Siemens 5SU1656-6KK10 data sheet

Data sheet 5SU1656-6KK10
RCBO, 6 kA, 1P+N, type A, 300 mA, B char., In: 10 A, Un AC: 230 V
product brand name
SENTRON
product designation
RCBO
design of the product
Instantaneous
number of poles
2
number of poles / note
1P+N
number of poles / with protection
1
tripping characteristic class
B
mechanical service life (switching cycles) / typical
10 000
overvoltage category
III
degree of pollution
2
surge current resistance / at (8/20) µs
1 kA
type of voltage
AC
operational current / at AC / rated value
10 A
supply voltage
● at AC / rated value
230/240 V
● for testing equipment / minimum
100 V
operating frequency
50 Hz
supply voltage frequency / rated value
50 Hz
protection class IP
IP20, if the distribution board is installed, with connected conductors
breaking capacity short-circuit current (Icn) / according to EN 61009-1 / rated value
6 kA switching capacity current
● acc. to EN 60898 / rated value
6 kA
● acc. to IEC 60947-2 / rated value
15 kA
rated residual switching capacity (IΔm) / according to IEC 61009-1
6 kA energy limitation class
3
power loss [W]
● for rated value of the current / at AC / in hot operating state / per pole
1.8 W
● maximum
3.6 W
5SU16566KK10 Page 1/2
12.22.2020
Subject to change without notice
© Copyright Siemens
tripping fault current / rated value
300 mA
residual current type
A
product function / neutral conductor switching
Yes
product feature / touch protection
Yes
product feature
● halogen-free
Yes
● silicon-free
Yes
connectable conductor cross-section / solid
● minimum
0.75 mm²
● maximum
35 mm²
connectable conductor cross-section / stranded
● minimum
0.75 mm²
● maximum
35 mm²
connectable conductor cross-section / finely stranded / with core end processing
● minimum
0.75 mm²
● maximum
25 mm²
tightening torque / with screw-type terminals
● minimum
2.5 N·m
● maximum
3 N·m
position / of power supply cord
Either top or bottom
height
90 mm
width
36 mm
depth
77 mm
installation depth
70 mm
number of modular width units
2
mounting position
any
net weight
264 g
weight / with packaging
264 g
influence of the surrounding temperature
Max. 95% humidity
ambient temperature / during operation
● minimum
-25 °C
● maximum
55 °C
ambient temperature / during storage
● minimum
-40 °C
● maximum
75 °C
number of test cycles / for environmental testing / acc. to IEC 60068-2-30
28
reference code
● acc. to DIN EN 61346-2
F
● acc. to IEC 81346-2
F
General Product Approval
Miscellaneous
Declaration of Conformity
Test Certificates
Marine / Shipping
other
Railway
5SU16566KK10 Page 2/3
12.22.2020
Subject to change without notice
© Copyright Siemens
Loading...