015-05-19
4.2 Modulating control
The modulating positioning signal drives the actuator steplessly. The positioning si gnal range (DC 0...10 V / DC 4...20 mA /
0...1000 Ω) corresponds i n a linear manner to the positioning range (fully closed...f ully open, or 0…100 % stroke).
The actuator is controlled via terminal Y or forced control Z (page 30). The desired stroke / the desired rotation is transferred to the valve stem / the valve spindl e.
1Calibration slot 2LED (2 colors)
3
DIL switches
Changeover of characteristic Positioning signal
4A/D conversion 5Power supply
6
Control functions
Identification of seat Position control Motor control Detection of foreig n bodies Calibration Forced control Characteristics function Manual adj us tment
7Brushless DC motor 8Gear train
Fail safe function Manual adj us ter
Pos itioni ng signal Stroke actuator Rotary actuator
Control path valve
AàAB
Bypass valve
B à AB
Signal Y, Z increasing Actuator’s stem extends
Actuator’s spindle turns in clockw ise direction
Opening Closing
Signal Y, Z decreasing Actuator’s stem retracts
Actuator’s spindle turns in counter c l ock wise directi on
Closing Opening
Signal Y, Z constant
Actuator’s stem maintains the position
Actuator’s spin dle maintains the position
Maintai ns t he position
No voltage at Y1 and Y2; with fail safe function
Actuator’s stem retra cts
Actuator’s spindle turns in counter c l ock wise directi on
Closing Opening
Observe the information given in chapter 4.2.1 Positioning signal and flow characteri stic selection on page 26.
Note
Page 26
26 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Functions and control 2015-05-19
4.2.1 Positioning signal and flow characteristic selection
1)
Factory setting: All DIL switches set to OFF
Flow characteristic
Actuator Valve VVG44.. / VXG44.. Valve & actuator combined
Valve & actuator & heat
exchang er co mbined
lin
Actuator Valve VVG55.. / VVG549.. Valve & actuator combined
Valve & actuator & heat
exchang er co mbined
log
Y, Z Positioning signal H Stroke
Volumetric flow Heat transfer capacity
Pos itioni ng signal
"Y"
Position
feedback "U"
Flow characteristic
OFF
1)
DC 0…10 V DC 0…10 V
log = equal­percentage
ON DC 4…20 mA DC 0…10 V
lin = linear
DIL switches
Page 27
27 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Functions and control 2015-05-19
4.2.2 Position feedback U
The position feedback U (DC 0...10 V) is always proport ional to stroke H of the actuator’s stem.
Actuator
Positioning signal Y, Z
Actuator
Position feedback U
lin = linear
log = equal­percentage
Actuator
Positioning signal Y, Z
Actuator
Position feedback U
Y, Z Positioning signal H Stroke U Position feedback
4.2.3 Calibration
To match the actuator to production-related mechanical tolerances of the individual valves and to guarantee accurate positioning and position feedback, a calibration should be perform ed when the plant is commissioned (page 20). During commissioning, the actuator detects the valv e’s end positions and files the exact stroke in its internal memory.
Calibration takes place in the following phases:
· Act uator drives to the upper end positi on (1), valve closes. Detect ion of upper end position.
· Act uator drives to the lower end position (2), valve opens. Detection of lower end position.
· The detected values are stored (3). Then the actuator follows the positioning signal.
Observe status indication (LED) during and after calibration (page 34).
Note
Page 28
28 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Functions and control 2015-05-19
4.2.4 Signal priorities
The actuators are c ontrolled via different interli nked positioning signal paths (positioning signal “Y“, forced control input “Z“, manual adjuster). The signal paths are assigned the following priorities (1 = highest priority, 4 = lowest priority):
Priority Description
1
The manu al adjuster always has priority 1, thus overriding all si gnals acti ve at “Z“ or “Y“, indep endent of wh ether or not power is appl ied.
2
Only SA..61..: As soon as a valid positioning signal is active at input “Z“, the position is determined via positionin g signal “Z“ (forced control). Prerequisite: The manual adjuster is not used.
Z
3
The position is determined via positioning sig nal “Y“ at Y, Y1 or Y2. The manual adjust er is not used and on “Z“ there is no ac tive signal.
