Siemens ACVATIX G B111.9E/KN, ACVATIX GDB111.9E/KN, ACVATIX GLB111.9E/KN Series Manual

Page 1
ACVATIX™
Rotary actuator for ball valves KNX / PL-Link
s
G..B111.9E/KN
Rotary actuator 5 / 10 Nm with KNX communication for 6-port control ball valves and ball valves
A6V10725318_en--_e Siemens 2018-06-05 Building Technologies
GLB111.9E/KN with 10 Nm nominal torque
Operating voltage AC 24 V
Supports KNX S-Mode and PL-Link
For use with VWG41.. 6-port control ball valves and with 2-port and 3-port
ball valves up to DN 25 / DN 50
Page 2
Features
Type overview
Feature Description Communication - KNX-TP, galvanic ally separated
- Max. 256 nodes per line (with repeaters)
- Busload 5 mA
Functions - Setpoint and actual value for actuator position 0..100%
- Operating mode “heating / c ooling control” for 6-port control ball valve or operating mode “position contr ol” for 2-/3-port control ball valves
- Override control with binary communication objects
- Setpoint monitoring and backup mode
Product no. Ordering no. Operating
voltage
GDB111.9E/KN S55499-D203
AC 24 V KNX-TP
GLB111.9E/KN S55499-D 207
1)
Actuator rotates
Ordering information (example)
Product no. Ordering no. Description Volume
GDB111.9E/KN S55499-D 203 Rotary actuator KNX for 6-port ball valve or
Equipment combinations
6-port control ball valves PN 16 GDB..9E..
Medium: 5…90 °C G..B kvs[m
VWG41.10.. G ½ B 0.25 ..1.9 10 200
VWG41.20.. G 1 B 0.25 ..4.25 20 200
Control signal Power
consumption
1 VA / 0.5 W
3 VA / 2.5 W
control ball valves
Running time
150 s Yes Yes
1)
3
/h] DN ∆p
Manual override
Position feedback
1
[kPa]
max
2 / 12
Siemens A6V10725318_en--_e Building Technologies 2018-06-05
Page 3
2- and 3-port control ball valves PN 40 GDB..9E GLB..9 E internally threaded Rp externally threaded G..B k
3
[m
/h] DN Χp
vs
max
Χp
Χp
s
max
2-port control ball valves
VAG61.15.. G 1 B 1…6.3 15 VAI61.15.. Rp ½“ 1…10 15 VAI61.20.. Rp ¾” VAG61.20.. G 1 ¼ B 4…10 20
350 1400 - -
VAI61.25.. Rp 1” VAG61.25.. G 1 ½ B 6.3…16 25 VAI61.32.. Rp 1¼” VAG61.32.. G 2 B 10…25 32 VAI61.40.. Rp 1½” VAG61.40.. G 2 ¼ B 16…40 40 800
- - 350
1000
VAI61.50.. Rp 2” VAG61.50.. G 2 ¾ B 25…63 50 600
3-port control ball valves
VBI61.15.. Rp ½“ VBG61.15.. G 1 B 1.6…6.3 15 VBI61.20.. Rp ¾” VBG61.20.. G 1 ¼ B 4…6.3 20
350
-
VBI61.25-10 Rp 1” VBG61.25-10 G 1 ½ B 10 25 VBI61.32-16 Rp 1¼” VBG61.32-16 G 2 B 16 32 VBI61.40-25 Rp 1½” VBG61.40-25 G 2 ¼ B 25 40
VBG61.50-40 G 2 ¾ B 40 50
- 350
-
VBI61.50.. Rp 2” 40…63 50
Cf. section “product documentation” for datasheet numbers
Χp
s
-
Open/close 2-port and changeover ball valves 3-port PN 40 GDB..9E GLB..9E internal ly
threaded
Rp externally threaded
G..B
k
vs
[m3/h]
DN Χp
max
Χp
s
Χp
max
Χp
Open/close 2-port ball valves
VAI60.1 5-9 G 1 B 9 15 VAI60.15-15 Rp ½“ 15 15