Y
Manual
adjuster
Forced control
(Z)
Positioning
signal (Y)
Stroke actuator Rotary actuator
Automatic mode
Not connected 5 V
Actuator’s stem travels to position (50%)
Actuator’s spindle travels t o pos iti on (50%)
Automat ic mode
G 3 V Actuator’s s tem extends
Actuator’s spindle turns in clock w ise direction
Automatic mode
G0 3 V Actua tor’s stem retracts
Actuator’s spindle turns in counterclockwise direction
Operated (30%) and
engaged
G 8 V
Actuator’s stem extends manual (to 30%)
Actuator’s spindle turns manually in counte rclockwise directi on (to 30%)
Bold pri nting = posi tioning signal currently active
Priority Description
1
The fail safe function responds in the event of a power failure.
2
The position is solely determined via positioning signal ”Z” (forced control), provid ed p ower is applied.
Z
3
The position is determined by positi oning signal Y, provided power is applied and positioning signal ”Z” is not used.
Y
4
Upon actuation and s lightl y turning in countercl ockwise direction, the manual adjust er remains engaged.
Power applied:
After 5 seconds, the manual adjuster disengages itself and p ositionin g s ignal ”Y” or ”Z” determines the position.
No power applied:
The actuator maintains the p osition defined by the manual adjuster until power returns. Upon restoration of power, an automatic C losedPos ition­Synchr onisation w ill be perf ormed.
Operating
voltage (G/G0)
Manual
adjuster
Forced
control (Z)
Positioning
signal (Y)
Stroke actuator
Applied
Automatic mode
Not connected 5 V
Actuator’s stem travels to position (50%)
Applied
Automatic mode
G 3 V Actuator’s stem extends
Applied
Automatic mode
G0 3 V Act uator’s stem retracts
Interrupted (fail
safe function)
Automatic mode
G 6 V
Actuator’s stem retracts (until end position is reached)
Interrupted (fail safe function)
Operated (30%)and
engaged
G 8 V
Actuator’s stem retracts (until end position is reached), then: Actuator’s stem extends manually (to 30%)
Bold pri nting = posi tioning signal currently active
Actuator without fail safe function
Examples
Actuator with fail safe function
Examples
Page 29
29 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Functions and control 2015-05-19
4.2.5 Detection of valve seat
The actuators feature force-dependent valve seat detection. After calibration, the exact valve stroke is filed in the actuator’s memory . If no force is built up in the calculated end position (e.g. in the event of temperature effects for instance), the actuator continues to operate at a reduced positioning speed until the nominal positioning force is restored. This ensures that the valve always fully closes. After a power failure, valve seat identification is not active – the actuators without fail safe function define their stroke position on power resoration to be at 50%. From now on, the actuator follows the positioning signal. When the valve plug reaches its seat for the first time, the actuator readjusts its stroke model.
The supposed position is 50%, Y = 2 V, the actuator travels 30% of the stored valve stroke in the direction of "Actuator’s stem retracted". If the actuator reaches the seat within this 30% travel, it interprets the position as "Valve fully closed" and shifts the position of t he valve’s stroke accordingly without changing the extent of travel. From now on, the actuator follows the changed valve stroke position. This means: New position 0%, Y = 2 V, actuator travels 20% of the stored valve stroke in the direction "Actuator’s stem extended".
SAS..
Example
Page 30
30 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Functions and control 2015-05-19
4.2.6 Detection of foreign bodies
The actuator detects when the v alve is clogged and adjusts its operational behavior accordingly to prevent damage to itself or the valve. If the actuator hits an obstacle within the calibrated stroke and is not abl e to overcome it with its nominal positioning forc e, it stores the position at which the obstacle was hit. Depending on the direction of travel, as …
"Upper limit of valve clogging", if the clogging was detected when traveling in the direction of "Actuator’s stem ex tending".
Now, the status LED blinks red and the actuator only follows the positioning signal between the positions "Actuator’s stem retracted" and "Lower limit of valve clogging". After detection of cl ogging, 3 attempts are made to overcome clogging by traveling about 15% in the opposite direction and then trying again to overcome the position of clogging. If the attempts made are unsuccessful, the actuator continues to follow the positioning signal within the restricted range only and the LED continues to blink red (see "Status indication " page 34).