VAG60.20-17 G 1 ¼ B 17 20
350 1400 - -
VAI60.20-22 Rp 1” 22 20 VAI60.25-22 Rp 1” VAG60.25-22 G 1 ½ B 22 25 VAI60.32-35 Rp 1¼” VAG60.32-35 G 2 B 35 32
VAI60.40-68 Rp 1½” VAG60.40-68 G 2 ¼ B 68 40 800
- - 350
1000
VAI60.50-96 Rp 2” VAG60.50-96 G 2 ¾ B 96 50 600
Changeover ball valves 3-port VBI60.15-5L Rp ½“ 5 15
350 - -VBI60.20-9L Rp 1” 9 20
VBI60.25-9L Rp 1” 9 25 VBI60.32-13L Rp 1¼”
VBI60.40-25L Rp 1½” VBI60.50-37L Rp 2”
13 32
25 40
37 50
- - 350 -
VBG60.15-8T G 1 B 8 15 VBI60.15-12T Rp ½“ 12 15 VBG60.20-13T G 1 ¼ B 13 20 VBI60.20-16T Rp 1” 16 20
350 - - -
VBG60.25-13T G 1 ½ B 13 25 VBI60.25-16T Rp 1” 16 25 VBI60.32-25T Rp 1¼” VBG60.32-25T G 2 B 25 32
VBI60.40-49T Rp 1½” VBG60.40-49T G 2 ¼ B 49 40
- - 350 -
VBI60.50-73T Rp 2” VBG60.50-73T G 2 ¾ B 73 50
Cf. section “product documentation” for datasheet numbers
s
3 / 12
A6V10725318_en--_e Siemens 2018-06-05 Building Technologies
Page 4
Controller s and room unit s Product no. Ordering no. Documentation
Room thermostat KN X RDG160KN S55 770-T297 A6V10629627
Flush-mount room sensor KN X AQR2532NNW with
Room contr ol unit UP227/11 5WG1227-2AB11 A6V 10387579
Software versions
G..B111.9E/KN series B are designed for using ETS device profile v2.x. ETS device profile v1.x is supported for backward compatibility reasons.
Note: The Software-Tools ACS931 / 941 and the handheld tool AST20 are not supported by
the GDB111.9E/KN and GLB111.9E/KN.
Product documentation
(N3191)
AQR2570N F or AQR2576N F
Series informatio n Series A Series B
Production period 12/2015 – 01/2017 01/2017
ETS devic e profile v1.x supported supported
ETS devic e profile v2.x not supported supported
S55720-S 136 S55720-S 203 S55720-S 207
A6V10389050
(N1411)
Title Topic Doc ument ID
Communic ation via the KNX bus Communic ation via the KNX bus A6V10075840 (P3127)
Mounting instruction Mounting instructions rotary actuator A6V10523083 (M4657)
Datasheet 6-port control ball valve Technical information on 6-port control ball valves
VWG41..
Datasheet 2-port and 3-port c ontrol ball valves, PN 40, with internally threaded connection
Datasheet 2-port and 3-port c ontrol ball valves, PN 40, with externally threaded connection
Datasheet 2-port shutoff valves and 3-port changeover ball valves, PN 40, with internally threaded connection
Datasheet 2-port shutoff valves and 3-port changeover ball valves, PN 40, with externally threaded connection
Technical information on 2- port and 3-port control ball valves VA I61… and VBI61..
Technical information on 2- port and 3-port control ball valves VAG61… and VBG61..
Technical information on 2- port shutoff and 3-port changeover ball valves VAI60… and VBI60..
Technical information on 2- port shutoff and 3-port changeover ball valves VAG60… and VBG60..