4.2.7 Forced control Z
Forced control uses the following operating modes:
Z mode
No function Full y op en Fully closed
Overriding
positioning signal “Y“
by 0…1000 Ω
ConnectionsTransmission
Equal-p ercentage or
linear characteristic
Equal-p ercentage or
linear characteristic
Contact “Z“ not
connected,
valve follows
positioning signal ”Y”
Contact “Z“ is
connected directly to
“G“,
positiong signal ”Y”
has no impact
Contact “Z“ is
connected directly to
“G0“,
positiong signal ”Y” has
no impact
Contact “Z“ is
connected to “M“ via
resistor “R“,
starting point at 50 Ω,
end point at 900 Ω,
positioning signal ”Y”
has no impact
Page 31
31 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Functions and control 2015-05-19
4.3 Technical and mechanical design
4.3.1 Transmission of power
Incoming positioning signals are translat ed to positioning commands for the motor. A gear train transmits the motor’s positioning steps to the output stage. Here, the
translation from rotary to stroke movement takes place. Attached to the gear train are the electrical and mechanical accessory items and the manual adjuster. With the stroke actuators with fail safe function, the gear train also accommodates the return spring.
In the case of the rotary actuators, the adjustment to the required torque is made i n the output stage.
Power transmission of stroke actuator:
1 Actuator stem 2 Contact point
actuator stem – valve stem 3 Valve stem 4 Valve spring
The transmission of power has no f ix connection. If the actuator stem extends, it presses on the valve stem and against the force of the spring in the valve. If the actuator stem retracts, the valve stem follows the actuator stem due to the force of the valve spring.
4.3.2 Coupling
SAS.., SAT..
Actuator stem and valve stem run int o each other. They are not permanently connected.
Function principle
Page 32
32 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Functions and control 2015-05-19
4.3.3 Fail safe function
The fail safe function works mechanically with a return spring and ensures the protecti on of the plant. It guarantees the safe operation in uncontrolled operating states. In the event of a power failure, the actuator will return to its 0 % stroke position with the help of the return spring, closing the valve. The Y positioning signal is not valued.
Fail safe function
Actuator Valve
Spring return
time
At positioning
time
Active
Actuator’s stem retracts
Spring in valv e closes
Valve closes
<8 s
1)
<14 s
1)
<28 s
1)
15 s 30 s
120 s
1)
Spring return time increased slightly at low temperatures
Page 33
33 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Functions and control 2015-05-19
4.3.4 Manual adjuster
Without fail safe function With fail safe function (SA..33..)
When the motor drives the manual adjus ter turns. T hus in autom atic mod e, the manu al adjuster is used for i ndication of travel. If the manu al adjuster is held firm in this mode, there is no transmiss ion of power to the gear train.
When pus hing the manu al adjuster down (1), it en gages and th e actuator can be manually operat ed.
Stroke actuator: When turning the manual adjuster in clockwise / counterclockwise direction (2), the act uator’s st em extends / retracts.
Rotary actuator: The actuator spindle turns in the same direction
When turning the manu al adjust er in c l ockwise directi on (2), the ac tuator’s stem extends.
CAUTION: Turning the manual adjuster in counterc lockwise direction is not possible.
An overl oad prot ection prevents damag e to the manual adjuster.
Upon actuation and locking the slide sw itch, the manual adjuster remains eng aged.
When in this mode, do not turn the manual adjust er (manual adjuster locked).
After push ing and slig htly turni ng t he manual adjust er in counterclockwise direction, it remains engaged, provided no power is applied.
If power is applied, refer to "Disengaging the fixing".
When resetting the slide switch, the manual adjust er returns to automatic mode.
Coupling disengages automatically…
· after 5 seconds if power is applied,
· when power returns; a restart is made
(actuator’s stem retr acts), then, the actuat or follows t he active positioni ng signal.
Coupling is disengaged manually by slight ly turning the manual adjuster in clockwise directi on.
Automatic
Manual operation
Fixing the position
Disengaging the fix i ng
Page 34
34 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Functions and control 2015-05-19
4.3.5 Indicators
A Indication of travel
B Scale
Position indication
C Indicator
D LED Status indication
In Automatic mode, the manual adjuster serves for the indication of travel. See "Automatic" (page 33).
When turning the manual adjuster, the indicator also moves. The scale indicates the stroke. When reaching the stops, the valve is either fully open or fully closed.
Housing cover fitted Housing cover removed
When the h ousing cover is fitted, the LED can be viewed through a light conductor.
When the housing cover is removed, the LED can b e vi ewed throu gh a hole.
The status indication informs about the operational state of the actuator.
LED Indication Operating state Remarks, troubleshooting
Green
On Automatic mode Normal op er at i on
Blinkin g
Calibration Wait until calibration is finished
(then green or red light)
In manual mode Manual adj uster in MAN positi on
Red
On
Calibration error Start calibration again Undervoltage (AC 13 V) Check op erating voltag e
Blinkin g
Clogged valve, det ection of foreign b odi es
Check val ve / actuator
Dark Dark No power or electronic s faulty Ch eck operating voltage
Operational status indication
Positio n indication
Status indication (LED), only with modulating control (only SA..61..)
Page 35
35 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Functions and control 2015-05-19
4.3.6 Electrical accessories
The auxiliary switch ASC10.51 switches on or off when a certain position is reached. The switching point can be set between 0…100%.
Adjustable switching point
Switching point for S1–S2 and S1–S3 cannot be set separately. If S1–S2 is open then S1–S3 is closed.
When using an auxiliary switch, position f eedback can trigger an automati c stop of the circulati ng pump in the end position "Fully closed".
4.3.7 Mechanical accessories
To protect the actuator from weather effects when used outdoors, the weather shield ASK39.2 must always be fitted. The housing protectionIP54 remains unchanged.
Auxiliary switch ASC10.51
Application exam ple:
Weather shield ASK39.2
Page 36
36 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Technical data 2015-05-19
5 Technical data
SAS.. SAT..
Power supply Operating voltage SA..31.. AC 230 V ± 15 %
SA..61..
AC 24 V ± 20 % / DC 24 V + 20 % / -15%
or AC 24 V class 2 (US)
SA..81.. AC/DC 24 V ± 20 %
or AC 24 V class 2 (US)
Frequency 45…65 Hz External supply line protection (EU) 6 A...10 A slow or
Circuit breaker max. 13 A Characteristic B, C, D according to
EN 60898
Power source with current limitation of max. 10 A Power consumption at 50 Hz Stem retr acts / extends Stem retracts / extends SAS31.00 SAT31.008 2.8 / 2.4 VA
1)
5.0 / 2.5 VA
1)
SAS31.03 SAT31.51 3.5 / 2.9 VA
1)
5.5 / 3.2 VA
1)
SAS31.50 SAT61.008 3.5 / 2.9 VA
1)
7.1 / 4.6 VA
1)
SAS31.53 SAT61.51 5.5 / 3.8 VA
1)
6.4 / 4.8 VA
1)
SAS61.03 5.3 / 4.5 VA
1)
SAS61.03U 5.3 / 4.5 VA
1)
SAS61.33 5.9 / 4.8 VA
1)
SAS61.33U 5.9 / 4.8 VA
1)
SAS61.53 5.8 / 5.0 VA
1)
SAS81.00 2.2 / 2.0 VA
1)
SAS81.00U 2.2 / 2.0 VA
1)
SAS81.03 2.5 / 2.1 VA
1)
SAS81.03U 2.5 / 2.1 VA
1)
SAS81.33 3.4 / 2.4 VA
1)
SAS81.33U 3.4 / 2.4 VA
1)
Function data Positioning times with the specified nominal
stroke / nominal angular rotation SAS..0 SAT..008 120 s 8 s SAS..3/..3U SAT..51 30 s 15 s
Positioning force 400 N 300 N Nominal stroke 5.5 mm 5.5 mm Torque Nominal angular rotation Permissible medi um te mperature
(valve fitted)
1...130 °C 1…130 °C
briefly 150 °C
Signal inputs Y positioning signal
SAS31.. SAT31.008
3-position
SAS81.. SAT31.51 SAS61.. SAT61.008
DC 0...10 V / DC 4...20 mA / 0... 1000 Ω
SAT61.51
SA..61.. (D C 0...10 V) Current draw ≤ 0.1 mA
Input imp ed ance ≥ 100 kΩ
SA..61.. (DC 4...20 mA) Current draw DC 4...20 mA ± 1 %
Input imp ed ance ≤ 500 Ω
Parallel operation SA..61.. 10 (depending on controler output)
Forced control Positioning signal Z SA..61.. R= 0…1000 Ω, G, G0
R = 0…1000 Ω Stroke / rotation proportional to R
Z connected to G Max. str oke 100 % Max. stroke 100 %
Z connected to G0 Min. stroke 0 % Min. stroke 0 %
Voltage Max. AC 24 V ± 20 % / Max. DC 24 V + 20 % / -15%
Current draw ≤ 0.1 mA
Position feedback U SA..61.. DC 0...10 V ± 1 %
Load imped ance > 10 kΩ res.