How to obtain documentation and product-related software
Related documents such as environmental declarations, CE declarations, etc., can be down­loaded at the following Internet address:
http://siemens.com/bt/download
or A6V10636144
A6V10564480
N4211
N4212
N4213
N4114
The ETS device profile can be downloaded at the following Internet address:
http://siemens.com/hvac-td
4 / 12
Siemens A6V10725318_en--_e Building Technologies 2018-06-05
Page 5
HMI (Human-Machine In terface)
Push-bu tt on operation
Activity Push-button op eration Confirmation
Enter / leave addressing mode Press button <1 s LED turns red or gets off
Res et to f actor y s ett in gs Press button >20 s LED flashes orange unt il device
PL-Link connection test
1)
Function or part of the function available in PL-Link operation only
1)
LED colors and patterns
Color Pattern Description
Off --- Fault free operation or device not powered
Green steady Connection test successful
Orange flashing a) Factory reset in progress
Red steady a) Devic e is in programming/addressing mode
1)
Function or part of the function available in PL-Link operation only
Addressing and bus test with push butto n
res tar ts
Press key >2 s and <20 s LED flashes 1x orange
1)
b) When a connection test was triggered: wait
b) When a connection test was triggered: Connection test f ailed
1)
1)
The rotary actuators can be set into addressing/programming mode by push-button:
Press push button (<1 s) KNX bus wiring OK LED turns red until addressing/programming is finished KNX bus wiring not OK LED stays dark
Reset with push button
The rotary actuators can be reset by push-button:
Press push button >20 s LED flashes orange Device restarts
All parameters are reset to the default values.
5 / 12
A6V10725318_en--_e Siemens 2018-06-05 Building Technologies
Page 6
Commissioning and parameterization
The following operating modes are available:
Heating / cooling control: The actuator uses two separate setpoints for heating and cool-
ing each with a range 0...100%.
Position control: The actuator is controlled with a 0...100% position setpoint.
Operating mode “Heating / cooling control”
When using “heating / cooling control” the parameters as listed below are available. Parame­ter sets for 6-port control ball valves DN 10 and DN 20 can be selected. Details on the char­acteristic curves of these two valves can be found in the datasheet A6V10564480.
Note that the valve angle [°] moves counter-clockwise, whereas the actuator position [%] moves clockwise. Therefore valve angle 15° is achieved by an actuator position of 84% etc.
One of the two setpoints (heating or cooling) needs to be “0%” in order for the actuator to be able to move. Are both setpoints not equal to “0%”, the actuator doesn’t move until the setpoint conflict is resolved.
Valve an gle and act uator posi ti on, exam ple for VWG41.20
Parameters for standard piping of heating / cooling:
Parameter VWG41.10 VWG41.20
Valve angle Actuator position Valve angle Actuator position
Max. position heating 15° 84% 15° 84%
Min. position heating 30° 67% 40° 55%
Closed position 45° 50% 45° 50%
Min. position cooling 60° 33% 50° 45%
Max. position cooling 75° 16% 75° 16%
By parameter inversion, heating and cooling are swapped:
Parameter VWG41.10 VWG41.20
Valve angle Actuator position Valve angle Actuator position
Max. position heating 15° 16% 15° 16%
Min. position heating 30° 33% 40° 45%
Closed position 45° 50% 45° 50%
Min. position cooling 60° 67% 50° 55%
Max. position cooling 75° 84% 75° 84%
The 6 port control ball valve can be mounted as shown in the mounting instruction A6V10636144 (coil facing upward) or rotated by 180° (coil facing downward). The ETS parameter settings remain the same, but heating and cooling change their sides (cf. tables below).
6 / 12
Siemens A6V10725318_en--_e Building Technologies 2018-06-05
Page 7
Operating mode “Position control”
Parameters available in “position control”:
Parameter Range Description Factory setting
Opening direction CW (R) / CCW (L) Opening dir ection of the actuator CW (R)
Max. position 0…100% Setting for the upper position limit 100%
Min. position 0…100% Setting f or the lower position limit 0%
Parameterization of the KNX bus integration
The following parameters are usually checked and set by the systems integrator to achieve the right level of bus traffic generated by the actuator or to define the behavior in case of communication interruption. Parameters in the group “advanced” can be left unchanged unless a special configuration is required.
Parameter group “Standard”:
Parameter Range Description Factory setting
Backup timeout 0…60 min
0 min = disabled
Backup mode Backup position
Keep last position
Backup value 0…100% Position the actuator drives to in case of
Time interval to detect communication interruption.
If disabled, the actuator controls to the last received setpoint until a new setpoint is received.
Actuator behavior when the communication timeout has been exceeded (no setpoint received within the defined time inter val).
Backup position: Actuator drives to defined
position
Keep last position: Actuator keeps position
communic ation interruption
30 min.
Backup position
50%
Parameter group “Advanced”:
Parameter Range Description Factory setting
Hysteresis (COV) act uator pos ition
Min. repetition time act uator pos ition
Override position 1 0…100% Position to which the actuator drives if the associated
Override position 2 0…100% Position to which the actuator drives if the associated
1)
COV = Change of value
1...20% Threshold for the actuator position. CO V below this
1)
10...900 s Minimum waiting time until a COV above the
value are not sent over the bus
hysteresis threshold is sent over the bus
group object is triggered (override priority)
group object is triggered (override priority)
1%
10 s
0%
100%
7 / 12
A6V10725318_en--_e Siemens 2018-06-05 Building Technologies
Page 8
Notes
Nati onal s afety regulations
Safety
Mounting
Caution
Failure to comply with national safety regulations may result in personal injury and property damage.
Observe national provisions and comply with the appropriate safety regulations.
Mounting positi ons
IP54 in the following mounting positions
Maintenance
Disposal
Warranty
The rotary actuators are maintenance-free.
Disconnect the electrical connections from the terminals if you want to work at the device.
The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as do­mestic garbage.
Dispose of the device through channels provided for this purpose. Comply with all local and currently applicable laws and regulations.
Technical data on specific applications are valid only together with Siemens products listed under "Equipment combinations". Siemens rejects any and all warranties in the event that third-party products are used.
Note When using the actuators in connection with components of other manufacturers,
correct functioning must be ensured by the user, and Siemens will assume no responsibility.
8 / 12
Siemens A6V10725318_en--_e Building Technologies 2018-06-05
Page 9
KNX Group Objects
Nr. Name in ETS Object
function
Flags Data point type KNX Range
C R W T U ID DPT_Name Format Un it
1 Fault information Transmit 1 1 0 1 0 219.001 _AlarmInf o 6 Byte --- [0...255 ] = Log Nr.
[0...2] = Alarm priority [0...14] = Application area [0...4] = Error class [0...7] = Attributes [0...7] = Alarm status
2 Fault state Transmit 1 1 0 1 0 1.005 _Alarm 1 bit --- 0 = No alarm
1 = Alarm
3 Fault transmission Receive 1 0 1 0 1 1.003 _Enable 1 bit --- 0 = Disable
1 = Enable
4 Setpoint position /
Setpoint pos. heating
5 Actual position /
Actual position heating
Receive 1 1 1 0 1 5.001 _Scaling 1 Byte % 0..100%
1)
Transmit 1 1 0 1 0 5.001 _Scaling 1 Byte % 0..100%
1)
6 Setpoint pos. cooling1) Receive 1 1 1 0 1 5.001 _Scaling 1 Byte % 0..100%
7 Actual position cooling1) Transmit 1 1 0 1 0 5.001 _Scaling 1 Byte % 0..100%
8 Fault Transmit 1 1 0 1 0 1.005 _Alarm 1 bit --- 0 = No alarm
1 = Alarm
9 Override position 1 Rec eive 1 1 1 0 1 1.003 _Enable 1 bit --- 0 = Disable
1 = Enable