Load Max. 1 mA
Connecting cable Wire cross-secti onal areas 0.7 5…1.5 mm2, AWG 20…16
2
)
Page 37
37 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Technical data 2015-05-19
SAS.. SAT..
Cable entries SA.. EU:
1 entry Æ 16.4 mm (for M16) 1 entry Æ 20.5 mm (for M20)
SA..U US:
2 entries Æ 21.5 mm for ½“ tube connection
Degree of protection Housing protection IP 54 as per EN 60529
3
)
Mounting position vertic al Insulation class As per EN 60730 Actuators SA..31.. AC 230 V II Actuators SA..61.. AC / DC 24 V III Actuators SA..81.. AC / DC 24 V III
Environmental conditions
Operation IEC 60721-3-3
Climatic conditions Class 3K5 Mounting location Indoors, outdoors
4)
Temperature general -5…55 °C Humidity (noncondensing) 5…95 % r. h. Transport IEC 60721-3-2 Climatic conditions Class 2K3 Temperature -25…70 °C Humidity <95 % r. h. Storage IEC 60721-3-1 Temperature -15…55 °C Humidity 5…95 % r. h.
Directives and Standards
Product sta nd ar d EN60730-x Electromagnetic compatibility (Application) For residential, commercial and in dus trial en vironments EU Conformity (CE) CE1T4581xx
5)
RCM Conformity CE1T4581en_C1
5)
UL, cUL AC / DC 24 V
UL 873 http://ul.com/database
Environmental compatibility
The product environmental declarati on CE1E4581
5
)
contains
data on environment ally compati ble product design an d
assessments (RoHS compliance, materials composition,
packaging, environmental b enefit, disposal).
Dimensions See Dimensions (page 42) Weight Excl. packaging See Dimensions (page 42) Accessories
6)
Auxiliary switch ASC10.51
Switching capacity AC 24…230 V , 6 (2) A, floating
External supply lin e protect ion See section power supply
US installation, UL & cUL AC 24 V class 2, 5 A general purpose
Data sheet N4581 N4584
1)
Sec ond value: P ow er consumption in neutral position
2)
AWG = American wire gauge
Wire cross-sectional areas and fuses have to be well- matching, wh ich is the responsibility of the planner / installer. Observe norm of pr otection m easures - pr ot ec tion agai nst overcurrent: IEC 60364-4-43:2008 resp. german adoption HD 60364-4-43:2010.
3)
Also with weather shield ASK39.2
4)
Outdoors alw ays with weather shield ASK39.2, housing protecti on IP54 rem ains unchanged
5)
The d ocuments can be downloaded from http://siem ens.com/b t/download
6)
UL recog nized component
Page 38
38 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Connect ion diagrams and dim ensions 2015-05-19
6 Connection diagrams and
dimensions
6.1 Internal diagrams
SA..31..
SA..31.5..
Accessor y plug-in space A
1x ASC1 0.51
ASC10. 51
Accessor y plug-in space A
1x ASC1 0.51
ASC10. 51
SAS81..
SAS81.33, SAS81.33U
Accessor y plug-in space A
1x ASC1 0.51
ASC10. 51
SA T31.008
Accessor y plug-in space A
-
SA..61..
Page 39
39 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Connect ion diagrams and dim ensions 2015-05-19
6.2 Connection terminals
6.2.1 Actuators
AC 230 V, 3-position
System neutral (SN) Positioning sign al (actuator’s st em extends / actuat or’s spindle turns clockwise) Positioning signal (actuator’s stem retracts / actuator’s spindle turns counter-clockwise)
AC 230 V, 3-position
System neutral (SN) Positioning sign al (actuator’s st em extends / actuat or’s spindle turns clockwise) Positioning signal (actuator’s stem retracts / actuator’s spindle turns counter-clockwise) Fail safe function
AC/DC 24 V, DC 0…10 V / 4…20 mA / 0…1000 Ω
Sytem neutral (SN) System potential (S P) Positioning signal for DC 0…10 V / 4…20 mA Measuring neutral Position feedback DC 0...10 V Positioning signal forced control AC/DC 24 V, 0...1000 Ω
AC/DC 24 V, 3-position
System potential (S P) Positioning sign al (actuator’s st em extends / actuat or’s spindle turns clockwise) Positioning signal (actuator’s stem retracts / actuator’s spindle turns counter-clockwise)
AC/DC 24 V, 3-position
System potential (S P) Positioning sign al (actuator’s st em extends / actuat or’s spindle turns clockwise) Positioning signal (actuator’s stem retracts / actuator’s spindle turns counter-clockwise) System neutral (SN)
AC 230 V, 3-position
System neutral (SN) Positioning sign al (actuator’s st em extends / actuat or’s spindle turns clockwise) Positioning signal (actuator’s stem retracts / actuator’s spindle turns counter-clockwise) System potential (S P)
SA..31..
(without SAT31.008)
SA..31.5..
SA..61..
SA..81..
SAS81.33U
SAT31.008
Page 40
40 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Connect ion diagrams and dim ensions 2015-05-19
6.2.2 Electrical accessories
Adjustable switching points, AC 24…230 V
System potential (S P) Closing (actuator’s stem extends / actuator’s spindl e turns cl ockwise) Opening (actuator’s stem extends / actu ator’s spindle turns clockwise)
6.2.3 Cable labeling
The wires are color coded and labeled.
Connection
Cable
Description
Code No. Color Abbreviation
Actuators AC 230V N 4 blue BU System neu tral
Y1 6 black BK Positioning signal
Y2 7 white WH Positioning signal
L - System p otenti al
21 - Fail safe function
Actuators AC 24 V resp. AC/DC 24 V
G 1 red RD System potential
G0 2 black BK Syst em neutral
Y1 6 violet VT Positioning signal
Y2 7 orange OG Positioning signal
Y 8 grey GY Positioning signal
M - - Measuring neutral
U 9 pink PK P ositi on feedbac k
Z - - Positi onin g sig n al f orc ed cont r ol
Auxiliary switch ASC10.51
Page 41
41 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Connect ion diagrams and dim ensions 2015-05-19
6.3 Connection diagrams
SA..31.. SA..31.5..
A Actuator L Phase N Neutral N1 Controller Y1, Y2 Positioning signals 21 System pot enti al
SA..61..
SAS61.33 SAS61.33U SAS61.53
A Ac tuator F1 Temperature limit er F2 Frost protection thermostat; terminals:
1 – 2 frost hazard / sensor is interrupted (thermostat closes with frost) 1 – 3 normal operation
F3 Temperature detect or F4 Frost protection m onitor with 0…1000 sig nal output,
does NOT support QAF21.. or QAF61..
M Measuring neutral N1 Controller SN S yst em n eutral SP System potential AC/DC 24 V U Position feedback Y Positioning signal Z Positioning signal forced control
SA..81.. SAS81.33, S AS 81. 33 U
A Ac tu ator F1 Temperatur e limi ter N1 Controller SN System n eutral SP System potential AC/DC 24 V Y1, Y2 Positioning signals
SA..31..
SA..61..
SA..81..
Page 42
42 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Connect ion diagrams and dim ensions 2015-05-19
6.4 Dimensions
6.4.1 Stroke actuators
Dimensions in mm, weights in kg
1 SA..: M16 SA..U: ½" (Ø 21.5 mm) 2 SA..: M20 SA..U: ½" (Ø 21.5 mm)
Product no. A B C C1 C2 D E ►►
SAS.. / SAT.. 151 80 93 21.9 71.1 29.9 21.8 100 200 0.40 With ASK39.2 155 126 248 99 149 29.9 21.8 100 200 0.55
With manual adjuster
Page 43
43 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Connect ion diagrams and dim ensions 2015-05-19
1 SA..: M16 2 SA..: M20
Product no. A B C C1 C2 D E ►►
SAT.. / SAT.. 13 7.6
1)
151
2)
80 106.5 21.9 84.6 29.9 21.8 100 200 0.68
With ASK39.2 155 126 248 99 149 29.9 21.8 100 200 0.83
1)
Black cover
2)
Blue manual adjuster
Without manual adjuster
Page 44
44 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Revisi on nu mb ers 2015-05- 19
Revision numbers
Product no.