10 O verride position 2 Recei ve 1 1 1 0 1 1.003 _Enable 1 bit --- 0 = Disable
1 = Enable
1)
For operating mode “heating / cooling control”
Technical data
Power supply
Operating voltage G..B111.9E/KN AC 24 V ± 20% (SELV) or
AC 24 V class 2 (US)
Frequenc y 50/60 Hz
Power c onsumption at 50 Hz
Actuator holds 1 VA / 0.5 W
Actuator rotates 3 VA / 2.5 W
Function data
Positioning time for nominal rotation angle
G..B111.9E/.. 150 s (50 H z)
120 s (60 H z)
Nominal torque GDB.. 5 Nm
Maximum torque GDB.. < 7 Nm
Nominal / maximum
90° / 95° ± 2°
rotation angle
Direction of rotation Adjustable over bus ( operating mode
“position control”)
Clockwise (CW) / Counter-clockwise (CCW )
Connection cables
Cable length 0.9 m
Power supply Number of cores and cr oss-sectional ar ea 2 x 0.75 mm
Communication Number of cores and cross-sectional area 2 x 0.75 mm
2
2
9 / 12
A6V10725318_en--_e Siemens 2018-06-05 Building Technologies
Page 10
Communication
Communication protocol Connection type KNX-TP (el. isolated)
Bus load 5 mA
Degree of protection
Degree of protection Degree of protection acc. to EN 60529
IP54
(see mounting instruction)
Saf et y class Safety class acc. to EN 60730 III
Environmental conditions
Applicable standard IEC 60721-3-x
Operation Climatic conditions Class 3K5
Mounting location Indoors
Temperature general 0…50 °C
Humidity (noncondensing) 5…95 % r. F.
Transport Climatic conditions Class 2K3
Temperature -25…70 °C
Humidity 5...95 % r. h.
Storage Climatic conditions Class 1K3
Temperature -5…45 °C
Humidity 5...95 % r. h.
Directives and Standards
Product standard EN 60730- x
Product f amily standard EN 50491-2, EN 50491-3, EN 50491-5
General requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS)
Electromagnetic compatibility (Application) For residential, commercial and industrial
environments
EU Conformity (CE) A5W00003842
RCM Conf ormity A5W00003843
1)
1)
UL, cUL AC 24 V UL 873 http://ul.com/database
Environmental compatibility
The product environmental declaration A6V 102099381) contains data on environmentally compatible product design an d assessments (RoHS compliance, materials composition, packaging, environmental benefit, dis posal).
Dim ensions / Weight
Weight Without packaging 0.6 kg
Dimensions 71 x 158 x 61 mm
1)
The documents can be downloaded from http://siemens.com/bt/download
10 / 12
Siemens A6V10725318_en--_e Building Technologies 2018-06-05
Page 11
Diagrams
wiring, operation, etc.
Internal diagram / Power supply and communication cables
The KNX rotary actuator is supplied with two prewired power supply and communication cables.
G..B111. 9E/KN
Note
Dimensions
Core desig.
Cable 1: P ower / black sheathing
1 red (RD) G System voltage AC 24 V
2 black (BK) G0 System neutral AC 24 V
Cable 2: KNX / green sheathing
1 red (RD) CE+ KNX CE+
2 black (BK) CE- KNX CE-
Core color Terminal
code
Description
The operating voltage at terminals G and G0 must comply with the requirements under SELV or PELV.
Safety transformers with twofold insulation as per EN 61558 required; they must be designed to be on 100 % of the time.
G..B111. 9E/KN
Minimumdistance from walls
or ceilings during mounting,
= > 100 mm
►► = > 200 mm
Dimensions in mm
A6V10725318_en--_e Siemens 2018-06-05 Building Technologies
11 / 12
Page 12
Issued by
www.siemens.com/buildingtechnologies
Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 58-724 24 24
Dokument-ID A6V10725318_en--_e
Ausgabe 2018-06-05
© Siemens Switzerland Ltd, 2015
Technical specific ations and availability subject to change without notice.