Valid f rom
rev. no.
Product no.
Valid f rom
rev. no.
Product no.
Valid f rom
rev. no.
SAS31.00 ..A SAT31.008 ..A SAS31.03 ..A SAT31.51 ..A SAS31.50 ..A SAT61.008 ..A SAS31.53 ..A SAT61.51 ..A SAS61.03 ..A SAS61.03U ..A SAS61.33 ..A SAS61.33U ..A SAS61.53 ..A SAS81.00 ..A SAS81.00U ..A SAS81.03 ..A SAS81.03U ..A SAS81.33 ..A SAS81.33U ..A
Page 45
45 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Glossary 2015-05-19
7 Glossary
7.1 Symbols
Caution, general danger – read the notes!
Caution, hot surface – read the notes!
Condition as supplied to costumer
Crosstip screwdriver (Po zidriv) Slotted screwdriver
Screw wrench
Allen key
7.2 Terms
The Synchronisation of the mechanical position and the internal position control will be perform ed (after manual operation).
A DIL switch shows the switching choices in the form of a place value system (dual in line) in relation to basis 2 (on and off).
Nominal size [mm]: Characteristic for matching parts of the piping system.
The fail safe function ensures that the actuator is driven to a defined end position also in the event of a power f ailure. In normal situations, dampers are shut or valves closed, thus cutting off the medium flow.
Unit of pressure: 100 kPa = 1 bar = 10 mWS.
Nominal flow rate: Nominal flow rate of cold water (5…30 °C) through the fully open valve (H
100
) at a differential pressure of 100 kPa (1 bar).
Light emitting diode.
The actuator stem lifts off the valve stem slightly (0.2 mm), so that the valve closed securely. If the valve opens again, this idle stroke has to be overcome, before the valve really opens (valve characteristic has an effect).
PN class [bar]: Charac teristic relating to the combination of mechanical und dimensional properties of a component in the piping system.
Signal used to acquire the position, fed back via an input.
Forced control serves for overriding automatic mode and is implemented in the structure.
ClosedPosition­Synchronisation
DIL switches
DN
Fail safe function
kPa
k
vs
LED
Idle strok e
PN
Position feedback
Forced control
Page 46
46 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Glossary 2015-05-19
Maximum permissible differential pressure across the valve's control path, valid for the entire actuating range of the motorized valve (V = diverting mode).
Maximum permissibl e differential pressure at which the motorized valve will close securely against t he pressure (close off pressure).
Δp
max /ΔpmaxV
Δp
s
Page 47
47 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Index 2015-05-19
Index
3-positio n control.............................................. 23
A/D conver s ion ........................................... 23, 25
About this documenta tion .................................. 5
Acces sories ...................................................... 10
Electrica l acce sso ries ...................................... 10
Mechan ical accesso ries ................................... 10
Automa tic operation ......................................... 3 3
Auxilia ry switch ......................... 16, 19, 21, 35 , 40
Before you star t .................................................. 5
Brushles s DC m otor ................................... 23, 25
Cable entries ..................................................... 18
Cable glands ..................................................... 18
Cable labelin g ................................................... 4 0
Calibrati on ............................................. 20, 25, 27
Calibrati on slot .................................................. 25
Changeov er of characteris tic ........................... 25
Charac teristic s functi on ................................... 25
Commissioning ................................................. 20
Connectio n dia gra ms ................................. 38, 41
Connectio n terminal ......................................... 39
Actuator ........................................................... 39
Electrica l acce sso ries ...................................... 40
Content s .............................................................. 3
Control ............................................................... 23
Control functi ons ........................................ 23, 25
Control of directi on ........................................... 23
Copyright ............................................................ 5
Coupling ............................................................ 31
Cross-s ectional area ......................................... 1 3
Deliver y ............................................................... 8
Detection of fore ig n bodies ........................ 25, 30
Detection of va lve sea t ..................................... 29
Deviations ......................................................... 24
DIL switch .................................................... 25, 26
Dimensio ns ....................................................... 42
Stro ke actua tors .............................................. 42
Disposal ............................................................ 22
Document use ..................................................... 6
Electric al acce ssories ....................................... 3 5
Electric al connec tions ........................................ 7
Electric al planners .............................................. 6
Engineering ......................................................... 7
Equipment combinations
2-port threaded valves ....................................... 9
3-port threaded valve ......................................... 9
3-port threaded valves ....................................... 9
Fail safe function ......................... 8, 23, 25, 28, 32
Fitting
Accessories ..................................................... 15
Stro ke actua tors .............................................. 14
Forced con tr ol ............................................. 25, 30
Foreign bodies.................................................. 30
Formula s for wir e le ngt hs ................................ 13
Function chec k ................................................. 20
Function principle ............................................ 31
Functions .......................................................... 23
Gear train ..................................................... 23, 25
Glossa ry ............................................................ 45
Handlin g ............................................................ 14
Housing cover ................................................... 11
Housing of sprin g return .................................... 7
HV AC plants ........................................................ 6
Identifica tion of seat .................................... 23, 25
Indicator s .......................................................... 34
Indoor use ......................................................... 14
Instal lati on ........................................................ 14
Interior vie w ...................................................... 15
Interna l dia gr a m s.............................................. 38
L/P-dia gra m ...................................................... 13
LED.................................................................... 25
Maintena nc e ..................................................... 22
Manual adjus te r ............................. 7 , 8, 23, 25, 33
Manual operati on .............................................. 33
Mechanic al access ories ................................... 35
Mechanic al desi gn ............................................ 31
Modulat ing c ontr ol ........................................... 25
Motor control ............................................... 23, 25
Mountin g ........................................................... 14
Mountin g pos itions .......................................... 1 4
Navigatio n ........................................................... 5
Operati ng volt age ..........................................8, 13
Operati on .......................................................... 20
Operati onal sta tus ............................................ 34
Orderi ng .............................................................. 8
Outd oor use ...................................................... 14
Paralle l opera ti on ............................................. 12
Permis sible cable length .................................. 12
Permis sible v oltage dr o p ................................. 13
Permis sible wire length .................................... 13
Plug-in spa ce .................................................... 16
Positio n control ................................................ 25
Positio n feed back ..........................................8, 27
Positio n in dic a tion ........................................7 , 34
Positioning signal.................. 8, 20, 21, 23, 25, 26
Positioning time ............................................8, 24
Power consumptio n ......................................8, 13
Power supply .................................................... 25
Power trans m iss i on ........................................... 7
Print..................................................................... 7
Product descripti on ............................................ 7
Product rep lac eme nt s ...................................... 10
Electrica l access ories ....................................... 11
Page 48
48 / 50 Siemens Actuators SAS.., SAT.. for valves CE1P4041en
Building Technologies Index 2015-05-19
Stro ke actuato rs SQX.. zu SAX.. ...................... 10
Quality assurance ............................................... 6
Refere nce documents ......................................... 5
Request to the reader ......................................... 6
Revision history .................................................. 5
Revision numbers ............................................. 44
Scope of this docume nta tion ............................. 6
Signal priorit ies................................................. 28
Sizing................................................................. 12
Spa re parts ........................................................ 11
Sta tus indica tion ................................................. 7
Strok e model ..................................................... 2 4
Symbols ............................................................ 4 5
Tec hnica l data ................................................... 3 6
Tec hnical design ............................................... 31
Ter ms .................................................................45
Tra demarks ......................................................... 5
Transmission of power......................................31
Type summary
Stro ke actuato rs ................................................ 8
Use ...................................................................... 7
User interfa ce ..................................................... 7
voltage drop .......................................................12
V olumendurc hflus s ...........................................26
W a r ranty ............................................................13
Wea ther shield ............................................. 17 , 35
Wire cr oss-sectional area .................................12
Wire endin gs ......................................................18
Wiring ........................................................... 17, 18
Y oke .................................................................... 7
Page 49
49 / 50
Siemens Actuators SAS.., SAT.. for valves CE1P4041en Building Technologies Index 2015-05-19